Section 26 Outside receptacles Rule 26-726(a) requires a separate circuit to be supplied solely for the purpose of outdoor receptacles. 26-700(11) Receptacles having CSA configuration 5-15R or 5-20RA installed within 1.5m (5ft) of sinks (wash basins complete with drain pipe), bathtubs or shower stalls shall be protected by a ground fault circuit interrupter of the Class A type. 26-710 (c) Receptacles shall not be mounted facing up in the work surfaces of counters in the kitchen or dining area. 26-712(d) In dwelling units there shall be installed in each kitchen: (iii) A sufficient number of receptacles (15 A split or 20 A T-slot) along the wall behind counter work surfaces (excluding sinks, built-in equipment, and isolated work surfaces less than 300 mm long at the wall line) so that no point along the wall line is more than 900 mm from a receptacle, measured horizontally along the wall line. (IV) At least one receptacle (15 A split or 20 A T-slot) installed at each permanently fixed island counter space with a long dimension of 600 mm or greater. (v) At least one receptacle (15 A split or 20 A T-slot) installed at each peninsular counter space with a long dimension of 600 mm or greater. Note: If the island or peninsular counter are long enough, or the island is divided by a sink creating two surfaces over 300 mm, two receptacles may be required to meet the requirements of 712-(d) (iii) above. Page 1 of 2 Page 2 of 2
© Copyright 2026 Paperzz