UC8 Fault and Display Messages

temperzone ltd
Unit Controller (UC8) - for Hydronic systems
Condensate Pump and Water Valve
12V DC / 24V AC thermostat input
High Medium Low Com1
Comp Heat Com2
Flow
switch
LP
switch
DC outputs & 0-10V control inputs
+5V DC Fan Ground +12V DC Capacity Ground
Expansion Valve
Fault relay
Run status
Earth
B
A
Ground
RS485 #1
+12V DC
B
A
Ground
RS485 #2
0-10V out #1
Ground
Dip switches
0-10V out #2
Ground
Display
Sump float switch
DRM1
DRED
DRM3
Sc (Ground)
Push Button
Remote on/off
Ground
Live Neutral High Medium Low Com3 Com4 Compressor
Fan output relays
230V AC
contactor
Low pressure protection active
HP
High pressure protection active
HI-t
High temperature protection active
LO-t
Water freeze protection
Circulating Capacity solenoid
pump
or EHC2
Display Messages (Normal Operation)
Faults
LP
Reverse cycle
valve or EHC1
UC8 X.X.X
dF
dELAY
Name and software version (shown only after power-on) e.g. 1.5.2
Digital scroll or fixed speed compressor
Unit waits for a random delay time (up to 25s, shown only after power-on)
• (flashing)
Normal mode
- (flashing)
Unit is OFF by Remote On/Off signal
nO-FLO
Circulating water flow protection
FLOOd
Sump condensate protection
FROSt
Indoor coil frost protection active
HI-SL
High suction line temperature protection active
dr
DRED energy consumption restriction active
High discharge superheat protection active
H
Indoor fan High speed selection
OL
Overload protection active
L
Indoor fan Low speed selection
F11
Indoor fan fault
E
Compressor model selection
F12
Low pressure transducer fault
A
Modbus device Address selection
F13
High pressure transducer fault
F14
Suction line temperature sensor fault (SL)
F15
Discharge line temperature sensor fault (DL)
F18
Indoor coil temperature sensor fault (IC)
F19
Hi-dSH
c
Commissioning mode (lasts for 30 minutes)
t
Test mode (lasts about 1 minute)
HOLd
Compressor held-on or held-off by a timer
Monitoring of pressures and temperatures.
Press the push button to cycle through the following options (round robin fashion):
• or c
sLP
No temperature display (default)
Suction line pressure (kPa)
Et
Evaporating temperature (°C)
Ambient temperature sensor fault (AMB)
SLt
Suction line temperature (°C)
F20
Superheat unknown
SSH
Suction side superheat (K)
F21
Thermostat communication lost
dLP
Discharge line pressure (kPa)
F22
BMS communications lost
Ct
Condensing temperature (°C)
F26
Error reading DIP switch settings
dLt
Discharge line temperature (°C)
F27
Invalid fan selection
dSH
Discharge side superheat (K)
F29
High controller temperature
ICEt
Outdoor coil de-ice sensor temperature (°C)
CAP
Unit capacity (%)
F30
Supply voltage out of bounds
EE1
Expansion valve 1 opening (%)
F32
Controller internal communication problem
EE2
Expansion valve 2 opening (%)
F34
Problem with pressures or transducer readings
F35
Reverse cycle valve fault
How to activate Special Modes
• Thermostat and compressor must be OFF.
F36
Invalid dip switch settings on TZT-100 thermostat
F39
Variable speed compressor driver fault
F40
Compression ratio too high
F41
Compression ratio too low
F42
Evaporating pressure / temperature too high
• Available special modes are:
t - Test mode
H - Indoor fan high speed selection
E - Compressor model selection
F43
Condensing pressure / temperature too low
• Release the push button as soon as the display shows the correct letter.
• Press and hold pushbutton until the display shows the letter that corresponds to the special mode. Note: depending on the model some special modes may not be available.
c - Commissioning mode
L - Indoor fan low speed selection
A - Modbus address selection
020-001-245 06/15