Power pack and LED driver Power pack LED Nexus

Technical data sheet
Power pack and LED driver
Power pack LED Nexus® emergency
Nexus products
Catalogue no.
Description
PPNXSLED5W
Power pack LED Nexus LX 20-45V 5W max 4D cell NiCad
PPNXSLED5W-1*
Power pack LED Nexus LX SC1* 5W max 4D cell NiCad
PPNRFLED5W
Power pack LED Nexus RF 20-45V 5W max 4D cell NiCad
PPNRFLED5W-1*
Power pack LED Nexus RF SC1* 5W max 4D cell NiCad
Note: * specific optimized configuration for Davis Lighting Luminaire
Spare parts
Range
Non-standard range
Catalogue no.
Description
03-CBMA035P
Battery 4 cell NiCad 4.8V 4.5Ah
Dimensions
Product group
Power pack and LED driver
Description
The power pack LED emergency is designed to convert a
wide range of LED luminaires. The power pack is designed
to be installed by breaking into the low voltage connection
between the mains LED driver and the LEDs and allows
the LEDs to be operated as normal under mains healthy
conditions and operated at reduced light output in an
emergency.
Features
−− 3 year warranty***
−− Constant current intelligent battery charger
−− High temperature 70oC NiCad battery for longer life
−− SELV for output voltage <50V
−− Low profile main module casing (42 x 31mm cross-section)
−− Low profile RF module, can easily stick using good quality
double sided tape on side of the main module
−− Deep discharge protection
−− Short-circuit-proof battery connection
−− Polarity reversal protection for battery
−− Constant power output
−− Compatible with various brand of LED luminaires in the
market
Note: *** LED luminaire is assessed and power pack installed as recommeded by ABB
10
Part
Length
Width
Height
Main module
255mm
42mm
31mm
RF module
81mm
31mm
21mm
Battery pack
170mm
60mm
32mm
Antenna cable
500mm
Serial cable
250mm
Test switch and LED
220mm
Weight
Model
Weight
Nexus LX/RF
0.8kg
Construction
Part
Construction
Main module
Polycarbonate
RF module
Polycarbonate
Battery pack
NiCad
Technical data
Part
Specifications
Rated supply voltage
220-240V
Mains frequency
50/60 Hz
LED module forward voltage range
20-45V
Time to light up on mains failure
<0.25 seconds of emergency event
Maximum output voltage
45V
Battery charging time
16 hours**
Ambient temperature ta
+5oC to +55oC
Maximum casing temperature tc
75oC
Type of protection
IP20
Note: ** 16 hours battery charging time for 2 hours emergency lighting duration as
per AS2293
Note: Designed to comply with AS2293 and meet relevant Australian EMC standards
9AKK106930A3846 - May 2017
For more information please contact:
ABB Australia Pty Limited
Phone: 1300 666 595
Fax: 1300 666 594
E-mail: [email protected]
www.stanilite.com.au
Note: We reserve the right to make technical changes or modify the contents of
this document without prior notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB does not accept any responsibility whatsoever for
potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations
contained therein. Any reproduction, disclosure to third parties or utilisation of its
contents – in whole or in parts – is forbidden without prior written consent of ABB.
Copyright © 2017 ABB
All rights reserved