KN630 - KONČAR - NISKONAPONSKE SKLOPKE I PREKIDAČI doo

Instruction Manual
for MCCB Type
KN630-HE
Please retain this manual for future reference.
!
Handling precautions
Caution
Electrical work should only be undertaken by suitably qualified persons.
The Manufacturer assumes no responsibility for damages resulting from
non-application or incorrect application of the instructions provided herein.
1
!
!
Be careful to prevent foreign objects (debris, concrete powder, iron
powder etc.) and rainwater from entering product.
Safety Notices
Be sure to read these instructions and other documents accompanying
the product thoroughly before mounting, using, servicing or inspecting
the product. In these instructions, safety notices are divided into
"Warning" and "Caution" according to the hazard level.
For 4-pole breakers, be sure to connect a nautral conductor to the
N pole. Otherwise, an over-current may hinder the product from tripping
thus resulting in a fire.
! CAUTION : A caution notice with this symbol indicates that neglecting
the suggested procedure or practice could result in moderate or slight
personal injury and/or property damage.
Maintenance precautions
When connecting cable or busbar to the product, tighten terminal screws
to the torque specified in this manual.
insul. tubes
or
insul. tape
interpole
barriers
CAUTION
Note that failing to observe
notices could result in serious
injury and/or property damage in some instances. Because safety
notices contain important information, be sure to read and observe them.
!
For front connected breakers,
insulate all bare conductors
of the line side until the breaker
end. If interpole barriers are packed,
be sure to use the barriers, moreover, insulate all bare conductors by
insulating tape the like so that the tape overlaps with the barriers.
Mounting Precautions
For detailed mounting dimensions, refer to either the Loadline or
System Loadbank catalogues.
Caution
When the breaker trips open automatically, remove the cause, then
return the handle to the ON position. should a fault be interrupted,
the breaker must be inspected.
Prior to commencing any work on the product, open an upstream
circuit breaker or isolator to ensure that no voltage is applied to the
product. Otherwise electrical shock may result.
! WARNING
: A warning notice with this symbol indicates that neglecting
the suggested procedure or practice could result in moderate or slight
personal injury and/or property damage.
Warning
Do not touch the handle catch. Doing so may cause personal injury.
Do not place the product in an area that is subject to high temperature,
high humidity, excessive dusty air, corrosive gas, strong vibration and
shock, or under unusual conditions.
.
.
.
..
!
Caution
Service and/or inspection of the product must be done by persons
heving expert knowledge.
Prior to commencing any work on the product, open an upstream
circuit breaker or isolator to ensure that no voltage is applied to the
product. Otherwise electrical shock may result.
Regularly check that the breaker terminal screws are tightened to
torque values shown within this manual, failure to do so may result
in fire.
Other precautions
Do not carry this product by accessory leads, as this may cause damage
to the product.
Do not block the arc gas vents of the product to ensure edequate arc
space. Blocking these vents could result in failure of circuit interruption.
Unauthorised opening of breaker cover will invalidate product warranty.
KON AR-Niskonaponske sklopke i prekida i d.o.o.
p.p.209; 10002 ZAGREB, CROATIA
Tel: +385 1 236 92 62
Fax: +385 1 233 95 77
e-mail: [email protected]
[email protected]
2
B53128
3
Packaged Items / Assembly Tools
4
Operating Instructions
Fitting Internal Accessories
Instruction Manual
Breaker
Auxiliary Switch
Interpole Barrier
M Type
TRIPPED
(only FC)
T2AX00M
3P: 2 pcs.
4P: 3 pcs.
tip M
B Type
*
T2AX00B
*
Ring mark
Alarm Switch
M Type
T2AL00M
Handle
Shunt
trip
T2SH00 *
ON
Type
630A
OFF
Auxiliary Switch
B Type
*
T2AL00B
a kontakt
b kontakt a kontakt b kontakt
11/AXc-14/AXa 11/AXc-12/AXb 91/ALc 91/ALc
21/AXc-24/AXa 21/AXc-22/AXb
31/AXc-34/AXa 31/AXc-32/AXb 94/ALa 92/ALb
Undervoltage
trip
T2UV00 *
10mm
*Symbols of Accesories
Shunt trip
Power Source
C1-C2
Connections/Poles
Qty.
Front
Connected
(FC)
Rear
Connected
(RC)
Plug in
Connected
3P
4P
3P
4P
3P
4P
3P
4P
3P
4P
6
8
4
4
6
8
4
4
4
4
Trip Button
OFF
Combination
(M10x30)
Removal
(ON)
(M6x100)
(M12x35)
(OFF)
(M6x100)
RESET
(M6x120)
(ON)
Slits of pulling out leads
(OFF)
Operation
17
19
8
OFF-ON
ON-OFF
TRIP-OFF
Operation effort
110N
115N
125N
In case of fitting one (or two) auxiliary
switch, fit in an order from left side slot.
AX
AL
SH
UV
Alarm Switch
*
V
After fittin, verify the function of the Accessories.
Undervoltage trip
Power Source
D1-D2
6 Conductor connection procedure for RC
5 Breaker mounting procedure for FC / RC
7 Conductor connection procedure for FC
19
D
8
N
oC
B
P
Q
8
B
8
oK
oO
Flat bar stud
19
J
M
*: 3 or 4 poles
B
C
D
A
A
M10x20
18.6~29.4 Nm
13mm
M12x35
40.2~65.7Nm
9
8 Plug in mounting block mounting procedure
< 30mm
=
< 12.5mm
=
I
J
K
L
M
N
O
M6x100
6.0~7.4Nm
*: 3 or 4 poles
10.5 mm
<= 30 mm
< 12 mm
=
< 12 mm
=
P
11 mm
10 Rated current for PM
Conductor connection procedure for PM
Flat bar
P
8
11 Drilling plan
Y
Y
Maximum rated current for PM is 535,5A
oU
V
S
T
U
V
R
M5x30
3.6~4.4Nm
Temperature
30oC
40oC
50oC
55oC
60oC
65oC
<= 30 mm
<= 20mm
11 mm
W
<= 20 mm
M10
18.6~29.4Nm
procedure
14 Terminal cover mounting
Rated current
535.5A
535.5A
504.0A
396.9A
396.9A
396.9A
X
X
Y
13 Interpole barrier mounting
12 Breaker mounting procedure for PM
Y
Maximum rated current in each temperature
refer to the following list:
17
T
R
Y
Y
Y
W
oU
Q
Insulate all bare conductors of the line side until the breaker end.
M10x30
13.7~22.5Nm
M12x40
40.2~65.7Nm
Panel cut-out
FC
RC
16 Adjustable electronic type
15 Handle holder / Lock mounting procedure
procedure
Electronic type
Char.
R
0.8
0.9
4
0.95
1
0.63
5
6
3
2
0.5
0.4
1
(OFF)
Optional
Ground fault trip
ON/OFF switch
Handle holder / Lock
ON
or
OFF
(OFF)
17 Time/Current characteristic curves
Electronic type
Adjustable
R
0.4,0.5,0.63,0.8,0.9,0.95,1 (x n) ( A)
Interpole barrier
*: 3 or 4 poles
(ON)
6
Terminal cover lock
5
4
*
Connection
1
2
Terminal cover
FC (without flat bar)
5,6
max x 3 (o5~8)
0.2S
0.1S
RC (with flat bar)
X
When removing, remove the items in
reverse order of mounting.
X
Handle holder / lock can be fitted in any position of ON and OFF.
RC/ PM
M6x120
6.0~7.4Nm
*: 3 or 4 poles
When removing, remove the items in
reverse order of mounting.
3
When removing, remove the items in
reverse order of mounting.
When you use this item as the handle lock, please fit padlocks in the procedure of
2.5
When removing, remove the items in reverse order of mounting.
3
1,2
4
.
5
8 14 x
R
Under bar is default setting!