DUCTGARD Duct Mounting Smoke and Fire Control Dampers SFB (57.9) X UDC 697.9 Dampers 1 Features - Certified to Current test standards BS EN 1366-2 Fully tested and CE marked and compliant Galvanised or stainless interlocking double skin blades Stainless steel frame side seals 4 modes of operation Connections to suit most proprietary ductwork Extensive range of supporting controls NOV 2014 INTRODUCTION Gilberts Ductgard presents an ‘engineered’ range of combined smoke and fire dampers suitable for use in all types of HVAC ductwork. Benefitting from over 50 years of engineering experience in the industry considerable ingenuity has been applied in the design and construction of this product to produce a damper of high efficiency, reliability, durability and ease of use. Ductgard has been tested to the latest BS-EN1366-2 fire test standard and includes mandatory CE marking. Control Mode Options The Gilbert’s 2014 Ductgard presents a re-engineered range of combined fire and smoke dampers Mode Fully automatic opening operating on 24v with failsafe spring return closure via 72˚c electro thermal link release 4 9B Fully automatic opening operating on 230v with failsafe spring return closure via 72˚c electro thermal link release 4 10A Fully automatic closure operating on 24v with failsafe spring return opening via 72˚c electro thermal link release 4 10B Fully automatic closure operating on 230v with failsafe spring return opening via 72˚c electro thermal link release 4 Developed from a well proven heritage of tried and tested damper designs, considerable ingenuity and manufacturing expertise has been applied to produce a robust, effective, competitive unit that is easy to install and maintain. The unit is designed to fit within all types of ductwork at its junction with a fire barrier wall, where it can be fixed directly in or immediately adjacent to the building structure in both the horizontal and vertical positions. With a choice of 4 different modes of operation all units are fully automatic and motorised. All units comprise of an air-tight galvanised casing (DW144 Class C Specification) with stainless steel interlocking blades and frame side seals, which provides a four-hour fire rated assembly. Sizes range from 200 x 200 upto a maximum of 1000 x 1000 in one unit. Dampers over this size are supplied in multiple units. Page 9A suitable for use in HVAC ductwork systems. Description DUCTGARD Duct Mounting Smoke and Fire Control Dampers Mode 9 Description Motor Voltage Control Options Mode 9 provides a fully automatic type of smoke and fire damper that operates on the basis of fail safe closure with automatic reset. It has been designed to close in smoke and fire conditions upon a failure of the supply voltage to the motor or in the event of an electro thermal fusible link separating at a pre-determined temperature (72°C standard). Volt free microswitches are included as standard. Mode A: 24V AC or DC supply. Mode B: 230V AC supply. Note: All options include position microswitches as standard. Operation Mode 9 is fitted with a spring return square drive motor which will hold the damper open for as long, as the supply voltage is available. Interruption of this supply will cause controlled damper closure by way of the motors spring return operation. In addition however, the damper is fitted with an electro thermal fusible link which will fail at a pre-determined temperature (72°C standard) and close the damper irrespective of the status of the motor. An integral test pushbutton on the electro thermal fuse housing allows for the local testing of the damper operation. Mode 10 4 Description Mode 10 performs in exactly the same manner as the Mode 9 except that the operation is reversed and the units are fail safe open. The motor sets the unit in the full closed position and the unit will only open in the event of an interruption of the supply voltage to the motor or separation of the thermal fusible link. Re-set Procedure Provided the fusible link is intact the damper will automatically reset after an interruption of the supply voltage to the motor. The motor will take approximately 80 seconds to open the damper. The spring return motor and terminal box (if fitted) are mounted on the ductwork connection sleeve. Fully assembled prior to despatch they require only the external electrical connections to be made. Dimensional Data 336* 50 39 DUCT WIDTH - 4mm (100 to 1000) 40 40 40 DUCT HEIGHT - 4mm (100 to 1000) 40 198* * Allow extra 50mm for cables 90 ALLOW FOR ACTUATORREMOVAL 120 Dimension ‘A’ See Table 39 198* Square/Rectangular Spigot Connection 194 25 VARYING LENGTHS OF OPTIONAL STUB DUCT AVAILABLE E 210MM TO 450MM. PLEASE REFER TO SALES OFFICE 41 B 50 Dimension ‘A’ See Table * Allow extra 50mm for cables 198* B Dimension: Up to 350mm dia = 41mm Over 350mm dia = 55mm 90 39 DUCT DIAMETER - 3mm (100 to 1000) 39 16 39 120 16 16 DUCT DIAMETER - 3mm (100 to 1000) 41 ALLOW FOR ACTUATOR REMOVAL B 198* Circular Spigot Connection 39 38 16 194 16 336* Damper Handing Dimension ‘A’ Duct Height/Dia. 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 Dimension ‘A’ 84 109 84 159 184 159 184 259 284 259 284 359 384 359 384 459 484 459 484 Right hand motor positioning (as shown) as standard 5 DUCTGARD Duct Mounting Smoke and Fire Control Dampers Installation Dimensional Data 34 34 131 DUCT WIDTH OR DIA. + 136mm DUCT HEIGHT OR DIA. + 136mm Installation Frame (HEVAC) Ref. IF DUCT WIDTH OR DIA. + 189 285 Sleeve with Angle * DUCT WIDTH OR DIA. + 109 DUCT HEIGHT OR DIA. + 81mm Ref. SF DUCT HEIGHT OR DIA. +161mm CONNECTING DUCTWORK BY OTHERS * Suitable for walls up to 200mm. Above this thickness refer to our technical sales office. DIMENSION = X + 25mm DIMENSION = X CENTRE LINE OF DUCT O 12mm HOLE FOR DROP RO 50 50 18 50 18 50 Drop Rod Cleats 40 40 40 Ref. DF Angle Frame DUCT WIDTH or DIA. + 225 120 35 85 60 60 DUCT HEIGHT OR DIA. + 198mm Ref. AF 60 DIMENSION = X + 25mm DIMENSION = X CENTRE LINE OF DUCT 6 Installation Methods Ductgard can be installed in a wide variety of approved ways using the different installation options detailed on page 6. Please remember that only the installation methods detailed are tested and approved to EN1366-2. If your installation varies from these options you will need to confirm approval with Building Control. Manufacturers are not able to approve alternative installation methods. Concrete/masonry floor with HEVAC frame (Ref...IF) Block/masonry wall with HEVAC frame (Ref...IF) Single section sizes (mm): 100 x 100 to 1000 x 1000 Single section sizes (mm): 100 x 100 to 1000 x 1000 MIN. 150MM FRAME POSITIONED CENTRALLY OR THE CENTRE TO BE AT LEAST 50MM AWAY FROM NEAREST WALL FACE BLOCK WALL BUILDING TIES MIN. 150MM MORTAR OR CONCRETE BACK FILL MORTAR OR CONCRETE BACK FILL BUILDING TIES FRAME POSITIONED CENTRALLY OR THE CENTRE TO BE AT LEAST 50MM AWAY FROM NEAREST WALL FACE SOLID FLOOR Tested to BS EN 1366-2 for 4 hours Equivalent to BS EN 13501-3 classification: ES240 (E240s) BS EN 1366-2 test/assessment references: 216413/cc 254958/cc 261450 Meets the requirements of BS 476-20/22 - refer BS 476-10.6.6.3 Tested to BS EN 1366-2 for 4 hours Equivalent to BS EN 13501-3 classification: ES240 (E240S) BS EN 1366-2 test/assessment references: 256538/CC 261450 Meets the requirements of BS 476-20/22 - refer BS 476-10.6.6.3 Block/masonry wall with sleeve & angles (Ref...SF) ALL ROUND GAP 5MM Single section sizes (mm): 100 x 100 to 1000 x 1000 M1 M2 SLEEVE ANGLES Tested to BS EN 1366-2 for 4 hours Equivalent to BS EN 13501-3 classification: ES240 (E240S) BS EN 1366-2 test/assessment references: 256538/CC 261450 Meets the requirements of BS 476-20/22 - refer BS 476-10.6.6.3 M3 7 DUCTGARD Duct Mounting Smoke and Fire Control Dampers Dry wall with sleeve & angles (Ref...SF) Dry wall with drop rod cleats (Ref...DF) Single section sizes (mm): 100 x 100 to 1000 x 1000 Single section sizes (mm): 100 x 100 to 1000 x 1000 ALL ROUND GAP 5MM MIN. 100MM MAX. 200MM M10 DROP RODS TYPE 5 PLASTERBOARD STONE WOOL STONE WOOL TYPE 5 PLASTERBOARD SLEEVE ANGLES OPENING LINED WITH TRACK AND BOARD OPENING LINED WITH TRACK AND BOARD Tested to BS EN 1366-2 for 4 hours Equivalent to BS EN 13501-3 classification: ES240 (E240S) BS EN 1366-2 test/assessment references: 256538/CC 261450 Meets the requirements of BS 476-20/22 - refer BS 476-10.6.6.3 Tested to BS EN 1366-2 for 4 hours Equivalent to BS EN 13501-3 classification: ES240 (E240S) BS EN 1366-2 test/assessment references: 256538/CC 261450 Meets the requirements of BS 476-20/22 - refer BS 476-10.6.6.3 Dry wall - with angle frame (Ref...AF) Single section sizes (mm):100 x 100 to 1200 x 1200 MIN. 100MM MAX. 200MM STONE WOOL FLANGE SCREWED TO TRACK M5 M6 OPENING LINED WITH TRACK AND BOARD TYPE 5 PLASTERBOARD Tested to BS EN 1366-2 for 4 hours Equivalent to BS EN 13501-3 classification: ES240 (E240s) BS EN 1366-2 test/assessment references: 216413/cc 254958/cc 261450 Meets the requirements of BS 476-20/22 - refer BS 476-10.6.6.3 8 M9 Actuator - Inboard Mounting Option The actuator is normally fitted to the outside face of the motor mounting bracket. Where limited clearence or other factors dictate it is posible to move the motor to an inboard position. The motor can also be rotated into three alternative positions either on site or in the factory. CLAMP BRACKET REVERSE MOUNTED TRANSFER DRIVE M6 BOLTS & WASHERS (X4) Reverse Mounted Actuator Clamping Kit ACTUATOR WITH FIXING BRACKET SUB ASSEMBLY Standard Position 439.5 40 195.5 DUCT WIDTH - 4MM 40 145 40 198 DUCT HEIGHT - 4MM 25.5 50MM FOR CABLE 40 268 105 Alternative Position 1 Alternative Position 2 565 195.5 439.5 195.5 270.5 145 145 198 50MM FOR CABLE 198 50MM FOR CABLE 268 268 * If your proposed installation method has minor variations to that shown, please confirm acceptance with the local Building Control Authority (BCA) before proceeding. Manufacturers are not able to "approve" specific installation methods. 9 DUCTGARD Duct Mounting Smoke and Fire Control Dampers Wiring Diagrams Mode 9 and 10 Ductgards are normally controlled, by a remote switch on the Motor Supply. Note: To interface with Gilberts remote indicators it is easier to switch the negative rather than the positive. Control Option A - + 1 2 M S1 - S2 made when damper closes S4 - S6 made when damper open 24 V WIRING DIAGRAM Power Supply 24V AC +-20% 50/60 Hz 24V DC +-20% S1 Current Rating 380mA AC max S2 S3 S4 S5 S6 5° 80° POWER CONSUMPTION Opening 5 watts Holding 2.5 watts Control Option B - + 1 2 S1 M All Modes Addressable S2 S3 5° S4 S5 240V WIRING DIAGRAM Power Supply 240V AC +15% -10% 50/60 Hz 240V AC +10% 50Hz Current Rating 200mA AC max S6 80° Mode 9 and 10 Ductgards in this option are interfaced with our Gardex Controller as described on Page 11. Motorised dampers are fitted with the Belimo BLF-T range as standard. Other actuators are available upon request. 2 Core Screened Communication Cable Belimo Damper Motor M 240V 50HZ Fused Spur (option 24V DC) 1 2 3 4 5 6 L N E N L 1 2 3 4 5 6 + + - - S S DCM Damper Control Module 10 POWER CONSUMPTION Opening approx 6 watts Holding approx 3 watts Control Systems Gilberts offer a wide choice of hard wired and multiplex controlled systems to meet the challenge of effective fire and smoke control monitoring. Available as stand alone, or suitable for interfacing or incorporating with building management or fire/smoke control systems designs, the range includes four simple off the shelf packages through to bespoke designs to satisfy the most demanding criteria. Gardex (Modes 9/10 Options Only) Multiplex System The Gardex system has been designed to reduce the cost of electrical wiring installations and satisfy the most complex of control changes. Up to 126 dampers can share the same 2 wire communication line to transmit information to and from the central controller. Features Housing Metal wall mounted enclosure complete with a clear hinged lockable front cover and lower cabling chamber. Protection rating IP55 Keyboard and Display - Directory command programming via arrow keys and 2 line x 40 character LCD display are provided as an operator interface. Fault reporting Faults are identified on the LCD display and the controller can be interrogated to determine the nature of the fault and its location. TYPICAL OPTIONAL FEATURES CENTRAL CONTROLLER - MIMIC AND DAMPER STATUS INDICATOR LIGHTS - INTEGRAL FIREMANS INTERFACE SWITCH - MECHANICAL FAN CONTROL RESET POWER ON SYSTEM FAULT PROGRAM ACKNOWLEDGE Gardex Controller - LINE ISOLATION FIRE COMMAND 500mm FAULT ACKNOWLEDGED 1 2 3 4 5 6 7 LAMP TEST 8 - REMOTE ALARM INTERFACE 9 10 11 12 13 14 15 16 17 18 19 20 SMOKE DAMPER STATUS INDICATION 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 SMOKE DAMPER STATUS INDICATION 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 SMOKE DAMPER STATUS INDICATION 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 SMOKE DAMPER STATUS INDICATION Damper Indicator Damper Indicator Expander 400mm Field Stations (DCM) Available as an integral part of the damper, or as a separate enclosure, the addressable module has been designed to provide independent operation of individual or groups of dampers in accordance with a preprogrammed logic sequence of events. Individual dampers are controlled and have there status constantly monitored by the module in response to signals from the pre-programmed controller. Maximum length of communications 2km. In the event of communications failure dampers assume failsafe position. Bottom Entry Gland Plate 300x90mm (approx) Bespoke Control Panels These are available in a number of configurations and are designed and manufactured to suit individual specific requirements. The electro-mechanical control/monitoring panels are based on IP55 wall mounting enclosures, which can be provided to include such features as: - FIREMANS/BMS INTERFACE - MULTI ZONE CONTROL & DAMPER STATUS INDICATIONS - UPS - VOLT FREE CONTROLS FOR REMOTE INDICATION OR ALARM Please contact Head Office to discuss specific requirements. 11 DUCTGARD Duct Mounting Smoke and Fire Control Dampers Gilberts range of ancillary Items have been designed for use in conjunction with both the Ductgard and Smokegard models. Purpose built for straightforward connection and compatibility they offer a number of useful services. Remote Indicators/Master Monitors YELLOW UNIT No. GREEN LIGHT SYSTEM SET AIIFA No. -VE DC FROM DUCTGARD 100mm Gilberts remote indicator panels can be linked to damper Modes 5 and 6 and will provide remote indication of the status of one or more dampers. Ref:RT1 (1 damper) MM1-12 (upto 12 dampers) Larger Panels available upon request BLUE Ancillary Items O R G RED LIGHT SYSTEM TRIPPED OUTLINE OF PCB NOTE: When damper is open yellow is +VE When damper is closed blue is +VE 35mm 76mm Master Monitor -VE DC BLUE YELLOW 240mm A more advanced form of remote indication is available with a master monitor. This unit provides remote indication for the status of up to 12 individual dampers. Ref:MM1-12* * dependant on number of dampers on the system FROM DUCTGARD Master Monitor O R G O R G UP TO 12 PCBs IN 1 MASTER MONITOR NOTE: When damper is open yellow is +VE When damper is closed blue is +VE 87mm 240mm Standard Power Supply MAIN POWER SUPPLY 240v AC Standard power supplies are available in two sizes to suit up to 6 or up to 12 dampers. They provide conversion from 240v AC input to a smooth and stabilised 24v DC output. Ref:G6 = 6 UNIT OUTPUT G12 = 12 UNIT OUTPUT G6R = 6 UNIT OUTPUT + RELAY G12R = 12 UNIT OUTPUT + RELAY POWER SUPPLY UNIT TYPE G12 240mm MAINS INPUT 240 V.A.C.l OUTPUT TO DAMPER 24 V.A.C.l E N L WARNING - ISOLATE MAINS SUPPLY BEFORE ENTERING 24v DC POWER OUT 87mm 240mm Uninterruptible Power Supply MAIN POWER SUPPLY 240v AC UNINTERUPTABLE POWER SUPPLY CELLS:- 27.6v DC MAX: TEST YEARLY MAINS INPUT: 240v AC OUTPUT TO DAMPERS 24v DC ON ON E N L 350mm Uninterruptible power supplies operating on a 240v AC input provide a smooth 24v DC output to power up to 12 dampers. Unlike standard power supplies however, in the event of a power failure, there will be an automatic changeover to in-built batteries without tripping the dampers providing continued power for a period of up to 1 hour. Ref:UPS6 = 6 UNIT OUTPUT UPS12 = 12 UNIT OUTPUT UPS6R = 6 UNIT OUTPUT + RELAY UPS12R = 12 UNIT OUTPUT + RELAY THIS UNIT IS DESIGNED TO SUPPLY UP TO 12 DAMPERS FOR UP TO 1 HOUR THE INTERNAL DRY-FIT CELLS DO NOT REQUIRE SERVICE OR ELECTROLYTE LEVEL TOPPING-UP. WARNING: TAKE CARE WHEN INSIDE THIS UNIT CELLS GIVE 100+ AMPS IF SHORTED OUT 24v DC POWER OUT 240mm 87mm Smoke Detectors Smoke Detectors are available for in duct or ceiling mounting and can link directly into Modes 5 & 6 or the output relay of the Power Supply units. Detectors are 24v DC Ionisation type Ref: In-duct 4 wire SD3 4 wire SD2 12 Test Data Pressure Drop BSRIA Report 15633/1 Casing Leakage Calculated performance at various damper settings Size tested: 500mm x 600mm Ductgard was tested and found to meet Class ‘C’ Classification BS EN 1751:1999. Leakage recorded at less than 0.1l/s/m² at 2000 Pa 50% 100 %O PE N 75% OP EN OP EN OP EN 100 25% Pressure Drop (Pa) 1000 Class C (BS EN 1751) 10 1 0.01 100 0.1 1 10 Velocity (m/s) Blade Leakage for a 500mm square Damper Blade Leakage 100mm x 100mm (smallest) unit as tested to BS EN 1366-2 500mm x 500mm unit as tested to BS EN 1366-2 1000mm x 1000mm (largest) unit as tested to BS EN 1366-2 500 Duct Pressure (Pa) Pressure Drop (Pa) 1000 300 3 ss la 1C 5 17 EN ult es R ted s Te 100 ss 5 17 EN s1 las 10 10 50 100 200 0 1000 5 Leakage (m3/hr/m2) Weight Chart (kg approx.) Square/Rectangular Spigot C 51 17 EN 100 2 la 1C 50 Leakage (l/s/m2) Weight Chart (kg approx.) Circular Spigot To include a HEVAC/ HVCA Installation Frame, apply the following multiplier: 1.4 Width (mm) Height (mm) 100 200 300 400 500 600 700 800 900 1000 Dia. (mm Weight (kg) Dia. (mm Weight (kg) 7.8 9.0 9.8 10.8 11.9 13.2 14.3 15.4 16.5 17.7 100 8.4 600 30.0 150 9.8 650 33.2 200 11.8 700 36.0 250 13.4 750 39.5 300 15.1 800 42.5 350 17.2 850 46.3 400 19.1 900 49.6 950 53.6 1000 57.1 100 200 300 400 500 600 700 9.0 10.3 11.6 12.9 14.2 15.5 10.5 11.9 13.4 14.9 16.3 17.8 11.3 12.8 14.4 16.0 17.6 19.1 12.4 14.1 15.8 17.6 19.3 21.0 13.6 15.4 17.3 19.1 21.0 22.8 15.4 17.7 20.0 22.3 24.6 26.9 16.7 19.3 21.8 24.3 26.9 29.4 18.1 20.8 23.6 26.4 29.1 31.9 19.4 22.4 25.4 28.4 31.4 34.3 20.7 23.9 27.2 30.4 33.6 36.8 800 16.8 19.3 20.7 22.7 24.6 29.3 31.9 34.6 37.3 40.0 450 21.3 900 18.1 20.8 22.3 24.4 26.5 31.6 34.5 37.4 40.3 43.2 500 23.4 1000 19.4 22.3 23.9 26.1 28.3 33.9 37.0 40.2 43.3 46.4 550 25.8 13 DUCTGARD Duct Mounting Smoke and Fire Control Dampers Operation & Maintenance Instructions TroubleShooting Operating and Maintenance Instructions All Ductgard units are tested before leaving the factory but should be test operated prior to commissioning to ensure correct operation. Quick and easy testing and reset procedures for each operational mode are detailed on their respective data pages in this brochure. In addition to their initial test however, being a fire safety product, it is also recommended that the units are test operated regularly thereafter . Test frequency will depend upon the damper environment but, in the absence of any other information, a maximum interval of 6 months is recommended. In addition an annual visual inspection is also advisable to permit cleaning and removal of any airborne contaminants which may affect the dampers operation. Note Since the drive, linkage, motors and electronic components on the ductgard units are ‘sealed for life’ there should be no requirement for periodic maintenance and spares are not normally required. Items such as reset levers and test keys however can be misplaced over time. In this event replacements are readily available from Head Office. For safety the damper blades should be closed on modes 9 and open on modes 10, before personally approaching them for inspection/cleaning. All Ductgard units are both inspected and tested before leaving our premises. Manufactured using maintenance free ‘sealed for life’ components there is no reason why they should not reach site in full working order and continue to function when installed providing that our fitting and wiring instructions have been adhered to. In the event of operational difficulties please contact our Head Office for on-line guidance and advice. Telephone: (01253) 766911 Ductgard units carry a full 1 year warranty from the date of delivery for all parts and labour. Gilberts Damper, Smoke and Fire Control Range Smokegard Door, Wall and Partition Mounted Smoke and Fire Dampers Firegard Curtain Fire Dampers 14 Series 54 Smoke Evacuation Damper Airgard Volume Control Dampers Series RD Iris Duct Damper Declaration of Performance: Ductgard Range 1. Unique identification code of the product-type: DUCTGARD fire damper (see table below for specific damper installation type) To be used in conjunction with walls/partitions/floors to maintain fire compartments in heating, ventilating and air conditioning Installations 2. Name, registered trade name or registered trade mark and contact address of the manufacturer as required under Article 11(5): Gilberts (Blackpool) Ltd, Clifton Road, Blackpool, FY4 4QT 3. System or systems of assessment and verification of constancy of performance of the construction product as set out in CPR, Annex V: System 1 4. In case of the declaration of performance concerning a construction product covered by a harmonized standard: BRE Global Ltd (0832) performed the determination of the product type on the basis of type testing (including sampling), type calculation, tabulated values or descriptive documentation of the product, the initial inspection of the manufacturing plant and of factory production control and continuous surveillance, assessment and evaluation of factory production control under system 1 and issued the certificate of constancy of performance of the factory production control (no. CPR-P0007). 5. Declared performance according to: EN 15650 (Ventilation for Buildings — Fire Dampers) Fire resistance according to EN 1366-2 and Classification according to EN 13501.3 and Harmonised Technical specification to EN 15650:2010: Range Type Supporting Construction Document Ref Classification 100x100mm - 1000x1000mm DUC/IF Blockwork Wall 287719F E240 (ve i -> o) S 100x100mm - 1000x1000mm DUC/SF Dry Wall 287719A E120 (ve i -> o) S 100x100mm - 1000x1000mm DUC/DF Dry Wall 287719B E120 (ve i -> o) S 100x100mm - 1200x1200mm DUC/AF Dry Wall 287719C E120 (ve i -<> o) S 100x100mm - 1000x1000mm DUC (No Frame) Dry Wall 287719E E120 (ve i -> o) S Nominal activation conditions/sensitivity according to ISO 10294-4: - sensing element load bearing capacity - sensing element response tine Pass Pass Response delay (response time) according to EN 1366-2: - closure time 50 Cycles Pass Operational reliability according to EN 1366-2: - cycling Pass Durability of response delay according to EN 1366-2: - sensing element response temperature and load bearing capacity Pass Durability of operational reliability according to EN 15650: - open and closing cycle 10.000 cycles Pass 15 DUCTGARD Duct Mounting Smoke and Fire Control Dampers Ordering Specification SERIES: DUC S 450 x 200 9 A FC/NC 15 TYPE: Square/Rectangular:..............S Circular...................................C SIZE (mm width x Height or Dia) MODE 9 or 10 CONTROL OPTION A or B FIXING OPTION Installation Frame (HEVAC)....IF Sleeve and Angle...SF Drop Rod...DF Angle Frame...AF NUMBER REQUIRED STANDARD POWER SUPPLIES: 6 Way.....................................................................G6 6 Way c/w output relay...........................................G6R 12 Way...................................................................G12 12 Way c/w/ output relay........................................G12R REMOTE INDICATORS: Single unit.........................................................SR1 MASTER MONITOR: 1 - 12 unit..........................................................SMM1 -12 plus per damper UNINTERRUPTIBLEPOWER SUPPLIES: 6 Way.....................................................................UPS6 6 Way c/w output relay...........................................UPS6R 12 Way...................................................................UPS12 12 Way c/w/ output relay........................................UPS12R SMOKE DETECTORS: 24V DC wire ionisation......................................SD2 Specification Damper Blades &Linkage Fire and smoke dampers shall be LPCB certificated and pass the test requirements stated in EN 1366-2 with an ES classification to EN 13501-3. Dampers to be fitted with an actuator that can respond to a smoke alarm signal to ensure closure at the first sign of smoke. Dampers to have opposed blade operation with interlocking double skinned blades on robust 19mm spindles for both resistance to fire and daily airflow exposure. The drive linkage shall be fully enclosed and set outside of the air stream for protection against damage and air contamination. Motors Casing Dampers to be motor operated with a failsafe thermal fuse set to operate at 72°C. The damper will close (or open) in less than 30 seconds. Stainless steel gaskets shall be provided at the top, bottom and sides to reduce casing leakage to below the levels stated in EN 1366-2. Damper casings shall be fully welded to meet the air tightness test requirements of HVCA specification DW144 to classes A, B and C at up to 1500Pa. Approvals The fire and smoke damper shall have a tested or assessed installation method that matches the requirement of the supporting construction into which it is built. GILBERTS Head Office and Works GILBERTS (BLACKPOOL) LTD Gilair Works, Clifton Road, Blackpool. Lancashire FY4 4QT. Telephone: (01253) 766911 Fax: (01253) 767941 e-mail: [email protected] Web: www.gilbertsblackpool.com Gilberts (Blackpool) Ltd reserve the right to alter the specification without notice. The information contained in this leaflet is correct at time of going to press © 2014. For our latest product data please visit www.gilbertsblackpool.com.
© Copyright 2026 Paperzz