Variable Refrigerant Flow Systems Ceiling 4-Way Air - Indoor Unit SUBMITTAL DATA 1 1/2 Tons - Model JXHX1852N Capacities: Cooling: Btu/h Heating: Btu/h 19,000 21,000 Cooling Mode Nominal Conditions: Indoor: °F WB/ °F DB Outdoor: °F DB Pipe Length: Feet Level Difference: Feet Sensible Heat Ratio: 0.74 Heating Mode Nominal Conditions: 80/67 95 25 0 Indoor: °F DB Outdoor: °F DB/ °F WB Pipe Length: Feet Level Difference: Feet 70 47/43 25 0 Full Load Amps Max. Overcurrent Protection (MOCP) Nominal Power Input - Heat(W) 1 15 25 / 25 Power Supply: V/PH/Hz. Minimum Circuits Amps (MCA):Amps Nominal Power Input - Cooling(W) Refrigerant and Piping: Refrigerant Type Metering Device (Electronic Expansion Valve) 208/230/1/60 15 30/33 410A EEV Liquid Piping (inches) Gas Piping (inches) 1/4 1/2 Turbo Direct Fan Motor Output: W Airflow rate (L/M/H) 50 450/495/565 Fan: Type: Drive: Sound Data: Sound Level (H/M/L) 5' below unit Weight:(lbs) 31/29/27 56 Coil: Coil Face Area:(sq. ft.) 3.88 Condensate: Drain Piping (OD) Inches 1.25 Number of Rows: 2 Submittal Data: Job Name: Location: Parts Warranty: One Year. Built in Drain Pump Washable Filters Wired or Wireless Remote Control Engineer: Submitted To: Submitted By: Reference: Approval: Date: Construction Unit #: Drawing # Form 121.00-PA8 (512) Supersedes: 121.00-PA8 (1110) © 2012 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53201 www.johnsoncontrols.com