FANs 637.5, 1637.5 Appendix Section Issue Date 0400 APPLICATION NOTE Appendix D: Multi-zone Hot and Cold Deck Reset Resetting Hot and Cold Deck Setpoints .............................................3 Introduction......................................................................................................... 3 Key Concepts...................................................................................................... 4 Hot and Cold Deck Reset ............................................................................................... 4 Zone Temperature vs. Zone Demand ............................................................................. 4 Parameter Names........................................................................................................... 5 Controlling the Zone Mixing Dampers ............................................................................ *6 Pneumatic Zone Temperature Control ............................................................................ 6 Digital Zone Temperature Control................................................................................ *12 Pneumatic Control Reset Based on Temperature ........................................................ *16 Digital Zone Control Reset Based on Temperature....................................................... 18 Procedure Overview ......................................................................................... 20 Detailed Procedures ........................................................................................*21 Defining the Analog Inputs (Pneumatic Zone Temperature Control) ............................ *21 Determining the Milliampere Range for Each Transducer (Pneumatic Control Reset Based on Temperature)....................................................... 23 Determining the Output High and Low Range for the Analog Inputs (Pneumatic Control Reset Based on Temperature)....................................................... 25 * Indicates those sections where changes occurred since the last printing. © 2000 Johnson Controls, Inc. Code No. LIT-6375195 www.johnsoncontrols.com 2 Appendix Appendix D: Multi-zone Hot and Cold Deck Reset Resetting Hot and Cold Deck Setpoints Introduction This application note is relevant when using an AHU (Air Handling Unit) to control a multi-zone air handler. It explains how to use the AHU to reset the hot deck and cold deck setpoints. This bulletin describes how to: • define the analog inputs (pneumatic zone temperature control) • determine the milliampere range for each transducer (pneumatic control reset based on temperature) • determine the output high and low range for the analog inputs (pneumatic control reset based on temperature) 3 4 Appendix Key Concepts Hot and Cold Deck Reset An Air Handling Unit (AHU) controller can control a multi-zone air handler. Typically, the AHU controller also resets the hot deck and cold deck setpoints, and controls the zone mixing dampers. This application note is relevant when using an AHU to control a multi-zone air handler. It explains how to use the AHU to reset the hot deck and cold deck setpoints. The hot deck is reset based on the zone with the greatest heating demand. The cold deck is reset based on the zone with the greatest cooling demand. Zone with greatest Heating demand controls the ... Hot Deck Zone 3 Zone 2 N.O. Zone 1 N.C. Resets the Cold Deck Setpoint Zone with greatest Cooling demand... zondemnd Figure 1: Zones with Greatest Cooling and Heating Demands Zone Temperature vs. Zone Demand Understanding the difference between zone temperature and zone demand is essential. Usage of the coldest zone and warmest zone may create some confusion. In common usage, the coldest zone would be the zone with the lowest temperature. However, the coldest zone may not be the zone with the greatest heating demand. Example Zone 1 is in the warehouse, and the occupants of Zone 1 have set their thermostat to 60°F. The temperature in Zone 1 is approximately 58°F. Zone 1 is technically the coldest zone. However, the zone temperature is 2°F below the zone setpoint, so Zone 1 has only a 2°F demand for heating. 5 Appendix D: Multi-zone Hot and Cold Deck Reset Zone 2 is the accounting office, and the thermostat is set at 74°F. The current temperature is 68°F, which is well below the setpoint. Zone 2 has a 6°F demand for heating. Although it is not the coldest zone, Zone 2 has the greatest demand for heating. In Zone 1, the thermostat is set to 60°F 60 and the temperature is 58°F. In Zone 2, Zone 1 is the COLDEST zone, but ... the thermostat is set to 74°F 74 and the temperature is 68°F. Zone 2 has the greatest heating demand. htgdemnd Figure 2: Zone Temperature vs. Zone Demand Parameter Names The multi-zone applications use parameters that contain the phrases coldest zone and warmest zone. This application note describes how to define these parameters, so it refers to the parameters by their given names. Table 1: Parameter Names and Meanings Parameter Name In this Application Note, Refers to: Coldest Zone Zone with greatest heating demand Warmest Zone Zone with greatest cooling demand This application performs reset based on zone demand, which is the difference between the zone setpoint and the zone temperature. Zone Demand = Zone Temperature - Zone Setpoint Reset should not be based solely on zone temperature or zone setpoint. 6 Appendix Table 2: Zone Temperature vs. Zone Demand Zone Number Zone Temperature Zone Setpoint Zone Demand Heating or Cooling 1 58 60 -2 Heating 2 68 74 -6 Heating 3 74 72 2 Cooling 4 77 72 5 Cooling 5 72 72 0 none Controlling the Zone Mixing Dampers Each zone has its own set of zone mixing dampers. A zone mixing damper modulates the supply air to that zone based on the zone thermostat. The zone with the greatest demand for cooling has its zone mixing damper fully open to the cold deck. The zone with the greatest demand for heating has its zone mixing damper fully open to the hot deck. All other zones must mix the hot and cold deck air streams to satisfy the load demands in that particular zone. Depending on the job, zone control may be accomplished either with pneumatic or digital controllers. Each method is first discussed in terms of pneumatics. For the digital application, only the necessary application information is given. Reading both pneumatic and digital sections may be required for a full understanding of the digital application. Pneumatic Zone Temperature Control A pneumatic loop with a T-4002 thermostat controlling the zone mixing damper is one option for zone temperature control. The supply pressure to all zone thermostats is reliably 19 psig. All zones in this application have mixing dampers with a nominal spring range of 8 to 13 psig. Spring range shift is assumed to be negligible and is ignored in the calculations. Identifying the Zones with the Largest Demands A T-4002 thermostat produces a 0-19 psig signal, based on the difference between the zone temperature and the zone setpoint. The output is approximately 19 psig on a call for full cooling, and 1 psig for full heating. The output varies linearly between the two endpoints. The exact values vary depending upon the calibration. Appendix D: Multi-zone Hot and Cold Deck Reset 7 19 Cold Deck Setpoint Reset Typical Output (psig) 13 Zone Mixing Dampers 8 Hot Deck Setpoint Reset 1 - 0 + Zone Temperature Minus Setpoint T4002 Figure 3: Zone Temperature vs. T-4002 Thermostat Output Pneumatic signals from each zone thermostat are fed into a C-2220 high/low signal selector. The C-2220 selects the largest and smallest pneumatic signals. The largest pneumatic signal represents the zone with the largest cooling demand. The smallest pneumatic signal is the zone with the largest heating demand. Two pneumatic-to-electric transducers are required if the two pneumatic signals produced by the C-2220 are to become analog inputs on the AHU controller. The FM-IAP101-0 is a suitable transducer. The pneumatic signals are converted into 4 to 20 mA signals. The current signals can then be fed into the AHU controller, as shown in Figure 4. The AHU controller resets the hot deck and cold deck setpoints, based on these two inputs. 8 Appendix Mixing Damper Control Zone Mixing Damper (8-13 psig) Pneumatic Zone Controller 19 Zone Mixing Damper Signal Pneumatic Output (psig) 1-19 psig 1 Zone Temperature minus Zone Setpoint Zone Setpoint and Zone Temperature AHU Controller Hot and Cold Deck Setpoint Reset High Signal 1-19 psig H L Zone A Zone .. B . Zone Y Zone Z Pneumatic -toElectric Transducer 4-20 mA AI-7 Cold Deck Setpoint Cold Deck Setpoint Cooling Valve Signal Hot Deck Setpoint Heating Valve Signal Cold DeckReset Band Signal Low Signal 1-19 psig C-2220 High/Low Signal Selector Pneumatic -toElectric Transducer 4-20 mA AI-8 Hot Deck Setpoint Hot DeckReset Band Signal AHUMULT Figure 4: Multi-zone Hot and Cold Deck Reset HVAC PRO can scale each of these two current inputs to match the sensitivity range of the zone thermostat, such as a T-4002. The first step in scaling the inputs is described in the Defining the Parameters topic in this section. Hot and Cold Deck Reset Figure 5 shows the output range for a pneumatic zone controller, such as a T-4002. The range is divided into thirds. The upper third is used to reset the cold deck setpoint. The lower third is used to reset the hot deck setpoint. The middle third is used to modulate the zone mixing damper. Appendix D: Multi-zone Hot and Cold Deck Reset 9 19 Cold Deck Reset 13 Zone Mixing Damper 8 Hot Deck Reset 1 Output of the Zone Controller (psig) SEQUENCE Figure 5: Output from Pneumatic Zone Controller On zones other than warmest and coldest, the pneumatic signal will be in the middle third, between 8 and 13 psig. This signal tells the zone mixing damper what mixture of hot deck and cold deck air to supply to the zone. If the zone temperature rises far enough above the zone setpoint, the pneumatic zone controller calls for full cooling. The zone mixing damper is fully open to the cold deck. At this point, the signal from the pneumatic zone controller is used to reset the cold deck setpoint. If the current cold deck setpoint cannot meet the cooling needs, the cold deck setpoint should be lowered. This procedure corresponds to the upper one third of the pneumatic sequence. If the zone temperature falls far enough below the zone setpoint, the pneumatic zone controller calls for full heating. The zone mixing damper is fully open to the hot deck. At this point, the signal from the pneumatic zone controller is used to reset the hot deck setpoint. If the current hot deck setpoint cannot meet the heating needs, the hot deck setpoint should be raised. This procedure corresponds to the lower one third of the pneumatic sequence. Choosing a Method for Scaling the Analog Inputs There are two methods for defining the zone limits and reset bands in the AHU controller. 1. Scaling the Analog Inputs into Psig (Demand) This method allows each zone to have its own setpoint, plus the multi-zone unit still maintains true zone load sequencing of the zone mixing damper, as well as the cold and hot deck setpoints. 2. Scaling the Analog Inputs into Temperature (% Demand) This method is only valid when the setpoints of all zones are identical (fixed). Refer to Zone Temperature vs. Zone Demand at the beginning of this document. 10 Appendix Defining the Parameters The first step is defining the parameters for hot and cold deck reset in HVAC PRO. The following two tables list the parameters and their appropriate values. Note: The AHU Applications Application Note (LIT-6375080) in the HVAC PRO User’s Manual (FAN 637.5) has a description of each parameter. Table 3: Defining the Hot Deck Reset Schedule Parameters Parameter Long Name Value Is Obtained from... Determines... Hot Deck RBand 20.00°F normal range for hot deck output range of hot deck reset schedule lower one third of sequence bar in Figure 5 input range of hot deck reset schedule Hot Deck Low Lim 75.00°F Cld Zone RBand - 7.00 psig* Cld Zone Hi Lim 8.00 psig * The minimum signal produced by a C-2220 signal selector is 1 psig by design. Table 4: Defining the Cold Deck Reset Schedule Parameters Parameter Long Name Value Is Obtained from... Determines... Cold Deck RBand 20.00°F normal range for cold deck output range of cold deck reset schedule upper one third of sequence bar in Figure 5 input range of cold deck reset schedule Cold Deck Low Lim 55.00°F Hot Zone RBand - 6.00 psig Hot Zone Hi Lim 19.00 psig* *The maximum signal produced by a C-2220 signal selector is 19 psig. The deck reset bands and limits are in degrees. The zone reset bands and limits are in psig. The analog inputs are scaled in units of psig. The range of each analog input is determined by the zone low/high limit and the zone reset band. The range for the cold zone is from 1.0 to 8.0 psig. The range for hot zone is from 13.0 to 19.0 psig. The range of the cold zone becomes the input range for the hot deck reset schedule. The range of the hot zone is used as the range of inputs for the cold deck reset schedule. The output range of the reset schedules is determined by the deck’s low or high limit and the deck reset band. The range for the hot deck setpoint is 75.0 to 95.0. The range for the cold deck setpoint is 55.0 to 75.0. Appendix D: Multi-zone Hot and Cold Deck Reset 75 Cold Deck Setpoint ( F) 55 13 19 Analog Input Range (psig) (N.C. to Cooling) cdreset Figure 6: Cold Deck Reset Schedule 95 Hot Deck Setpoint ( F) 75 1 8 Analog Input Range (psig) (N.O. to Heating) hdreset Figure 7: Hot Deck Reset Schedule 11 12 Appendix Input Range The range for the analog inputs must be determined so that is does not become unreliable. To review, each zone’s controller is producing a pneumatic signal. This signal could be any value in the output range of the zone controller. From all of these zone signals, the C-2220 selects the lowest and highest signals. Again, the output range of the C-2220 could be any value in the output range of the zone controller. The two outputs from the C-2220 are transduced into a current signal. The output range of the transducer determines the range for the analog input. An analog input will become unreliable if the signal is less than the input range low value or greater than the input range high. These two values must be set to the low and high ends of the transducer’s output. Digital Zone Temperature Control A digital controller, such as a UNT (Unitary) using a 0 to 10 VDC signal, could be used to control the zone mixing damper. Since a generic input/output point multiplexer UNT controller is capable of sideloops, we could control two zones with a two analog output controller. In this application, we define two side loops. They are AI (Analog Input) to AO (Analog Output), PI (Proportional plus Integral) control with reset schedule. Each controls a zone damper. The reset input is the setpoint potentiometer and is used to provide a remote setpoint for each loop. Most likely the TE-6400 room sensor would be used for the room element and setpoint potentiometer. The temporary occupied/boost modes would not be usable in this application. Table 5 and Table 6 show the parameters necessary in HVAC PRO configuration of remote zone setpoints. Table 5: Remote Setpoint AI Ranges Value Input Range Output Range Low 0.0 ohms 18°C (65.0°F) High 1660.0 ohms 29°C (85.0°F) Table 6: Reset Schedule Values Input/Output Value Input 1 18°C (65.0°F) Input 2 29°C (85.0°F) Output 1 18°C (65.0°F) Output 2 29°C (85.0°F) Appendix D: Multi-zone Hot and Cold Deck Reset 13 Identifying the Zones with the Largest Demands Each side loop provides a zone demand for heating or cooling as indicated by an analog output value of 0 to 100. A zero indicates that full heating is required and a value of 100 indicates that full cooling is required. Further, since these loops are proportional plus integral, setpoint error could be eliminated over time by integration biasing of the output signal to the limits of 0 and 100. The tuning values of each loop should be similar so that one zone would not dominate the heating or cooling demand. 100.0 Cold Deck Reset 66.6 Zone Mixing Dampers 33.3 Hot Deck Reset 0.0 - 0 + Zone Temperature Minus Setpoint ZONETEMP Figure 8: Zone Temperature vs. Controller Output Signal Selection As in the pneumatic applications, define the AHU controller as a dual duct with hot/cold deck reset. HVAC PRO defines two analog inputs as the coldest and warmest zone temperatures. The default for these inputs are resistive nickel, they must be changed to voltage type inputs. Networked applications would use GPL, JC-BASIC, or signal selection to choose the greatest heating and cooling demands. Alternately, standalone applications can use a UNT to signal select the greatest heating and cooling demand for up to six zones. Each zone controller output (6-10 VDC) is wired in parallel to the zone mixing damper actuator and an AI of the UNT acting as a signal selector. 14 Appendix AI-1 Zones Temperature AI-2 Zone 1 Setpoint SL-1 AI/AO with Reset UNT 1 AO-1 Zone 3 AO-1 Zone 1 AO-2 Zone 2 AO-2 Zone 4 AO-1 Zone 5 UNT 2 AO-2 Zone 6 UNT 3 TE-6400 Room Sensor Zone 1 (Typical of 6) AI-6 AI-5 AI-4 AI-3 AI-2 AI-1 Zone 1 Damper Actuator (Typical of 6) AHU SL-1 MIN SL-2 MAX Coldest Zone AI-7 AO-1 Coldest Warmest Zone AI-8 AO-2 Warmest UNT 4 ditgwire Figure 9: Application Using UNTs for Zone and Signal Selection for AHU In the UNT designated for signal selection, define six analog inputs as voltage according to Table 7. Table 7: Signal Selection AI Definition Value Input Range Output Range Low 0.0 VAC (Volts Alternating Current) 0.0% High 10.0 VAC 100.0% In this same UNT, define the AOs as coolest and warmest. They default to voltage. 0-100% command gives 0-10 volts. See Table 8. Table 8: Analog Output Definition for Deck Setpoint Reset Command Range Voltage 0.0 % Command 0.0 VAC 100.0 % Command 10.0 VAC Appendix D: Multi-zone Hot and Cold Deck Reset 15 Define two multiple AIs to AO side loops, choosing all of the used AIs as the inputs. The first is defined as input conditioning: Select minimum value, with the output going to AO-1, previously defined as the coldest zone. You must chose a control logic, so select reset schedule and set the input1/output1 to 0.0 and input2/output2 to 100.0. The second is defined as input conditioning: Select maximum value, with the output going to AO-2, previously defined as the warmest zone. Set up the control logic parameters the same as the first side loop. The two analog outputs of the side loops defined in this UNT represent the greatest heating and cooling demand of zones, and serve as inputs to the AHU controller on the multi-zone unit. The bottom one third of the signal, 0 to 3.3 volts, will reset the hot deck temperature, middle one-third, 3.3 to 6.6 volts, will throttle the zone mixing damper, and top one-third, 6.6 to 10.0 volts will reset the cold deck temperature. In HVAC PRO, definition of hot and cold deck reset schedules (for the AHU) is a bit unusual. The cold zone low limit is not temperature. Rather, it is the voltage that is applied to the actuator when it is fully open to the hot deck, i.e., 3.3 volts. The cold zone range is 3.3 volts as well. The hot zone high limit is 6.6 volts and has a range of 3.4 volts. Note that the (filename) .PRN print out shows these as temperatures. By following this procedure, this multi-zone now has load based deck temperature reset. The first step is defining the parameters for hot and cold deck reset in HVAC PRO. Table 9 and Table 10 list the parameters and their appropriate value. The deck reset bands and limits shown in Table 9 and Table 10 are in degrees Fahrenheit. The zone reset bands and limits are in % of the command sent to the zone actuator. The analog inputs are scaled in units of %. Note: AHU Applications Application Note (LIT-6375080) in the HVAC PRO User’s Manual (FAN 637.5) has a description of each parameter. Table 9: Defining Hot Deck Reset Schedule Parameters Parameter Long Name Value Is Obtained from... Determines... Hot Deck RBand 20.0°F Hot Deck Low Lim 75.0°F normal range for hot deck output range of hot deck reset schedule Cld Zone RBand 33.3% Cld Zone Hi Lim 33.3% lower one third of sequence bar in Figure 11 input range of hot deck reset schedule 16 Appendix Table 10: Defining Cold Deck Reset Schedule Parameters Parameter Long Name Value Is Obtained from... Determines... Cold Deck RBand 20.0°F Cold Deck Low Lim 55.0°F normal range for cold deck output range of cold deck reset schedule upper one third of sequence bar in Figure 5 input range of cold deck reset schedule Hot Zone RBand 33.3% Hot Zone Hi Lim 100.0% Pneumatic Control Reset Based on Temperature The analog inputs are defined as units of temperature, vs. scaling in psig as in the Pneumatic Zone Temperature Control and Digital Zone Temperature Control topics in this section. The analog input, in degrees, is used to reset the hot deck and cold deck setpoints. Optional Procedure This section describes the complete procedure for scaling the inputs into units of temperature. This provides a good tool for learning how the analog inputs are scaled. You can also use a BASIC program to perform this task. This program runs under BASIC on an IBM®-compatible PC (Personal Computer), and automatically does all of the scaling of the analog inputs into units of temperature. The program can be retrieved from The Advisor online network. The filename is PNEUAHMZ.EXE. Required Information The following information must be known to scale the analog input into units of temperature: ! cold zone high limit ! cold zone reset band ! hot zone high limit ! hot zone reset band ! milliamperes that define zone limits and reset bands Parameters in the Print File The first four items in the previous list can be viewed in the HVAC PRO print file (filename.prn). It is created and updated when a configuration file is saved in HVAC PRO and the Options/Generate PRN on Save is selected. Default values for these four items are shown in Table 11. Appendix D: Multi-zone Hot and Cold Deck Reset 17 Table 11: Parameters Obtained from the Print File Long Name Type Address Default Cld Zone Hi Lim ADF 138 72.00°F Cld Zone RBand ADF 139 -4.00°F Hot Zone Hi Lim ADF 142 78.00°F Hot Zone RBand ADF 143 -6.00°F Selecting a Range to Prevent an Unreliable Input The pneumatic signal could be any value in the output range of the zone controller. It is not confined to the range of pressure above and below the zone mixing damper’s spring range. The maximum and minimum pneumatic signals that the zone controller could produce are determined. Then, the maximum and minimum outputs that the transducer could produce are determined. Since the transducer output is the analog input on the AHU controller, the output low range and output high range values are designed so the input value never goes out of range. This prevents the input from becoming unreliable. The input may become unreliable if the range is any smaller. After calculating and entering the new values for low and high range, an unreliable condition could only be the result of a component failure, such as a transducer malfunction. 18 Appendix Digital Zone Control Reset Based on Temperature Required Information The following information must be known to scale the analog input into units of temperature: ! cold zone high limit ! cold zone reset band ! hot zone high limit ! hot zone reset band ! voltages that define zone limits and reset bands Parameters in the Print File The first four items in the previous list can be viewed in the HVAC PRO print file (filename.prn). It is created and updated when a configuration file is saved in HVAC PRO and the Options/Generate PRN on Save is selected. Default values for these four items are shown in the following table: Table 12: Parameters Obtained from the Print File Long Name Type Address Default Cld Zone Hi Lim ADF 138 72.00°F Cld Zone RBand ADF 139 -4.00°F Hot Zone Hi Lim ADF 142 78.00°F Hot Zone RBand ADF 143 -6.00°F Item 5 is determined by the following: This application, as in the previous method that relies on demand, uses UNT controllers for both the zone control and the coldest and warmest zone selection. The advantage of this application over the demand method is that the zone dampers could be modulated using incremental dampers. Note: Do not use the remote setpoint so that all zone setpoints can be set to identical values. This is because the selection UNT selects the coldest and warmest zones based on actual zone temperature as opposed to the control signal. Appendix D: Multi-zone Hot and Cold Deck Reset 19 All of the zone temperature AIs are paralleled with the six AIs on the selection UNT. Sensor sharing is accomplished in the selection UNT by defining the AIs as Resistive Nickel (R-NI) and then setting the AI switches for 2 volts. Define two multiple AIs to AO side loops, choosing all of the used AIs as the inputs. The first is defined as input conditioning: Select minimum value, with the output going to AO-1, previously defined as the coldest zone. You must choose a control logic, so select reset schedule and set the input1/output1 to 65 and the input2/output2 to 85. The second is defined as input conditioning: Select maximum value, with the output going to AO-2, previously defined as the warmest zone. Set up the control logic parameters the same as the first side loop. 20 Appendix Procedure Overview Table 13: Resetting Hot and Cold Deck Setpoints To Do This Follow These Steps: Define the Analog Inputs (Pneumatic Zone Temperature Control) Double-click on AI-7 and verify that its long name is coldest zone. Change the sensor type to Current (C). Double-click on AI-8 and verify that it is the warmest zone, and make it a current input. For an FM-IAP101, set the input range low to 4 mA and input range high to 30 mA. Enter the remainder of the analog input definitions as shown in Table 14. Determine the Milliampere Range for Each Transducer (Pneumatic Control Reset Based on Temperature) Determine the pressure ranges below and above the zone damper for the application. Determine the sensitivity of the transducer. Calculate the output range (in milliamperes) for the coldest and warmest zones. Determine the Output High and Low Range for the Analog Inputs (Pneumatic Control Reset Based on Temperature) Use the algebraic equation for a straight line to determine the high and low range for the analog inputs. Determine sensitivity for the coldest zone in mA/degree by using the milliampere range. Use a linear equation to scale the input into engineering units. Solve the equation for the analog input by substitution. Determine the sensitivity for the warmest zone in mA/degree by using the milliampere range. Appendix D: Multi-zone Hot and Cold Deck Reset 21 Detailed Procedures Defining the Analog Inputs (Pneumatic Zone Temperature Control) Note: These procedures are performed with the dual path hot/cold deck reset configuration file open in HVAC PRO. To define the analog inputs: 1. Double-click on AI-7 and verify that its long name is coldest zone. Change the sensor type to Current (C), as shown in Figure 10. 2. Double-click on AI-8 and verify that it is the warmest zone, and make it a current input. Sensor type is Current (C). Input Range Low and Input Range High Must be changed to 4.00. aimod10 Figure 10: Input Range Note: Because these are current inputs, the input ranges low and high are defaulted to 0.00 and 20.00 milliamperes, respectively. This default range is suitable for a pressure-toelectric transducer, which produces a 0-20 mA current. To use a transducer that produces 4-20 mA output, such as an FM-IAP101, change the input range low to 4.00. 3. For an FM-IAP101, set the input range low to 4 mA and input range high to 30 mA. The conversion remains correct for the transducer even though the supply pressure only reaches 19 psig. 4. Enter the remainder of the analog input definitions as shown in Table 14. 22 Appendix Table 14: Defining the Analog Inputs Parameter AI7 Value AI8 Long Name Coldest Zone Hottest Zone Sensor Type Current (C) Current (C) Decimal Precision 1 1 Units psig psig Filter Value 1 1 Input Range Low (mA) 4.0 4.0 Input Range High (mA) 20.0 20.0 Output Range Low (psig) 0.0 0.0 Output Range High (psig) 25.0 25.0 Enable Alarm N N Since we do not know the calibration of each T-4002, it is more practical to display the values in psig. In this example, all of the T-4002s are direct acting, so the highest pressure is the warmest zone and the lowest pressure is the coolest zone. Appendix D: Multi-zone Hot and Cold Deck Reset 23 Determining the Milliampere Range for Each Transducer (Pneumatic Control Reset Based on Temperature) Note: Refer to the example application described earlier in this document for details of the pneumatic sequencing and transducer type. To determine the milliampere range for each transducer: 1. Determine the pressure ranges below and above the zone damper for the application. The ranges for this example are shown in Table 15. 19 Cold Deck Reset 13 Zone Mixing Damper 8 Hot Deck Reset 1 Output of the Zone Controller (psig) SEQUENCE Figure 11: Pressure Ranges for Reset Signals Table 15: Pressure Ranges for Reset Signals Signal Range (psig) Coldest Zone Reset Signal 1 to 8 Warmest Zone Reset Signal 13 to 19 2. Determine the sensitivity of the transducer. The equation for the sensitivity of a transducer is: Sensitivity (mA/psig) = Transducer’s Output Range (mA) Transducer’s Input Range (psig) Applying this equation for sensitivity to the FM-IAP101 (a 4-20 mA transducer) yields the following calculations: Transducer Output Range = (20-4) mA = 16 mA Transducer Input Range = (25-0) psig = 25 psig Sensitivity = 16 mA/25 psig Sensitivity = 0.64 mA/psig 24 Appendix 3. Calculate the output range (in milliamperes) for the coldest and warmest zones. The following equation uses the pneumatic signal and the transducer sensitivity to determine the transducer output, in milliamperes: (Signal Sensitivity) + 4 mA = Output (mA) where signal is the pneumatic signal in psig The pneumatic signals from Table 15 and the previously calculated sensitivity are substituted into the above equation. Table 16: Milliampere Output for the Coldest Zone Reset Signal Signal (psig) Sensitivity Signal Sensitivity + 4.0 mA Output 1 0.64 0.64 4.0 4.64 8 0.64 5.12 4.0 9.12 The range is determined by the difference between the high and low outputs, in milliamperes. The milliampere range for the coldest zone reset signal is: Coldest Zone Range = High Output - Low Output Coldest Zone Range = (9.12-4.64) mA Coldest Zone Range = 4.43 mA Table 17: Milliampere Output for the Warmest Zone Reset Signal Signal (psig) Sensitivity Signal Sensitivity + 4.0 mA Output 13 0.64 8.32 4.0 12.32 19 0.64 12.16 4.0 16.16 The milliampere range for the warmest zone reset signal is: Warmest Zone Range = High Output - Low Output Warmest Zone Range = (16.16-12.32) mA Warmest Zone Range = 3.84 mA Appendix D: Multi-zone Hot and Cold Deck Reset 25 Determining the Output High and Low Range for the Analog Inputs (Pneumatic Control Reset Based on Temperature) To determine the high and low range for the analog inputs: 1. Use the algebraic equation for a straight line to determine the high and low range for the analog inputs. The analog input processing follows the standard linear equation: y = mx + b Y represents the value of the analog input, which has units of degrees temperature. A correlation must be made between the zone thermostat’s pneumatic output signal, in psig, and the transducer’s current output signal, in milliamperes. This correlation determines the zone limit temperature. The first two columns in Table 18 and Table 19 use results from Table 16 and Table 17. The Limit column is determined by the cold zone low limit, found in the .PRN file. The coldest zone limit and the warmest zone limit can be the same temperature value but must not overlap. Table 18: Coldest Zone Signal (psig) 8 Output Limit 9.12 72 Output Limit 12.32 72 Table 19: Warmest Zone Signal (psig) 13 26 Appendix 2. Determine sensitivity in mA/degree by using the milliampere range. The sensitivity of the transducer in this example is 0.64 mA/psig. Sensitivity (mA/degree) = milliampere range absolute value of coldest zone reset band Sensitivity = (9.12 - 4.64)/4°F Sensitivity = 4.43 mA/4°F Sensitivity = 1.1075 mA/degree 3. Use a linear equation to scale the input into engineering units. The slope m of that equation is the reciprocal of sensitivity, or: m = 1/sensitivity m = 1/1.1075 mA/degree m = 0.9029 degree/mA 4. Solve the equation for the analog input by substitution. By doing this, you will determine the effective output low range and output high range of the analog input. B is the y-intercept of the value y when x equals zero. y = mx + b 72.0°F = (0.9029 degree/mA * 9.12 mA) + b Solving for b: b = 63.7656°F 80 72 Y ( F) 70 63.8 60 0 5 10 9.12 X (mA) CLDZN2 Figure 12: Coldest Zone Appendix D: Multi-zone Hot and Cold Deck Reset 27 The output low range for the coldest zone is: y = (0.9029 degree/mA * 4 mA) + 63.7656°F y = 67.4°F The output high range for the coldest zone is: y = (0.9029 degree/mA * 20 mA) + 63.7656°F y = 81.8°F Table 20: Coldest Zone Output Range Signal (psig) Output (mA) Value Low 0 4 67.4 High 25 20 81.8 5. Determine the sensitivity in mA/degree by using the milliampere range. The sensitivity of the transducer in this example is 0.64 mA/psig. Sensitivity (mA/degree ) = milliampere range absolute value of warmest zone reset band Sensitivity = (16.16 - 12.32) mA/6°F Sensitivity = 3.84 mA/6°F Sensitivity = 0.64 mA/degree m = 1/sensitivity m = 1/0.64 mA/degree m = 1.5625 degree/mA Solve for b: y = mx + b 72.0°F = (1.5625 degree/mA* 12.32 mA) + b Solving for b: b = 52.75°F 28 Appendix 70 72 Y ( F) 60 52.75 50 0 5 10 15 12.32 X (mA) wrmzn2 Figure 13: Warmest Zone The output low range for the warmest zone is: y = (1.5625 degree/mA * 4 mA) + 52.75°F y = 59.0°F The output high range for the warmest zone is: y = (1.5625 degree/mA * 20 mA) + 52.75°F y = 84.0°F Table 21: Warmest Zone Output Range Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 Signal (psig) Output (mA) Low 0 4 Value 59.0 High 25 20 84.0 www.johnsoncontrols.com Release 8.0 Printed in U.S.A.
© Copyright 2025 Paperzz