ngc-40-bridge - Pentair Thermal Management

NGC-40-BRIDGE
CONTROL AND MONITORING MODULES FOR USE WITH THE RAYCHEM NGC-40 SYSTEM
INSTALLATION INSTRUCTIONS
DESCRIPTION
The NGC-40-BRIDGE module provides the interface between
a panel's internal CAN-based network and upstream devices.
Multiple communications ports are supported, allowing serial and
Ethernet connections to be used with external devices.
A
B
TOOLS REQUIRED
• Small flat-blade screwdriver
C
ADDITIONAL MATERIALS REQUIRED
• Power supply 24 Vdc @150 mA per NGC-40-BRIDGE
• Custom built CAN cables with RJ-45 connections
D
KIT CONTENTS
ItemQty Description
Shown
not to scale
APPROVALS
Hazardous Locations
Class I, Div. 2, Groups A,B,C,D T4
Class I, Zone 2, AEx nC IIC T4 IP20
Ex nL IIC T4 X
3128486 –40˚C ≤ Ta ≤ +65˚C
Conforms to:
FM Class Number 3600 (11/98)
FM Class Number 3611 (10/99)
ANSI/UL STD. 60079-15-2009
UL STD. 61010-1
A
1
NGC-40-BRIDGE module
B
2
CAN bus termination block
C
2
RS-485 termination resistors 120 Ω – 1% - 1/4 watt
D
1
NGC-40-BRIDGE serial cable TTC# 10332-005
PTM# 10392-043
Certified to:
CAN/CSA STD. C22.2 No. 213-M1987 (R2004)
CAN/CSA STD. C22.2 No. 61010-1:2004
EN 61010-1 (2001)
CAN/CSA STD. E60079-15:02 (R2006)
(Russia, Kazakhstan, Belarus)
For other countries contact your
local Pentair representative.
WARNING:
This component is an electrical device that must be installed
correctly to ensure proper operation and to prevent shock or fire.
INDUSTRIAL HEAT TRACING SOLUTIONS
For technical support, call Pentair Thermal Management at
(800) 545-6258.
EN-RaychemNGC40Bridge-IM-H58089 02/16
1 / 10
GENERAL
Supply voltage
Internal power consumption
Ambient operating temperature
Ambient storage temperature
Environment
Max. altitude
Humidity
Mounting
24 Vdc ± 10%
< 3.6 W per NGC-40-BRIDGE
–40ºC to 65ºC (–40ºF to 149ºF)
–40ºC to 75ºC (–40ºF to 167ºF)
PD2, CAT III
2,000 m (6,562 ft)
5 – 90% noncondensing
Din Rail – 35 mm
ELECTROMAGNETIC COMPATIBILITY
Emissions
Immunity
EN 61000-6-3 Emission standard for residential, commercial and light industrial environments
EN 61000-6-2 Immunity standard for industrial environments
COMMUNICATIONS COM1, COM2
Type
Cable
Length
Quantity
Data rate
Data bits
Parity
Stop bits
Tx delay
Protocol
Connection terminals
2-wire RS-485
One shielded twisted pair
1,200 m (4,000 ft) maximum
Up to 255 devices per port
9600, 19.2K, 38.4K, 57.6K, 115.2K baud
7 or 8
None, even, odd
0, 1, 2
0 – 5 sec.
Modbus RTU or ASCII
Wago cage clamp terminals
COMMUNICATIONS COM3
Type
Cable
Length
Data rate
Data bits
Parity
Stop bits
Tx delay
Protocol
Connection terminals
RS-232
Custom TTC# 10332-005
15 m (50 ft) maximum
9600, 19.2K, 38.4K, 57.6K, 115.2K baud
7 or 8
None, even, odd
0, 1, 2
0 – 5 sec.
Modbus RTU or ASCII
RJ-11
CAN NETWORKING PORT
Type
Connection
Protocol
Topology
Length
Quantity
Address
2-wire isolated CAN-based peer-peer network. Isolated to 300 V.
Two 8-pin RJ-45 connectors (both may be used for Input or Output connections)
Proprietary NGC-40
Daisy chain
10 m (33 ft) maximum
Up to 80 CAN nodes per network segment
Unique, factory assigned
ETHERNET
Type
Length
Data rates
Protocol
Connection terminals
10/100 BaseT Ethernet network
100 m (328 ft)
10 or 100 MB/s
Modbus/TCP
Shielded 8-pin RJ-45 connector on front of module
PROGRAMMING AND SETTING
LED indicators
Alarm conditions
Configuration switch
CONNECTION TERMINALS
Wiring terminals
CAN networking and module power
RESET, Configuration lost, CAN communications fail
SET/RUN slide switch on front of module
Cage clamp, 0.5 to 2.5 mm2 (24 to 12 AWG)
Two RJ-45s, one each IN and OUT. Provides CAN bus signals and +24 Vdc power.
HOUSING
Size
INDUSTRIAL HEAT TRACING SOLUTIONS
45.1 mm (1.78 in) wide x 87 mm (3.43 in) high x 106.4 mm (4.2 in) deep
EN-RaychemNGC40Bridge-IM-H58089 02/16
2 / 10
System Components
45.1 mm (1.78 in)
45.1 mm (1.78 in)
45.1 mm (1.78 in)
45.1 mm (1.78 in)
RESET
Front
Top
A. Wiring Terminals
COM 1 (485) + in
2
COM 1 (485) + out
3
COM 2 (485) + in
4
COM 2 (485) + out
5
COM 1 (485) – in
6
COM 1 (485) – out
7
COM 2 (485) – in
8
COM 2 (485) – out
9 – 12
Not used
Bottom
Back
C. Communication Slide Switch
TerminalsFunction
1
87 mm (3.43 in)
87 mm (3.43 in)
106.4 mm (4.2 in)
NGC-40 BRIDGE MODULE
D. RS-232 Port
Status: Indicates status of RS-232 port
Top LED
Off
No activity
Green (flashing) Receipt of data packet
Bottom LED
Off
No activity
Yellow (flashing) Transmit of data packet
E. Ethernet Port
Status: Indicates status of the LAN
B. Status LEDs
Status: Indicates status of the module
Off
No power
GreenOK/Normal
Yellow (flashing) Configuration mode
Red
(flashing) Internal fault
Network: Indicates CAN network activity
Off
No link detected
Green Link OK, receive data packets
Yellow Transmit data packets
Red
(flashing) Network error
Top LED
Off
No LAN detected
Green ON, LAN detected
Bottom LED
Off
No LAN activity
Yellow (flashing) LAN activity (data packet)
F. CAN Bus/Module Power
G. Reset Button
COM: Indicates COM1 & 2 (RS-485) activity
Off
No activity
Green (flashing) Receipt of data packet
Yellow (flashing) Transmit of data packet
INDUSTRIAL HEAT TRACING SOLUTIONS
EN-RaychemNGC40Bridge-IM-H58089 02/16
3 / 10
Mounting the NGC-40-BRIDGE
REMOVAL: Push the module upwards
to disengage the clip, then rotate the
module toward you.
Each NGC-40-BRIDGE mounts on a DIN 35 rail.
MOUNTING: Insert the rear bottom of the module into the DIN rail, then push up
and inwards to engage the clip.
2
2
1
1
RS-485 Connection Diagrams – North American Installation Technique
COM 1&2 Connections (In)
COM 1&2 Connections (Out) and RS-485 Termination Resistor
Wiring for Com 1 & Com 2 must be terminated on a panel
mounted terminal block. No ground wires should be
terminated on terminals 9 & 11. Terminate Com shields at
the panel mounted field terminal block chassis ground.
Wiring for Com 1 & Com 2 must be terminated on a panel
mounted terminal block. No ground wires should be
terminated on terminals 10 & 12. Terminate Com shields
and 120 Ω termination resistors (included) at the panel
mounted field terminal block as shown.
RESET
RESET
NGC-40 BRIDGE MODULE
COM 1 In
1
+
5
NGC-40 BRIDGE MODULE
COM 2 In
9
–
3
+
7
11
–
COM 1 Out
2
Field
terminal
block +
+
–
To upstream
device
INDUSTRIAL HEAT TRACING SOLUTIONS
+
–
To upstream
device
COM 2 Out
10
6
–
4
+
8
12
–
Field
terminal
block
120 ohm
termination
resistor
EN-RaychemNGC40Bridge-IM-H58089 02/16
120 ohm
termination
resistor
4 / 10
RS-485 Connection Diagrams – European Installation Technique
COM 1&2 Connections (In)
COM 1&2 Connections (Out) and RS-485 Termination Resistor
Wiring for Com 1 & Com 2 must be terminated on a panel
mounted terminal block. No ground wires should be
terminated on terminals 9 & 11. Terminate Com shields at
the panel mounted field terminal block chassis ground. The
Com cable shield from the field terminal block to the Bridge
should be terminated at the earth ground bar.
Earth grounding
bar located at the
bridge module
COM 1 In
1
5
+
9
Wiring for Com 1 & Com 2 must be terminated on a panel
mounted terminal block. No ground wires should be
terminated on terminals 10 & 12. Terminate Com shields
and 120 Ω termination resistors (included) at the panel
mounted field terminal block as shown. The Com cable
shield from the field terminal block to the Bridge should be
terminated at the earth ground bar.
COM 1 Out
2
–
RESET
NGC-40 BRIDGE MODULE
10
6
+
Earth grounding
bar located at the
bridge module
–
RESET
+
Field
terminal
block
–
NGC-40 BRIDGE MODULE
Field
terminal
block
120 ohm
termination
resistor
To upstream
device
COM 2 In
3
7
+
11
Earth grounding
bar located at the
bridge module
COM 2 Out Earth grounding
4
–
+
+
8
12
bar located at the
bridge module
–
–
120 ohm
termination
resistor
To upstream
device
Local RS-232 (COM 3) & Ethernet
Switch Setting RS-232
User Interface – Configuration Switch
A slide switch is provided on the front of the module to
allow the user to set the bridge into a known state for
configuration of the communication ports, as shown in the
following table:
RESET
NGC-40 BRIDGE MODULE
Switch Position
RS-232
Local RS-232
to Laptop
Ethernet
To upstream
device
INDUSTRIAL HEAT TRACING SOLUTIONS
Bridge
Module Settings
SET
Configuration mode
Modbus address
1
RUN
Normal operating
mode
Local RS-232
Protocol
RTU
Settings based on the
Data rate
9600 baud
user configuration
Data bits
8
parameters
Stop bits
2
Parity
No parity
EN-RaychemNGC40Bridge-IM-H58089 02/16
5 / 10
RMM2 Connection – Optional
When using the field mounted RMM2 for RTD input, it must be
connected to the COM 2 In as shown below.
RESET
NGC-40 BRIDGE MODULE
COM 2 In
3
Panel
+
7
11
Earth grounding
bar located at the
bridge module
–
Panel Terminal Block
+
–
~ ~–
+
RS-485 Shielded
Twisted Pair
To next
RMM2
~ ~
+
–
+
–
+
–
Field
INDUSTRIAL HEAT TRACING SOLUTIONS
EN-RaychemNGC40Bridge-IM-H58089 02/16
6 / 10
NGC-40 CAN Bus Connections for Up to 10 Modules
Termination
Block
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
Termination
Block
CAN / 24 Vdc
CAN/Term CAN / 24 Vdc
Power/
Termination
Module
Redundant Supply*
24 Vdc
+
–
20 Modules
per Power Supply
OUT
OUT
IN
OUT
IN
OUT
IN
OUT
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
Bridge
Module
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
Module 2
Module 3
Module 4
Module 10
Module 1
+
IN
CAN / 24 Vdc
80 Modules
per Bridge
100-240 Vac In
100-240 Vac In
Primary Supply*
24 Vdc
IN
–
20 Modules
per Power Supply
Optional redundant supply
* Power supply shall have a means for disconnect from line voltage
NGC-40 CAN Bus Connections for Up to 20 Modules
Termination
Block
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN/Term CAN / 24 Vdc
Power/
Termination
Module
+
–
20 Modules
per Power Supply
OUT
OUT
IN
OUT
IN
OUT
IN
OUT
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
Bridge
Module
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
Module 2
Module 3
Module 4
Module 10
80 Modules
per Bridge
Redundant Supply*
24 Vdc
IN
CAN / 24 Vdc
100-240 Vac In
100-240 Vac In
Primary Supply*
24 Vdc
IN
CAN / 24 Vdc
Module 1
+
–
20 Modules
per Power Supply
Optional redundant supply
CAN / 24 Vdc
CAN / 24 Vdc
Power/
Termination
Module
CAN / 24 Vdc
IN
OUT
IN
CAN / 24 Vdc
OUT
IN
CAN / 24 Vdc
OUT
IN
Termination
Block
CAN / 24 Vdc
OUT
IN
OUT
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
Module 11
Module 12
Module 13
Module 14
Module 20
* Power supply shall have a means for disconnect from line voltage
INDUSTRIAL HEAT TRACING SOLUTIONS
EN-RaychemNGC40Bridge-IM-H58089 02/16
7 / 10
CAN Bus Termination Block
A termination block (included) is required at each end of the
CAN/24 Vdc bus. See NGC-40 CAN bus connection wiring diagram for more details.
Termination
block
N
CA
M
ER
/T
N
CA
Termination
block
DC
4V
/2
CAN / TERM CAN / 24 VDC
PTM
HTC/HTC3/IO
PTM
HTC/HTC3/IO
Provide Suitable Panel Enclosure and Determine Locations for NGC-40-BRIDGE Assembly in Panel*
The NGC-40-BRIDGE should be located in the rear of the
panel. The NGC-40-BRIDGE assembly is an electronic unit
and must not be located where it will be exposed to strong
magnetic fields or excessive vibration.
HTC10
HTC20
HTC30
I/O3
I/O4
I/O5
HTC9
HTC8
HTC7
C8
C9
C10
HTC29
HTC19
C18
HTC28
C5
C20
C19
HTC27
C28
C30
HTC18
I/O1
I/O2
C29
HTC17
HTC6
HTC5
HTC4
C5
C6
C7
HTC16
HTC26
HTC15
HTC25
C27
HTC14
HTC24
C25
C16
PS1
CBM
C26
C17
HTC2
HTC3
C4
C3
HTC12
HTC13
C4
C24
C113
HTC22
HTC23
C23
PS2
PTM2
HTC1
C2
C1
PS3
HTC11
PTM3
C11
C12
PS4
2. Determine locations for the NGC-40-BRIDGE assembly in
the electrical panel.
Alarm
light
PTM4
Note: The Raychem NGC-40-BRIDGE is designed for
operation in ambient temperatures from –40°C to 65°C
(–40°F to 149°F ). If the ambient temperature is outside
this range, a space heater and/or cooling fan will be required in the panel.
Panel
PTM1
Panel
door
HTC21
The NGC-40-BRIDGE must be mounted in an enclosure to
protect its electronic components. For indoor applications,
use a minimum NEMA 1 enclosure (NEMA 12 recommended). For outdoor applications, use a NEMA 4 or NEMA 4X
enclosure depending on the requirements.
C21
C22
1. Provide suitable panel enclosure
TB
*North American panel installation techniques
INDUSTRIAL HEAT TRACING SOLUTIONS
EN-RaychemNGC40Bridge-IM-H58089 02/16
8 / 10
NGC-40 CAN Bus Connections for Up to 40 Modules
Termination
Block
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN/Term CAN / 24 Vdc
Power/
Termination
Modules
100-240 Vac In
IN
+
20 Modules
–
per Power Supply
IN
OUT
IN
OUT
IN
OUT
IN
OUT
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
Bridge
Module
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
Module 2
Module 3
Module 4
Module 10
80 Modules
per Bridge
100-240 Vac In
Primary Supply*
24 Vdc
OUT
CAN / 24 Vdc
Module 1
Redundant Supply*
24 Vdc
+
20 Modules
–
per Power Supply
Optional redundant supply
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN/Term CAN / 24 Vdc
Power/
Termination
Module
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
Bridge
Module
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
Module 12
Module 13
Module 14
Module 20
80 Modules
per Bridge
Module 11
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN/Term CAN / 24 Vdc
Power/
Termination
Board
100-240 Vac In
Primary Supply*
24 Vdc
+
20 Modules
–
per Power Supply
IN
OUT
IN
OUT
OUT
IN
OUT
IN
OUT
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3)
or
I/O
HTC/HTC3
or
I/O
Module 21
Module 22
Module 23
Module 24
Module 30
100-240 Vac In
Redundant Supply*
24 Vdc
+
20 Modules
–
per Power Supply
Optional redundant supply
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
* Power supply shall
have a means for
disconnect from line
voltage
IN
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
Termination
Block
CAN / 24 Vdc
CAN/Term CAN / 24 Vdc
Power/
Termination
Module
INDUSTRIAL HEAT TRACING SOLUTIONS
IN
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
CAN / 24 Vdc
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
HTC/HTC3
or
I/O
Module 31
Module 32
Module 33
Module 34
Module 40
EN-RaychemNGC40Bridge-IM-H58089 02/16
9 / 10
WWW.PENTAIRTHERMAL.COM
NORTH AMERICA
EUROPE, MIDDLE EAST, AFRICA
ASIA PACIFIC
LATIN AMERICA
Tel: +1.800.545.6258
Fax: +1.800.527.5703
Tel: +1.650.216.1526
Fax: +1.650.474.7711
[email protected]
Tel: +32.16.213.511
Fax: +32.16.213.603
[email protected]
Tel: +86.21.2412.1688
Fax: +86.21.5426.2917
[email protected]
Tel: +1.713.868.4800
Fax: +1.713.868.2333
[email protected]
Pentair, NGC and Raychem are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves
the right to change specifications without prior notice.
© 2007-2016 Pentair. INDUSTRIAL HEAT TRACING SOLUTIONS
EN-RaychemNGC40Bridge-IM-H58089 PCN 1244-009547 02/16