NGC-40-BRIDGE CONTROL AND MONITORING MODULES FOR USE WITH THE RAYCHEM NGC-40 SYSTEM INSTALLATION INSTRUCTIONS DESCRIPTION The NGC-40-BRIDGE module provides the interface between a panel's internal CAN-based network and upstream devices. Multiple communications ports are supported, allowing serial and Ethernet connections to be used with external devices. A B TOOLS REQUIRED • Small flat-blade screwdriver C ADDITIONAL MATERIALS REQUIRED • Power supply 24 Vdc @150 mA per NGC-40-BRIDGE • Custom built CAN cables with RJ-45 connections D KIT CONTENTS ItemQty Description Shown not to scale APPROVALS Hazardous Locations Class I, Div. 2, Groups A,B,C,D T4 Class I, Zone 2, AEx nC IIC T4 IP20 Ex nL IIC T4 X 3128486 –40˚C ≤ Ta ≤ +65˚C Conforms to: FM Class Number 3600 (11/98) FM Class Number 3611 (10/99) ANSI/UL STD. 60079-15-2009 UL STD. 61010-1 A 1 NGC-40-BRIDGE module B 2 CAN bus termination block C 2 RS-485 termination resistors 120 Ω – 1% - 1/4 watt D 1 NGC-40-BRIDGE serial cable TTC# 10332-005 PTM# 10392-043 Certified to: CAN/CSA STD. C22.2 No. 213-M1987 (R2004) CAN/CSA STD. C22.2 No. 61010-1:2004 EN 61010-1 (2001) CAN/CSA STD. E60079-15:02 (R2006) (Russia, Kazakhstan, Belarus) For other countries contact your local Pentair representative. WARNING: This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. INDUSTRIAL HEAT TRACING SOLUTIONS For technical support, call Pentair Thermal Management at (800) 545-6258. EN-RaychemNGC40Bridge-IM-H58089 02/16 1 / 10 GENERAL Supply voltage Internal power consumption Ambient operating temperature Ambient storage temperature Environment Max. altitude Humidity Mounting 24 Vdc ± 10% < 3.6 W per NGC-40-BRIDGE –40ºC to 65ºC (–40ºF to 149ºF) –40ºC to 75ºC (–40ºF to 167ºF) PD2, CAT III 2,000 m (6,562 ft) 5 – 90% noncondensing Din Rail – 35 mm ELECTROMAGNETIC COMPATIBILITY Emissions Immunity EN 61000-6-3 Emission standard for residential, commercial and light industrial environments EN 61000-6-2 Immunity standard for industrial environments COMMUNICATIONS COM1, COM2 Type Cable Length Quantity Data rate Data bits Parity Stop bits Tx delay Protocol Connection terminals 2-wire RS-485 One shielded twisted pair 1,200 m (4,000 ft) maximum Up to 255 devices per port 9600, 19.2K, 38.4K, 57.6K, 115.2K baud 7 or 8 None, even, odd 0, 1, 2 0 – 5 sec. Modbus RTU or ASCII Wago cage clamp terminals COMMUNICATIONS COM3 Type Cable Length Data rate Data bits Parity Stop bits Tx delay Protocol Connection terminals RS-232 Custom TTC# 10332-005 15 m (50 ft) maximum 9600, 19.2K, 38.4K, 57.6K, 115.2K baud 7 or 8 None, even, odd 0, 1, 2 0 – 5 sec. Modbus RTU or ASCII RJ-11 CAN NETWORKING PORT Type Connection Protocol Topology Length Quantity Address 2-wire isolated CAN-based peer-peer network. Isolated to 300 V. Two 8-pin RJ-45 connectors (both may be used for Input or Output connections) Proprietary NGC-40 Daisy chain 10 m (33 ft) maximum Up to 80 CAN nodes per network segment Unique, factory assigned ETHERNET Type Length Data rates Protocol Connection terminals 10/100 BaseT Ethernet network 100 m (328 ft) 10 or 100 MB/s Modbus/TCP Shielded 8-pin RJ-45 connector on front of module PROGRAMMING AND SETTING LED indicators Alarm conditions Configuration switch CONNECTION TERMINALS Wiring terminals CAN networking and module power RESET, Configuration lost, CAN communications fail SET/RUN slide switch on front of module Cage clamp, 0.5 to 2.5 mm2 (24 to 12 AWG) Two RJ-45s, one each IN and OUT. Provides CAN bus signals and +24 Vdc power. HOUSING Size INDUSTRIAL HEAT TRACING SOLUTIONS 45.1 mm (1.78 in) wide x 87 mm (3.43 in) high x 106.4 mm (4.2 in) deep EN-RaychemNGC40Bridge-IM-H58089 02/16 2 / 10 System Components 45.1 mm (1.78 in) 45.1 mm (1.78 in) 45.1 mm (1.78 in) 45.1 mm (1.78 in) RESET Front Top A. Wiring Terminals COM 1 (485) + in 2 COM 1 (485) + out 3 COM 2 (485) + in 4 COM 2 (485) + out 5 COM 1 (485) – in 6 COM 1 (485) – out 7 COM 2 (485) – in 8 COM 2 (485) – out 9 – 12 Not used Bottom Back C. Communication Slide Switch TerminalsFunction 1 87 mm (3.43 in) 87 mm (3.43 in) 106.4 mm (4.2 in) NGC-40 BRIDGE MODULE D. RS-232 Port Status: Indicates status of RS-232 port Top LED Off No activity Green (flashing) Receipt of data packet Bottom LED Off No activity Yellow (flashing) Transmit of data packet E. Ethernet Port Status: Indicates status of the LAN B. Status LEDs Status: Indicates status of the module Off No power GreenOK/Normal Yellow (flashing) Configuration mode Red (flashing) Internal fault Network: Indicates CAN network activity Off No link detected Green Link OK, receive data packets Yellow Transmit data packets Red (flashing) Network error Top LED Off No LAN detected Green ON, LAN detected Bottom LED Off No LAN activity Yellow (flashing) LAN activity (data packet) F. CAN Bus/Module Power G. Reset Button COM: Indicates COM1 & 2 (RS-485) activity Off No activity Green (flashing) Receipt of data packet Yellow (flashing) Transmit of data packet INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40Bridge-IM-H58089 02/16 3 / 10 Mounting the NGC-40-BRIDGE REMOVAL: Push the module upwards to disengage the clip, then rotate the module toward you. Each NGC-40-BRIDGE mounts on a DIN 35 rail. MOUNTING: Insert the rear bottom of the module into the DIN rail, then push up and inwards to engage the clip. 2 2 1 1 RS-485 Connection Diagrams – North American Installation Technique COM 1&2 Connections (In) COM 1&2 Connections (Out) and RS-485 Termination Resistor Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 9 & 11. Terminate Com shields at the panel mounted field terminal block chassis ground. Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 10 & 12. Terminate Com shields and 120 Ω termination resistors (included) at the panel mounted field terminal block as shown. RESET RESET NGC-40 BRIDGE MODULE COM 1 In 1 + 5 NGC-40 BRIDGE MODULE COM 2 In 9 – 3 + 7 11 – COM 1 Out 2 Field terminal block + + – To upstream device INDUSTRIAL HEAT TRACING SOLUTIONS + – To upstream device COM 2 Out 10 6 – 4 + 8 12 – Field terminal block 120 ohm termination resistor EN-RaychemNGC40Bridge-IM-H58089 02/16 120 ohm termination resistor 4 / 10 RS-485 Connection Diagrams – European Installation Technique COM 1&2 Connections (In) COM 1&2 Connections (Out) and RS-485 Termination Resistor Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 9 & 11. Terminate Com shields at the panel mounted field terminal block chassis ground. The Com cable shield from the field terminal block to the Bridge should be terminated at the earth ground bar. Earth grounding bar located at the bridge module COM 1 In 1 5 + 9 Wiring for Com 1 & Com 2 must be terminated on a panel mounted terminal block. No ground wires should be terminated on terminals 10 & 12. Terminate Com shields and 120 Ω termination resistors (included) at the panel mounted field terminal block as shown. The Com cable shield from the field terminal block to the Bridge should be terminated at the earth ground bar. COM 1 Out 2 – RESET NGC-40 BRIDGE MODULE 10 6 + Earth grounding bar located at the bridge module – RESET + Field terminal block – NGC-40 BRIDGE MODULE Field terminal block 120 ohm termination resistor To upstream device COM 2 In 3 7 + 11 Earth grounding bar located at the bridge module COM 2 Out Earth grounding 4 – + + 8 12 bar located at the bridge module – – 120 ohm termination resistor To upstream device Local RS-232 (COM 3) & Ethernet Switch Setting RS-232 User Interface – Configuration Switch A slide switch is provided on the front of the module to allow the user to set the bridge into a known state for configuration of the communication ports, as shown in the following table: RESET NGC-40 BRIDGE MODULE Switch Position RS-232 Local RS-232 to Laptop Ethernet To upstream device INDUSTRIAL HEAT TRACING SOLUTIONS Bridge Module Settings SET Configuration mode Modbus address 1 RUN Normal operating mode Local RS-232 Protocol RTU Settings based on the Data rate 9600 baud user configuration Data bits 8 parameters Stop bits 2 Parity No parity EN-RaychemNGC40Bridge-IM-H58089 02/16 5 / 10 RMM2 Connection – Optional When using the field mounted RMM2 for RTD input, it must be connected to the COM 2 In as shown below. RESET NGC-40 BRIDGE MODULE COM 2 In 3 Panel + 7 11 Earth grounding bar located at the bridge module – Panel Terminal Block + – ~ ~– + RS-485 Shielded Twisted Pair To next RMM2 ~ ~ + – + – + – Field INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40Bridge-IM-H58089 02/16 6 / 10 NGC-40 CAN Bus Connections for Up to 10 Modules Termination Block CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc Termination Block CAN / 24 Vdc CAN/Term CAN / 24 Vdc Power/ Termination Module Redundant Supply* 24 Vdc + – 20 Modules per Power Supply OUT OUT IN OUT IN OUT IN OUT CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc Bridge Module HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3 or I/O Module 2 Module 3 Module 4 Module 10 Module 1 + IN CAN / 24 Vdc 80 Modules per Bridge 100-240 Vac In 100-240 Vac In Primary Supply* 24 Vdc IN – 20 Modules per Power Supply Optional redundant supply * Power supply shall have a means for disconnect from line voltage NGC-40 CAN Bus Connections for Up to 20 Modules Termination Block CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN/Term CAN / 24 Vdc Power/ Termination Module + – 20 Modules per Power Supply OUT OUT IN OUT IN OUT IN OUT CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc Bridge Module HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3 or I/O Module 2 Module 3 Module 4 Module 10 80 Modules per Bridge Redundant Supply* 24 Vdc IN CAN / 24 Vdc 100-240 Vac In 100-240 Vac In Primary Supply* 24 Vdc IN CAN / 24 Vdc Module 1 + – 20 Modules per Power Supply Optional redundant supply CAN / 24 Vdc CAN / 24 Vdc Power/ Termination Module CAN / 24 Vdc IN OUT IN CAN / 24 Vdc OUT IN CAN / 24 Vdc OUT IN Termination Block CAN / 24 Vdc OUT IN OUT CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3 or I/O Module 11 Module 12 Module 13 Module 14 Module 20 * Power supply shall have a means for disconnect from line voltage INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40Bridge-IM-H58089 02/16 7 / 10 CAN Bus Termination Block A termination block (included) is required at each end of the CAN/24 Vdc bus. See NGC-40 CAN bus connection wiring diagram for more details. Termination block N CA M ER /T N CA Termination block DC 4V /2 CAN / TERM CAN / 24 VDC PTM HTC/HTC3/IO PTM HTC/HTC3/IO Provide Suitable Panel Enclosure and Determine Locations for NGC-40-BRIDGE Assembly in Panel* The NGC-40-BRIDGE should be located in the rear of the panel. The NGC-40-BRIDGE assembly is an electronic unit and must not be located where it will be exposed to strong magnetic fields or excessive vibration. HTC10 HTC20 HTC30 I/O3 I/O4 I/O5 HTC9 HTC8 HTC7 C8 C9 C10 HTC29 HTC19 C18 HTC28 C5 C20 C19 HTC27 C28 C30 HTC18 I/O1 I/O2 C29 HTC17 HTC6 HTC5 HTC4 C5 C6 C7 HTC16 HTC26 HTC15 HTC25 C27 HTC14 HTC24 C25 C16 PS1 CBM C26 C17 HTC2 HTC3 C4 C3 HTC12 HTC13 C4 C24 C113 HTC22 HTC23 C23 PS2 PTM2 HTC1 C2 C1 PS3 HTC11 PTM3 C11 C12 PS4 2. Determine locations for the NGC-40-BRIDGE assembly in the electrical panel. Alarm light PTM4 Note: The Raychem NGC-40-BRIDGE is designed for operation in ambient temperatures from –40°C to 65°C (–40°F to 149°F ). If the ambient temperature is outside this range, a space heater and/or cooling fan will be required in the panel. Panel PTM1 Panel door HTC21 The NGC-40-BRIDGE must be mounted in an enclosure to protect its electronic components. For indoor applications, use a minimum NEMA 1 enclosure (NEMA 12 recommended). For outdoor applications, use a NEMA 4 or NEMA 4X enclosure depending on the requirements. C21 C22 1. Provide suitable panel enclosure TB *North American panel installation techniques INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40Bridge-IM-H58089 02/16 8 / 10 NGC-40 CAN Bus Connections for Up to 40 Modules Termination Block CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN/Term CAN / 24 Vdc Power/ Termination Modules 100-240 Vac In IN + 20 Modules – per Power Supply IN OUT IN OUT IN OUT IN OUT CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc Bridge Module HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3 or I/O Module 2 Module 3 Module 4 Module 10 80 Modules per Bridge 100-240 Vac In Primary Supply* 24 Vdc OUT CAN / 24 Vdc Module 1 Redundant Supply* 24 Vdc + 20 Modules – per Power Supply Optional redundant supply CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN/Term CAN / 24 Vdc Power/ Termination Module IN OUT IN OUT IN OUT IN OUT IN OUT CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc Bridge Module HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3 or I/O Module 12 Module 13 Module 14 Module 20 80 Modules per Bridge Module 11 CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN/Term CAN / 24 Vdc Power/ Termination Board 100-240 Vac In Primary Supply* 24 Vdc + 20 Modules – per Power Supply IN OUT IN OUT OUT IN OUT IN OUT CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3) or I/O HTC/HTC3 or I/O Module 21 Module 22 Module 23 Module 24 Module 30 100-240 Vac In Redundant Supply* 24 Vdc + 20 Modules – per Power Supply Optional redundant supply CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc * Power supply shall have a means for disconnect from line voltage IN CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc Termination Block CAN / 24 Vdc CAN/Term CAN / 24 Vdc Power/ Termination Module INDUSTRIAL HEAT TRACING SOLUTIONS IN OUT IN OUT IN OUT IN OUT IN OUT CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc CAN / 24 Vdc HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3 or I/O HTC/HTC3 or I/O Module 31 Module 32 Module 33 Module 34 Module 40 EN-RaychemNGC40Bridge-IM-H58089 02/16 9 / 10 WWW.PENTAIRTHERMAL.COM NORTH AMERICA EUROPE, MIDDLE EAST, AFRICA ASIA PACIFIC LATIN AMERICA Tel: +1.800.545.6258 Fax: +1.800.527.5703 Tel: +1.650.216.1526 Fax: +1.650.474.7711 [email protected] Tel: +32.16.213.511 Fax: +32.16.213.603 [email protected] Tel: +86.21.2412.1688 Fax: +86.21.5426.2917 [email protected] Tel: +1.713.868.4800 Fax: +1.713.868.2333 [email protected] Pentair, NGC and Raychem are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice. © 2007-2016 Pentair. INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGC40Bridge-IM-H58089 PCN 1244-009547 02/16 10 / 10
© Copyright 2026 Paperzz