CPD Review Manual NOTES Equation 14-1 Q0.381 1,917 (∆H/[Cr x L])0.206 where D = Inside diameter of the pipe, in. Q = Input rate appliance, cfh at 60°F L = Equivalent length of pipe, ft ∆H = Pressure drop (upstream pressure – downstream pressure), in. wc Cr = Natural gas: 0.6094; Undiluted propane:1.2462 D= Equation 14-2 Q0.381 18.93 [(P1 – P22)*Y/(Cr x L)]0.206 where P1 = Upstream pressure, pounds per square inch absolute (psia) (P1+14.696) P2 = Downstream pressure, psia (P1+14.696) Y = Natural gas: 0.9992; Undiluted propane: 0.9910 D= 2 Longest Length Method This is the traditional method used to determine the longest equivalent piping length (from the meter or delivery point to the farthest outlet), which then is used in conjunction with pipe sizing tables to determine the appropriate pipe diameter for all other sections of piping in the system. In simple terms, only the cfh quantities listed in the tables for this pipe length are used to size each branch and section of pipe. This method is the simplest to use, and it generally yields the most conservative siz- Table 14-1 Capacity of Gas Pipe for Pressures Less than 2 psi (where SG = 0.6 and pressure drop = 0.3 in. wc), cfh ing because the short Pipe size, in. nominal runs of piping located Pipe Length, close to the meter can ½ ¾ 1 1¼ 1½ 2 2½ 3 4 ft be somewhat over10 131 273 514 1,060 1,580 3,050 4,860 8,580 17,500 sized. One advantage 20 90 188 353 726 1,090 2,090 3,340 5,900 12,000 of using this method 30 72 151 284 583 873 1,680 2,680 4,740 9,660 is that it can provide 40 62 129 243 499 747 1,440 2,290 4,050 8,270 some cushion in the 50 55 114 215 442 662 1,280 2,030 3,590 7,330 branch piping, al60 50 104 195 400 600 1,160 1,840 3,260 6,640 lowing for future re70 46 95 179 368 552 1,060 1,690 3,000 6,110 configuration of the piping system with80 42 89 167 343 514 989 1,580 2,790 5,680 out replacing entire 90 40 83 157 322 482 928 1,480 2,610 5,330 branch lengths. 100 38 79 148 304 455 877 1,400 2,470 5,040 Table 14-1 can 125 33 70 131 269 403 777 1,240 2,190 4,460 be used to determine 150 30 63 119 244 366 704 1,120 1,980 4,050 the capacity of a wide 175 28 58 109 224 336 648 1,030 1,820 3,720 range of pipe sizes to 200 26 54 102 209 313 602 960 1,700 3,460 be used in the longest 250 23 48 90 185 277 534 851 1,500 3,070 length method. Table 300 21 43 82 168 251 484 771 1,360 2,780 14-1 is a tabular solu350 19 40 75 154 231 445 709 1,250 2,560 tion of the Spitzglass 215 414 660 1,170 2,380 formula for the case 400 18 37 70 143 450 17 35 66 135 202 389 619 1,090 2,230 where the specific 191 367 585 1,030 2,110 gravity S = 0.6 and the 500 16 33 62 127 550 15 31 59 121 181 349 556 982 2,000 pressure drop H = 0.3 173 333 530 937 1,910 in. wc. If the gas used 600 14 30 56 115 165 318 508 897 1,830 for the system has a 650 14 29 54 110 108 Section 2: Design — Chapter 14: Fuel Gas Systems Table 14-2 Specific Gravity Capacity Multipliers Specific Multiplier Gravity 0.35 1.310 0.40 1.230 0.45 1.160 0.50 1.100 0.55 1.040 0.60 1.000 0.65 0.962 0.70 0.926 0.75 0.895 0.80 0.867 0.85 0.841 0.90 0.817 1.00 0.775 1.10 0.740 1.20 0.707 1.30 0.680 1.40 0.655 1.50 0.633 1.60 0.612 1.70 0.594 1.80 0.577 1.90 0.565 2.00 0.547 2.10 0.535 Table 14-3 Conversion Factors for Pressure Drop Pressure Multiplier Drop 1.00 2.236 0.90 2.121 0.80 2.000 0.70 1.871 0.60 1.732 0.50 1.561 0.40 1.414 0.35 1.323 0.30 1.225 0.25 1.118 0.20 1.000 0.10 0.707 Table 14-4 Conversion Factors for Pipe Lengths X* Multiplier X* Multiplier 1.0 1.000 3 0.577 1.1 0.953 4 0.500 1.2 0.913 5 0.447 1.3 0.877 6 0.408 1.4 0.845 7 0.378 1.5 0.817 8 0.354 1.6 0.791 9 0.333 1.7 0.767 10 0.316 1.8 0.745 20 0.224 1.9 0.725 30 0.182 2 0.707 NOTES *X = Length of pipe divided by length given in Table 14-1 for Q different specific gravity, obtain the multiplier from Table 14-2. Table 14-3 shows the conversion factors for pressure drop, and Table 14-4 shows the conversion factors for pipe length. In all cases, the pressure drop is for the length given and not the drop per 100 feet. A value of 0.2 is recommended for horizontal piping and 0.5 for vertical piping. The purpose of Table 14-4 is to find the conversion factor to use for values of L other than those in Table 14-1. The multiplier is to be applied to the value of Q in Table 14-1. For example, Table 14-1 does not give Q for an L of 1,000 feet. In this case, use the value of Q for 500 feet; thus, X is then 1,000/500 = 2, and the value of Q from Table 14-1 for 500 feet is multiplied by 0.707 (from Table 14-4). Example 14-1 What would be the capacity of a 110-foot run of 1¼-inch gas piping with a 0.45 specific gravity gas and a pressure drop of 0.35 inch? From Table 14-1, the capacity of 100 feet of 1¼-inch pipe is 230 cfh at a 0.65 specific gravity and 0.2-inch pressure drop. From Table 14-2, for a 0.45 specific gravity, the multiplier is 1.202. From Table 14-3, for a 0.35 pressure drop, the multiplier is 1.323. To correct for the length, X = 110/100 = 1.1, and the multiplier for 1.1 in Table 14-4 is 0.953. Therefore, the correct capacity is 230 × 1.202 × 1.323 × 0.953 = 348.6 cfh. Branch Length Method This is an alternate sizing method that could allow slightly smaller pipe diameters in some segments of a piping system when compared to the longest length method. The pipe size of each section of the longest pipe length (from the meter or delivery point to the farthest outlet) shall be determined using the longest equivalent length of piping and the associated cfh quantity listed in the tables for that section. Then, the pipe sizes of each section of branch piping not previously sized shall be determined using the equivalent lengths of piping from the point of delivery to the most remote outlet of each individual branch and the associated cfh quantity listed for that particular section. Hybrid Pressure Method This method is used when it is necessary to design a piping system that utilizes multiple supply pressures within a single distribution system. The pipe size for each section of high-pressure gas piping shall be determined using the longest equivalent length of piping from the meter or delivery point to the farthest pressure regulator. The pipe size from the 109
© Copyright 2026 Paperzz