Submittal Data: CHDX09663 Heat Pump 8 tons VRF Outdoor Unit

Submittal Data:
CHDX09663
Heat Pump
8 tons VRF Outdoor Unit
Capacities:
Cooling: Btu/h
Power input: kW
Heating: Btu/h
Power input: kW
96,000
7.69
108,000
8.60
Cooling Mode Nominal Conditions:
Indoor: °F WB/ °F DB
Outdoor: °F DB
Pipe Length: Feet
Level Difference: Feet
80/67
95
25
0
Heating Mode Nominal Conditions:
Indoor: °F DB
Outdoor: °F DB/ °F WB
Pipe Length: Feet
Level Difference: Feet
Operating Range:
Cooling: °F DB
Heating: °F WB
14
-4
70
47/43
25
0
to
to
113
59
Compressor:
Fan:
Type/Quantity:
Fan Motor Output: kW
1 Propeller
0.7 kW
Power Supply:
V/PH/Hz.
208 - 230/ 3/ 60
Minimum Circuits Amps (MCA): (A)
34
Max. Overcurrent Protection (MOCP): (A)
45
Weight:(lbs)
683
Refrigerant:
410A
Coil:
Coil Face Area:(sq. ft.)
Number of Rows:
29.5
4
Protection Devices:
High Pressure Switch:
Overcurrent (CT Method)
Crankcase Heaters:(W)
External Finish:
Yes
Yes
25 + 32
Electrostatic Powder Coating
Type/Quantity:
1 Inverter driven Rotary & 1 fixed speed scroll
Capacity Control Range:
10% - 100%
Submittal Data:
Job Name:
Location:
Engineer:
Submitted To:
Submitted By:
Reference:
Approval:
Date:
Compressor Warranty: Six Years.
Parts Warranty: One Year.
Construction
Unit #:
Drawing #
Salt Protected units available.