How to connect the MT3x0 to the test circuit and electricity meter. How to use AC-current clamps safely. How to disconnect the MT3x0 from the test circuit and electricity meter. How to use AC-current clamps safely. • Mains supply should always be connected properly and never disconnected when the device is linked to the test circuit. • First connect the neutral cable and afterwards other voltage cables. Connect all cables properly. • First connect the socket to the instrument and afterwards to the current carrying conductor (cable)/circuit. • Take always care of safety against electrical shock. • The operator should read the manual and be well-known with equipment and detail safety instructions. • • • • • • Disconnect the device from the mains after removal of test voltage and clamps from the test circuit. First remove the phase voltage cables and afterwards the neutral cable. First remove the AC-current clamps from the test circuit and afterwards the socket from the device. Take always care of safety against electrical shock. The operator should read the manual and be well-known with equipment and detail safety instructions. All accessoiries should be packed properly to avoid mechanical damages. Scanning head Remove the scanning head 1. Connect the socket of the 1. from the meter under test and 1. current clamps to the MT3x0. Not to the test circuit! ZERA 1. LED disconnect the scanning head cable from the MT3x0. 2. Connect the test voltage 1 2 circuit to the UN, U1, U2* and U3 * of the MT3x0. Not to the test circuit! 2. Remove the test voltage cables U1, U2*, U3* and UN from the meter under test. Not from the MT3x0! 3 4 5 6 7 8 9 10 11 12 2. L1 L2 L3 3. 3. Connect the mains power supply of the MT3x0. First to the mains, afterwards to the MT3x0! 2. 3. Remove the AC-current 3. clamps from the current Mains supply circuit. Not from the MT3x0! Scanning head ZERA LED 4. Connect the voltage cable to Use only cables of category IV for MT310-01! Remove the mains power the meter under test. 1 2 3 4 5 6 7 8 9 10 11 12 4. First from the MT3x0, afterwards from the mains! 4. 5. Connect the AC-current clamps to the current circuit. Ensure the correct current flow direction and tight connection of the jaws. 4. supply cable from the MT3x0. L1 Mains supply L3 L2 5. Remove the test voltage 5. cables U , U *, U * and U 1 2 3 N from the MT3x0. 5. Scanning head 6. Mount the scanning head on 7. ZERA 6. 6. Remove the AC-current clamp LED the meter under test. First connect the scanning head cable to the MT3x0 and then to the scanning head. plug from the MT3x0. 6. Scanning head * in case of three phase network ZERA LED * in case of three phase network 7. ZERA GmbH | Hauptstr. 392 | D-53639 Königswinter | Germany | Tel: +49 (0) 2332 704-0 | Fax: +49 (0) 2332 704 70 ZERA GmbH | Hauptstr. 392 | D-53639 Königswinter | Germany | Tel: +49 (0) 2332 704-0 | Fax: +49 (0) 2332 704 70 How to connect the MT3x0 to the test circuit and electricity meter. How to use „Direct mode“ safely. How to disconnect the MT3x0 to the test circuit and electricity meter. How to use „Direct mode“ safely. • Do not disconnect mains supply from the device while connected to the test circuit. • Never open the secondary side of the external CT while making current connection. CT secondary open will cause high voltage, damage to equipment and danger of life of the operator. • First connect the neutral cable afterwards other voltage cables. Connect all cables properly. • Take always care of safety against electrical shock and properties of CT/VT. • The operator should read the manual and be well-known with equipment and detail safety instructions. 1. Connect the current cables to the MT3x0. Not to the test circuit! • Ensure that the secondary side of the external CT is not open while removing the current connection. CT secondary open will cause high voltage, damage to the equipment and danger of life of the operator. • Disconnect the device from power supply after removal of test voltage and clamps from test circuit. • First remove the phase voltage cables afterwards the neutral cable. • Take always care of safety against electrical shock and properties of CT/VT. • The operator should read the manual and be well-known with equipment and detail safety instructions. • All accessoiries should be packed properly to avoid mechanical damages. 1. Scanning head Remove the scanning head Use only cables of category IV for MT310-01! 1. from the meter under test and ZERA disconnect the scanning head cable from the MT3x0. 2. Connect the test voltage cir- LED 1. cuit to the UN, U1, U2* and U3* of the MT3x0. Not to the test circuit! Scanning head ZERA LED 3. 2. Remove the test voltage 2. cables U , U *, U * and U 1 2 3 N 3. Connect the mains power supply of the MT3x0. First to the mains, afterwards to the MT3x0! Mains supply 1 2 from the meter under test. Not from the MT3x0! Scanning head ZERA 3 4 5 6 7 8 9 10 11 12 2. LED Short circuit the CT at the se- 4. 4. Connect the current cables to the test current circuit. Ensure the CTs are never open at the secondary side in any case! 1 2 3 4 5 6 7 8 9 10 11 12 MT3x0 External CT 3. condary side and afterwards remove the current cables from the current circuit. Not from the MT3x0! Reconnect the meter under test to the secondary side of the CT! Scanning head ZERA LED 3. 1 2 3 4 5 6 7 8 9 10 11 12 Scanning head 5. Connect the voltage cable to ZERA the meter under test. LED External CT Remove the mains power 6. Mount the scanning head on 7. the meter under test. First connect the scanning head cable to the MT3x0 and then to the scanning head. 1 2 3 4 5 6 7 8 9 10 11 12 5. 4. supply cable from the MT3x0. First from the MT3x0, afterwards from the mains! 4. Scanning head 6. 5. ZERA LED Remove the voltage and cur- 5. rent cables from the MT3x0. * in case of three phase network 7. ZERA GmbH | Hauptstr. 392 | D-53639 Königswinter | Germany | Tel: +49 (0) 2332 704-0 | Fax: +49 (0) 2332 704 70 * in case of three phase network ZERA GmbH | Hauptstr. 392 | D-53639 Königswinter | Germany | Tel: +49 (0) 2332 704-0 | Fax: +49 (0) 2332 704 70
© Copyright 2026 Paperzz