T/PC PRT Contact Temperature Sensor

Installation Instructions
T/PC
PRT Contact Temperature Sensor
Important: Retain these instructions
UNPACKING
T/PC Installation
Instructions TG100508
Installation
97 mm (3.82”)
Dimensions
109 mm (4.29”)
1
2 m (6’6”) cable
T /P C
M A N U F A C T U R E D IN E U
T R E N D C O N T R O L S Y S T E M S
L T D U K
57 mm (2.24”)
2
Requirements
measurement range
/-40
/40
/110
/160
-40 °C to +50 °C
(-40 °F to +122 °F)
-10 °C to +40 °C
(+14 °F to +104 °F)
-10 °C to +110 °C
(+14 °F to +230 °F)
-10 °C to +160 °C
(+14 °F to +320 °F)
0 %RH
95 %RH
H O
2
Protection
:IP67, NEMA6
2 m (6’6”) max
T /P C
M A N U F A C T U R E D IN E U
T R E N D C O N T R O L S Y S T E M S
L T D U K
-40 °C to +50 °C
(-40 °F to +122 °F)
T/PC PRT Contact Temperature Sensor Installation Instructions TG100508A Issue 4/B 13/02/07
1
T/PC
Installation Instructions
Installation (continued)
3
b Tighten 2 screws
Drill 2 pilot holes
85 mm (3.35”)
a
Fix to Wall
2 off No 6 (M3.5) screws
Fix Probe
4
or use cable tie(s) (not provided)
either use jubilee clip (provided)
recommended use of thermally conductive paste
Remove Lid
5
b
a
6
Remove Connector
Caution: This unit contains static
sensitive devices. Suitable
anti-static precautions
should be taken throughtout
the operation to prevent
damage to the units. BS EN100015/
1 Basic Specification: protection of
electrostatic sensitive devices.
2
T/PC PRT Contact Temperature Sensor Installation Instructions TG100508A Issue 4/B 13/02/07
Installation Instructions
T/PC
Installation (continued)
Insert Cable
7
or use M16 cable gland
either use M20 flexible conduit
8
Wire to Controller
IQ1xx, IQ2xx
24 Vdc
Sensor
IN
polarity independent
IQ system TP/I/22/HF/200 (Belden
8761) cable recommended.
Terminal size 0.5 to 2.5 mm2 (14 to
20 AWG)
I
Terminate screen at IQ end only
IQ3
0 (0 V)
Sensor
N (in)
+ (24 V)
Analogue input
channel linked
for current (I)
Note that if connecting to an IQ22x controller (including /ADL or /OC), do not connect directly to C (+24V),
instead connect to AUX+ (+24V).
9
Replace Connector
Replace Lid
10
b
a
Note that IP67 (NEMA6) rating is only achieved if the sensor is correctly installed with
cable or conduit connection fully tightened.
T/PC PRT Contact Temperature Sensor Installation Instructions TG100508A Issue 4/B 13/02/07
3
T/PC
Installation Instructions
Installation (continued)
11
Configure IQ
IQ
or
IQ
12
IQ Configuration Manual
90-1533
Set up IQ Sensor Type
It is recommended to use SET (Software Tool) for the setting of the sensor type module.
For all IQ2 series controllers with firmware version 2.1 or greater, or IQ3 series controllers,
the following SET Unique Sensor References should be used:
(T/PC/-40)
PRT I -40+50 (°C)
PRT I -40+122 F (°F)
(T/PC/40)
PRT I -10+40 (°C)
PRT I +14+104 F (°F)
(T/PC/110)
PRT I -10+110 (°C)
PRT I +14+230 F (°F)
(T/PC/160)
PRT I -10+160 (°C)
PRT I +14+320 F (°F)
Alternatively enter scaling manually as defined in table below.
For all other IQ controllers see Sensor Scaling Reference Card TB100521A
tYpe Sensor digI/P Driver Function loGic Loop scHedule seQnc Analog
digBit Knob sWitch Time Zone Oss User addRess intcoN calarM reView Plot
calEndar
Unit
/-40
/40
/110
/160
= ?
Y
E
Yn<CR>
TYPE n
:=?
S=5 (characterise)
Y= , E= , U= , L= , P= , I1= , I2= , O1= , O2=
X <CR>
13
U
L
P
x
1
2
ΔT
IQ
T /P C
T R E N D
C O N T R O L S Y S T E M S
L T D U K
2 (current)
3
°C
°F
50
122
-40
-40
2
2
Ox
Ox
-40
-40
50
122
2 (current)
3
°C
°F
40
104
-10
14
2
2
Ox
Ox
-10
14
40
104
2 (current)
3
°C
°F
110 230
-10
14
2
2
Ox
Ox
-10
14
110 230
2 (current)
3
°C
°F
160 320
-10
14
2
2
Ox
Ox
-10
14
160 320
Disposal
Test system
M A N U F A C T U R E D IN E U
input type
Exponent
Units
Upper
Lower
Points
Ix
4
20
WEEE Directive :
At the end of their useful life the
packaging and product should be
disposed of by a suitable recycling
centre.
Do not dispose of with normal household waste.
Do not burn.
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route
du Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof
without obligation to notify any person of such revisions or changes.
Trend Control Systems Limited
P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 21888 Fax:+44 (0)1403 241608 www.trend-controls.com
Trend Control Systems USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-3900, Fax: (425)869-8445 www.trend-controls.com
4
T/PC PRT Contact Temperature Sensor Installation Instructions TG100508A Issue 4/B 13/02/07