Thermal-Magnetic Square D For Mining Applications Class 600 www.squared.com FOR CURRENT INFORMATION Molded Case Circuit Breakers for Mining Applications These circuit breakers with the properly selected trip range provide protection for trailing cables in compliance with the Federal Register for Mining Applications. The thermal-magnetic circuit breakers listed below have thermallyresponsive trip elements in addition to adjustable instantaneous trip Adjustable Magnetic Trip Range Amperes* Low High 50 180 75 260 150 580 400 800 500 1000 625 1250 750 1500 1000 2000 Circuit Breaker Catalog Number FAL36030 FAL36050 FAL36100 KAL36080 KAL36090 KAL36100 KAL36110 KAL36125 KAL36150 KAL36175 KAL36200 KAL36100 KAL36110 KAL36125 KAL36150 KAL36175 KAL36200 KAL36225 KAL36250 LAL36125 LAL36150 LAL36175 LAL36200 LAL36225 LAL36250 KAL36125 KAL36150 KAL36175 KAL36200 KAL36225 KAL36250 KAL36150 KAL36175 KAL36200 KAL36225 KAL36250 LAL36150 LAL36175 LAL36200 UVL36225 LAL36250 LAL36300 LAL36350 LAL36400 MAL36300 MAL36350 KAL36200 KAL36225 KAL36250 LAL36200 LAL36225 LAL36250 LAL36300 LAL36350 LAL36400 Suffix Number Price 13T 14T 16T 21T 21T 21T 21T 21T 21T 21T 21T 22T 22T 22T 22T 22T 22T 22T 22T 22T 22T 22T 22T 22T 22T 25T 25T 25T 25T 25T 25T 26T 26T 26T 26T 26T 26T 26T 26T 26T 26T 26T 26T 26T 26T 26T SOT SOT SOT SOT SOT SOT SOT SOT SOT $ 632. 632. 778. 1650. 1650. 1650. 1650. 1650. 1650. 1650. 1650. 1650. 1650. 1650. 1650. 1650. 1650. 1650. 1650. 2932. 2932. 2932. 2932. 2932. 2932. 1650. 1650. 1650. 1650. 1650. 1650. 1650. 1650. 1650. 1650. 1650. 2932. 2932. 2932. 2932. 2932. 2932. 2932. 2932. 4800. 4800. 1650. 1650. 1650. 2932. 2932. 2932. 2932. 2932. 2932. mechanisms. They allow for independent selection of thermal and magnetic trip characteristics. The circuit breakers are identified by a T" in the suffix of the catalog number. See selection chart below. For MAG-GARD® instantaneous trip magnetic-only circuit breakers refer to Square D Digest. Adjustable Magnetic Trip Range - Circuit Breaker Amperes* Catalog Number Low High MAL36300 MAL36350 1000 2000 MAL36400 MAL36450 MAL36500 KAL36225 1125 2250 KAL36250 KAL36250 LAL36250 LAL36300 LAL36350 LAL36400 1250 2500 MAL36350 MAL36400 MAL36450 MAL36500 MAL36600 LAL36300 LAL36350 LAL36400 MAL36300 MAL36350 1500 3000 MAL36400 MAL36450 MAL36500 MAL36600 MAL36700 MAL36800 LAL36350 3500 1750 LAL36400 MAL36400 MAL36450 MAL36500 MAL36600 2000 4000 MAL36700 MAL36800 MAL36900 MAL361000 MAL36500 MAL36600 MAL36700 2500 5000 MAL36800 MAL36900 MAL361000 MAL36600 MAL36700 MAL36800 3000 6000 MAL36900 MAL361000 MAL36800 7000 MAL36900 3500 MAL361000 MAL36800 4000 MAL36900 8000 MAL361000 MAL36900 4500 9000 MAL361000 Suffix Number Price SOT 30T 30T SOT SOT 31T 31T 32T 32T 32T 32T 32T 32T 32T 32T 32T 32T 33T 33T 33T 33T 33T 33T 33T 33T 33T 33T 33T 35T 35T 36T 36T 36T 36T 36T 36T 36T 36T 40T 40T 40T 40T 40T 40T 42T 42T 42T 42T 42T 44T 44T 44T 45T 45T 45T 46T 46T $4800. 4800. 4800. 4800. 4800. 1650. 1650. 1650. 2932. 2932. 2932. 2932. 4800. 4800. 4800. 4800. 4800. 2932. 2932. 2932. 4800. 4800. 4800. 4800. 4800. 4800. 4800. 4800. 2932. 2932. 4800. 4800. 4800. 4800. 6303. 6303. 8067. 8067. 4800. 4800. 6303. 6303. 8067. 8067. 4800. 6303. 6303. 8067. 8067. 6303. 8067. 8067. 6303. 8067. 8067. 8067. 8067. * Magnetic trip setting tolerances are -20% and +30% from nominal values shown. MAG-GARD is a Registered Trademark of Square D Company or related companies. DE1 Discount Schedule 5-13 Selection Information Class 500, 600, 800 www.SquareD.com For the most up-to-date information 100 A Frame 100 A Frame GJL Circuit Breaker Type FH FHh FH FC FI FY Number of Poles FA (240 V) 1, 2, 3 1 FA 2, 3 1 1 2, 3 2, 3 2, 3 1 GJL 3 Current Range 15–100 15–100 15–100 15–30 35–100 15–100 15–100 20–100 15–30 15–100 240 Vac 10 18 25 65 25 65 100 200 14 100 480Y/277 Vac ... 18 18 65 25 25 65 200 14 65 480 Vac ... ... 18 ... ... 25 65 200 ... 65 600Y/347 Vac ... ... 14 ... ... 18 ... 100 ... 18 600 Vac ... ... 14 ... ... 18 ... 100 ... ... 250 Vdc 5c 10c 10 10c 10c 50 ... ... ... ... 500 Vdc b ... ... ... ... ... 20 ... ... ... ... 10/2.5 10/2.5 10/2.5 10/2.5 10/2.5 10/2.5 10/2.5 6/1.5 ... 65/65 6 CIRCUIT BREAKERS Interrupting Ratings UL/CSA/NOM Rating (kA RMS) (50/60 Hz AC) DC Ratings IEC 415/240 Vac (Icu/lcs) f IEC 50/60 Hz For additional IEC ratings, see Supplemental Digest. Special Ratings Fed. Specs W-C-375B/GEN ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ... ... HACR (2, 3-pole) ✓ ... ✓ ... ... ✓ ✓ ... ... ✓ Unit Mount ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ... ✓ I-Line® ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ... ... Connections/Terminations Rear Connection ✓ ✓ ✓ ... ... ✓ ... ... ... Drawout ... ... ... ... ... ... ... ... ... ... Optional Lugs ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ... ... Accessories and Modifications Shunt Trip ✓ag ... ✓a ... ... ✓a ✓a ✓a ... ✓ Undervoltage Trip ✓ag ... ✓a ... ... ✓a ✓a ✓a ... ✓ ✓ Auxiliary Switches ✓ag ... ✓a ... ... ✓a ✓a ✓a ... Alarm Switch ✓ag ✓a ✓a ✓a ✓a ✓a ✓a ✓a ... ✓ ✓ ✓ ✓ ... ... ✓ ✓ ✓ ... ... ✓ ... ✓ ✓ ✓ ✓ ✓ ... ... ✓ ✓d ... ✓d ... ... ✓d ... ... ... ... Motor Operator Handle Operators Mechanical Interlocks (3-pole) ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ Cylinder Lock (3-pole) ✓a ... ✓a ... ... ✓a ✓a ... ... ... Optional GF Protection ✓e ... ✓e ... ... ✓e ✓e ✓e ... ... Handle Padlock Attachment Trip System Type Thermal-magnetic ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ Instantaneous-only (MCP) ... ... ✓ ... ... ✓ ... ... ... ✓ Molded Case Switch (Automatic) ... ... ... ... ... ✓ ... ... ... ... Electronic ... ... ... ... ... ... ... ... ... ... Enclosures (Pages 6-51–6-54) General Purpose (NEMA 1) ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ... ... Raintight (NEMA 3R) ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ... ... Dustight (NEMA 12) ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ... ... Watertight (NEMA 4, 4X, 5) ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ... ... Explosion Proof (NEMA 7, 9) ✓ ✓ ✓ ✓ ✓ ✓ ✓ ... ... Height IN (mm) Dimensions (3P Unit Mount) 6 (152) 6 (152) 6 (152) 8 (203) ... 4.72 (120) Width IN (mm) 4.5 (114) 4.5 (114) 4.5 (114) 4.5 (114) 3.54 (90) Depth IN (mm) 4.13 (105) 4.13 (105) 4.13 (105) 4.75 (121) 3.94 (100) 6-20/8-25 Pages 6-20/8-25 Pages (Unit Mount)/(I-Line) Pages 6-20/8-25 Page 6-21 Note: All circuit breakers on this chart are UL Listed and CSA Certified unless otherwise noted. a Factory-installed option only e Requires factory-installed “G” Shunt trip and 3-pole module. b Ungrounded UPS systems only. f Dual UL and IEC ratings and CE markings on circuit breakers. For additional IEC ratings, see Supplemental Digest. See Supplemental Digest. g Not available on 1-pole FA (240 V). c 1-pole has 125 Vdc rating only. h 65 kA @120 Vac. d Requires breaker with WB suffix. 5/11/05 6-4 © 2005 Schneider Electric All Rights Reserved 5/11/05 Thermal-magnetic Molded Case Circuit Breakers 100 Ampere Frame Class 650 Thermal-magnetic molded case circuit breakers shown on pages 6-20–6-24 are permanent trip UL Listed, CSA Certified, IEC rated, and also meet the requirements of Federal Specification W–C–375B/GEN as indicated on pages 6-4–6-7. For I-Line® molded case circuit breakers, see listings on pages 8-25–8-28. www.SquareD.com For the most up-to-date information F-frame—100 A, Thermal-magnetic (240 Vac) AC Magnetic Trip Settings Hold Trip Ampere Rating Terminal Wire Range Standard Interrupting Catalog Number Price 1-pole, 120 Vac 15 20 25 30 35 40 45 50 60 70 80 90 100 275 275 275 275 400 400 400 400 800 800 800 900 900 600 600 600 600 850 850 850 850 1450 1450 1450 1700 1700 FAL12015 FAL12020 FAL12025 FAL12030 FAL12035 FAL12040 FAL12045 FAL12050 FAL12060 FAL12070 FAL12080 FAL12090 FAL12100 $132. 132. 132. 132. 132. 132. 132. 132. 132. 174. 174. 174. 174. 275 275 275 275 400 400 400 400 800 800 800 900 900 600 600 600 600 850 850 850 850 1450 1450 1450 1700 1700 FAL22015 FAL22020 FAL22025 FAL22030 FAL22035 FAL22040 FAL22045 FAL22050 FAL22060 FAL22070 FAL22080 FAL22090 FAL22100 $222. 222. 222. 222. 222. 222. 222. 222. 222. 362. 362. 362. 362. 275 275 275 275 400 400 400 400 800 800 800 900 900 600 600 600 600 850 850 850 850 1450 1450 1450 1700 1700 FAL32015 FAL32020 FAL32025 FAL32030 FAL32035 FAL32040 FAL32045 FAL32050 FAL32060 FAL32070 FAL32080 FAL32090 FAL32100 $330. 330. 330. 330. 330. 330. 330. 330. 330. 469. 469. 469. 469. AL50FA #14–#4 AWG Cu or #12–#4 AWG Al AL100FA #14–#1/0 AWG Cu or #12–#1/0 AWG Al 2-pole, 240 Vac 15 20 25 30 35 40 45 50 60 70 80 90 100 CIRCUIT BREAKERS FAL 1-pole 15–100 Amperes AL50FA #14–#4 AWG Cu or #12–#4 AWG Al AL100FA #14–#1/0 AWG Cu or #12–#1/0 AWG Al 3-pole, 240 Vac 6 15 20 25 30 35 40 45 50 60 70 80 90 100 FAL/FHL 2-pole 15–100 Amperes AL50FA #14–#4 AWG Cu or #12–#4 AWG Al AL100FA #14–#1/0 AWG Cu or #12–#1/0 AWG Al F-frame—100 A, Thermal-magnetic (480 Vac) Ampere Rating AC Magnetic Trip Settings Hold Trip Standard Interrupting Catalog Price Number Extra High Interrupting Catalog Price Number Terminal Wire Range FA Lugs FC Lugs AL50FA #14–#4 AWG Cu or #12–#4 AWG Al ... AL100FA #14–#1/0 AWG Cu or #12–#1/0 AWG Al ... 1-pole, 277 Vac, 125 Vdc 15 20 25 30 35 40 45 50 60 70 80 90 100 FAL/FHL/FCL 3-pole 15–100 Amperes 275 275 275 275 400 400 400 400 800 800 800 900 900 600 600 600 600 850 850 850 850 1450 1450 1450 1700 1700 FAL14015 $167. FAL14020 167. FAL14025 167. FAL14030 167. FAL14035 167. FAL14040 167. FAL14045 167. FAL14050 167. FAL14060 167. FAL14070 208. FAL14080 208. FAL14090 208. FAL14100 208. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 2-pole, 480 Vac, 250 Vdcba Interrupting Ratings (kA) FAL240 FAL480 FCL 240 V 10 18 (1P), 25 (2, 3P) 100 480 V ... 18 65 600 V ... ... ... Circuit Breaker Termination Options (Third character of catalog number) F=No Lugs L=Lugs both ends M=Lugs “ON” end only P=Lugs “OFF” end only Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 6-36–6-38 Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 6-43, 6-44 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 6-49, 6-50 Enclosures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 6-51–6-54 15 20 25 30 35 40 45 50 60 70 80 90 100 275 275 275 275 400 400 400 400 800 800 800 900 900 600 600 600 600 850 850 850 850 1450 1450 1450 1700 1700 FAL24015 $406. ... FAL24020 406. ... FAL24025 406. ... FAL24030 406. ... FAL24035 406. ... FAL24040 406. ... FAL24045 406. ... FAL24050 406. FCL24050 FAL24060 406. FCL24060 FAL24070 525. FCL24070 FAL24080 525. FCL24080 FAL24090 525. FCL24090 FAL24100 525. FCL24100 ... AL50FA CU30FA4 ... #14–#4 AWG Cu or (1) #14–#10 AWG ... #12–#4 AWG Al Cu only ... ... ... ... AL100FA4 $ 965. AL100FA AWG Cu 965. #14–#1/0 AWG Cu or (1) #14–#3 or 1188. #12–#1/0 AWG Al (1) #12–#1 AWG Al 1188. 1188. 1188. 3-pole, 480 Vac, 250 Vdcb 15 20 25 30 35 40 45 50 60 70 80 90 100 275 275 275 275 400 400 400 400 800 800 800 900 900 600 600 600 600 850 850 850 850 1450 1450 1450 1700 1700 FAL34015 $521. FCL34015 FAL34020 521. FCL34020 FAL34025 521. FCL34025 FAL34030 521. FCL34030 FAL34035 521. FCL34035 FAL34040 521. FCL34040 FAL34045 521. FCL34045 FAL34050 521. FCL34050 FAL34060 521. FCL34060 FAL34070 616. FCL34070 FAL34080 616. FCL34080 FAL34090 616. FCL34090 FAL34100 616. FCL34100 $1206. AL50FA CU30FA4 1206. #14–#4 AWG Cu or (1) #14–#10 AWG 1206. #12–#4 AWG Al Cu only 1206. 1206. 1206. 1206. AL100FA4 1206. AL100FA AWG Cu 1206. #14–#1/0 AWG Cu or (1) #14–#3 or 1484. #12–#1/0 AWG Al (1) #12–#1 AWG Al 1484. 1484. 1484. a FCL 2-pole circuit breaker built using 3-pole module. b FCL circuit breakers are not rated for 250 Vdc. 6-20 10/23/04 DE2 Discount Schedule © 2004 Schneider Electric All Rights Reserved 10/23/04 Thermal-magnetic Molded Case Circuit Breakers 100, 250 Ampere Frame Class 525, 650, 734, 820 www.SquareD.com For the most up-to-date information F-frame—100 A, Thermal-magnetic (600 Vac) Ampere Rating AC Magnetic Trip Settings Hold Trip Standard Interrupting High Interrupting Current Limiting Terminal Wire Range Catalog Number Price Catalog Number Price Catalog Number Price ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... FHL16015 FHL16020 FHL16025 FHL16030 FHL16035 FHL16040 FHL16045 FHL16050 FHL16060 FHL16070 FHL16080 FHL16090 FHL16100 $301. 301. 301. 301. 301. 301. 301. 301. 301. 339. 339. 339. 339. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... FAL26015 FAL26020 FAL26025 FAL26030 FAL26035 FAL26040 FAL26045 FAL26050 FAL26060 FAL26070 FAL26080 FAL26090 FAL26100 $469. 469. 469. 469. 469. 469. 469. 469. 469. 593. 593. 593. 593. FHL26015 FHL26020 FHL26025 FHL26030 FHL26035 FHL26040 FHL26045 FHL26050 FHL26060 FHL26070 FHL26080 FHL26090 FHL26100 $775. 775. 775. 775. 775. 775. 775. 775. 775. 902. 902. 902. 902. ... FIL26020 FIL26025 FIL26030 FIL26035 FIL26040 FIL26045 FIL26050 FIL26060 FIL26070 FIL26080 FIL26090 FIL26100 ... AL50FA $1755. #14–#4 AWG Cu or 1755. #12–#4 AWG Al 1755. 1755. 1755. 1755. 1755. AL100FA 1755. #14–#1/0 AWG Cu or 1755. #12–#1/0 AWG Al 1755. 1755. 1755. FAL36015 FAL36020 FAL36025 FAL36030 FAL36035 FAL36040 FAL36045 FAL36050 FAL36060 FAL36070 FAL36080 FAL36090 FAL36100 $604. 604. 604. 604. 604. 604. 604. 604. 604. 743. 743. 743. 743. FHL36015 FHL36020 FHL36025 FHL36030 FHL36035 FHL36040 FHL36045 FHL36050 FHL36060 FHL36070 FHL36080 FHL36090 FHL36100 $ 905. 905. 905. 905. 905. 905. 905. 905. 905. 1027. 1027. 1027. 1027. ... FIL36020 FIL36025 FIL36030 FIL36035 FIL36040 FIL36045 FIL36050 FIL36060 FIL36070 FIL36080 FIL36090 FIL36100 ... AL50FA $2197. #14–#4 AWG Cu or 2197. #12–#4 AWG Al 2197. 2197. 2197. 2197. 2197. AL100FA 2197. #14–#1/0 AWG Cu or 2197. #12–#1/0 AWG Al 2197. 2197. 2197. 1-pole, 277 Vac, 125 Vdc 15 20 25 30 35 40 45 50 60 70 80 90 100 FIL36100 275 275 275 275 400 400 400 400 800 800 800 900 900 600 600 600 600 850 850 850 850 1450 1450 1450 1700 1700 AL50FA #14–#4 AWG Cu or #12–#4 AWG Al AL100FA #14–#1/0 AWG Cu or #12–#1/0 AWG Al 275 275 275 275 400 400 400 400 800 800 800 900 900 600 600 600 600 850 850 850 850 1450 1450 1450 1700 1700 3-pole, 600 Vac, 250 Vdc 15 20 25 30 35 40 45 50 60 70 80 90 100 GJL 3-pole circuit breaker 275 275 275 275 400 400 400 400 800 800 800 900 900 600 600 600 600 850 850 850 850 1450 1450 1450 1700 1700 Powerpact® G-frame—100 A, Thermal-magnetic (600Y/347 Vac) AC Magnetic Trip Settings J Interrupting Hold Trip Catalog Number Price Ampere Rating Terminal Wire Range 3-pole, Vac, Vdc 15 20 30 40 50 60 70 80 90 100 QBL 2 and 3-pole 70–250 Amperes 600 600 600 600 800 800 800 800 800 800 1200 1200 1200 1200 1400 1400 1400 1400 1400 1400 GJL36015 GJL36020 GJL36030 GJL36040 GJL36050 GJL36060 GJL36070 GJL36080 GJL36090 GJL36100 $1327. 1327. 1327. 1327. 1327. 1327. 1632. 1632. 1632. 1632. #14–#1/0 AWG Cu #8–#1/0 AWG Al Powerpact Q-framea—250 A, Thermal-magnetic (240 Vac) Ampere Rating AC Magnetic Trip Settings Hold Trip B Interrupting Catalog Number D Interrupting Priceu Catalog Number Priceu G Interrupting Catalog Number Priceu J Interrupting Catalog Number Priceu 2-pole, 240 Vac 70 80 90 100 110 125 150 175 200 225 250 Interrupting Ratings (kA) FAL FHL FIL 240 V 25 25 (1P:35–100 A), 65 (2, 3P) 200 480 V 18 25 (2, 3P) 200 600 V 14 18 (2, 3P) 100 GJL QB QD QG QJ 240 V 100 10 25 65 100d 480 V 65 ... ... ... ... 600 V 18c ... ... ... ... © 2004 Schneider Electric All Rights Reserved 7/14/04 7/14/04 pages 6-36–6-38 pages 6-43, 6-44 pages 6-49, 6-50 pages 6-51–6-54 1800 1800 1800 2400 2400 2400 2400 2400 2400 2400 2400 QBL22070 QBL22080 QBL22090 QBL22100 QBL22110 QBL22125 QBL22150 QBL22175 QBL22200 QBL22225 QBL22250b $316. 316. 316. 316. 316. 316. 316. 316. 316. 316. 462. QDL22070 QDL22080 QDL22090 QDL22100 QDL22110 QDL22125 QDL22150 QDL22175 QDL22200 QDL22225 QDL22250b $ 762. 762. 762. 762. 762. 762. 762. 762. 762. 762. 1029. QGL22070 QGL22080 QGL22090 QGL22100 QGL22110 QGL22125 QGL22150 QGL22175 QGL22200 QGL22225 QGL22250b $1014. 1014. 1014. 1014. 1014. 1014. 1014. 1014. 1014. 1014. 1313. QJL22070 QJL22080 QJL22090 QJL22100 QJL22110 QJL22125 QJL22150 QJL22175 QJL22200 QJL22225 QJL22250b $1260. 1260. 1260. 1260. 1260. 1260. 1260. 1260. 1260. 1260. 1565. 1800 1800 1800 2400 2400 2400 2400 2400 2400 2400 2400 QBL32070 QBL32080 QBL32090 QBL32100 QBL32110 QBL32125 QBL32150 QBL32175 QBL32200 QBL32225 QBL32250b 832. 832. 832. 832. 832. 832. 832. 832. 832. 832. 1208. QDL32070 QDL32080 QDL32090 QDL32100 QDL32110 QDL32125 QDL32150 QDL32175 QDL32200 QDL32225 QDL32250b 1189. 1189. 1189. 1189. 1189. 1189. 1189. 1189. 1189. 1189. 1628. QGL32070 QGL32080 QGL32090 QGL32100 QGL32110 QGL32125 QGL32150 QGL32175 QGL32200 QGL32225 QGL32250b 1628. 1628. 1628. 1628. 1628. 1628. 1628. 1628. 1628. 1628. 2100. QJL32070 QJL32080 QJL32090 QJL32100 QJL32110 QJL32125 QJL32150 QJL32175 QJL32200 QJL32225 QJL32250b 1864. 1864. 1864. 1864. 1864. 1864. 1864. 1864. 1864. 1864. 2310. 3-pole, 240 Vac 70 80 90 100 110 125 150 175 200 225 250 c GJL is rated 18 kA at 600Y/347 Vac. d 3-pole QJ circuit breakers are rated at 208Y/120 Vac only. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . Enclosures. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000 1000 1000 1200 1200 1200 1200 1200 1200 1200 1200 1000 1000 1000 1200 1200 1200 1200 1200 1200 1200 1200 a Replacement lugs are not available for Powerpact Q-frame circuit breakers. Lugs for the Powerpact Q-frame circuit breakers accept (1) #4 AWG–300 kcmil. b 250 A lugs are suitable for copper conductors only. uDE2A DE2 Discount Schedule 6-21 6 15 20 25 30 35 40 45 50 60 70 80 90 100 CIRCUIT BREAKERS 2-pole, 600 Vac, 250 Vdc Electrical Accessories Used on Thermal-magnetic and Electronic Trip Circuit Breakers www.SquareD.com For the most up-to-date information Molded Case Circuit Breakers—Factory-installed Electrical Accessories Description Trips the circuit breaker from a remote location by means of a trip coil energized from a separate circuit. A 120 V shunt trip will operate at 55% or more of rated voltage. All other shunt trips will operate at 75% or more of rated voltage. AC 24 120 208 240 277 480 DC 24 48 125 250 ... Application • For use with momentary or maintained push button. • Sure Trip Capacitor Unit requires 48 Vdc shunt trip. • Leads: (2) Black #18 AWG Cu. $ 503. 503. 503. 503. 503. 503. 503. 503. 503. 503. 503. Application • For use only with obsolete GP Ground-Censor® system or add on ground-fault module. • Leads: (2) Orange #18 AWG Cu. Note: Trips the circuit breaker electrically when a control circuit falls below 35 to 70% of nominal (not field adjustable). Picks up at 35–85% of nominal voltage. AC 24 120 240 DC 24 DC 48 Application • UVR must be energized in order to close the circuit breaker. • Leads: (2) Brown #18 AWG Cu leads. TIME DELAY UNIT Suffix -1042a -1021c -1021 -1021 -1037a -1037a -1027 -1028 -1029 -1030b -Gb Provides adjustable time delay for UVR of 0.1 to 0.6 second before circuit breaker trips. AC 120 5 VA 8 VA 8 VA 2 VA 3 VA -1143b -1121 -1124 -1127 -1128 503. 503. 503. 503. 503. Catalog No. Unit Mt. I-Line® Application AUXILIARY SWITCHES • For use only with -1121 UV trip. • Adjustable time delay (0.1 to 0.6 second). • I-Line unit requires 1.5 in. (38 mm) of mounting space. • Leads: (2) Brown #18 AWG Cu and (2) Black/White #18 AWG Cu. Monitors circuit breaker contact status and provides a remote signal indicating the circuit breaker contacts are OPEN or CLOSED. 690UVTD 1A/1B Application • Max. Load = FA, FH, FC, FI, KA, KH, LC, LE, LI, LX, LXI. 10 A @ 125–250 Vac π hp @ 125–250 Vac, 5 A @ 30 Vdc • Leads: Yellow for “A’’, Blue for “B’’, Striped for common #18 AWG Cu. ALARM SWITCHES Electrical accessories are available on all molded case circuit breakers except FY, QB, QD, QG, QJ and QOM1 circuit breakers. All AC electrical accessories shown at left are rated for 50/60 Hz. Add 20% to accessory price for each field-installable accessory that is factoryinstalled. See page 6-38 for field-installable accessories. 2A/2B 3A/3B Used with control circuits and actuated only when the circuit breaker has tripped. Standard construction includes a normally open contact. Application • Max. Load = 10 A @ 125–250 Vac • Max. Load = 15 A @ 30 Vdc • Leads: (2) Red #18 AWG Cu. See load info. in App. text at left 1A AC 250 1A DC 1B AC 250 1B DC 28 28 See load info. in App. text at left See load info. in App. text at left 690UVTDI 1294. -1212 208. -1352 415. Alarm switch is the only accessory available for 1-pole FA circuit breakers. Combination accessories may be ordered by description, i.e., 1021 and 1212. a Not available on FI, KI or KC circuit breakers. b Not available on LC, LE, LI, LX, LXI circuit breakers. c LC, LE, LI, LX, and LXI circuit breakers operate at 75% or more of rated voltage. d Not available in FA, FC, FH, FI and KI circuit breakers. e Coil burden values do not apply to LC, LE, LI, LX and LXI. Consult Field Sales Office for more information. f List price for field-installed accessories. See page 6-38. 690UVTD Wiring Diagram -1364d 533. -2100 208. -2100 208. -2103 208. -2103 208. Time Delay Unit 690UVTD Black Wire 120 Vac White Wire Neutral Brown Wire SQUARE D CIRCUIT BREAKER with 120 Vac 50/60 Hz 60 mA Undervoltage Trip GJL Circuit Breaker Accessories Electrical and mechanical accessories listed below are for use with GJL instantaneous-trip and thermal-magnetic circuit breakers. All AC electrical accessories shown below are rated for 50/60 Hz. Field-installable Electrical Accessories for GJL Circuit Breakers Accessory Shunt Trip for GJL Circuit Breaker Shunt Trip Undervoltage Trip Undervoltage Trip for GJL Circuit Breaker Auxiliary Switch Alarm Switch Description Rated Voltage Coil Burden AC 120 50 mA 208 29 mA 240 25 mA Trips the circuit breaker from a remote location by 277 22 mA means of a trip coil energized from a separate 480 13 mA circuit. All shunt trips will operate at 55% or more of DC 24 250 mA rated voltage. 48 125 mA 125 48 mA 250 24 mA AC 120 50 mA 208 29 mA Trips the circuit breaker electrically when a control 240 25 mA circuit falls below 35 to 70% of nominal voltage. 277 22 mA (Not field adjustable.) Picks up at 35 to 85% of 480 13 mA nominal voltage. UVR must be energized in order to DC 24 250 mA close the circuit breaker. 48 125 mA 125 48 mA 250 24 mA Monitors circuit breaker contact status and provides a remote signal indicating the circuit breaker contacts are OPEN or CLOSED. Ratings: 3A-600 Vac, 6A-480 Vac, 0.3A-250 Vdc, 0.8A-125 Vdc Used with control circuits and is actuated only when the circuit breaker has tripped. Ratings: 3A-600 Vac, 6A-480 Vac, 0.3A-250 Vdc, 0.8A-125 Vdc Catalog No. GSA GSB GSC GSD GSH GSO GSP GSR GSS GUA GUB GUC GUD GUH GUO GUP GUR GUS Price $478. 478. 478. 478. 478. 478. 478. 478. 478. 478. 478. 478. 478. 478. 478. 478. 478. 478. AACg 198. AACg 198. Field-installable External Accessories DIN Rail Adapter Terminal Shields Padlock Attachment Alarm/Auxiliary Switch for GJL Circuit Breaker Cover Screw Seal Hardware that allows mounting on 35 x 15 mm DIN rail. Used to prevent accidental contact with live parts. Prevents access to unauthorized personnel. Locks in OFF position only. Suitable for padlock with a shaft diameter up to 0.312 in. (8 mm). (10) Cover Screw Seals to prevent unauthorized removal of circuit breaker cover. GYR GYT 62.00 50.00 AHP 13.10 ACS 12.30 g Same accessory—Application depends on installation location. Switch has common and both normally open and normally closed contacts. See pages 6-40–6-42 for accessories for Powerpact® circuit breakers. © 2005 Schneider Electric All Rights Reserved 5/11/05 5/11/05 DE2 Discount Schedule CIRCUIT BREAKERS UNDER VOLTAGE TRIP Trips the circuit breaker electrically using the signal from a Micrologic® Ground-Fault Module. 21 VA 24 VA 107 VA 154 VA 14 VA 45 VA 36 VA 36 VA 44 VA 15 VA ... List Price Adder f 6 GROUNDFAULT SHUNT TRIP Coil Burdene Brown Wire Accessory SHUNT TRIP Rated Voltage 6-37
© Copyright 2026 Paperzz