Metro Controller

Metro Controller
The Metro controller is
capable of monitoring up
to 250 Metro remote
addressable gas detectors
Metro Controller
Cost Effective
•
•
•
•
•
Low cost controller and detector
Installation costs minimized
No booster supplies required
Uses industry standard cable
Return on investment through reduced
site running costs verified through
system data log
Flexible by Design
• U p to 2 x 125 detectors over 2 x 1km (3000 feet)
• 8 user configurable relays
• Grouping, voting, instantaneous or time delayed operation
• Automatic and manual operation with override facility
The Metro controller is capable of
monitoring up to 250 Metro remote
addressable gas detectors. Together they
form the Metro system designed to protect
people from flammable and toxic gas
hazards commonly found in car parks,
tunnels or other areas where automotive
vehicles may operate.
One Stop Shop
•
•
•
•
ontroller complete with mounting bracket
C
Detector including base and vandal proof guard
CO, LPG, LNG, CH4 and NO2 available
Range of accessories including UPS, evacuation
signs, audible and visual alarms
Proven Gas Detector Technology
• SurecellTM electrochemical toxic sensors
• Poison resistant catalytic bead flammable sensors
• Fast and reliable
• Complies with relevant standards
Convenient to Use
• A uto-backlit display for dark environments
• Unhindered access to large terminal
compartment
• M20 and 3⁄4" pre-formed knockouts in base
• Auto-recognition of field devices
• Infrared remote control supplied for set up and configuration of field devices and inputs
Life Costs Minimized
•
•
•
•
Plug in, serviceable gas detectors
odular construction minimizes downtime
M
Simple design reduces spare part inventory
Full support via Honeywell Analytics Service
Centres throughout the world
The Metro controller provides automatic control
of ventilation systems that maintain gas levels at
or below a safe level. Where gas levels rise above
maximum exposure limits the Metro system raises
alarms to instigate site evacuation. By integrating
the gas monitoring system and ventilation control
not only are harmful gases kept to safe levels but
building running costs are also minimised.
The system allows for two separate radial
circuits up to 1km (3000 feet) long using industry
standard cable. Each circuit provides power and
communications for up to 125 detectors.
Each system is able to monitor 250 toxic, 125
flammable or a mix of 80 toxic and 80 flammable
detectors. The AC system design ensures no
booster power supplies are required to achieve
long cable runs, greatly simplifying the system
specification, installation and operation.
Equipment installation and commissioning is kept
as simple as possible. A wall-mounting bracket is
provided to which the slim line controller is fitted.
All cables and conduits enter the lower side of the
controller via the pre-formed knockouts. Clearly
marked terminals ensure cabling connections are
rapidly completed.
Once the controller and detectors are installed
and powered up, the controller automatically
recognises which detectors are fitted. Adjustment
of detector settings can be made via an infrared
remote control unit as required.
With up to 250 addressable gas detectors
fitted to a system, each with 4 alarm levels, up
to 1000 alarm events can be detected by the
controller, all of which are logged for later review.
Grouping, voting and activation of up to eight fully
programmable relays can be set up via the
push-button interface or optional PC software.
Each relay can be configured for normally
energized/de-energized, latching/non-latching
and on/off delay operation. Manual override
switches for all relays are included as standard
in the controller. In addition system operation
may be forced remotely via a Remote Override
Box if required.
Easy to specify, install and operate, used as a
standalone gas monitoring system or as part of
a wider building management system, the Metro
gas detection system ensures people are kept safe
from gas hazards and building operating costs
are minimised.
Installation Details/
Technical Summary
Other Equipment Available
Text Signs
all or ceiling mounted warning signs. Text only viewable once light is activated. Available in W
multiple languages.
Audible & Visual Alarms
R ange of ultra-bright Xenon flashing lights and high intensity audible alarms. Available singly or as
combined audiovisual alarm units.
UPS (Battery Backup)
nline and line interactive range of uninterruptible power supplies (UPS) depending on site O
requirements. Varying back up capacity subject to project needs.
Application Example
Underground Car Park
Typical Equipment Requirements
Item Quantity Power Total Power
Metro Controller x1
15VA each 15VA Capable of monitoring up to 250 detectors over 2km (6000 feet)
Metro CO Detector
x 11 4.8VA each 52.8VA 1 per 400m2 typically required mounted at 1.5m (5 feet) above
ground level
Metro LPG Detector
x 11 8VA each 88VA Mounted at approximately 0.2m (0.7 feet) from ground level below CO detector Not required in all countries
Vandal Proof Guard x 22 N/a N/a Flush or surface mounting option available
Text Signs x5
160VA each 800VA Should be positioned so as to be visible every 30m (100 feet)
Audible/Visual Alarm x5
15VA each 75VA Installed along side Text Signs typically
Total Power Required (Normal Operation) 155.8VA
Total Power Required (Full Alarm) 1030.8VA
1500VA Battery Backup / UPS provides nominal run time of:
> 60 minutes (normal operation)
> 9 minutes (full alarm)
A range of supplies are available that can be tailored to specific project needs as required
Extended run times available upon request
Other equipment will be required to complete installation. Contact your Honeywell Analytics representative
General Specification
Use etro addressable gas detector control system for monitoring of flammable and toxic gas hazards commonly found where motor vehicles operate such as car parks,
M
tunnels or warehouses. Provides central monitoring of detector status, local annunciation and automatic control of ventilation and evacuation systems. Suitable for use as an indoor standalone solution or as part of a larger distributed control system
Operation
Display Ultra-cleardisplay with automatic backlight operation for dark environments. Details relay and detector status, first alarm indication with scrolling history of events, as well as providing alternate pages for review of relay output and fault histories
Other Indication
Ultra bright alarm and power LEDs
Response Time
All factory set alarms are instantaneous i.e. time weighted function is disabled. Instantaneous alarm response time 33 seconds (maximum). Time weighted alarms may be set from 1 minute to 8 hours. Alarms may be set between 10% and 90% of full scale
Audible Alarm 85dBA at 1m / 90dBA at 1 foot, user hush facility with re-activation on subsequent events. Can be permanently disabled for ‘silent’ operation
User Interface T hree level access for normal user, supervisor and service engineer. Normal user: Accept/reset of alarms or review of current events only
Supervisor (via key locked door): As above plus configuration/system interrogation using concealed pushbuttons
Service: As above with access to all terminal compartments via removable isolation plates
System Override Automatic/manual operation of all relays via manual override switches (service function) or via Remote Override Box
ZHC2 Infrared Remote Control Supplied with each system the ZHC2 allows convenient set up and configuration of all field devices. Field configured detector information is then downloaded
into controller to configure all inputs
Installation Details
Highlights
The Metro controller should be mounted with
the display at eye level using the mounting
bracket provided.
All cable entries are made from the bottom via
pre-formed M16/M20 and 3/4" NPT
knockouts as appropriate to the method of
cable installation.
The system electrical supply should be made via
a lockable fused isolator suitable for the overall
power requirements.
5 core, AC rated, 1mm2 (17AWG) minimum,
with overall screen should be used for
installation. Cable may be channelled though
conduit depending on site practice. Continuity of
the screen should be maintained throughout the
system for maximum resistance to RFI.
Dimensions
Wiring Arrangement Screening
Power wires must loop through Ferrite, as shown.
Controller
Detector 1
(L)ive
(N)eutral
S+
S- To next detector
Shield terminated
through gland
Star point
FE Screen
To avoid ‘ground loops’ screens should only be bonded to Earth at the controller.
For improved EMC/RFI performance ensure
continuity of screen throughout all detectors.
Via Functional Earth (FE) Installation Details
System Overview
The maximum installed cable length is 1km
(3000 feet) per circuit of up to 125 gas
detectors. Two inputs are available providing
a maximum system capacity of up to 250
detectors over 2km (6000 feet).
A range of associated equipment is available for
use with the Metro system providing users with
a ‘one stop shop’ for all their requirements.
For further information also see the Metro
Detector datasheet or request our
installation guide from your
Honeywell Analytics representative.
Terminal Detail
AC INPUT
230Vac +/- 10% 50Hz
(1.1kVA maximum)
FE
Functional Earth
FE
Functional Earth
General Specification cont...
Electrical
Supply
2 30Vac +/- 10% 50Hz
Maximum power (controller only) 15VA
Add power consumption for ‘other’ field devices as required
Detector Inputs E ach circuit provides power and communications for up to 125 detectors. Each system is able to monitor 250 toxic, 125 flammable or a mix of 80 toxic and 80 flammable detectors.
Each detector provides 4 levels of alarm (instantaneous or time weighted) and fault indication
Pulse width modulated digital link for robust communications between detector and controller
Communications R S485 bus providing detector address, gas type and general status via:
9 pin ‘D’ connector (for local commissioning and setup)
Wired terminals (for permanent connection to control rooms etc)
Relays 8 x SPCO 5A, 240Vac relays (non inductive load). Fully programmable as normally
energized/de-energized, on/off delay, grouping and voting logic
Environmental
IP Rating Indoor use, IP44 in accordance with EN60529:1992
Weight 3.8kg (8.4lb) 0
Operating Temperature -10°C to +40°C (14°F to 104°F)
Operating Humidity 10-90%RH (non condensing)
Operating Pressure 90-110Kpa
Storage Conditions -40°C to +80°C (-40°F to +176°F), 20 to 80%RH (non condensing)
Ordering Information
Contact Honeywell Analytics:
Contact Honeywell Analytics:
Europe, Middle East, Africa
Europe, Middle East, Africa
Life Safety Distribution AG
Life Safety Distribution AG
Wilstrasse 11-U31
Wilstrasse 11-U31
CH-8610 Uster
CH-8610 Uster
Switzerland
Switzerland
Tel: +41 (0)44 943 4300
Tel: +41 (0)44 943 4300
Fax: +41 (0)44 943 4398
Fax: +41 (0)44 943 4398
[email protected]
[email protected]
Americas
Americas
Honeywell Analytics Distribution, Inc.
Honeywell Analytics Distribution, Inc.
405 Barclay Blvd.
405 Barclay Blvd.
Lincolnshire, IL 60069
Lincolnshire, IL 60069
USA
USA
Tel: +1 847 955 8200
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
Toll free: +1 800 538 0363
Fax: +1 847 955 8208
Fax: +1 847 955 8208
[email protected]
[email protected]
Asia Pacific
Asia Pacific
Honeywell Analytics Asia Pacific
Honeywell Analytics Asia Pacific
#508, Kolon Science Valley (1)
#508, Kolon Science Valley (1)
187-10 Guro-Dong, Guro-Gu
187-10 Guro-Dong, Guro-Gu
Seoul, 152-050,
Seoul, 152-050,
Korea
Korea
Tel: +82 (0)2 2025 0307
Tel: +82 (0)2 2025 0307
Fax: +82 (0)2 2025 0329
Fax: +82 (0)2 2025 0329
[email protected]
[email protected]
Technical Services
Technical Services
[email protected]
[email protected]
www.honeywell.com
www.honeywell.com
Each control panel is supplied complete with mounting bracket, ZHC2 Infrared Remote
Control and Operating Instructions
Part Number Description
MCXX Metro control panel for up to 250 gas detectors. 230Vac +/- 10% 50Hz
Shipping Details S hipping carton dimensions: 445mm x 405mm x 180mm (17.5" x 15.9" x 7.1")
Gross weight: 5.1kg (11.2lb)
Other Equipment
MDF1S Metro flammable gas detector (0-100% LEL Propane) c/w surface mount guard
MDF1F Metro flammable gas detector (0-100% LEL Propane) c/w flush mount guard
MDC1S Metro CO gas detector (0-300ppm) c/w surface mount guard
MDC1F Metro CO gas detector (0-300ppm) c/w flush mount guard
MDN1S
Metro NO2 gas detector (0-10ppm) c/w surface mount guard
MDN1F
Metro NO2 gas detector (0-10ppm) c/w flush mount guard
MKXX
Remote override box
Calibration Equipment
MDCC Calibration cup for detector
ZCALREG1 Pre-set 0.3l/m (300cc/min) flow regulator
SPPPTUB 1m Tygon tubing (suitable for all gases)
2302D0765 Carry case for up to 2x2AL gas cylinders, regulators, tubing
For calibration gas contact your local Honeywell Analytics representative
Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions. Data may change, as well as legislation, and you are strongly advised to obtain copies of the most
recently issued regulations, standards, and guidelines.
This publication is not intended to form the basis of a contract.
H_Metro Controller_DS0330_V2_EMEA
09/07
© 2007 Honeywell Analytics
11134