/LQH WHVW IXQFWLRQ /,7( 1MRK 580 127-BEN Page 1 Revision: Issued: November 2002 Data subject to change without notice )HDWXUHV • Intended for railway systems (16 2/3, 50 or 60 Hz) • Based on single voltage measurements • Tests the line before the regular breaker closes $SSOLFDWLRQ The line testing function, LITE is intended for single-phase systems where a test breaker is installed in parallel with the regular circuit breaker. The line testing function is part of a test function that determines whether the line is clear of faults before the line-breaker receives the closing pulse. This should occur with manual closing and breaker closing from automatic reclosing (AR) control equipment. In addition to the line check function, the test equipment principally consists of the reclosing function, paralleling/energizing function, test breaker, line breaker and measuring unit. )XQFWLRQDOLW\ The function continuously measures the voltage on the line and the busbar. The input voltage signals are filtered, and a separate trip counter prevents high overreaching or under- )XQFWLRQEORFN LITE- /,7( BLOCK OPENCB TESTON STARTAR CBCLOSED CLOSECB TROPEN BLKTB TESTOFF NOTEST TBCLOSED INTEST START en02000557.vsd • Reduces the risk of closing against fault • Based on line voltage measurement after closing test breaker or line and busbar voltage mesurement • The function can be disabled by selected external conditions Two different operating methods can be chosen. • • Closing of the line-breaker is permitted if the test-breaker is connected and the line voltage, when energized via the testbreaker, is higher then the set minimum line voltage. Closing of the line-breaker is permitted if both the line and busbar voltage is higher then the minimum voltage or if the line is energized via the test-breaker and the line voltage is higher than the set minimum line voltage. reaching of the measuring elements. A check is made in the function's measuring and logic circuits to see whether the established conditions to allow breaker closing are met. /LQH WHVW IXQFWLRQ /,7( 1MRK 580 127-BEN Page 2 ,QSXWDQGRXWSXW VLJQDOV 7DEOH ,QSXWVLJQDOVIRUWKH/,7(/,7(IXQFWLRQEORFN 6LJQDO 'HVFULSWLRQ BLOCK Signal that blocks the line testing function TESTON Start signal for testing the line testing equipment CBCLOSED Signal for line-breaker closed TROPEN Signal for test-breaker open TESTOFF Resetting signal for testing the line testing function. TBCLOSED Signal for test-breaker closed START Start signal for line testing function Path in local HMI: ServiceReport/Functions/LineTest/FuncOutputs 7DEOH 2XWSXWVLJQDOVIRUWKH/,7(/,7(IXQFWLRQEORFN 6LJQDO 'HVFULSWLRQ OPENCB Tripping signal to the line-breaker STARTAR Start signal to the reclosing equipment CLOSECB Closing signal to the line-breaker BLKTB Signal that blocks the closing of the test-breaker NOTEST Indication for manual line-testing, Off INTEST Indication for manual line-testing, On 7HFKQLFDOGDWD 7DEOH /,7(/LQHWHVWIXQFWLRQ )XQFWLRQ 6HWWLQJ5DQJH $FFXUDF\ +] +] ULTest 10 - 80 % of U1b in steps of 1 % +/- 2.5 % of Ur +/- 3.0 % of Ur ULNormal 30 - 100 % of U1b in steps of 1 % +/- 2.5 % of Ur +/- 3.0 % of Ur UBNormal 30 - 100 % of U5b in steps of 1 % +/- 2.5 % of Ur +/- 3.0 % of Ur t 0.000 - 60.000 in steps of: 0.001 s +/- 0.5 % +/- 10 ms +/- 0.5 % +/- 10 ms 0DQXIDFWXUHU $%%$XWRPDWLRQ7HFKQRORJ\3URGXFWV$% Control & Force Measurement Substation Automation SE-721 59 Västerås Sweden Tel: +46 (0) 21 34 20 00 Fax: +46 (0) 21 14 69 18
© Copyright 2025 Paperzz