NA2XS(FL)2Y 6/10 kV, 12/20 kV, 18/30 kV

NA2XS(FL)2Y 6/10 kV, 12/20 kV, 18/30 kV
XLPE-insulated, alu-conductor, single core, longitudinally and crosswise watertight, screened,
PE-sheath
Technical data
Cable structure
Properties
• XLPE-insulated power cables acc. to
DIN VDE 0276 part 620, HD 620 S2
and IEC 60502
• Temperature range
during installation up to -20°C
• Operating temperature
max. + 90°C
• Short circuit temperature
250°C (short circuit duration max. 5 s)
• Nominal voltage
U0/U 6/10 kV, 12/20 kV, 18/30 kV
• Operating voltage, 50 Hz
for 6/10 kV = max. 12 kV
for 12/20 kV = max. 24 kV
for 18/30 kV = max. 36 kV
• Test voltage
for 6/10 kV = 21 kV
for 12/20 kV = 42 kV
for 18/30 kV = 63 kV
• Minimum bending radius
15x cable Ø
• Power ratings
see "Technical Infromations"
• Aluminium-conductor, to
DIN VDE 0295 cl.2, multi-wire,
BS 6360 cl.2, IEC 60228 cl.2
• Inner semi-conducting coating
• Core insulation of cross-linked polyethylene
(XLPE), compound type DIX8 to HD 620 S2
• Outer conductive layer extruded and permanently welded with the core insulation
• Longitudinally watertight,
conductive wrapping
• Screen: Braiding of copper wires with
one or two tapes applied helically
• Longitudinally watertight wrapping
• Aluminium tape spliced with
PE sheath
• Outer sheath of PE
compound type DMP2 to HD 620 S2
• Sheath colour: black
• Sheath wall thickness
nominal value 2,5 mm
• The materials used during manufacturing
are cadmium-free, contain no silicone
and are free from substances harmful
to the wetting properties of lacquers
• Installation notes
To guarantee an optimum on operating
reliability the extruded semi-conductive
layer is spliced with the insulation for long
duration. For this reason we recommend
a peeling tool for installation
Note
• rm = round conductor, multi-wire
• Further types and dimensions on request.
• AWG sizes are approximate equivalent
values. The actual cross section is in mm².
Application
Installation primarily for power utility grids and in cable ducts, outdoors, underground and in water, and also on pallets for manufacturing plants,
switchgear and power stations. The resistant Al/PE-laminated sheathing acts as a cross water barrier. It inhibits the diffusion of water. In case of
sheathing damage, water impact is contained at the flaw. The cable can be severely mechanically stressed during installation and operation. The PE
sheathing is not flame-retardant to DIN EN 60332-1-2. The internal conductive layer between conductor and VPE insulation and the adherent external
conductive layer on the VPE insulation guarantees a design with high operational safety and no partial discharge.
Part no.
27.09.2016 / Dimensions and specifications may be changed without prior notice.
38062
38063
38064
38065
38066
38067
38068
38069
38070
38071
38072
38073
38074
38075
38076
33089
38077
38078
38079
38080
38081
38082
No.cores x
cross-sec.
mm²
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
1 x 630
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
1 x 630
rm / 16
rm / 16
rm / 16
rm / 16
rm / 25
rm / 25
rm / 25
rm / 25
rm / 35
rm / 35
rm / 35
rm / 16
rm / 16
rm / 16
rm / 16
rm / 25
rm / 25
rm / 25
rm / 25
rm / 35
rm / 35
rm / 35
Operation
voltage
max.
12
12
12
12
12
12
12
12
12
12
12
24
12
24
24
24
24
24
24
24
24
24
Nominal
voltage
kV
6 / 10
6 / 10
6 / 10
6 / 10
6 / 10
6 / 10
6 / 10
6 / 10
6 / 10
6 / 10
6 / 10
12 / 20
12 / 20
12 / 20
12 / 20
12 / 20
12 / 20
12 / 20
12 / 20
12 / 20
12 / 20
6 / 10
Insulation
thickness
mm
3,4
3,4
3,4
3,4
3,4
3,4
3,4
3,4
3,4
3,4
3,4
5,5
5,5
5,5
5,5
5,5
5,5
5,5
5,5
5,5
5,5
5,5
Screen
cross-sec.
mm²
16
16
16
16
25
25
25
25
35
35
35
16
16
16
16
25
25
25
25
35
35
35
Outer Ø
app. mm
30,0
32,0
33,0
34,0
36,0
38,0
40,0
42,0
46,0
49,0
51,0
35,0
36,0
38,0
39,0
41,0
43,0
45,0
47,0
50,0
54,0
55,0
Cop.
weight
kg / km
182,0
182,0
182,0
182,0
283,0
283,0
283,0
283,0
394,0
394,0
394,0
182,0
182,0
182,0
182,0
283,0
283,0
283,0
283,0
394,0
394,0
394,0
Alu weight Weight
AWG-No.
kg / km
app. kg / km
145,0
203,0
276,0
348,0
435,0
537,0
696,0
870,0
1160,0
1450,0
1827,0
145,0
203,0
276,0
348,0
435,0
537,0
696,0
870,0
1160,0
1450,0
1827,0
710,0
890,0
1100,0
1330,0
1450,0
1580,0
1780,0
1990,0
2320,0
2690,0
3160,0
870,0
1060,0
1280,0
1520,0
1650,0
1800,0
2000,0
2230,0
2580,0
2980,0
3480,0
1
2/0
3/0
4/0
300 kcmil
350 kcmil
500 kcmil
600 kcmil
750 kcmil
1000 kcmil
1250 kcmil
1
2/0
3/0
4/0
300 kcmil
350 kcmil
500 kcmil
600 kcmil
750 kcmil
1000 kcmil
1250 kcmil
Continuation NA2XS(FL)2Y 6/10 kV, 12/20 kV, 18/30 kV
XLPE-insulated, alu-conductor, single core, longitudinally and crosswise watertight, screened,
PE-sheath
Part no.
33084
33085
38083
38084
38085
38086
38087
38088
38089
38090
38091
No.cores x
cross-sec.
mm²
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
1 x 630
rm / 16
rm / 16
rm / 16
rm / 16
rm / 25
rm / 25
rm / 25
rm / 25
rm / 35
rm / 35
rm / 35
Operation
voltage
max.
36
36
36
36
36
36
36
36
36
36
36
Nominal
voltage
kV
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
10 / 30
18 / 30
18 / 30
18 / 30
18 / 30
Insulation
thickness
mm
8
8
8
8
8
8
8
8
8
8
8
Screen
cross-sec.
mm²
16
16
16
16
25
25
25
25
35
35
35
27.09.2016 / Dimensions and specifications may be changed without prior notice.
Dimensions and specifications may be changed without prior notice. (RQ03)
Outer Ø
app. mm
39,0
40,0
42,0
44,0
45,0
47,0
49,0
52,0
55,0
30,0
60,0
Cop.
weight
kg / km
182,0
182,0
182,0
182,0
283,0
283,0
283,0
283,0
394,0
394,0
394,0
Alu weight Weight
AWG-No.
kg / km
app. kg / km
145,0
203,0
276,0
348,0
435,0
537,0
696,0
870,0
1160,0
1450,0
1827,0
1100,0
1300,0
1530,0
1780,0
1920,0
2080,0
2300,0
2550,0
2960,0
3380,0
3900,0
1
2/0
3/0
4/0
300 kcmil
350 kcmil
500 kcmil
600 kcmil
750 kcmil
1000 kcmil
1250 kcmil