1 A Wide Area Synchrophasor Based ANN Transient Stability Predictor for the Egyptian Power System Fahd Hashiesh, Member, IEEE, Hossam E. Mostafa, Member, IEEE, Ibrahim Helal, Member, IEEE and Mohamed M. Mansour, Senior Member, IEEE Abstract--This paper proposes an Artificial Neural Networks (ANN) based technique for transient stability prediction. The ANN makes use of the advent of Phasor Measurements Units (PMU) for real-time prediction. Rate of change of bus voltages and angles is used to train a two layers ANN. Potential of the proposed approach is tested using the Egyptian Power System (EPS) as a study system. common reference for the phasor calculations at all different locations. Index Terms-- Artificial Neural Networks, Egyptian Power System, Phasor Measurements Units, Synchrophasor, Transient Stability Prediction, Wide Area Applications. R I. INTRODUCTION eal time data can be highly valuable information for proper protection and control actions, which could be taken to ensure the reliability of power system. Also the availability of real time system information will enable advanced smart grid applications that were not possible before. The primary benefits of a real-time wide area monitoring system could be to [1]: • Provide early warning of unstable system conditions, so operators can take fast corrective actions. Early warning or indication of grid problems include (abnormal angle difference; inter-area oscillations; voltage stability); • limit the cascading effect of disturbances (by providing wide-area system visibility); and • Improve transmission reliability planning and allow for immediate post-disturbance analysis and visualization through the use of archived monitoring system data. Now Phasor technology is considered to be one of the most important measurement technologies in power systems due to its unique ability to sample voltage and current waveforms data in synchronism with a GPS-clock and compute the corresponding 50/60 Hz phasor component from widely dispersed locations as shown in Fig. 1. This synchronized sampling process of the different waveforms provides a Fahd Hashiesh is with ABB Limited, Staffordshire, United Kingdom (e-mail: [email protected]). Hossam E. Mostafa is with Electrical Department, Faculty of Industrial Education Suez Canal University, Egypt (e-mail: [email protected]) Ibrahim Helal is with Department of Electrical Power and Machines Engineering, Faculty of Engineering, Ain Shams University, Cairo, Egypt. Mohamed M. Mansour is with Department of Electrical Engineering, King Fahd University of Petroleum & Mineral, KSA (email: [email protected]) Fig.1 Phasor Measurements at Remote Locations After predicting instability, the power systems should be ideally separated to maintain a balance between load and generation in each of the separated areas. To accomplish this, out-of-step tripping should be used at the desired points of separation and out-of -step blocking used elsewhere to prevent separating the system in an indiscriminative manner. Where a load-generation balance can’t be achieved in a separated area and there is excess load as compared to generation, some means of shedding for non-essential loads have to be done in order to avoid a complete shutdown of the area [2]. Planning studies of power system dynamics have resulted in number of techniques used to detect power system instabilities. In the past decade two techniques have become popular for this application. They are; the Lyapunov or energy function approach and the extended equal area criterion. It should be noted that this techniques were not developed with real time applications in mind [3]. Liancheng Wang and Adly A. Girgis in [4] proposed a method for power system transient instability detection. The method is based on generator angle, angular velocity and their rate of changes. According to the proposed method, system instability or out-of step condition is detected by identifying the characteristics-concave or convex of a surface on which the post-fault system trajectory lies. The system is unstable when the surface is convex. 2 The authors in reference [5] present a development of an adaptive out-of-step relay. The adaptive relay seeks to make adjustments to its characteristics as system conditions change, thereby making it more attuned to the prevailing power system conditions. The reference also describes the theory of such a relay and its hardware configuration. Also, the development of these relay with the use of PMUs is given in [6, 7]. On the other hand, one of the primary objects of the Power System Engineering Research Center (PSERC) projects [8] is to develop an application that dealt with on-line transient stability assessment using measurements from PMUs. This is done through the development of a software tool that uses artificial intelligence (decision trees). The proposed tool is developed by training a set of trees based on simulations conducted offline. Another concept of using decision trees is presented in [9]. Development of different techniques and approaches to determine the system instabilities are also the aim of many other researchers. In reference [10], an approach based on observation of the difference between substations phase angles is presented. Another approach using equal area criteria is given in [11]. In [12] a concept of using autoregressive model, a kind of time-series analysis, is also demonstrated. A method for predicting transient stability using fuzzy hyper rectangular composite neural network (FHRCNN) is proposed in [13]. It computes the velocities and acceleration for generator angles on a time window of eight cycles, with a total of six FHRCNN inputs per generator. The criterion for instability used is whether the difference between any two generator angles exceeds π radian in the first second after clearing time or not. Reference [13] indicates that the selection of π radian is just for illustration of the used scheme and it must be calculated as it heavily depends on the characteristics of power system under study. Some other new methods using the advance of real time monitoring and/or ANN methods to predict the transient instability are presented in [14 - 16]. In this paper an on-line ANN predictor is proposed to predict transient instabilities in the power system. The proposed ANN predictor makes use of the advent of PMU for real-time monitoring. The determination of angle of instability is carried out with only two inputs for each generator and is processed within three cycles prediction window. Implementation of the proposed approach is applied on the Egyptian Power System (EPS) as a case study. Good prediction is achieved through the tested conditions. II. ON-LINE DETERMINATION OF ANGLE OF INSTABILITY In this study, the used algorithm for on-line determination of angle of instability given in [17] is selected to be the base of the proposed predictor. The algorithm detects the fast separation of phase angle among the critical areas using the PMUs. In general center of angles can be defined as: N δ COA ∑ δ j=1 N = ∑ ' j H H j (1) j j=1 Where, N is the number of generators δj’ is the internal rotor angle of generator j Hj inertia time constant of generator j Although the internal machine rotor angle cannot be directly measured, researchers in [18] built an ANN platform to estimate rotor angles and speeds from measurements of PMUs installed at generator buses. In this work, as per assumption given in [17], the internal angle will be substituted with the phase angle of the high side bus voltage, which is normally monitored by PMUs. Similarly, the inertia time constant H is substituted by the high side active power injections for the generator as machine inertia is typically proportional to the real power output. Assuming the availability of installed PMUs at all generators buses, the on-line phase angle measurement for each generator bus δj can be measured. Where, j=1, 2, 3, ..n and n is the number of generator bus. Therefore equation (1) can be re-written as: ∑ = ∑ n δc j =1 n δ j Pj P j =1 j (2) Where, δc is the center of angles of the system δj is the phase angle of bus voltage for generator bus j n is the number of generator buses in the network Pj is the current MW generation schedule at generator bus j Another term Δδj can defined as: Δδ j = δ j − δ c (3) Two accumulated integral terms are then computed, Ωa and Ωd, respectively to denote the speeding up or slowing down of generator j with respect to the center of angles calculated in the previous step. Defining Ωa as the integral for Δδj, whenever Δδj continuously stays above a threshold, say Δδ*a. When Ωa grows above a pre-specified value, say Ω*a, a remedial action is initiated. This remedial action can be either generator tripping or activating load shedding. In this case as generator j is speeding away from the rest of the system, accordingly tripping generation is the right choice. This process can be clarified using Fig 2. From figure, it is clear that generators G1 & G2 are speeding away from reset of the system, as angle of generator G1 reaches Δδ*a, we start calculating the area under the curve as this area reaches the value of Ω*a, a tripping action should be 3 initiated at time t. For G2 the area under the curve doesn’t reach Ω*a, so, there is no action tacking. Fig. 2 A Graph Represent The Implementation of The On-line Determination of Angle of Instability Technique The computation of the Ωd is similar to accumulate the integral of Δδj below threshold, denoted Δδ*d. When Ωd grows above a pre-specified value, say Ω*d, load shedding, as a remedial action, would be initiated to mitigate the disturbance event. The threshold Δδ*a is set to be 60 degrees, and Δδ*d is set to be -70 degrees, where Ω*a and Ω*d are set to be 5 and -5 respectively. III. DEVELOPMENT OF ANN FOR ON-LINE STABILITY PREDICTION With the advent of PMU and availability of on-line measurements, it is desirable to predict system instabilities before out of step occurs and taking appropriate remedial action, such as system splitting, to avoid unnecessary cascading tripping. By using the mentioned technique, an ANN can be trained to predict system transient instabilities. In next sections a two-layer ANN for on-line transient stability predication is proposed. A. Artificial Neural Networks Neural networks are composed of simple elements operating in parallel. These elements are inspired by biological nervous systems. As in nature, the network function is determined largely by the connections between elements. Neural networks can be trained to perform a particular function by adjusting the values of the connections (weights) between elements. Commonly neural networks are adjusted, or trained, so that a particular input leads to a specific target output. Therefore, the network is adjusted, based on a comparison of the output and the target, until the network output matches the target. Typically many such input/target pairs are needed to train a network. B. Stages needed to build an ANN predictor Stage 1 Input selection; this is the first step in any pattern recognition problem; it has a direct effect on the performance and size of the ANN. Stage 2 Selection of training data. Stage 3 Selection of ANN Size (hidden neurons & layers) Stage 4 Train ANN. Stage 5 Tests and compare results. Input Selection The input data is based on number of phasor measurements cycles window, which begins one cycle after the fault clearing. The actual number of cycles will be determined in throughout the implementation on the study system (section IV) as it is strongly depends on system parameters. The rate of change for both generators bus voltages and angles are found to give more accurate instability detection status, for a total of two inputs per generator. The input vector X can be written as: X = {x1 , x2 ,..., xi ,..xn } (4) Where, xi = ( dvi dδ i , ) dt dt (5) and, v is the generator bus voltage magnitude δ is generator bus voltage angle t is the time window n is the number of generators buses ANN Selection The ANN proposed is a two layer feed-forward type, with two hidden layers as shown in Fig. 3. ANN Output The output of the ANN consists of one neuron representing the system status. Its values are as follows 0 Æ System is stable after fault clearing 1 Æ System is unstable after fault clearing Fig. 3 Proposed Artificial Neural Networks 4 Table 1 Simulated Components in PSAF for EPS IV. IMPLEMENTATION ON THE EGYPTIAN POWER SYSTEM (EPS) The total installed generation capacities of the EPS in 2008 are about 23,530 MW with a peak load of 21,250 MW during summer [19]. The generation types of the EPS vary between thermal, which represents 89.8% of total generation, hydro 9.3% & wind 0.9%. The Egyptian grid’s transmission system is covering Egypt and linked by interconnector lines to neighborhood countries as Jordan from east & Libya from West. The total length of transmission lines within Egypt is more than 430,000 km, covering different high voltage levels of 500 kV, 400 kV, 220 kV, 132 kV & 66 kV. Figure (4) shows EPS transmission lines where voltage levels are presented by different line styles, also main generation stations are indicated. Total number of Buses Transmission Lines Power Transformers Generation Stations Shunt Capacitors Shunt Reactors Load Buses System Frequency Total Generation Total Demand Fig. 4 Egyptian Power System 500/220/132 kV transmission lines The Power Systems Analysis Framework (PSAF) software [20] is chosen for simulating the dynamic response of the EPS. Fig 5 shows a single line diagram for the simulated system including buses (stations), generating stations and transmission lines. The total numbers of simulated components using PSAF are summarized in Table 1. 218 400 154 31 6 11 134 50 Hz 19.5 GW 19.0 GW Fig. 5 EPS 500/220/132/kV Single Line Diagram The test steps for implementing & evaluating the proposed ANN predictor are as follows: Step 1 Step 2 Applying line faults at different locations in the system to test the stability of the EPS after fault clearing. Building the on-line ANN predictor. (Using the five stages in the last section) 5 A. Step 1- Applying line faults at different system locations A number of 52 fault cases are applied at different system locations to cover all the grid zones. All faults are applied at 0.1 second (5 cycles) and cleared by removing the fault and disconnect the faulted line or double lines with fault duration of 10 cycles. A MATLAB [21] m-file is created using the algorithm early discussed in section II to detect the system stability after clearing the fault. As a result, 27 cases appeared to be unstable after fault clearing. The results for this step can be summarized Table (2). The table also indicates the time (in cycles) required to initiate a remedial action. Using that time the size of predication window can be determined. that A.SOLT generation station is the first to lose its synchronism from rest of system (move away from center of angles). Also from Table 2 the maximum recommended time to initiate remedial action is 20 cycles (5 cycles after tripping the fault). TABLE 2 THE 27 UNSTABLE CASES & RAS ACTIONS Case # Faulted Bus Lines Removed Time to initiate remedial action (Cycles) 20 1 A.SOLT. A.SOLT - SUEZ 220 2 A.SOLT. A.SOLT. - MANAYEF 20 3 ABU_KIR ABU_KIR - I. BAROD 20 4 C.SOUTH C.SOUTH - W. HOUF 41 5 DAM.GAS DAM.GAS - DAMANH 19 6 DAM.GAS DAM.GAS - MAHMOUDI 19 7 GN.CN2 GN.CN2 - HELOPLS 45 8 GN.CN2 GN.CN2 - BASOUS 2 48 9 HIGH-DAM HIGH.DAM - D1 HD 5 19 10 D1 HD 5 D1 HD5 - N. HAMADY 19 11 ISNA P ISNA P - ISNA 20 12 ISNA ISNA - LUXOR 21 13 K.DWAR K.DWAR - ABIS 21 14 K.DWAR K.DWAR - DAMANH 21 15 AMERIYA AMERIYA - K.DWAR 26 16 AMERIYA AMERIYA - DEKHALA 26 17 DEKHALA DEKHALA – EZZ DEK. 27 18 EZZ-DEK. DEKHALA – EZZ DEK. 27 19 KURIMAT KURIMAT - FAYOUM 19 20 KURIMAT KURIMAT - BENI SUEF E. 19 21 KRIMA500 KRIMA500 - TABEN 22 22 MAHMOUDI MAHMOUDI - DAM.GAS 20 23 A.MOUSA A.MOUSA - TABA 22 24 A.MOUSA A.MOUSA - SUEZ 500 22 25 SUEZ 500 A.MOUSA - SUEZ 501 22 26 N.ASSP N.ASSP - MALAWI 48 27 N.H.P.S N.H.P.S - NH 220 24 To evaluate the results given in Table 2, case#2 and case #7 will be demonstrated in more details. Starting with case#2, Fig 6 shows the generators bus angle after fault clearing. It is clear Fig. 6 Bus Angles for Case # 2 For case #7, Fig 7 shows that the generation station CN2 is the first to lose synchronism. Again and from Table 2 the required time to initiate a remedial action is 30 cycles after clearing the fault. Fig. 7 Bus Angles for Case # 7 Table 3 highlights the final conclusion of the first step of the implementation test. It can be noted from this step that the minimum time required to initiate a remedial action is 19 cycles (i.e. 4 cycles after clearing the fault). TABLE 3 RESULTS OF APPLYING FAULTS AT DIFFERENT SYSTEM LOCATIONS Total number of applied faults System stable cases after clearing faults System unstable cases after clearing faults Min. time to initiate the remedial action Max. time to initiate the remedial action 52 25 27 19 cycles 48 cycles 6 B. Step (2) - On-line transient stability predictor for EPS The Neural Network toolbox in MATLAB software is used to design the online ANN predictor. After many trial & errors for different structures of ANN networks with different inputs pattern, the rate of change of bus voltages & angles obtained from PMUs within a specific window of time, found to give the most accurate results. A proposed ANN with two hidden layers Feed–Forward Back Propagation is chosen to predict system instabilities. The ANN is built using 3 cycle prediction window, total number of 62 inputs (2 input for each generation bus) and one output (0 for stable system or 1 for unstable systems). The training & transfer functions of the ANN predictor are TRAINLM and TANSIG respectively 38 % of the study cases (from last step) are used to train the ANN, the rest 62% of the cases (Which the ANN never seen before) are used for the testing purpose. The proposed ANN predictor succeeded in estimating the system stability status in 91 % of the tested cases (Fig. 8 & 9). Egyptian Power System about 38 % of the simulated cases on the Egyptian Grid are chosen for training purpose, resulting in right estimation of 91 % of the tested cases. VI. REFERENCES [1] [2] [3] [4] [5] [6] [7] [8] Training 38% [9] Testing 62% [10] Fig. 8 A Chart Showing the Percentage of the Training & Testing Sets. [11] [12] Failed 9% [13] [14] Succeeded 91% [15] Fig. 9 A Chart Showing the Percentage of Success of the Proposed ANN Predictor [16] V. CONCLUSION A two layer on-line ANN transient stability predictor is proposed. This predictor makes use of PMU readings to estimate the stability status after system disturbance. Rate of change of bus voltage and angles, resulted from PMU, are used to train and test the proposed ANN. Dynamic behavior under different disturbances of the Egyptian power system is considered for different case studies. The proposed predictor uses only 3 cycles prediction window, giving enough time for activating remedial action in case of instabilities. With the implementation of the proposed On-line ANN Predictor in the [17] [18] [19] [20] [21] D. Novosel, V. Madani, B. Bharagava, K. Vu, and J. Cole, “Dawn of the Grid Synchronization,” IEEE Power & Energy Magazine, pp. 49–60, 2008. John Berdy, “Application of Out of Step Blocking and Tripping Relays”, General Electric Company, GE Publication GER-3180. A. G. Phadke and J. S. Thorp, “Monitoring and simulating electric power system operation by phasor measurements,” Prepared by Virginia Polytechnic Institute and State University, Blaksburg, VA 24061, January 1995. Liancheng Wang and Adly A. Girgis, “A New Method for Power System Transient Instability Detection”, IEEE Transactions on Power Delivery, Vol. 12, No. 3, pp. 1082-1089, July 1997. V. Centeno, A. G. Phadke, A. Edris, J. Benton, M. Gaudi, and G. Michel, "An Adaptive Out-of-Step Relay", IEEE Transactions on Power Delivery, Vol. 12, No. 1, pp. 61-71, January 1997. Virgilio Centeno, Jaime De La Ree, A.G. Phadke, Gary Michel, J. Murphy, and R. Burnett, "Adaptive Out-of-Step Relaying Using Phasor Measurement Techniques", IEEE Computer Applications in Power, pp. 12-17, October 1993. Bozchalui M.C. and Sanaye-Pasand M., "Out of step relaying using phasor measurement unit and equal area criterion” IEEE Power India Conference, 2006. Vijay Vittal et al,” A Tool for On-line Stability Determination and Control for Coordinated Operations between Regional Entities Using PMUs”, Power Systems Engineering Research Center, PSERC Publication 08-01, January 2008. Steven Rovnyak, Stein Kretsinger, James Thorp, and Donald Brown, "Decision Trees for Real-Time Transient Stability Prediction", IEEE Transactions on Power Systems, Vol. 9, August 1994. Y. Ohura et al,” A predictive out-of-step protection system based on observation of the phase difference between substations”, IEEE Transaction on Power Delivery, Vol. 5, No. 4, pp. 1695-1704 , November 1990. Shengli Cheng and Sachdev M.S., “Out-of-step protection using the equal area criterion”, IEEE Electrical and Computer Engineering, Canadian Conference on 1-4 May 2005, pp. 1488 – 1491, 2005. Yamashita K. and Kameda H., “Out-of-step prediction logic for widearea protection based on an autoregressive model”, IEEE Power Systems Conference and Exposition, PES 2004, Vol. 1, pp. 307-312, 10-13 October 2004. C-W. Liu et al., "Neuro-Fuzzy Approach to Real-Time Transient Stability Prediction Based on Synchronized Phasor Measurements," Electric Power Systems Research 49 (1999), pp. 123-127. R. Ebrahimpour and E. Abharian, “An Improved Method in Transient Stability Assessment of a Power System Using Committee Neural Networks,” IJCSNS International Journal of Computer Science and Network Security, VOL.9 No.1, January 2009. A. Bahbah, and Adly A. Girgis, “New Method for Generators’ Angles and Angular Velocities Prediction for Transient Stability Assessment of Multimachine Power Systems Using Recurrent Artificial Neural Network,” IEEE Transaction on Power Systems, Vol. 19, No. 2, May 2004. F. Hashiesh, H. Mostafa, M. M. Mansour, A. Khatib and I. Helal, "Wide Area Transient Stability Prediction Using On-line Artificial Neural Networks", Proceeding of IEEE Conference, Electrical Power and Energy Conference 2008, EPEC08, Vancouver, Canada, 2008. D. Hu and Mani Venkatasubramanian, “New wide-area algorithms for detecting angle instability using synchrophasors,” Proceeding of the Western Protective Relay Conference, Spokane, WA, 2006. Alberto Del Angel et al, “Estimation of rotor angles of synchronous machines using artificial neural networks and local PMU-based quantities”, ELSEVIER Neurocomputing, Vol. 70, 2007. Ministry of Electricity & Energy (Egypt) - http://www.moee.gov.eg PSAF version 3.00, CYME International T & D Inc. Matlab Software, MathWorks, version 7.1 7 VII. BIOGRAPHY Fahd Hashiesh (M'09): was born in Cairo, Egypt, on June 7, 1973. He received his B.Sc., M.Sc. & PhD. from Faculty of Engineering, Ain Shams University, Egypt in 1995, 2003 &2009 respectively. He worked for ABB High Voltage, Egypt as a projects manager for turnkey HV substations projects from 1996 to 2001. Also he worked for SABA Electric, Egypt from 2002 to 2009. Currently he is substations design team leader with ABB Limited in the UK. His current research interests are power system control, operation and protection, power line communication, smart grid implementation & applications. His email is: [email protected] Hossam E. Mostafa (M'09): was born in Cairo, Egypt. He received his B. Sc, M. Sc & Ph. D. From Ain Shams University, Cairo, Egypt in 1987, 1994 and 1999. From 1991 to 2001, he was working in Egypt Air as second engineer. Since 2001, he has been a faculty member with the Electrical Department at the Faculty of Industrial Education (FIE), Suez Canal Univ., Egypt. He is currently an Associate Professor and Vice Dean for Student Affairs. His research interests are applying AI techniques in power system control, protection & operation. His email is: [email protected] Ibrahim Helal: was born in Kalubia, Egypt, received his B.Sc. and M.Sc. in Electrical Eng. in 1982 & 1988 from Ain Shams University, Egypt. He received his Ph.D. in 1995 from University of New Brunswick, Canada. Currently, he is Professor in the of Electrical Power and Machines, Ain Shams Univ,. He is registered as Professional Engineer in Egyptian Syndicate, and acted as independent consultant for several electrical installation and power networks planning projects. He is a member in IEEE, IEC regional committee and is the secretary of energy saving committee in the Scientific Research Academy of Egypt. Prof. Mohamed M. Mansour: (M’81, SM’08) B.sc & M. Sc. From Ain Shams University, Cairo, Egypt in 1975 and 1980 respectively. His PhD was from University of Manitoba, Canada, in 1983. He has been a Prof. of power system in Dept of Electrical Engineering in Ain Shams University (since 1995). He is currently on leave as a Chair Professor in King Fahd University of Petroleum & Minerals (KFUPM) in Suadi Arabia. He had been a visiting Prof in many universities in Canada, Egypt, Kuwait and Suadi Arabia. He has more than 100 published papers in journals and conferences. He supervised about 35 M. Sc. and PhD thesis (granted), mainly in protection and control on power system and/ or machine. His major research interest is in power system protection, measurement and control. His email is: [email protected]
© Copyright 2026 Paperzz