1 Sandia Frequency Shift Parameter Selection to Eliminate Non-Detection Zones H. H. Zeineldin, Member, IEEE, and S. Kennedy, Member IEEE Abstract—The Sandia Frequency Shift (SFS) method is one of the active islanding detection methods that posses small Nondetection Zones (NDZ). The effectiveness of the SFS depends to a great extent on its design parameters (cfo and k). In this letter, a formula is derived to aid protection engineers in determining the optimal parameter setting for the SFS islanding detection method. It is concluded that the parameter (k) has significant effect on the NDZ and a modified version of the SFS is proposed that relies only on this parameter. impedance load and a 100 kW inverter based DG. The DG interface control model presented in [3] was implemented and is given in Fig. 2. For the SFS islanding detection method, the inverter phase angle ( inv) can be expressed as a function of the island frequency (f), nominal frequency (fn), and the SFS parameters cfo and k [2]. (cf o + k ( f f n )) / 2 (1) inv = Index Terms— Distributed Generation, Sandia Frequency Shift, Inverter, Islanding. I I. INTRODUCTION SLANDING is a condition in which a part of the utility system, which contains both load and generation, is isolated from the rest of the utility system and continues to operate. It is important to equip a Distributed Generation (DG) with an efficient islanding detection method, capable of detecting islanding for all possible loading cases and thus minimizing, or even eliminating, the Non-Detection Zone (NDZ). The NDZ could be defined as the loading conditions for which an islanding detection method would fail. The majority of passive islanding detection methods, which rely on measuring a certain system parameter, suffer from large NDZ [1]. Active methods, on the other hand, are characterized by having smaller NDZ. Active methods that rely on frequency shifting include slide-mode frequency shift (SMS) [1], Active Frequency Drift (AFD) [2], and Sandia Frequency Shift (SFS) [2]. The SFS method has been proven to have an extremely narrow NDZ [1]. In [2] and [3], it has been shown that the performance of the SFS method is dependent on the design parameters. In this paper, we extend the work conducted in [2] by deriving a mathematical formula that aids in setting the SFS design parameters to eliminate the NDZ. A modified version of the SFS method is proposed and presented that relies on only one parameter. II. SYSTEM UNDER STUDY The system, shown in Fig. 1, consists of a distribution network represented by a source behind impedance, a constant This work was supported by the Masdar Institute of Science and Technology. H. H. Zeineldin and S. Kennedy are with the Masdar Institute of Science and Technology, Abu Dhabi, UAE (e-mail: [email protected]). Fig.1. System under study. Fig. 2. DG interface control for constant power operation. III. MODIFIED SANDIA FREQUENCY SHIFT METHOD The load phase angle can be expressed as a function of island frequency, the load resonant frequency, fo, and the load quality factor, Qf [2] tan 1[Q f ( f o / f f / f o )] (2) load = For this system to operate as a steady state island, the two phase angles in (1) and (2) must be equal, which results in the following equilibrium condition, or phase criteria [2]. (3) f o2 + f tan[ (cf o + k ( f f n )) / 2] f o / Q f f 2 = 0 Previous work has shown that the phase criteria for different islanding detection methods defines the NDZ and can be used to select appropriate parameters such that the NDZ is eliminated [2]. An important aspect of this approach, not emphasized by previous authors, is that the equilibrium point defined by the phase criterion must be unstable in order to ensure islanding detection and to eliminate the NDZ. Furthermore, the stability of the solution to (3) depends upon the relative magnitudes of the slopes of the phase angle – frequency curves defined by (1) and (2). This additional 2 “instability” condition can be expressed as: 62 (4) d load / df < d inv / df Following the slope criteria of (4), the value of k in (1) can be chosen to guarantee that the frequency will drift away from the equilibrium point defined by the phase criteria (outside of OFP/UFP threshold values). Differentiating the two expressions for the phase angle in (1) and (2), the instability condition can be expressed as follows [1 + Q 2f ( f o / f f / f o )] Load Resonant Frequency,f0 (5) It can be shown that the maximum value of the right-hand side of (5) occurs at f = fo, and hence this expression can be reduced to: (6) k > 4Q f / f 0 Equation (6) provides a guideline for protection engineers, which ensures there will be no NDZ for the SFS method. For example, to design the SFS such that it eliminates the NDZ for loads with Qf up to 7, fo would be set to 59.3 (minimum UFP limit) and Qf would be set to 7 in (6), resulting in a value of k equal to 0.15. The effect of k on the NDZ, with cf0 = 0, can be seen in the fo – Qf space shown in Fig. 3. Each pair of curves, for different values of k, define an envelope within which islanding will not be detected. As k increases, the envelope moves to the right, which confirms the result in (6). Figure 4 shows the NDZ for different values of cfo. It can be seen that k has a much more profound effect than cfo in constraining a targeted Qf within the NDZ. Thus, the proposed modified SFS equation would be (7) fn ) / 2 inv = k ( f The paper analyzes the impact of the SFS parameters on NDZ and proposes a modified SFS method. A simplified, yet equally effective, SFS is presented that relies on only one parameter “k” for islanding detection. A formula is derived to aid protection engineers to optimally set this parameter to eliminate the NDZ. Simulation results highlight the effectiveness of the proposed approach and coincide with the mathematical derivations. 61 60.5 60 59.5 59 58 0 10 1 10 Quality Factor, Q 10 2 f Figure 3 Dependence of non-detection zone on k. 62 cf = 0, k=0 0 cf = 0.05, k = 0.1 61.5 0 cf0 = 0.1, 61 k = 0.1 cf = 0.15, k = 0.1 0 60.5 60 59.5 59 58.5 58 0 10 1 10 Quality Factor, Qf 10 2 Figure 4 Dependence of non-detection zone on cfo. where k is calculated from (6) to guarantee negligible NDZ. By eliminating cfo, the effect of the SFS on power quality would be reduced [1]. The proposed islanding detection method was tested on the system shown in Fig. 1 and using the control circuit in Fig. 2. An islanding condition is simulated by opening the utility breaker at t = 3 seconds. Figure 5 show the frequency waveforms obtained using time domain simulations in the PSCAD/EMTDC environment for the various Qf values with loads that resonate at 60 Hz and k set to 0.15. It can be seen that for loads with Qf values less than 7, the island frequency becomes unstable. The frequency drifts more slowly as Qf approaches 7, while timely detection (within 2 seconds) is possible for loads with Qf values that are less than approximately 6.5. IV. CONCLUSIONS 0 0.05 0.1 0.15 58.5 Load Resonant Frequency,f0 k> 2[Q f ( f o / f 2 + 1 / f o )] k= k= k= k= 61.5 61 60.8 60.6 Q = 7.5 and Q =12.4 f 60.4 f Q =7 Frequency (Hz) f 60.2 60 59.8 Q = 5.3 f Q = 3.5 Q = 6.5 f f 59.6 59.4 Qf = 1.77 59.2 59 2 2.5 3 3.5 4 Time (s) 4.5 5 5.5 6 Figure 5 Frequency waveform for different load Qf with k set to 0.15. V. REFERENCES [1] [2] [3] M. Ropp, and W. Bower, "Evaluation of islanding detection methods for photovoltaic utility interactive power systems," International Energy Agency Implementing agreement on Photovoltaic Power Systems, Tech. Rep. IEA PVPS T5-09, March 2002. Lopes, L. A. C. and Sun, H. (2006). Performance assessment of active frequency drifting islanding detection methods. Energy Conversion, IEEE Transaction on, 21(1):171-180. X. Wang, W. Freitas, W. Xu, and V. Dinavahi, “Impact of DG Interface Controls on the Sandia Frequency Shift Antiislanding Method”, IEEE Trans. Energy Conversion, vol. 22, pp. 792-794, Sept. 2007.
© Copyright 2026 Paperzz