X26 X28 X32 X35 Y6 Y3 Y2 Y1.9

LINEAR BOX SERIES CEILING INSTALLATION NOTES:
1.
FIELD CUT CEILING PANELS AS REQUIRED TO CREATE A RANDOM STAGGERED SEAM PATTERN.
AVOID ALIGNED SEAMS.
2.
DO NOT SPLICE PANELS DIRECTLY BELOW UNIVERSAL CARRIERS. PANEL SPLICES DO NOT FIT
UNDER CARRIERS.
3.
IF UNIVERSAL CARRIERS ARE DIRECTLY FASTENED TO STRUCTURE, CARRIER-TO- CARRIER
ALIGNMENT TOLERANCES BECOME CRITICAL. CARRIER ALIGNMENT TOLERANCES SHOULD NOT
EXCEED 1/32" +/- IN ANY DIRECTION WHEN DIRECT FASTENING CARRIERS TO STRUCTURE.
FAILURE TO MAINTAIN TOLERANCES MAY RESULT IN CEILING PANEL DEFORMATION.
1 ", V.I.F.
1'-632
4.
1 Hunter Douglas Circle
5015 Oakbrook Parkway, Suite 100
Thornton, CO 80241
Norcross, GA 30093
866-556-1235
800-366-4327 / 770-806-9557
fax: 720-872-7850
fax: 770-806-0214
PROPER CARRIER TAB ALIGNMENT IS VERY DIFFICULT TO MAINTAIN WHEN CARRIER IS HARD
FASTENED TO A RIGID SUBSTRUCTURE SUCH AS T-GRID OR CR STEEL CHANNEL. FOR THIS
REASON, HUNTER DOUGLAS CANNOT ACCEPT RESPONSIBILITY FOR THE FINISHED APPEARANCE
OF THE CEILING IF THE STRICT TOLERANCE GUIDELINES OUTLINED IN NOTE #3 ARE NOT
FOLLOWED.
www.hunterdouglascontract.com
18'-919", V.I.F.
32
R
M E T A L
C E I L I N G S
R
W
O
O
D
C
E
I
L
I
N
G
S
R
11", V.I.F.
10'-916
17'-223
32", V.I.F.
15'-817
32", V.I.F.
1'-6", V.I.F.
A C O U S T I C A L
C E I L I N G S
2'-8" O.C. MAX.
CARRIER SPACING,
SEE DETAIL 1/5 THIS SET
X26
4'-0" MAX., TYP.
37'-225
32", V.I.F.
UNIVERSAL CARRIER
FOR INTERIOR
SUSPENSION REQUIREMENTS,
SEE DETAIL 1/4 THIS SET
FOR INTERIOR
SUSPENSION REQUIREMENTS,
SEE DETAIL 1/4 THIS SET
PROJECT SPECIFIC NOTES
FOR INTERIOR
SUSPENSION REQUIREMENTS,
SEE DETAIL 1/4 THIS SET
X28
9 ", V.I.F.
103'-832
UNIVERSAL CARRIER
GENERAL NOTES
10'-912", V.I.F.
FOR EXTERIOR
SUSPENSION REQUIREMENTS,
SEE DETAIL 1/5 THIS SET
FOR INTERIOR
SUSPENSION REQUIREMENTS,
SEE DETAIL 1/4 THIS SET
X32
Ceiling installation to be in accordance with ASTM C636 &
ASTM E580, and local code requirements for seismic
bracing.
2.
The purpose of these drawings is to represent installation
of Hunter Douglas products ONLY. All dimensions are to
be field verified and approved by the contractor prior to
fabrication.
3.
Return approved shop drawings to Hunter Douglas to
release for fabrication.
4.
All quantities are to be reviewed and approved by the
customer prior to fabrication.
5.
This material list is an ESTIMATE ONLY. The customer is
responsible for reviewing and verifying ALL information
listed above prior to ordering material. Excess material
will not be accepted for returns or credit. If additional
material is necessary, set-up charges may apply.
6.
Unless shown otherwise, all penetrations including light
fixtures, diffusers, speakers, sprinkler heads, etc., are to
be field located and field cut. Hunter Douglas will not be
responsible for final location and placement of
penetrations. Typically, penetrations are not dimensioned
or located on Hunter Douglas shop drawings unless the
holes are factory cut. All "fixtures" are to be
independently supported. Trim for all penetrations are by
others. Any fixture or other penetration shown is soley
based on information provided to Hunter Douglas.
7.
Architect
/ General Contractor: Please reference
appropriate contract documents for coordination with
other trades.
8.
If there are any questions in relation to Hunter Douglas
products on this project, please contact us at
1-800-366-4327 (8:00am - 5:00pm EST Monday-Friday).
36'-015
32", V.I.F.
UNIVERSAL CARRIER
FOR INTERIOR
SUSPENSION REQUIREMENTS,
SEE DETAIL 1/4 THIS SET
X35
ADD SUPPLEMENTAL CARRIERS AS
REQUIRED TO MAINTAIN MAX
PANEL OVERHANG
ADD SUPPLEMENTAL CARRIERS AS
REQUIRED TO MAINTAIN MAX
PANEL OVERHANG
UNIVERSAL CARRIER
FOR INTERIOR
SUSPENSION REQUIREMENTS,
SEE DETAIL 1/4 THIS SET
All rights reserved.
This drawing is the property of Hunter Douglas.
It may not be copied or multiplied, neither wholly nor partly.
It may not be submitted for perusal to third parties.
2'-2", V.I.F.
5 ", V.I.F.
31'-732
1.
1'-6", V.I.F.
UNIVERSAL CARRIER
FOR EXTERIOR
SUSPENSION REQUIREMENTS,
SEE DETAIL 1/5 THIS SET
UNIVERSAL CARRIER
2'-8" O.C. MAX.
CARRIER SPACING,
SEE DETAIL 1/5 THIS SET
FOR EXTERIOR
SUSPENSION REQUIREMENTS,
SEE DETAIL 1/5 THIS SET
71'-3 9 ", V
32 .I.F.
ADD SUPPLEMENTAL CARRIERS AS
REQUIRED TO MAINTAIN MAX
PANEL OVERHANG
REVISIONS:
1
1
1.
PARTIAL R.C.P. AT HD METAL CEILINGS
SCALE: 1/4" = 1'-0"
0
2'
4'
Y3
Y2
Y1.9
DATE
BY
-
-
8'
NOTES:
1. ALL EDGE TRIM PIECES TO
BE BLACK.
2. NO CLOSURE BETWEEN
PANELS AT INTERIOR.
3. ALL VISIBLE CEILING SUPPORT
MEMBERS TO BE PAINTED BLACK
AS REQUIRED.
Y6
-
FABRICATION MAY PROCEED IF
NOTES ON SUBMISSION ARE
FOLLOWED, RESUBMITTAL NOT
REQUIRED
CORRECTION & RESUBMITTAL FOR
RECORD PURPOSES REQUIRED
DRAWN BY: A PRICE
CHECKED BY:
DATE: 8/15/14
PAGE SIZE: 36" x 48" (ARCH "E")
PROJECT: SHAKE SHACK - LAS VEGAS
REJECTED AND RESUBMIT
This review is for general conformance with the
design concept and contract documents.
Markings or comments shall not be constructed
as relieving the Contractor from compliance
with the project plans and specifications. The
Contractor remains responsible for details and
accuracy for confirming and correlating all
quantities and dimensions which also shall be
confirmed at the site for selecting fabrication
processes for techniques of assembly and for
performing his work in safe manner.
By & Date : By Tim Grantham at 2:23 pm, Aug 22, 2014
CUSTOMER:
PAGE TITLE: R.C.P.
DRAWING NUMBER: 441181-1 SHEET: 1
OF 5
SCALE: 1/4" = 1'-0"
LINEAR BOX SERIES CEILING INSTALLATION NOTES:
5
3
EXTERIOR TRIM CONDITION P
CEILING ELEVATION
16'-11 3/4" AFF, V.I.F.
CEILING ELEVATION
16'-3 1/4" AFF, V.I.F.
1.
FIELD CUT CEILING PANELS AS REQUIRED TO CREATE A RANDOM STAGGERED SEAM PATTERN.
AVOID ALIGNED SEAMS.
2.
DO NOT SPLICE PANELS DIRECTLY BELOW UNIVERSAL CARRIERS. PANEL SPLICES DO NOT FIT
UNDER CARRIERS.
3.
IF UNIVERSAL CARRIERS ARE DIRECTLY FASTENED TO STRUCTURE, CARRIER-TO- CARRIER
ALIGNMENT TOLERANCES BECOME CRITICAL. CARRIER ALIGNMENT TOLERANCES SHOULD NOT
EXCEED 1/32" +/- IN ANY DIRECTION WHEN DIRECT FASTENING CARRIERS TO STRUCTURE.
FAILURE TO MAINTAIN TOLERANCES MAY RESULT IN CEILING PANEL DEFORMATION.
4.
1 Hunter Douglas Circle
5015 Oakbrook Parkway, Suite 100
Thornton, CO 80241
Norcross, GA 30093
866-556-1235
800-366-4327 / 770-806-9557
fax: 720-872-7850
fax: 770-806-0214
PROPER CARRIER TAB ALIGNMENT IS VERY DIFFICULT TO MAINTAIN WHEN CARRIER IS HARD
FASTENED TO A RIGID SUBSTRUCTURE SUCH AS T-GRID OR CR STEEL CHANNEL. FOR THIS
REASON, HUNTER DOUGLAS CANNOT ACCEPT RESPONSIBILITY FOR THE FINISHED APPEARANCE
OF THE CEILING IF THE STRICT TOLERANCE GUIDELINES OUTLINED IN NOTE #3 ARE NOT
FOLLOWED.
www.hunterdouglascontract.com
5
3
EXTERIOR TRIM CONDITION
W
R
INTERIOR TRIM CONDITION A
INTERIOR TRIM CONDITION A
CEILING ELEVATION
12'-0" AFF
1
3
1
3
PANEL NUMBER
CEILING ELEVATION
17'-2 3/16" AFF, V.I.F.
CEILING ELEVATION
16'-5 1/4" AFF, V.I.F.
CEILING ELEVATION
16'-1 15/16" AFF, V.I.F.
X26
EXTERIOR TRIM CONDITION P
5
3
1
3
C E I L I N G S
TABLE 1 - INTERIOR OBTUSE TRIM CONDITIONS @ WALLS
LINEAR BOX CEILING SYSTEM
INTERIOR TRIM CONDITION A
CEILING ELEVATION
10'-0" AFF
CEILING ELEVATION
12'-0" AFF
M E T A L
TYPICAL SECTION CONDITION
A
DETAIL 1/3
B
DETAIL 2/3
C
DETAIL 2/3
D
DETAIL 2/3
E
DETAIL 2/3
FF
DETAIL 2/3
JJ
DETAIL 2/3
R
W
ANGLE OF SLOPE
WALL ANGLE (TOTAL ANGLE)
O
O
D
C
E
I
L
I
N
G
S
R
A C O U S T I C A L
C E I L I N G S
TABLE 2 - INTERIOR TRIM CONDITIONS @ SEAMS
LINEAR BOX CEILING SYSTEM
PANEL NUMBER
FLEX TRIM AT COLUMN BY OTHERS,
NOT BY HUNTER DOUGLAS
INTERIOR TRIM CONDITION G
3
3
3
3
3
3
H
DITIO
N
CON
IM
TR
DETAIL 3/3
TYPICAL SECTION CONDITION
HH
DETAIL 4/3
CC
DETAIL 4/3
KK
DETAIL 4/3
W
EXTERIOR TRIM CONDITION Q
X32
DETAIL 5/3
S
DETAIL 5/3
T
DETAIL 5/3
U
DETAIL 5/3
V
DETAIL 5/3
W
DETAIL 5/3
TYPICAL SECTION CONDITION
X
DETAIL 6/3
Y
DETAIL 6/3
ANGLE OF SLOPE
WALL ANGLE (TOTAL ANGLE)
GENERAL NOTES
1.
Ceiling installation to be in accordance with ASTM C636 &
ASTM E580, and local code requirements for seismic
bracing.
TYPICAL SECTION CONDITION
Q
DETAIL 7/3
R
DETAIL 7/3
ANGLE OF SLOPE
WALL ANGLE (TOTAL ANGLE)
2.
The purpose of these drawings is to represent installation
of Hunter Douglas products ONLY. All dimensions are to
be field verified and approved by the contractor prior to
fabrication.
3.
Return approved shop drawings to Hunter Douglas to
release for fabrication.
4.
All quantities are to be reviewed and approved by the
customer prior to fabrication.
5.
This material list is an ESTIMATE ONLY. The customer is
responsible for reviewing and verifying ALL information
listed above prior to ordering material. Excess material
will not be accepted for returns or credit. If additional
material is necessary, set-up charges may apply.
6.
Unless shown otherwise, all penetrations including light
fixtures, diffusers, speakers, sprinkler heads, etc., are to
be field located and field cut. Hunter Douglas will not be
responsible for final location and placement of
penetrations. Typically, penetrations are not dimensioned
or located on Hunter Douglas shop drawings unless the
holes are factory cut. All "fixtures" are to be
independently supported. Trim for all penetrations are by
others. Any fixture or other penetration shown is soley
based on information provided to Hunter Douglas.
7.
Architect
/ General Contractor: Please reference
appropriate contract documents for coordination with
other trades.
8.
If there are any questions in relation to Hunter Douglas
products on this project, please contact us at
1-800-366-4327 (8:00am - 5:00pm EST Monday-Friday).
INTERIOR TRIM CONDITION A
CO
IM
IO
INTERIOR TRIM CONDITION HH
4
3
4
3
INTERIOR TRIM CONDITION A
INTERIOR TRIM CONDITION A
1
3
2
2
INTERIOR TRIM CONDITION G
SCALE: 1 1/2" = 1'-0"
INTERIOR INSTALLATION
NOTE:
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
4
3
INTERIOR TRIM CONDITION A
INTERIOR TRIM CONDITION A
CO
IN
T
M
ON
ITI
ND
1
3
K
2
2
SCALE: 1 1/2" = 1'-0"
INTERIOR INSTALLATION
CEILING ELEVATION
19'-9 3/8" AFF, V.I.F.
All rights reserved.
This drawing is the property of Hunter Douglas.
It may not be copied or multiplied, neither wholly nor partly.
It may not be submitted for perusal to third parties.
NOTE:
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
CEILING ELEVATION
20'-0 1/2" AFF, V.I.F.
TE
EX
5
3
O
RI
R
6
3
OR
RI
J
IO
IT
ND
ND
IM
J
N
ND
ND
IT
IO
CO
INTERIOR TRIM CONDITION C
INTERIOR TRIM CONDITION CC
INTERIOR TRIM CONDITION KK
1
3
INTERIOR TRIM CONDITION JJ
TE
RIO
R
K
TR
N
IM
CO
2
3
ITIO
4'
IM
2'
TR
0
R
SCALE: 1/4" = 1'-0"
RIO
PARTIAL R.C.P. AT HD METAL CEILINGS
TE
1
2
IN
1
3
INTERIOR TRIM CONDITION C
IN
IN
TE
CEILING ELEVATION
25'-1 13/16" AFF, V.I.F.
INTERIOR TRIM CONDITION JJ
RI
OR
K
TR
ON
X
CO
2
3
ITI
ON
7
3
CO
ITI
R
M
ND
I
TR
CO
NDITI
ON Y
TE
IM
TR
IM CO
IN
6
3
N
EXTERIOR TRIM CONDITION V
INTERIOR TRIM CONDITION G
1
3
4
3
3
2
SCALE: 1 1/2" = 1'-0"
INTERIOR INSTALLATION
NOTE:
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
INTERIOR TRIM CONDITION CC
INTERIOR TRIM CONDITION KK
ER
IO
I
TR
R
R
TR
INTERIOR TRIM CONDITION A
INTERIOR TRIM CONDITION HH
ND
IT
IO
N
J
4
3
INTERIOR TRIM CONDITION G
1
3
INTERIOR TRIM CONDITION A
INTERIOR TRIM CONDITION FF
INTERIOR TRIM CONDITION FF
X35
INTERIOR TRIM CONDITION C
IOR T
R
CONDITION
ANGLE OF SLOPE
WALL ANGLE (TOTAL ANGLE)
INTERIOR TRIM CONDITION A
R
TE
5
3
PROJECT SPECIFIC NOTES
1
3
IN
2
3
CEILING ELEVATION
14'-0" AFF, V.I.F.
ANGLE OF SLOPE
WALL ANGLE (TOTAL ANGLE)
TYPICAL SECTION CONDITION
P
L
EXTERIOR TRIM
CONDITION U
L
PANEL NUMBER
3
3
EXTER
EXTERIOR TRIM
CONDITION S
DETAIL 3/3
INTERIOR TRIM CONDITION G
3
2
CEILING ELEVATION
14'-7 13/16" AFF, V.I.F.
EXTERIOR T
RIM
K
ON
ITI
ND
INTERIOR TRIM CONDITION D
CO
CEILING ELEVATION
18'-3 15/16" AFF, V.I.F.
DETAIL 3/3
TABLE 6 - EXTERIOR OBTUSE TRIM CONDITIONS @ WALLS
LINEAR BOX CEILING SYSTEM
CEILING ELEVATION
12'-0" AFF
CEILING ELEVATION
14'-2 7/16" AFF, V.I.F.
EXTERIOR TRIM CONDITION T
J
PANEL NUMBER
EXTERIOR TRIM CONDITION
OR
RI
TE
IN
5
3
DETAIL 3/3
TABLE 5 - EXTERIOR CONDITIONS @ SEAMS
LINEAR BOX CEILING SYSTEM
5
3
INTERIOR TRIM CONDITION
B
CEILING ELEVATION
10'-0" AFF
TRIM
1
3
3
3
CEILING ELEVATION
16'-4 1/16" AFF, V.I.F.
H
PANEL NUMBER
7
3
3
3
5
3
DETAIL 3/3
TABLE 4 - EXTERIOR ACUTE TRIM CONDITIONS @ WALLS
LINEAR BOX CEILING SYSTEM
2
3
2
3
G
X28
2
2
INTERIOR TRIM CONDITION A
DETAIL 3/3
PANEL NUMBER
INTE
RIOR
CEILING ELEVATION
12'-0" AFF
F
ANGLE OF SLOPE
WALL ANGLE (TOTAL ANGLE)
TABLE 3 - INTERIOR ACUTE TRIM CONDITIONS @ WALLS
LINEAR BOX CEILING SYSTEM
INTERIOR TRIM CONDITION G
INTERIOR TRIM CONDITION E
INTERIOR TRIM CONDITION F
2
3
TYPICAL SECTION CONDITION
1
3
REVISIONS:
1.
-
DATE
BY
-
-
8'
4
3
3
2
SCALE: 1 1/2" = 1'-0"
INTERIOR INSTALLATION
NOTE:
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
DRAWN BY: A PRICE
CHECKED BY:
DATE: 8/15/14
PAGE SIZE: 36" x 48" (ARCH "E")
PROJECT: SHAKE SHACK - LAS VEGAS
CUSTOMER:
Y6
Y3
Y2
Y1.9
PAGE TITLE: HD R.C.P. REFERENCE GUIDE
DRAWING NUMBER: 441181-2
SHEET: 2 OF 5
SCALE: AS SHOWN
12" MAXIMUM,
TYPICAL ALL
INTERIOR HD
BOX CEILINGS
12 GA HANGER WIRE
BY OTHERS, NOT BY
HUNTER DOUGLAS
48" MAX O.C. CARRIER SPACING
12" MAXIMUM,
TYPICAL ALL
INTERIOR HD
BOX CEILINGS
12 GA HANGER WIRE
BY OTHERS, NOT BY
HUNTER DOUGLAS
5015 Oakbrook Parkway, Suite 100
Thornton, CO 80241
Norcross, GA 30093
866-556-1235
800-366-4327 / 770-806-9557
fax: 720-872-7850
fax: 770-806-0214
www.hunterdouglascontract.com
FASTENERS BY OTHERS, TYPICAL.
NOT BY HUNTER DOUGLAS
12" MAX PANEL OVERHANG, TYP. BOTH ENDS
UNIVERSAL BOX CARRIER
FIELD CUT & SPLICE TO FIT
ALLOW 14" FOR
EXPANSION
1" x 34" 'J' CAP TRIM, STANDARD
12 GA HANGER WIRE, TYP., NOT BY HUNTER DOUGLAS
R
UNIVERSAL BOX CARRIER
FIELD CUT & SPLICE TO FIT
FASTENERS BY OTHERS, TYPICAL.
NOT BY HUNTER DOUGLAS
1 Hunter Douglas Circle
M E T A L
VARIABLE ANGLE,
SEE TABLE 2 ON THIS SHEET
VARIABLE ANGLE,
SEE TABLE 1 ON THIS SHEET
R
W
UNIVERSAL CARRIER
1" WALL
ANGLE
BOX 6 CEILING PANEL
FIELD CUT & SPLICE TO FIT
FACTORY PANEL END, BOX 6 SHOWN,
ALL LINEAR BOX PANEL SIZE SIMILAR
C E I L I N G S
O
D
C
E
I
L
I
N
G
5"
532
S
R
FIELD CUT PANEL END, BOX 6 SHOWN,
ALL LINEAR BOX PANEL SIZE SIMILAR
27"
32
1" WALL ANGLE, USE ANGLE ABOVE AS HOLD
DOWN INSIDE PANEL IF REQUIRED
O
1"
1"
A C O U S T I C A L
C E I L I N G S
1"
BOX 6 CEILING PANEL
FIELD CUT & SPLICE TO FIT
5"
532
27"
32
DOUBLE SIDED ADHESIVE
TAPE TO SECURE ANGLE
INTERIOR INSTALLATION
1" x 1" ANGLE INSIDE
'J' TRIM TO SECURE
CUT PANEL EDGE
INTERIOR INSTALLATION
INTERIOR INSTALLATION
1-34" 'J' TRIM
1
3
2
3
NOTE:
SCALE: 3" = 1'-0"
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
SECTION DETAIL AT OBTUSE WALL ANGLES
3
3
NOTE:
SCALE: 6" = 1'-0"
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
SECTION DETAIL AT PANELS SEAMS
NOTE:
SCALE: 6" = 1'-0"
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
SEE DETAIL 1/5 THIS SET,
TABLE 1 FOR MAX O.C.
SPACING REQUIREMENTS
12 GA HANGER WIRE
BY OTHERS, NOT BY
HUNTER DOUGLAS
PROJECT SPECIFIC NOTES
6" MAX CARRIER OVERHANG,
SEE DETAIL 1/5
THIS SET, TABLE 1
FOR REQUIREMENTS
12" MAXIMUM,
TYPICAL ALL
INTERIOR HD
BOX CEILINGS
VERTICAL SUPPORT DIETRICH
STE-20 2-12" 20 GA GALV. STEEL
STUD OR EQUAL, MAX LENGTH
85", SEE DETAIL 1/5 THIS
SET, NOTE 3 FOR VERTICAL
SUPPORT REQUIREMENTS
12 GA HANGER WIRE,
WITHIN 3" OF VERTICAL
SUPPORT, TYP., NOT BY
HUNTER DOUGLAS
UNIVERSAL BOX CARRIER
FIELD CUT & SPLICE TO FIT
UNIVERSAL BOX CARRIER
FIELD CUT & SPLICE TO FIT
VARIABLE ANGLE,
SEE TABLE 3 ON THIS SHEET
ALLOW 14" GAP MIN. FOR
EXPANSION, TYP. BOTH SIDES
SEE DETAIL 1/5 THIS SET,
TABLE 1 FOR MAX O.C.
SPACING REQUIREMENTS
6" MAX CARRIER OVERHANG,
SEE DETAIL 1/5
THIS SET, TABLE 1
FOR REQUIREMENTS
27"
32
VARIABLE ANGLE,
SEE TABLE 4 ON THIS SHEET
FASTENERS BY OTHERS, TYPICAL.
NOT BY HUNTER DOUGLAS
VERTICAL SUPPORT DIETRICH
STE-20 2-12" 20 GA GALV. STEEL
STUD OR EQUAL, MAX LENGTH
85", SEE DETAIL 1/5 THIS
SET, NOTE 3 FOR VERTICAL
SUPPORT REQUIREMENTS
5"
532
FLAT RECESSED
CLOSURE
BOX 6 CEILING PANEL
FIELD CUT & SPLICE TO FIT
ALLOW 14"
VARIABLE ANGLE,
SEE TABLE 5 ON THIS SHEET
FIELD CUT PANEL SIDE, BOX 6
SHOWN, ALL LINEAR BOX
PANEL SIZE SIMILAR
UNIVERSAL BOX CARRIER
FIELD CUT & SPLICE TO FIT
1"X2" WALL ANGLE, USE ANGLE ABOVE
AS HOLD DOWN INSIDE PANEL IF
REQUIRED
1"
GAP MIN. FOR
EXPANSION, TYP. BOTH SIDES
FLAT RECESSED
CLOSURE
12 GA HANGER WIRE,
WITHIN 3" OF VERTICAL
SUPPORT, TYP., NOT BY
HUNTER DOUGLAS
FIELD CUT PANEL SIDE, BOX 6
SHOWN, ALL LINEAR BOX
PANEL SIZE SIMILAR
1"
GENERAL NOTES
1"
ALLOW 14" GAP MIN. FOR
EXPANSION, TYP. BOTH SIDES
INTERIOR INSTALLATION
EXTERIOR INSTALLATION
FLAT RECESSED
CLOSURE
EXTERIOR INSTALLATION
SECTION DETAIL AT ACUTE WALL ANGLES
SCALE: 6" = 1'-0"
4
3
NOTE:
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
SEE DETAIL 1/5 THIS SET,
TABLE 1 FOR MAX O.C.
SPACING REQUIREMENTS
SECTION DETAIL AT ACUTE WALL ANGLES
SCALE: 6" = 1'-0"
NOTE:
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
5
3
SECTION DETAIL AT PANEL SEAMS
13
4 " J-TRIM, USE ANGLE ABOVE
AS HOLD DOWN INSIDE PANEL IF
REQUIRED
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
3.
Return approved shop drawings to Hunter Douglas to
release for fabrication.
4.
All quantities are to be reviewed and approved by the
customer prior to fabrication.
5.
This material list is an ESTIMATE ONLY. The customer is
responsible for reviewing and verifying ALL information
listed above prior to ordering material. Excess material
will not be accepted for returns or credit. If additional
material is necessary, set-up charges may apply.
6.
Unless shown otherwise, all penetrations including light
fixtures, diffusers, speakers, sprinkler heads, etc., are to
be field located and field cut. Hunter Douglas will not be
responsible for final location and placement of
penetrations. Typically, penetrations are not dimensioned
or located on Hunter Douglas shop drawings unless the
holes are factory cut. All "fixtures" are to be
independently supported. Trim for all penetrations are by
others. Any fixture or other penetration shown is soley
based on information provided to Hunter Douglas.
7.
Architect
/ General Contractor: Please reference
appropriate contract documents for coordination with
other trades.
8.
If there are any questions in relation to Hunter Douglas
products on this project, please contact us at
1-800-366-4327 (8:00am - 5:00pm EST Monday-Friday).
1-34" 'J' TRIM
All rights reserved.
This drawing is the property of Hunter Douglas.
It may not be copied or multiplied, neither wholly nor partly.
It may not be submitted for perusal to third parties.
6" MAX CARRIER OVERHANG,
SEE DETAIL 1/5
THIS SET, TABLE 1
FOR REQUIREMENTS
VERTICAL SUPPORT DIETRICH
STE-20 2-12" 20 GA GALV. STEEL
STUD OR EQUAL, MAX LENGTH
85", SEE DETAIL 1/5 THIS
SET, NOTE 3 FOR VERTICAL
SUPPORT REQUIREMENTS
TABLE 1 - INTERIOR OBTUSE TRIM CONDITIONS @ WALLS
LINEAR BOX CEILING SYSTEM
PANEL NUMBER
VARIABLE ANGLE,
SEE TABLE 6 ON THIS SHEET
UNIVERSAL BOX CARRIER
FIELD CUT & SPLICE TO FIT
TYPICAL SECTION CONDITION
ANGLE OF SLOPE
WALL ANGLE (TOTAL ANGLE)
TABLE 4 - EXTERIOR ACUTE TRIM CONDITIONS @ WALLS
LINEAR BOX CEILING SYSTEM
PANEL NUMBER
DETAIL 1/3
P
DETAIL 5/3
B
DETAIL 2/3
S
DETAIL 5/3
C
DETAIL 2/3
T
DETAIL 5/3
D
DETAIL 2/3
U
DETAIL 5/3
E
DETAIL 2/3
V
DETAIL 5/3
FF
DETAIL 2/3
W
DETAIL 5/3
JJ
DETAIL 2/3
TABLE 2 - INTERIOR TRIM CONDITIONS @ SEAMS
LINEAR BOX CEILING SYSTEM
PANEL NUMBER
FIELD CUT PANEL SIDE, BOX 6
SHOWN, ALL LINEAR BOX
PANEL SIZE SIMILAR
1"X2" WALL ANGLE, USE ANGLE ABOVE
AS HOLD DOWN INSIDE PANEL IF
REQUIRED
TYPICAL SECTION CONDITION
A
1"
FLAT RECESSED
CLOSURE
The purpose of these drawings is to represent installation
of Hunter Douglas products ONLY. All dimensions are to
be field verified and approved by the contractor prior to
fabrication.
1" x 1" ANGLE INSIDE
'J' TRIM TO SECURE
CUT PANEL EDGE
ALLOW 14" GAP MIN. FOR
EXPANSION, TYP. BOTH SIDES
12 GA HANGER WIRE,
WITHIN 3" OF VERTICAL
SUPPORT, TYP., NOT BY
HUNTER DOUGLAS
2.
DOUBLE SIDED ADHESIVE
TAPE TO SECURE ANGLE
NOTE:
SCALE: 6" = 1'-0"
Ceiling installation to be in accordance with ASTM C636 &
ASTM E580, and local code requirements for seismic
bracing.
1"
FIELD CUT PANEL SIDE, BOX 6
SHOWN, ALL LINEAR BOX
PANEL SIZE SIMILAR
EXTERIOR INSTALLATION
4
3
1"X2" WALL ANGLE, USE ANGLE ABOVE
AS HOLD DOWN INSIDE PANEL IF
REQUIRED
1.
TYPICAL SECTION CONDITION
F
DETAIL 3/3
G
DETAIL 3/3
H
DETAIL 3/3
ANGLE OF SLOPE
WALL ANGLE (TOTAL ANGLE)
TABLE 5 - EXTERIOR CONDITIONS @ SEAMS
LINEAR BOX CEILING SYSTEM
PANEL NUMBER
ANGLE OF SLOPE
WALL ANGLE (TOTAL ANGLE)
TYPICAL SECTION CONDITION
X
DETAIL 6/3
Y
DETAIL 6/3
ANGLE OF SLOPE
WALL ANGLE (TOTAL ANGLE)
REVISIONS:
TABLE 6 - EXTERIOR OBTUSE TRIM CONDITIONS @ WALLS
LINEAR BOX CEILING SYSTEM
J
DETAIL 3/3
K
DETAIL 3/3
PANEL NUMBER
L
DETAIL 3/3
Q
DETAIL 7/3
R
DETAIL 7/3
TYPICAL SECTION CONDITION
1.
-
DATE
BY
-
-
ANGLE OF SLOPE
WALL ANGLE (TOTAL ANGLE)
TABLE 3 - INTERIOR ACUTE TRIM CONDITIONS @ WALLS
LINEAR BOX CEILING SYSTEM
PANEL NUMBER
EXTERIOR INSTALLATION
TYPICAL SECTION CONDITION
HH
DETAIL 4/3
CC
DETAIL 4/3
KK
DETAIL 4/3
ANGLE OF SLOPE
WALL ANGLE (TOTAL ANGLE)
DRAWN BY: A PRICE
CHECKED BY:
DATE: 8/15/14
PAGE SIZE: 36" x 48" (ARCH "E")
PROJECT: SHAKE SHACK - LAS VEGAS
CUSTOMER:
PAGE TITLE: INTERIOR/EXTERIOR BOX 6
DETAILS AND TRIM ANGLE CHARTS
DRAWING NUMBER: 441181-3
6
3
SECTION DETAIL AT OBTUSE WALL ANGLES
SCALE: 6" = 1'-0"
NOTE:
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
9
3
CHARTS FOR ANGLE OF WALL ANGLES
SCALE: NOT TO SCALE
NOTE:
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
SHEET: 3 OF 5
SCALE: AS SHOWN
SIDE VIEW OF UNIVERSAL CARRIER WITH PANEL
1 Hunter Douglas Circle
5015 Oakbrook Parkway, Suite 100
Thornton, CO 80241
Norcross, GA 30093
866-556-1235
800-366-4327 / 770-806-9557
fax: 720-872-7850
fax: 770-806-0214
48" MAX O.C. CARRIER SPACING
SCALE: 3" = 1'-0"
www.hunterdouglascontract.com
12" MAX PANEL OVERHANG, TYP. BOTH ENDS
R
12 GA HANGER WIRE, TYP., NOT BY HUNTER DOUGLAS
END VIEW OF UNIVERSAL CARRIER WITH PANEL
M E T A L
C E I L I N G S
SCALE: 3" = 1'-0"
1-34" 'J'
TRIM
R
W
O
O
D
C
E
I
L
I
N
G
S
UNIVERSAL CARRIER
R
FACTORY PANEL END, BOX 6 SHOWN,
ONLY STANDARD LINEAR BOX SIMILAR
1-34" 'J'
TRIM
BOX 6 PANEL
FIELD CUT PANEL END, BOX 6 SHOWN,
ONLY STANDARD LINEAR BOX SIMILAR
A C O U S T I C A L
C E I L I N G S
SUPPLEMENTAL CARRIER FOR 'J' TRIM
ATTACHMENT, TYP. BOTH ENDS
UNIVERSAL CARRIER*
SUSPENSION SPECIFICATIONS
MATERIAL:
0.040" ALUMINUM
FINISH:
MATTE BLACK
PART LENGTH:
16'-0"
*CARRIER SPLICE REQUIRED, SEE DETAIL A1.5
UNIVERSAL CARRIER
SCALE: NOT TO SCALE
INTERIOR INSTALLATION
1
4
SUSPENSION SPECIFICATIONS
SCALE: NOT TO SCALE
INTERIOR INSTALLATION
4
4
NOTE:
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
SECTION AT HD LINEAR BOX CEILING TERMINATION
NOTE:
SCALE: 3" = 1'-0"
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
INTERIOR INSTALLATION
PROJECT SPECIFIC NOTES
BOX 6 PANEL
BOX 6 PANEL SPLICE
48" MAX O.C. SPACING FOR CARRIER SPAN
BOX 6 PANEL
12" MAX CARRIER OVERHANG, TYP. BOTH ENDS
NO CLOSURE AT
INTERIOR
12 GA HANGER WIRE, TYP., NOT BY HUNTER DOUGLAS
BOX 6 PANEL
FLAT RECESSED
CLOSURE OPTIONAL
GENERAL NOTES
UNIVERSAL CARRIER
UNIVERSAL CARRIER
NOTE 1:
DO NOT SPLICE PANELS DIRECTLY BELOW UNIVERSAL CARRIERS.
PANEL SPLICES DO NOT FIT UNDER CARRIERS.
1" WALL
ANGLE
NOTE 2:
FIELD CUT PANELS AS REQUIRED TO CREATE A RANDOM
STAGGERED SEAM PATTERN. AVOID ALIGNED SEAMS.
BOX 6 PANEL SPLICE
FACTORY PANEL SIDE, BOX 6 SHOWN,
ALL LINEAR BOX PANEL SIZE SIMILAR
FIELD CUT PANEL SIDE, BOX 6 SHOWN,
ALL LINEAR BOX PANEL SIZE SIMILAR
1.
Ceiling installation to be in accordance with ASTM C636 &
ASTM E580, and local code requirements for seismic
bracing.
2.
The purpose of these drawings is to represent installation
of Hunter Douglas products ONLY. All dimensions are to
be field verified and approved by the contractor prior to
fabrication.
3.
Return approved shop drawings to Hunter Douglas to
release for fabrication.
4.
All quantities are to be reviewed and approved by the
customer prior to fabrication.
5.
This material list is an ESTIMATE ONLY. The customer is
responsible for reviewing and verifying ALL information
listed above prior to ordering material. Excess material
will not be accepted for returns or credit. If additional
material is necessary, set-up charges may apply.
6.
Unless shown otherwise, all penetrations including light
fixtures, diffusers, speakers, sprinkler heads, etc., are to
be field located and field cut. Hunter Douglas will not be
responsible for final location and placement of
penetrations. Typically, penetrations are not dimensioned
or located on Hunter Douglas shop drawings unless the
holes are factory cut. All "fixtures" are to be
independently supported. Trim for all penetrations are by
others. Any fixture or other penetration shown is soley
based on information provided to Hunter Douglas.
7.
Architect
/ General Contractor: Please reference
appropriate contract documents for coordination with
other trades.
8.
If there are any questions in relation to Hunter Douglas
products on this project, please contact us at
1-800-366-4327 (8:00am - 5:00pm EST Monday-Friday).
1" WALL ANGLE, USE ANGLE ABOVE AS HOLD
DOWN INSIDE PANEL IF REQUIRED
UNIVERSAL CARRIER BEYOND
PANEL SEAM
UNIVERSAL CARRIER
BOX 6 PANEL
SECTION 'A'
SCALE: 3" = 1'-0"
SECTION 'B'
BOX 6 PANEL SPLICE, WILL NOT FIT
UNDER UNIVERSAL CARRIER
SCALE: 3" = 1'-0"
BOX 6 PANEL SPLICE, WILL NOT FIT
UNDER UNIVERSAL CARRIER
BOX 6 PANEL
*HANGER WIRE OMITTED FOR CLARITY
2
4
PANEL SPLICES DETAILS
SCALE: 3" = 1'-0"
INTERIOR INSTALLATION
5
4
NOTE:
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
SECTION AT HD LINEAR BOX CEILING TERMINATION
NOTE:
SCALE: 3" = 1'-0"
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
INTERIOR INSTALLATION
All rights reserved.
This drawing is the property of Hunter Douglas.
It may not be copied or multiplied, neither wholly nor partly.
It may not be submitted for perusal to third parties.
UNIVERSAL CARRIER SPLICE
UNIVERSAL CARRIER
LATERAL BRACING: BRACE WITH HANGER WIRES AND STRUTS PER ASTM E-580 AND IN ACCORDANCE WITH LOCAL
CODE REQUIREMENTS.
UNIVERSAL CARRIER
SECTION 'A'
BOX 6 PANEL
'B'
'B'
UNIVERSAL CARRIER SPLICE
STRUT FASTENED TO MAIN RUNNER SHALL BE EXTENDED TO AND FASTENED TO STRUCTURE ABOVE. SPLAYED WIRE
AND STRUT BRACING TO BE PLACED NOT MORE THAN 12 FEET ON CENTER IN EACH DIRECTION, WITH FIRST POINT
WITHIN 4 FEET FROM EACH WALL.
E
BOX 6 PANEL
COMPRESSION STRUT/
VERTICAL SUPPORT
N
E
SCALE: 3" = 1'-0"
N
IF THE DESIRED CARRIER LENGTH EXCEEDS THE
MAXIMUM OF 16'-0", USE A LUXALON CARRIER
SPLICE TO CONNECT THE FACTORY CARRIER ENDS.
SNAP SPLICE TABS INTO
UNIVERSAL CARRIER
S
W
THE TABS OF THE SPLICE SNAP INTO THE HOLES IN THE
CARRIER AND ADDITIONAL FIXING IS NOT NECESSARY.
THE MODULE IS CONTINUED AUTOMATICALLY.
S
REVISIONS:
W
1.
-
DATE
BY
-
-
FIELD DRILL HOLES IN UNIVERSAL CARRIER
AS NEEDED TO ALLOW FOR THE FOUR
SPLAYED HANGER WIRES AS SHOWN
UNIVERSAL
CARRIER
BOX 4 PANEL SHOWN, ALL
LINEAR BOX SIMILAR
SECTION 'B'
DRAWN BY: A PRICE
CHECKED BY:
DATE: 8/12/14
PAGE SIZE: 36" x 48" (ARCH "E")
PROJECT: SHAKE SHACK - LAS VEGAS
SCALE: FULL (1:1)
CUSTOMER:
PAGE TITLE: INTERIOR BOX 6 DETAILS
INTERIOR INSTALLATION
DRAWING NUMBER: 441181-4 SHEET: 4
*HANGER WIRE OMITTED FOR CLARITY
OF 5
3
4
CARRIER SPLICE DETAIL
SCALE: NOT TO SCALE
INTERIOR INSTALLATION
NOTE:
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
3
4
ISOMETRIC VIEW OF HD LINEAR BOX SEISMIC DETAIL
SCALE: NOT TO SCALE
INTERIOR INSTALLATION
NOTE:
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
SCALE: 3" = 1'-0"
NOTE A:
CARRIER SPACING (PANEL SPAN) AND CARRIER SPAN (HANGER WIRE
& VERTICAL SUPPORT SPACING) VARIES DEPENDING ON DESIGN WIND
PRESSURE (POUNDS PER SQUARE FOOT). AS A GENERAL GUIDE, REFER
TO THE DETAIL AND WIND LOAD TABLE 1 BELOW FOR CARRIER SPACING
AND CARRIER SPAN. THE WIND LOAD CRITERIA IS BASED ON USING 3
OR MORE ROWS OF CARRIER. MAXIMUM PANEL OVERHANG = 6".
MAXIMUM CARRIER OVERHANG = 6".
UNIVERSAL CARRIER,
.040" ALUMINUM
VERTICAL SUPPORT
1/2" X 1-1/2" 16 GA
GALV. CRC , MAX
LENGTH 28", SEE
DETAIL 2/5 THIS SHEET
FOR VERTICAL SUPPORT
REQUIREMENTS
AND EQUALS
SEE TABLE 1 ON DETAIL 1/5
THIS SHEET FOR MAX O.C.
SPACING REQUIREMENTS, TYPICAL
1 Hunter Douglas Circle
5015 Oakbrook Parkway, Suite 100
Thornton, CO 80241
Norcross, GA 30093
866-556-1235
800-366-4327 / 770-806-9557
fax: 720-872-7850
fax: 770-806-0214
12 GA HANGER WIRE, WITHIN 3"
OF VERTICAL SUPPORT, TYPICAL,
NOT BY HUNTER DOUGLAS
HANGER WIRE (12 GA MIN.) MUST BE LOCATED AT EACH VERTICAL
SUPPORT STRUT. VERTICAL SUPPORT STRUT MUST NOT EXCEED SPACING
SHOWN FOR A GIVEN DESIGN WIND PRESSURE. SEE DETAIL 2/5 THIS SHEET
FOR VERTICAL SUPPORT SPECIFICATION. HANGER WIRE AND VERTICAL
SUPPORT STRUT MUST BE ATTACHED TO STRUCTURE ABOVE TO SAFELY
SUPPORT ALL LOADS IMPOSED BY SOFFIT SYSTEM. ATTACHMENT TO
STRUCTURE DESIGNED AND PROVIDED BY OTHERS, NOT BY HUNTER
DOUGLAS.
www.hunterdouglascontract.com
6" MAX AT CARRIER
SPLICE, TYPICAL
VERTICAL SUPPORT 1/2" X 1-1/2"
16 GA GALV. CRC OR EQUAL,
MAX LENGTH 28", SEE NOTE A
ON DETAIL 2/5 THIS SHEET FOR
VERTICAL SUPPORT REQUIREMENTS
NOTE B:
ALL PENETRATIONS IN CEILING TO BE FIELD LOCATED
AND FIELD CUT. TRIM FOR THESE ITEMS NOT BY
HUNTER DOUGLAS.
NOTE C:
ATTACHMENT TO STRUCTURE DESIGNED AND
PROVIDED BY OTHERS, NOT BY HUNTER DOUGLAS.
'B'
UNIVERSAL
CARRIER SPLICE
UNIVERSAL
CARRIER
R
M E T A L
'B'
SECTION 'A'
BOX 6 PANEL
C E I L I N G S
FLAT RECESSED CLOSURE
R
SCALE: 3" = 1'-0"
W
O
O
D
C
E
I
L
I
N
G
S
R
TABLE 1 - DESIGN WIND LOAD - LINEAR BOX EXTERIOR CEILING SYSTEM
A C O U S T I C A L
SNAP SPLICE TABS INTO
UNIVERSAL CARRIER
PANEL TYPE: .025", .032", OR .040" ALUMINUM, BOX 6 PANEL
CARRIER TYPE: .040" ALUMINUM, UNIVERSAL CARRIER
C E I L I N G S
ALLOWABLE CARRIER SPACING (PANEL SPAN)
ALLOWABLE CARRIER SUPPORT SPACING (HANGER WIRE/VERTICAL SUPPORT SPACING)
BOX 6 PANEL, .025", .032",
OR .040" ALUMINUM
REQUIRED FOR EXTERIOR
* NOTE: CARRIER SPACING BASED ON USING 3 OR MORE CARRIERS
** POUNDS PER SQUARE FOOT
DESIGN WIND PRESSURE
(POSITIVE OR NEGATIVE PSF**)
FLAT RECESSED CLOSURE REQUIRED
FOR EXTERIOR INSTALLATION
1
5
SUSPENSION SPECIFICATIONS
CARRIER SPACING *
(PANEL SPAN)
CARRIER SPAN
(VERTICAL SUPPORT SPACING)
20
2'-8"
2'-2"
25
2'-5"
2'-1"
30
2'-2"
1'-11"
35
2'-0"
1'-10"
40
1'-11"
1'-9"
45
1'-10"
1'-9"
NOTE:
SCALE: NOT TO SCALE
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
EXTERIOR INSTALLATION
PROJECT SPECIFIC NOTES
NOTE A:
DIETRICH STE-20 2-1/2" 20 GA
GALV. STEEL STUD
12 GA HANGER WIRE, WITHIN 3"
OF VERTICAL SUPPORT,
NOT BY HUNTER DOUGLAS
1/2" X 1-1/2" 16 GA
GALV. CRC
12 GA HANGER WIRE,
WITHIN 3" OF VERTICAL
SUPPORT, TYPICAL, NOT
BY HUNTER DOUGLAS
VERTICAL SUPPORT STRUTS (MINIMUM 1-1/2" 16 GA GALV.
'C' CHANNEL OR EQUAL, MAX LENGTH OF 28"). SEE DETAIL 1/5
THIS SHEET FOR EXTERIOR SUSPENSION REQUIREMENTS.
VERTICAL SUPPORTS SHALL BE LOCATED WITHIN 6" OF THE
ENDS OF EACH CARRIER AND WITHIN 6" ON BOTH SIDES OF A
CARRIER SPLICE.
12 GA (.109") MIN
X 3/4" WIDTH MIN
VERTICAL SUPPORT EQUALS:
1/2" X 1-1/2" 16 GA
GALV. CRC SECURED
TO CARRIER WITH
12 GA GALV.
BRACKET, NOT BY
HUNTER DOUGLAS
UNIVERSAL CARRIER
12 GA GALV. BRACKET, NOT
BY HUNTER DOUGLAS
DIETRICH STE-20 2-1/2" 20 GA GALV. MAX LENGTH OF 85"
1/2" MAX
*** ATTACHMENT TO STRUCTURE ABOVE SHALL BE DESIGNED
AND PROVIDED BY OTHERS TO SUPPORT ALL LOADS IMPOSED
BY CEILING SOFFIT SYSTEM ***
UNIVERSAL CARRIER
DIETRICH TRNB-25 MAX LENGTH OF 78"
BOX 6 PANEL
1" MIN
UNIVERSAL CARRIER SPLICE
GENERAL NOTES
FLAT RECESSED CLOSURE
OR
BOX 6 PANEL
FLAT RECESSED CLOSURE
1/4" DIAMETER X 20
GRADE 2 NUT &
BOLT IN PREPUNCHED CARRIER
HOLE, NOT BY
HUNTER DOUGLAS
12 GA BRACKET
GALV., NOT
BY HUNTER
DOUGLAS
NOTE A:
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
2
5
17"
32
BOX 6 PANEL, .025", .032",
OR .040" ALUMINUM
REQUIRED
FOR EXTERIOR
VERTICAL SUPPORT 1/2" X 1-1/2"
16 GA GALV. CRC, MAX LENGTH
28", SEE NOTE A THIS SHEET FOR
VERTICAL SUPPORT
REQUIREMENTS
12 GA HANGER WIRE, WITHIN 3"
OF VERTICAL SUPPORT,
NOT BY HUNTER DOUGLAS
VERTICAL SUPPORT DIETRICH
STE-20 2-1/2" 20 GA GALV.
STEEL STUD OR EQUAL, MAX
LENGTH 85", SEE NOTE A
THIS SHEET FOR VERTICAL
SUPPORT REQUIREMENTS
(2) NO. 10 TEK SCREWS,
NOT BY HUNTER DOUGLAS
(2) NO. 10 TEK SCREWS,
NOT BY HUNTER DOUGLAS
IF THE DESIRED CARRIER LENGTH EXCEEDS THE
MAXIMUM OF 16'-0", USE A UNIVERSAL CARRIER
SPLICE TO CONNECT THE FACTORY CARRIER ENDS.
THE TABS OF THE SPLICE SNAP INTO THE HOLES IN THE
CARRIER AND ADDITIONAL FIXING IS NOT NECESSARY.
THE MODULE IS CONTINUED AUTOMATICALLY.
5"
532
SECTION 'A'
27"
32
UNIVERSAL CARRIER,
.040" ALUMINUM
SCALE: NOT TO SCALE
EXTERIOR INSTALLATION
ITEM #
3.
Return approved shop drawings to Hunter Douglas to
release for fabrication.
4.
All quantities are to be reviewed and approved by the
customer prior to fabrication.
5.
This material list is an ESTIMATE ONLY. The customer is
responsible for reviewing and verifying ALL information
listed above prior to ordering material. Excess material
will not be accepted for returns or credit. If additional
material is necessary, set-up charges may apply.
6.
Unless shown otherwise, all penetrations including light
fixtures, diffusers, speakers, sprinkler heads, etc., are to
be field located and field cut. Hunter Douglas will not be
responsible for final location and placement of
penetrations. Typically, penetrations are not dimensioned
or located on Hunter Douglas shop drawings unless the
holes are factory cut. All "fixtures" are to be
independently supported. Trim for all penetrations are by
others. Any fixture or other penetration shown is soley
based on information provided to Hunter Douglas.
7.
Architect
/ General Contractor: Please reference
appropriate contract documents for coordination with
other trades.
8.
If there are any questions in relation to Hunter Douglas
products on this project, please contact us at
1-800-366-4327 (8:00am - 5:00pm EST Monday-Friday).
SCALE: 3" = 1'-0"
4
5
CARRIER SPLICE DETAILS
NOTE:
SCALE: NOT TO SCALE
ATTACHMENT TO STRUCTURE
DESIGNED AND PROVIDED BY
OTHERS, NOT BY HUNTER DOUGLAS
EXTERIOR INSTALLATION
All rights reserved.
This drawing is the property of Hunter Douglas.
It may not be copied or multiplied, neither wholly nor partly.
It may not be submitted for perusal to third parties.
BILL OF MATERIALS
HUNTER DOUGLAS LINEAR BOX 6 CEILING SYSTEM - INTERIOR
FINISH: #9125, HEMLOCK WOOD VENEER
PERFORATION: NONE
PANEL BACKING: NONE
MATERIAL: .025" ALUMINUM
DESCRIPTION
SIZE
QUANTITY
BOX 6 LINEAR PANEL - FINISH: AS ABOVE
16'-0" PANELS WITH FINGER JOINT
10'-0" PANELS WITHOUT FINGER JOINT
PANEL SPLICE - FINISH: BLACK
16'-0"
10'-0"
N/A
365
583
365 OR 583
UNIVERSAL CARRIER - FINISH: BLACK
UNIVERSAL CARRIER SPLICE
16'-0"
N/A
63
63
1x1 WALL ANGLE - .025" ALUMINUM
ANGLE A
10'-0"
6
1x2 WALL ANGLE - .025" ALUMINUM - OBTUSE ANGLE - FINISHED: TO BE DETERMINED
10'-0"
8
10'-0"
4
10'-0"
5
ANGLE E - 100.46
10'-0"
5
10'-0"
1
10'-0"
1
1x2 WALL ANGLE - .025" ALUMINUM - ACUTE ANGLE - FINISHED: TO BE DETERMINED
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
4
6
7
3
3
3
1
1
1
1-3/4" 'J' TRIM - .025" ALUMINUM - FINISHED: TO BE DETERMINED
ANGLE F
ANGLE G
ANGLE H
ANGLE J
ANGLE K
ANGLE L
4
6
7
3
3
3
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
***QUANTITIES CONTAIN ZERO OVERAGE- ADD AS REQUIRED
FOR ATTIC STOCK, ETC. BEFORE PRODUCTION***
ITEM #
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20
21.
22
23
24.
25.
26.
27
28.
29.
31.
32.
33.
34.
35.
36.
37.
BILL OF MATERIALS
HUNTER DOUGLAS LINEAR BOX 6 CEILING SYSTEM - EXTERIOR
FINISH: #8486, DECORATED NORTHWEST MOUNTAIN HEMLOCK
PERFORATION: NONE
PANEL BACKING: NONE
MATERIAL: .025" ALUMINUM
DESCRIPTION
SIZE
QUANTITY
BOX 6 LINEAR PANEL - FINISH: AS ABOVE
PANEL SPLICE - FINISH: BLACK
RECESSED CLOSURE - FINISH: BLACK
16'-0"
N/A
12'-0"
151
151
202
UNIVERSAL CARRIER - FINISH: BLACK
UNIVERSAL CARRIER SPLICE
16'-0"
N/A
37
37
1x2 WALL ANGLE - .025" ALUMINUM - OBTUSE ANGLE - FINISHED: TO BE DETERMINED
10'-0"
11
10'-0"
8
1x2 WALL ANGLE - .025" ALUMINUM - ACUTE ANGLE - FINISHED: TO BE DETERMINED
10'-0"
10'-0"
10'-0"
10'-0"
ANGLE V - 73.61
10'-0"
10'-0"
10'-0"
10'-0"
1-3/4" 'J' TRIM - .025" ALUMINUM - FINISHED: TO BE DETERMINED
ANGLE X
ANGLE Y
10'-0"
10'-0"
1
1
4
1
4
10
2
5
2
5
***QUANTITIES CONTAIN ZERO OVERAGE- ADD AS REQUIRED
FOR ATTIC STOCK, ETC. BEFORE PRODUCTION***
SHOP DRAWINGS - 441181 SHAKE SHACK - LAS VEGAS 8/15/14
N/A
ITEM #
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20
21.
22
23
24.
25.
26.
27
28.
29.
31.
32.
33.
34.
35.
36.
37.
HUNTER DOUGLAS LINEAR BOX 6 CEILING SYSTEM - HOLD DOWNS
FINISH: ANY
PERFORATION: NONE
PANEL BACKING: NONE
MATERIAL: .025" ALUMINUM
DESCRIPTION
SIZE
QUANTITY
1x2 WALL ANGLE HOLD DOWN - .025" ALUMINUM - OBTUSE ANGLE - FINISHED: ANY
10'-0"
10'-0"
10'-0"
ANGLE E - 100.46
10'-0"
10'-0"
10'-0"
8
4
5
5
1
1
1x2 WALL ANGLE HOLD DOWN - .025" ALUMINUM - ACUTE ANGLE - FINISHED: ANY
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
4
6
7
3
3
3
1
1
1
1x2 WALL ANGLE HOLD DOWN - .025" ALUMINUM - OBTUSE ANGLE - FINISHED: ANY
10'-0"
11
10'-0"
8
1x2 WALL ANGLE HOLD DOWN - .025" ALUMINUM - ACUTE ANGLE - FINISHED: ANY
10'-0"
10'-0"
10'-0"
10'-0"
ANGLE V - 73.61
10'-0"
10'-0"
10'-0"
10'-0"
1
1
4
1
4
10
2
5
1X1 WALL ANGLE HOLD DOWN FOR J-TRIM - .025" ALUMINUM
33
N/A
5 SHEET(S)
10'-0"
REVISIONS:
1.
-
DATE
BY
-
-
DRAWN BY: A PRICE
CHECKED BY:
DATE: 8/12/14
PAGE SIZE: 36" x 48" (ARCH "E")
PROJECT: SHAKE SHACK - LAS VEGAS
***QUANTITIES CONTAIN ZERO OVERAGE- ADD AS REQUIRED
FOR ATTIC STOCK, ETC. BEFORE PRODUCTION***
CUSTOMER:
PAGE TITLE: EXTERIOR BOX 6 DETAILS & B.O.M.
5 SHEET(S)
SHOP DRAWINGS - 441181 SHAKE SHACK - LAS VEGAS 8/15/14
SHOP DRAWINGS - 441181 SHAKE SHACK - LAS VEGAS 8/15/14
The purpose of these drawings is to represent installation
of Hunter Douglas products ONLY. All dimensions are to
be field verified and approved by the contractor prior to
fabrication.
SCALE: FULL (1:1)
BILL OF MATERIALS
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20
21.
22
23
24.
25.
26.
27
28.
29.
31.
32.
33.
34.
35.
36.
37.
38.
2.
FLAT RECESSED CLOSURE
REQUIRED FOR EXTERNAL
INSTALLATION
NOTE B:
ALL PENETRATIONS IN CEILING TO BE
FIELD LOCATED AND FIELD CUT. TRIM
FOR THESE ITEMS NOT BY HUNTER
DOUGLAS.
SUSPENSION SPECIFICATIONS
SECTION 'B'
125
32"
6"
Ceiling installation to be in accordance with ASTM C636 &
ASTM E580, and local code requirements for seismic
bracing.
SEE TABLE 1 ON DETAIL 1/5
THIS SHEET FOR MAX
O.C. SPACING REQUIREMENTS
114"
(2) NO. 10 TEK SCREWS, NOT
BY HUNTER DOUGLAS
OR
1.
N/A
5 SHEET(S)
DRAWING NUMBER: 441181-5
SHEET: 5 OF 5
SCALE: AS SHOWN