NR9000/NR9000-RT

Energon
Fan Coil Digital Controller
NR9000/NR9000-RT
NR9000
Code
Description
NR9000
Fan coil digital controller
NR9000-RT1A
Flush-mounting remote sensor charcoal colour
NR9000-RT1B
Flush-mounting remote sensor white colour
NR9000-RT2A
Wall mounting remote sensor charcoal colour
NR9000-RT2B
Wall mounting remote sensor charcoal colour
APPLICATION AND USE
NR9000 is a digital controller for 2- or 4-pipe terminal units (eg. Fan
Coil) with ON/OFF, 3-POINT floating or modulating control valves as
well as with 3-speed or modulating fan. NR9000 is equipped with
MODBUS (SLAVE) communication protocol enabling the communication with other MODBUS devices (MASTER).
NR9000 is composed by a M6 DIN rail unit and a remote terminal
(NR9000-RT) with integrated room terminal sensor. It is possible to use
the NR9000-TC remote control (optional) to set a daily switching on
and switching off; time table control can be carried out through the
supervisory system too.
NR9000-RT is the remote terminal which can be connected to the
controller (further details on page 16).
NR9000 can be connected to a receiver module (NR9000-RX, technical characteristics on page 18) and controlled by a infrared remote
control (NR9000-TC, technical characteristics on page 17).
NR9000-TC
NR9000-RT
NR9000-RX
TECHNICAL CHARACTERISTICS
Power supply NR9000: Power supply NR9000-RT:
Protection Degree:
Operation temperature: Storage temperature: Dimensions [mm]: NR9000 controller inputs
• Digital Input (DI1)
• Digital Input (DI2)
• Digital Input (DI3)
• Digital Input (DI4)
• Analogue Input (S1)
• Analogue Input (S2)
• Analogue Input (S3)
• Analogue Input (S4) 85-265Vac (isolated);
12Vdc (from controller);
IP 20;
2T45°C;
-25T65°C;
see page 18.
Window Contact
Remote Power off *
Winter/Summer Change Over
Comfort/Economy *
Return Temperature Sensor **
Remote Temperature Set **
Auxiliary loop sensor
Auxiliary loop set selector
*”Remote Power off” or “Comfort/Economy” digital inputs can be
used to interface the controller with a Presence Detector to minimize costs for heating and cooling.
When digital inputs are in use they have priority on remote sensor
and supervisory system.
** Sensors with a sensing element NTC10K Ohm @ 25°C.
Accuracy ± 1K, β @ 25°C = 3435
(reference Controlli room sensors S4xxA/B and SNTC-xL)
Digital inputs can be enabled using a configuration tool called
“Configuratore NR9000” thanks to which you can also reverse the inputs action. It can be downloaded by our web site www.controlli.eu.
The default status of digital inputs (factory setting) is the following:
N.B.: NR9000-TC and NR9000-RX
are accessories sold separately
DIGITAL INPUT
DEFAULT
DESCRIPTION
WINDOW
CONTACT***
N.C (normally
closed)
OPEN – window opened
CLOSED – window
closed
REMOTE POWER
OFF
N.O (normally
open)
OPEN – Comfort/
economy
CLOSED – off
WINTER/SUMMER
CHANGEOVER***
N.O (normally
open)
OPEN – winter
CLOSED – summer
COMFORT/
ECONOMY***
N.O (normally
open)
OPEN – Comfort
CLOSED – economy
*** These inputs are disabled by default because of the controller status word
(look at table page 15). If you need to enable them a supervisory system
is required.
For example, in case the window switch is normally opened (closed
window is equivalent to open contact), it is necessary to reverse the
action of the digital input.
Controlli S.p.A.
16010 Sant’Olcese (GE)
Tel. 010 73 06 1
Fax. 010 73 06 870/871
www.controlli.eu
1st Issue rev. c
12/2015
DBL408e
Page 1
NR9000 outputs
• 4 TRIAC Outputs to drive 3P valves (HOT valve and COOL valve).
Contact Rating 24-250V 4 A;
• 3 RELAY Outputs to drive 3 speed FAN (V1, V2, V3). Contact Rating 24..250V 8 A;
• 2 Analogue Output 0-10V to drive proportional valves. It is possible to use 0-10V outputs to drive a modulating FAN plus modulating valves in sequence (0-5/6-10);
• 2 Open Collector Outputs: OC1 and OC2. They have a maximum load of 18mA and can be used to drive 12Vdc relays
whose maximum power is 220mW and winding resistance >=
640Ohm (ref. Controlli relay module mod. DGSRMV);
• OC1 output follows the ON/OFF input and it can be used,
through an external relay, to enable electrical loads. If the
local operation mode is enabled (through controller password) OC1 follows the input DI2 (override turn off), so if DI2
is open, OC1 is ON too, instead if DI2 input is closed, OC1 is
OFF too. If the local operation mode is disabled, OC1 follows the value set at 9011 ModBus address;
• OC2 output is used to enable auxiliary functions described
in the “Controller functions” paragraph. If the temperature
sensor S3 is present, the ON/OFF auxiliary loop which controls OC2 will be automatically enabled; otherwise it is possible to enable the electrical coil in emergency (through
controller password) which controls OC2. If the sensor S3
is not present, OC2 follows the value set at 9013 ModBus
address;
• 1 Bus to connect remote terminal NR9000-RT;
• 1 Bus Modbus to connect supervisor system;
• 1 Bus Link to connect IO expansion;
• 1 communication connector with infrared receiver module
NR9000-RX (through a 80cm flat cable)
Installation of NR9000-RT remote sensor
Directives and Standards
54609-02
Standard CEI EN 60730-1 for EMC directive.
Standard CEI EN 60730-1 and CEI EN 60730-2-9 for LVD directive.
54609-03
INSTALLATION
Note: In case of orders for wall mounting models, back plate and
BTicino Living International (round cover) finishing plate are included.
Installation of NR9000 controller
NR9000-RT is suitable for flush mounting in standard box 503E or for
wall mounting on the basis of the model. The supporting frame is
compatible with BTicino cover plates Livinglight (square cover) or
Living International (round cover) otherwise with Vimar Plana cover
plates modifying the supplied supporting frame as shown in the following figure.
Using a screwdiver
press the snap and
push down.
ACCESSORIES
NR9000 accessories
NR9000-TC NR9000-RX infrared remote control
infrared receiver module
NR9000-RT accessories
BTicino LivingLight series (square cover) finishing cover
plate;
BTicino Living International series (round cover) finishing cover plate.
MAINTENANCE
NR9000 are suitable for mounting on a DIN rail with a quick coupling.
Connections shall be in compliance with existing rules and using max
2,5mm2 cross section wires for J1 and J2 terminals and 1,5mm2 cross
section wires for J3 and J4.
To use wire terminals on power supply wires follow the instructions in
order to prevent accidental contacts between cables at different
voltages in case of wrong installation.
The main power is fully isolated but we suggest to install a protection
device compliant to existing national rules with a 125mA intervention
threshold and a minimum 3mm contact opening. The device is not
supplied with the product.
To use the infrared remote control (NR9000-TC) it is necessary to connect NR9000 to the receiver module NR9000-RX through the cable
supplied with the controller.
The connection port of the receiver module is placed on the upper
side of the NR9000 controller. The receiver can be installed in the
range of the infrared remote control through the double-side tape
supplied with the receiver. The infrared remote control NR9000TC is
powered by 2 AAA batteries (included) and it is equipped with a
support for wall mounting (further information on page 17).
The controller is maintenance free.
TERMINALS
NR9000-RT terminals
NR9000 terminals
Pluggable terminals (J1 & J2) 5,08mm pitch for low voltage signals
(230Vac) and 3,5mm pitch (J3 & J4) for very low voltage signals.
Look at the table on the next page for details.
1st Issue rev. c
12/2015
DBL408e
Page 2
CONN # pin
J1
J2
J3
J4
Signal
Direction
Type of signal
Description
1
F
2
N
input
85-265Vac phase
Power supply
input
85-265Vac neutral
Power supply
3
HOT_CL
4
HOT_COM
output
24-230Vac TRIAC 4A
Hot valve (Close)
output
24-230Vac TRIAC COM
Hot valve (COM)
5
6
HOT_OP
output
24-230Vac TRIAC 4A
Hot valve (Open)
COLD_CL
output
24-230Vac TRIAC 4A
Cool valve (Close)
7
8
COLD_COM
output
24-230Vac TRIAC COM
Cool valve (COM)
COLD_OP
output
24-230Vac TRIAC 4A
Cool valve (Open)
9
RA_COM
output
24-230Vac COM
Fan Speed COM
10
R1
output
24-230Vac RELAY 8A
V1 Fan Speed
11
R2
output
24-230Vac RELAY 8A
V2 Fan Speed
12
R3
output
24-230Vac RELAY 8A
V3 Fan Speed
13
RB_COM
output
Not used
14
-
N/A
Not used
15
-
N/A
Not used
16
-
N/A
40
DI1
input
Not used
digital 1 /24Vac
Window contact
39
DI2
input
digital 2 /24Vac
ON-OFF contact
38
DI3
input
digital 3 /24Vac
Summer/Winter contact
37
DI4
input
digital 4 /24Vac
Comfort-economy contact
36
DI_COM
input
digital COM
COM
35
S1
input
analogue input
Return sensor
34
S2
input
analogue input
Remote set
33
S3
input
analogue input
Auxiliary Loop Return Sensor
32
S4
input
analogue input
Remote Set Auxiliary Loop
31
S_COM
input
COM
COM
30
OCC
output
COM Open Collector +12V
Com Open Collector +12V
29
OC1
output
Open Collector 1
Open Collector for external RELAY 1
28
OC2
output
Open Collector 2
Open Collector for external RELAY 2
27
AO2
output
Analogue output 2
Modulating cooling valve 2 – fan
26
AO1
output
Analogue output 1
Modulating heating valve 1 – sequence
25
AOC
output
COM
COM / Shield
24
485-
Bidir
BUS RS485 -
Supervisor Bus (-)
23
485+
Bidir
BUS RS485 +
Supervisor Bus (+)
22
+12Vcc
output
+12V (sensor NR9000-RT)
+12V (sensor NR9000-RT)
21
SDA
Bidir
BUS TX (sensor NR9000-RT)
BUS TX (sensor NR9000-RT)
20
SCL
Bidir
BUS RX (sensor NR9000-RT)
BUS RX (sensor NR9000-RT)
19
GND
Bidir
GND (sensor NR9000-RT)
GND (sensor NR9000-RT)
18
TTL+
Bidir
Link Bus +
Bus I/O expansion +
17
TTL-
Bidir
Link Bus -
Bus I/O expansion -
1st Issue rev. c
12/2015
DBL408e
Page 3
WIRING DIAGRAMS
Example of 4-pipe plant with 230V 3-point valves
Example of 4-pipe plants with 230V ON/OFF valves
1st Issue rev. c
12/2015
DBL408e
Page 4
Example of 4-pipe plants with 24V 3-point valves
Example of 4-pipe plant with 24V ON/OFF valves
1st Issue rev. c
12/2015
DBL408e
Page 5
Example of 2-pipe plant with 230V 3-point valves
Example of 2-pipe plant with 230V ON/OFF valves
1st Issue rev. c
12/2015
DBL408e
Page 6
Example of 2-pipe plant with 24V 3-point valves
Example of 2-pipe plant with 24V ON/OFF valves
1st Issue rev. c
12/2015
DBL408e
Page 7
OPERATION
room 1
The internally stored parameters used by the controller during operation can be changed using NR9000-RT Remote Sensor or using
a Supervisory System (MODBUS protocol). Remote Sensor NR9000-RT
allows to change the operation mode, the set point and the fan
speed; all other parameters can be modified only through the supervisory system or the dedicated configuration tool. The controller
can operate also without the Remote Sensor using a dedicated analogue input (Return Sensor).
link bus
controller
expansions
The controller will consider the data acquired by the Sensor and by
the Supervisory system (if present) and will perform a P or PI or PID
regulation to drive the valves and the fan.
The controller can operate also without NR9000-RT and supervisory
system (Modbus). In this case the room temperature is measured by
the return sensor and thanks to the remote selector it is possible to set
the correction of the temperature. In this configuration, the control
parameters can be changed only through a dedicated configuration tool.
The controller can be controlled by an infrared remote control
(NR9000-TC). The remote control is equipped with a wide display and
supplied together with batteries and frame for wall mounting. It allows to set the temperature in the range 10T30°C, the programming
of a daily switching on and switching off and the set of the operation
mode (ventilation only, heating only, cooling only and automatic).
In case both remote control and remote terminal are present together, the controller will follow the settings received by the last device. In
case the last control is sent by the remote control, the information of
the remote terminal will be overwritten too.
•
N Controllers + N Remote Sensor + Supervisor (with or without
remote control)
System configuration
The system can be configured as shown in the following diagrams:
•
Controller + Remote sensor (with or without remote control)
Supervisory system
The supervisory system can be implemented using the following
MODBUS-RTU (master) devices:
•
•
room 1
•
Controller (Stand Alone) with return sensor (with or without remote control)
room 1
return sensor
Operator Panel: MT-NET-PONR: it is possible to connect up to 50
controllers.
PC Supervisor: configuration tool “Configuratore NR9000” downloadable from www.controlli.eu site; in this case it is possible to
connect up to 250 controllers. It is possible to use also Micronet
View or Touch Screen GTO series on demand getting in touch
with our technical dept.; in this case it is possible to connect up
to 48 controllers.
ModBus - RS485 Connection
The RS485 network is implemented with a 3-conductor cable, which
will be later identified as “+” (pin 23), “-” (pin 24) and “GND” (pin 25).
For wiring is suggested Belden®, model 8762.
For “disturbed” areas is suggested a Belden®, model 3106A using the
twisted pair to connect the “+” and “-“, the reference wire to connect to “GND” and the shield to connect to ground.
Alternatively you can use a cable with the following electrical and
mechanical characteristics:
•
•
•
•
AWG 20/22;
characteristic impedance of 120Ω;
copper wire, “plait” type, twisted;
shielded braided and insulated;
The shield must be connected to controller GND (pin 25).
The network must be wired only in accordance with the principle
shown here, called “daisy chain” (the device is composed by a single RS485 port). Star connections are not allowed.
Connections warnings
•
N Controllers ( with N-1 expansions) + 1 Remote Sensor
(N max I/O expansions = 6) (with or without remote control)
1st Issue rev. c
12/2015
DBL408e
Page 8
For proper network cabling is recommended to take the following
precautions:
CONTROLLER FUNCTIONS
1.
Summer/Winter Changeover
The summer/winter changeover is used by the controller to reverse
the action (Hot/Cold) in 2-pipe systems: the temperature set in
economy mode will be increased with the set correction during summer and decreased during winter. This information can be defined
through a dedicated digital input or via parameter and it can be set
by the supervisory system or by a configuration tool using MODBUS
protocol.
N.B: by default Summer/Winter changeover is set by local mode; in
plants equipped with a supervisory system it has to be preconfigured
by remote mode;
Do not use different types of cable to achieve the same network, but always use only the same type of cable;
2. The network cable carries out safety voltage signals (SELV) and
must not be wired together with dangerous voltage signals
(e.g., 230Vac) or carriers of high currents, especially if in alternating current. Also avoid parallel paths to these power cables;
3. Wire the cable lying avoiding kinks, narrow bending radii and
unnecessary wrapping in hanks or skeins;
4. Do not twist the cable cord around the power conductors and,
if they should cross, consider an intersection at 90 ° between the
cable and these conductors;
5. Keep away from sources of electromagnetic field in particular
by large motors, electrical cabinet, reactors for neon, all types
of antennas;
6. Do not pull the power cable exceeds 110N (11.3kg) to prevent
ironing;
7. Assess in advance the route so that it will be as short as possible
and note addresses of connected instruments with particular
reference to its location in the orderly sequence. This can be
very useful in maintenance; we recommend to note the Modbus Address on the product label.
8. Do not reverse the polarity “+” and “-” of the connection terminals;
9. Avoid short lengths of cable terminations in connection tools
to make a maintenance without tearing or flues of the cables
possible;
10. Identify start and ending terminations and avoid cuts “open”;
Terminating transistors and network polarization
The slew rate control, mutual function in our 485 transceiver and the
limited baud rate to 9600 baud make the terminating resistors not
necessary.
RS485 network needs of polarization typically in charge of the master
device; the controller doesn’t have polarization resistors.
The transceiver used by the controller allows to drive up to 256 points.
RS485 standards require a maximum length of 1200m and/or 32 devices on the network.
It should be noted that more limits are exceeded, higher is the probability that problems in communication arise. The phenomenon is not
systematic and may not occur. Conversely, in case problems should
arise and none of the points mentioned in this paragraph has solved
them, it is recommended to connect a repeater (CONV RS485-RIP),
as shown in the picture below:
Repeater
R=100 - 120 Ohm
N4177-07
GND
Supervisory
System
+
R=100 - 120 Ohm
+
-
G
N
D
Device
+
-
G
N
D
Device
+
-
G
N
D
+
-
G
N
D
Device
+
-
G
N+ D
G
N
D
Device
N.B.: Connect the repeater if cables length exceeds 1200m or if devices are more than 32.
Operation modes
NR9000 works with 3 different operation modes:
•
•
•
COMFORT: the controller will control the temperature (driving
valves and fan) to satisfy the Comfort Temperature Set.
ECONOMY: the controller will control the temperature to satisfy
the Economy Temperature Set.
FROST PROTECTION: the controller is normally OFF; just during
winter operation it works with a set fixed at 8°C and heating
function only.
1st Issue rev. c
Initial Valve position
To drive a 3-point actuator is necessary to place the actuator in a
specific position. Each time the controller is powered up, the actuator will be driven in the closing position for a time equal to the overall
travel time plus 33%.
Cut-off
This function is used to stop the control of the 3 points actuator after
the overall travel time plus 33%. This function is used to ensure the
correct valve closing and to reduce the noise.
The function can be disabled by the supervisory system. In this case
at its stroke end the actuator will be powered indefinitely.
Window contact
This function is used to save energy when a Normally Closed contact
is opened (Open Window). In this case the controller will change
the operation mode from Comfort to Economy. When the window is
open, if the minimum fan speed or the air recirculation functions are
enabled, the fan will be anyway turned off when the set is reached.
Hot/Cold launch
This function is used to avoid the introduction of cold or hot air in the
ambient by delaying (for a set time) the fan start. To disable the
function, set the time = 0.
“Disposal”
The “Disposal” function is useful both for the hot and the cold channel and it helps to take off the energy stored in the fan coil radiator
by delaying the fan turning off.
To disable the function, set the time = 0.
Minimum speed activation
This function is used to prevent air stratification, especially when using
the Return Sensor, as it could be very low sensitive to temperature
variation that occurs at man’s height. A continuous air movement
helps to avoid /reduce air stratification and to optimize the regulation.
If the fan is connected to the relay output, it is necessary to set the
“minimum fan speed” parameter at 1. A system configuration with
Proportional Fan requires setting the minimum speed in % of the control value (0 - 10V), therefore, if the fan is connected to the 0-10V
output, it is necessary to set the “minimum fan speed” parameter
at a value between 0 and 50. In both cases the 0 value disables the
function. To disable this function, set 0 as minimum speed.
Auxiliary regulation ON/OFF (P action)
This function can be automatically enable when the sensor in position S3 is connected. If the remote set in S4 is connected, it is possible
to have a set in the range 10-30°C, otherwise it can be set through
the supervisory system together with the dead zone.
If the supervisory system is not present , this function will be carried on
at fixed point 20°C with dead zone = 1K. The output will be available
in OC2 and it will exclude the management of the electrical coil.
Air recirculation function
This function manages the minimum fan speed. It is enabled setting a
“period” and a “minimum speed” different from zero. When the “period” will be passed, the fan will be enabled at the minimum speed
for the time (minutes) set.
12/2015
DBL408e
Page 9
Electrical Coil
Electrical Coil function can be enabled in the configuration tool as
“emergency”.
The output provides an open collector signal (OC2) (with reference
to signal pin 30, +12V) to control an external auxiliary relay.
The output is activated when the room temperature is lower than:
“hot” operation set - Proportional Band - 1°C
and it goes off when the room temperature is higher than:
“hot” operation set - proportional band
Electrical Coil in “emergency” mode:
Control modes
NR9000 works with 7 different control modes selectable via dip switch
or by supervisory system:
ON/OFF Valves and 3-speed fan (“FAST” operation mode - Operation Diagram 1).
2. ON/OFF Valves and 3-speed fan (Operation Diagram 2).
3. 3-point Valves and 3-speed fan (Operation Diagram 3).
4. ON/OFF Valves and 1-speed fan (Operation Diagram 4).
5. 3-point Valves and 1-speed fan (Operation Diagram 5).
6. ON/OFF Valves and Modulating FAN (0–10V) (Operation Diagram 6).
7a. 2-pipe plant. Proportional Valve (0-10V) and Modulating Fan (010V) (Operation Diagram 7a).
7b. 4-pipe plant: Sequence Valves 0-5/6-10V and Modulating Fan
(0-10V) (Operation Diagram 7b).
1.
In case of use of 3-speed fans (3 relays), the 0-10V outputs are always
available and they follow the ON-OFF or 3-point valves characteristics.
The diagrams of the valves and fans share the Set point, instead proportional bands and hysteresis can be set independently.
Time table by remote control
It is possible to program a daily switching on and switching off
through the use of the optionals NR9000-TC infrared remote control
and NR9000-RX infrared receiver module (for further information look
at pages 17-18).
1.
It is possible to enable the functions hot/cold launch, “disposal” and
minimum speed activation with a priority over normal operation defined by the diagrams.
ON/OFF Valves and 3 Speed FAN - “FAST” operation mode
The valves are activated in ONOFF mode with a hysteresis.
Speed 1 is ON when the error (E) is
greater than 10%.
TSET-T
E % = ----------- * 100
PB
Speed 2 and 3 follow to the Proportional Band as shown in the
diagram aside.
2.
ON/OFF Valves and 3 Speed FAN
The valves are activated in ONOFF mode with a hysteresis.
Speed 1, 2 and 3 follow to the
Proportional Band as shown in the
diagram aside.
1st Issue rev. c
12/2015
DBL408e
Page 10
3.
3 point valves and 3 Speed FAN
The valves are activated in Proportional mode (0-100%) using
the set proportional band.
Speed 1, 2 and 3 follow to the
Proportional Band as shown in the
diagram aside.
4.
ON/OFF valves and 1 Speed FAN
The valves are activated in ONOFF mode with hysteresis.
Speed 1 follows to the Proportional Band as shown in the diagram
aside.
5.
3 point valves and 1 Speed FAN
The valves are activated in Proportional mode (0-100%) using a
proportional band.
Speed 1 follows to the Proportional Band as shown in the diagram
aside.
1st Issue rev. c
12/2015
DBL408e
Page 11
6.
ON/OFF Valves and Proportional Speed Fan (0-10V)
The valves are activated in ONOFF mode with hysteresis.
Speed fan follow to the Proportional Band as shown in the diagram aside generating a 0-10V
output control signal.
7a.
Proportional Valve (0-10V) and Proportional Speed Fan (0-10V) (2-pipe plant)
The valves are activated in Proportional mode (0-100%) using
the set proportional band, (heating during winter, cooling during
summer).
Fan speeds follow the Proportional Band as shown in the diagram
aside generating a 0-10V output
control signal.
7b.
0-5/6-10 V Sequence Valves and Proportional Speed Fan (0-10V) (4-pipe plant)
The valves are activated in sequence mode (0-5/6-10) with
hysteresis. If the set is satisfied the
output is 5,5V.
Fan speeds follow the Proportional Band as shown in the diagram
aside generating a 0-10V output
control signal.
Modulating valve and/or fan application example
Control modes diagrams
2-pipe plant
Out AO1
Out AO2
6
No
---
Fan
6
Yes
---
Fan
7
Yes
Hot/cool valve
Fan
7
No
Hot/cool sequence
Fan
1st Issue rev. c
12/2015
DBL408e
Page 12
NR9000 CONTROLLER DIP SWITCHES AND LEDs
The controller has 8 DIP switches accessible by removing the top
cover and two LEDs to check operation anomalies.
1
2
3
4
5
6
7
8
ON
DIP switches from 1 to 4 can be used to set MODBUS devices address
(up to 14) without the use of the configuration tool and to set the
controller in expansion mode duplicating the outputs.
If DIP 1-4 are all ON the controller is configured as expansion, duplicating the master controller outputs connected to the remote sensor
(NR9000-RT) and/or to the supervisory system.
If DIP switches 1 to 4 are all OFF the default ModBus address is 1 (factory eeprom setting).
In case of more than 14 devices, configuration can be carried out
via supervisory system or using a configuration tool via Modbus protocol.
DIP from 5 to 7 are used to select the operation diagram.
If DIP 5 to 7 are OFF the default operation diagram is nr. 2 - ON/OFF
Valves and 3 Speed FAN (factory eeprom setting).
DIP 8 is used to select 2/4 pipe system.
If DIP 8 is OFF the system is 2 pipe (factory eeprom setting).
Parameters set by DIP have the priority over the supervisory system. It
is possible to disable the DIP switch setting by ModBus.
It is necessary to power down and power up the controller in case of
any change in DIP switches configuration.
DIP switches 5-7 settings
DIP5 DIP6 DIP7
CONFIGURATION DIAGRAM
OFF
OFF
OFF
ON/OFF Valves and 3 FAN speed (factory
setting)
ON
OFF
OFF
ON/OFF Valves and 3 FAN speed “FAST”
(Operating Diagram 1)
OFF
ON
OFF
ON/OFF Valves and 3 FAN speed (Operating
Diagram 2)
ON
ON
OFF
3-point Valves and 3 FAN speed (Operating
Diagram 3)
OFF
OFF
ON
ON/OFF Valves and 1 FAN speed (Operating
Diagram 4)
ON
OFF
ON
3-point Valves and 1 FAN speed (Operating
Diagram 5)
OFF
ON
ON
ON/OFF Valves and Modulating FAN (0 – 10 V)
(Operating Diagram 6)
ON
ON
ON
0-5/6-10 Sequence Valves and Modulating
FAN (0 – 10 V). (Operating Diagram 7)
DIP switche 8 settings
DIP 8
PLANT
OFF
2-pipe
ON
4-pipe
DIP Switches 1-4 settings
DIP1 DIP2 DIP3 DIP4
MODBUS ADDRESS
OFF
OFF
OFF
OFF
Factory Setting (default address1)
ON
OFF
OFF
OFF
1
OFF
ON
OFF
OFF
2
ON
ON
OFF
OFF
3
OFF
OFF
ON
OFF
4
ON
OFF
ON
OFF
5
OFF
ON
ON
OFF
6
ON
ON
ON
OFF
7
OFF
OFF
OFF
ON
8
ON
OFF
OFF
ON
9
OFF
ON
OFF
ON
10
ON
ON
OFF
ON
11
OFF
OFF
ON
ON
12
ON
OFF
ON
ON
13
OFF
ON
ON
ON
14
ON
ON
ON
ON
Controller used as IO expansion
1st Issue rev. c
LEDs functionalities
Controller is equipped with 2 LEDs to check its behaviour and possible anomalies as shown in the following table:
RED LED
GREEN
LED
BLINKING
OFF
OFF
BLINKING RATE
1Hz – DUTY CYCLE 50% HOT VALVE OPENED
BLINKING 1Hz - DUTY CYCLE 50% COOL VALVE OPENED
BLINKING BLINKING 1Hz – DUTY CYCLE 10%
ON
ON
DESCRIPTION
ON
NA
BLINKING 2 Hz – DUTY CYCLE 50%
HOT & COOL VALVE
CLOSED
REMOTE SENSOR
COMUNICATION
FAILURE
LOCAL SENSOR
ERROR
Note: for a 2-pipe system the only connected 3-point or ON/OFF
valve is the HOT valve and so the only operative LED for hot
and cool fluid is the RED LED.
12/2015
DBL408e
Page 13
DEFAULT PARAMETERS
The controller is released with the DIP switches in OFF position (2-pipe, Modbus Address 1, ON / OFF valves and 3 fan speed) and with regulation parameters shown in the following table:
Parameter
Vmin
Vmax
Default
Hot Loop Set Point
100 (10°C)
350 (35°C)
200 (20°C)
Stroke Time for 3 Points actuators
30s
480s
60s
Derivative Constant for hot loop
1s
1000s
1s
Derivative Constant for cool loop
1s
1000 s
1s
Dead Zone
0 (0°C)
100 (10°C)
20 (2°C)
Auxiliary Loop Set
100 (10°C)
350 (35°C)
200 (20°)
Set adjustment for Economy operation mode
0 (0°C)
40 (4°C)
30 (3°C)
Action Type P(0), PI(1), PID(2)
0
2
0 (P)
Proportional Band Hot Valve
5 (0.5°C)
80 (8°C)
10 (1°C)
Proportional Band Cool Valve
5 (0.5°C)
80 (8°C)
10 (1°C)
Proportional Band Hot Fan
5 (0.5°C)
80 (8°C)
30 (3°C)
Proportional Band Cool Fan
5 (0.5°C)
80 (8°C)
30 (3°C)
Integration Time Hot loop
1 (min)
30 (min)
5 (min)
Integration Time Cool loop
1 (min)
30 (min)
5 (min)
Cut Off Function with Extra stroke of 33%
0
1
1 (ENABLE)
Summer/Winter Changeover
0
1
0 (WINTER)
Operation Mode: COMFORT(0), Economy(1), Frost(2)
0
2
0 (COMFORT)
Delay Time Fan Start
0
255
0 (DISABLE)
Delay Time Fan Stop
0
255
0 (DISABLE)
minimum fan speed
0
50
0 (DISABLE)
Controller Modbus Address
1
250
1
Operation Diagram
1
7
2
2/4 Pipe system
0
1
0 (2-PIPE)
NR9000-RT (*) “STATUS WORD”
0
8
8 (FULL ENABLE)
NR9000 (**) “STATUS WORD”
0
255
0
Fan Operation Mode (STOP(0),V1(1),V2(2),V3(3),AUTO(4))
0
4
4 (AUTO)
Digital Inputs reverse action (4 BIT, N.O.(0),N.C.(1))
0
15
1
Bit0: WINDOW CONTACT (N.C.)
Bit1:REMOTE POWER OFF (N.A.)
Bit2:W/S CHANGEOVER (N.A.)
Bit3: COMFORT/ECONOMY (N.A.)
Relay Commutation Time delay (Fixed 1 sec)
0
1
1 (ENABLE)
Auxiliary loop hysteresis
Auxiliary loop direct/reverse action
Air recirculation function Period
Air recirculation function time
0 (0.5°C)
0
0 (min)
1 (min)
80 (8.0°C)
1
60 (min)
10 (min)
10 (1.0°C)
1
0 (min)
1 (min)
1st Issue rev. c
12/2015
DBL408e
Page 14
* “STATUS WORD” parameter NR9000-RT
Value
Default
0
Display Off “---”
1
Display “Only” Room Temperature in page 0
2
Display “Only” Temperature Set in page 0
3
Display Room Temperature in page 0 with T. Set, Fan e Mode “fixed”.
4
Display Room Temperature in page 0 with T. Set, Fan “fixed” e only Mode “editable”
5
Display Temperature Set in page 0 with Fan e Mode “fixed”.
6
Display Temperature Set in page 0 with Fan “fixed” e only Mode “editable”
7
All enabled with Set Correction (+-3K)
8
All enabled with Temperature Set 10T35°C (default)
** “STATUS WORD” parameter NR9000
BIT
Description
“0”
“1”
0
Operation Mode
1
Ambient Temperature
Remote (comes from NR9000-RT)
Local (comes from “dedicated”
analogue input S1)
0
2
Summer / Winter Changeover
Remote (Disable digital input Summer/
Winter DI3)
Local (Enable digital input
Summer/Winter DI3)
1
3
Temperature Set
Remote (comes from NR9000-RT)
Local (comes from “dedicated”
analogue input S2)
0
4
Window Contact
Disable digital input DI1
Enable digital input DI1
0
5
Temperature Set Correction Mode
10-35°C
±3K
0
Remote (Disable digital input Comfort/
Local (Enable digital input
Economy and Power Off)
Comfort/Economy and Power Off)
Default
0
6
DIP switch
Enable
Disable
0
7
Electrical Battery
Disable
Enable
0
1st Issue rev. c
12/2015
DBL408e
Page 15
REMOTE SENSOR NR9000-RT
NR9002-RT remote sensor mounting instructions
Flush-mounting
1
2
Make wiring connections
Remove the cover plate
T amb
4
3
Fix to flush-mounting box 503
The remote sensor has 4 buttons and a 3 digit LCD display.
The functions of the sensor are:
•
•
•
•
Room Temperature Monitoring (T amb).
Temperature Set (buttons 2 & 3).
Fan Speed Set (Auto, OFF, V1, V2, V3 - button 1).
Operation Mode Set (Button 4).
Wall mounting
The sensor has several configurations (enabled/disabled functions)
that can be defined by the controller through the supervisory system
or the configuration tool:
•
Set Point Disabled
In this case the controller does not allow the user to change the
set point from the Remote Terminal.
•
Fan Speed Disabled
In this case the controller does not allow the user to change the
fan speed from the Remote Terminal.
•
Operating Mode Disabled
In this case the controller does not allow the user to change the
operation modes from the Remote Terminal.
•
Remote Sensor Disabled
In this case the controller does not allow the user to change all
the function listed above and the remote terminal can show
and send to controller only the room temperature.
Distance between holes [mm]
Make wiring connections
Remove the cover plate
It is possible to calibrate the room temperature displayed on the remote sensor of ± 3°C (label tAr) and to read and set the MODBUS address (label Add) of the controller connected to the sensor following
these instructions:
•
•
press button 4 and select the frost protection status (OFF)
press for more than 10s the button 1 (FAN)
Fix to wall with 2 Fisher screws
All functionalities are enabled by default.
The remote sensor NR9000-RT has a two-coloured LED to identify the
operation mode as shown in the following tables:
OPERATION MODE
LED
Comfort
green
Economy
orange
Frost protection (OFF)
green blinking
1st Issue rev. c
12/2015
DBL408e
Page 16
NR9000-TC REMOTE CONTROL
The remote control is infrared type with a graphic display and programming keyboard.
For a correct work, it is necessary a visual contact with the receiver
fitted on board of the unit to be controlled.
It is necessary that the infrared control is pointed towards the receiver and that the distance between infrared control and receiver is
max 5/6 meters.
The correct delivery of the information to the receiver module is signalled with an alternating blinking of the GREEN and YELLOW LED
placed on the receiver module.
Setting will be sent to the receiver module with a single message in
the moment in which you press the button “OFF” or “ON/SEND”.
Use of the infrared handset
TIMER PROGRAM
Start time:
Press SELECT button twice, the word PROGRAM and the word START
(lighting) will be displayed.
Press (+) or (-) button, the word START will become fix and the hours
value will start lighting.
Use (+) button to increase or (-) to decrease the hours.
Press SELECT button, the minutes value will light.
Use (+) button to increase or (-) to decrease minutes.
Stop time:
Press SELECT button, the word STOP will light on the display.
Press (+) or (-) button, the word STOP will become fix and the hours
value will start lighting.
Use (+) button to increase or (-) to decrease the hours.
Press SELECT button, the minutes value will light.
Use (+) button to increase or (-) to decrease the minutes.
ON or OFF Timer:
Press SELECT button, the TIMER icon will start lighting.
Press (+) button to start the timer (dark icon) or (-) button to de-activate it (light icon).
Press SELECT button to store the information.
Press ON/SEND button to send information to the unit.
General information on timer mode:
Once set up the timer program, it will be repeated day by day until
it will be cancelled (timer OFF).
It is possible to by-pass manually the set automatic program by pressing ON/SEND button to switch on the unit or pressing OFF button to
switch off the unit.
The manual mode will be ON until the next automatic mode of the
program.
NR9000-TC infrared remote control mounting instructions
NR9000-TC infrared remote control is supplied together with a support for wall mounting and batteries. To fix the support to the wall use
screws of correct diameter and length (not supplied).
1.
2.
Open the back cover and slide it outward;
insert the 2 alkaline batteries (size AAA 1,5V) according to polarity;
the display will power on;
close the cover again.
Description of the controls
3.
4.
ON/SEND
Switches on the unit and/or update the information.
NOTE: in case of batteries replacement, after removal of the exhausted ones, wait for 10 minutes before installing the new ones.
MODE
Press button MODE to change between only Ventilation, Heating,
Cooling and Automatic Work.
Press ON/SEND button to send information to the unit.
Dry function is not available.
FAN
Press FAN button to change between Min, Med, Max speed and
Auto (A) (automatic speed).
Press ON/SEND button to send information to the unit.
Description of the function visualized on the display
SET POINT TEMPERATURE
In order to set the desired temperature inside the room (set-point
temperature) in order to increase it press button (+), in order to decrease it press button (-) until the desired temperature.
Press ON/SEND button to send information to the unit.
SWING mode (not available)
CLOCK SET UP
Press SELECT button, the word CLOCK SET will light.
Press (+) or (-) button, the word CLOCK SET will become fix and the
hours value will start lighting.
Use (+) button to increase or (-) to decrease the hours.
Press SELECT button, the minutes value will light.
Use (+) button to increase or (-) to decrease minutes.
Press SELECT button to stop the set up.
Press ON/SEND button to send information to the unit.
1st Issue rev. c
12/2015
DBL408e
Page 17
NR9000-RX RECEIVER MODULE
DIMENSIONS [mm]
For operation with remote control NR9000-TC it is necessary to connect the receiver module NR9000-RX to the controller NR9000 through
the flat cable supplied with it using the connection port placed on
the upper side of the controller.
NR9000
The receiver module is equipped with 2 signalling LEDs:
•
•
GREEN LED to show the controller status (LED ON = controller ON,
LED OFF = controller OFF);
YELLOW LED to show the time table status (LED ON = time table
enabled, LED OFF = time table disabled).
The GREEN and YELLOW LED briefly blink when they receive a signal
coming from the remote control.
Further than the two LEDs the receiver module is equipped with a
button to override the switching on and switching off of the controller. If time table are enabled, by pressing the button they will be
disabled.
NR9000-RT1X
NR9000-RX infrared receiver module mounting instructions
The receiver module is supplied together with a flat connector
(80cm) to be connected to NR9000 controller and a double-side
tape for fixing on smooth surfaces.
In case the flat cable is not connected to the receiver, proceed as
follows:
4.
5.
6.
30
44
50,4
36,3
22,4
N.B.: In case the flat cable is already connected to the receiver
module, just follow the instructions on point 5 and 6.
NR9000-RT2X
136,5
3.
42,5
2.
unscrew the two screws on the receiver to open the back cover: a 6-terminal connector will be visible;
insert one end of the cable inside the connector. The connector
can be mounted in one direction only as it is polarized;
close again the back cover and tighten the screws making the
flat cable come out from the split you find between cover and
case;
in case it is necessary to place the flat cable in a duct, see the
picture below for duct dimensions;
connect the other end of the flat cable to the connector you
can see in the split on the upper side of the controller. The connector can be mounted in one direction only as the cable is
polarized;
Place the double-side tape on the back side of the receiver
module and pay attention not to force the flat cable.
134
1.
35
NR9000-TC
14,3
50
20
4,25
NR9000-RX
13,8
The performances stated in this sheet can be modified without any prior notice
1st Issue rev. c
12/2015
DBL408e
Page 18