Energon Fan Coil Digital Controller NR9000/NR9000-RT NR9000 Code Description NR9000 Fan coil digital controller NR9000-RT1A Flush-mounting remote sensor charcoal colour NR9000-RT1B Flush-mounting remote sensor white colour NR9000-RT2A Wall mounting remote sensor charcoal colour NR9000-RT2B Wall mounting remote sensor charcoal colour APPLICATION AND USE NR9000 is a digital controller for 2- or 4-pipe terminal units (eg. Fan Coil) with ON/OFF, 3-POINT floating or modulating control valves as well as with 3-speed or modulating fan. NR9000 is equipped with MODBUS (SLAVE) communication protocol enabling the communication with other MODBUS devices (MASTER). NR9000 is composed by a M6 DIN rail unit and a remote terminal (NR9000-RT) with integrated room terminal sensor. It is possible to use the NR9000-TC remote control (optional) to set a daily switching on and switching off; time table control can be carried out through the supervisory system too. NR9000-RT is the remote terminal which can be connected to the controller (further details on page 16). NR9000 can be connected to a receiver module (NR9000-RX, technical characteristics on page 18) and controlled by a infrared remote control (NR9000-TC, technical characteristics on page 17). NR9000-TC NR9000-RT NR9000-RX TECHNICAL CHARACTERISTICS Power supply NR9000: Power supply NR9000-RT: Protection Degree: Operation temperature: Storage temperature: Dimensions [mm]: NR9000 controller inputs • Digital Input (DI1) • Digital Input (DI2) • Digital Input (DI3) • Digital Input (DI4) • Analogue Input (S1) • Analogue Input (S2) • Analogue Input (S3) • Analogue Input (S4) 85-265Vac (isolated); 12Vdc (from controller); IP 20; 2T45°C; -25T65°C; see page 18. Window Contact Remote Power off * Winter/Summer Change Over Comfort/Economy * Return Temperature Sensor ** Remote Temperature Set ** Auxiliary loop sensor Auxiliary loop set selector *”Remote Power off” or “Comfort/Economy” digital inputs can be used to interface the controller with a Presence Detector to minimize costs for heating and cooling. When digital inputs are in use they have priority on remote sensor and supervisory system. ** Sensors with a sensing element NTC10K Ohm @ 25°C. Accuracy ± 1K, β @ 25°C = 3435 (reference Controlli room sensors S4xxA/B and SNTC-xL) Digital inputs can be enabled using a configuration tool called “Configuratore NR9000” thanks to which you can also reverse the inputs action. It can be downloaded by our web site www.controlli.eu. The default status of digital inputs (factory setting) is the following: N.B.: NR9000-TC and NR9000-RX are accessories sold separately DIGITAL INPUT DEFAULT DESCRIPTION WINDOW CONTACT*** N.C (normally closed) OPEN – window opened CLOSED – window closed REMOTE POWER OFF N.O (normally open) OPEN – Comfort/ economy CLOSED – off WINTER/SUMMER CHANGEOVER*** N.O (normally open) OPEN – winter CLOSED – summer COMFORT/ ECONOMY*** N.O (normally open) OPEN – Comfort CLOSED – economy *** These inputs are disabled by default because of the controller status word (look at table page 15). If you need to enable them a supervisory system is required. For example, in case the window switch is normally opened (closed window is equivalent to open contact), it is necessary to reverse the action of the digital input. Controlli S.p.A. 16010 Sant’Olcese (GE) Tel. 010 73 06 1 Fax. 010 73 06 870/871 www.controlli.eu 1st Issue rev. c 12/2015 DBL408e Page 1 NR9000 outputs • 4 TRIAC Outputs to drive 3P valves (HOT valve and COOL valve). Contact Rating 24-250V 4 A; • 3 RELAY Outputs to drive 3 speed FAN (V1, V2, V3). Contact Rating 24..250V 8 A; • 2 Analogue Output 0-10V to drive proportional valves. It is possible to use 0-10V outputs to drive a modulating FAN plus modulating valves in sequence (0-5/6-10); • 2 Open Collector Outputs: OC1 and OC2. They have a maximum load of 18mA and can be used to drive 12Vdc relays whose maximum power is 220mW and winding resistance >= 640Ohm (ref. Controlli relay module mod. DGSRMV); • OC1 output follows the ON/OFF input and it can be used, through an external relay, to enable electrical loads. If the local operation mode is enabled (through controller password) OC1 follows the input DI2 (override turn off), so if DI2 is open, OC1 is ON too, instead if DI2 input is closed, OC1 is OFF too. If the local operation mode is disabled, OC1 follows the value set at 9011 ModBus address; • OC2 output is used to enable auxiliary functions described in the “Controller functions” paragraph. If the temperature sensor S3 is present, the ON/OFF auxiliary loop which controls OC2 will be automatically enabled; otherwise it is possible to enable the electrical coil in emergency (through controller password) which controls OC2. If the sensor S3 is not present, OC2 follows the value set at 9013 ModBus address; • 1 Bus to connect remote terminal NR9000-RT; • 1 Bus Modbus to connect supervisor system; • 1 Bus Link to connect IO expansion; • 1 communication connector with infrared receiver module NR9000-RX (through a 80cm flat cable) Installation of NR9000-RT remote sensor Directives and Standards 54609-02 Standard CEI EN 60730-1 for EMC directive. Standard CEI EN 60730-1 and CEI EN 60730-2-9 for LVD directive. 54609-03 INSTALLATION Note: In case of orders for wall mounting models, back plate and BTicino Living International (round cover) finishing plate are included. Installation of NR9000 controller NR9000-RT is suitable for flush mounting in standard box 503E or for wall mounting on the basis of the model. The supporting frame is compatible with BTicino cover plates Livinglight (square cover) or Living International (round cover) otherwise with Vimar Plana cover plates modifying the supplied supporting frame as shown in the following figure. Using a screwdiver press the snap and push down. ACCESSORIES NR9000 accessories NR9000-TC NR9000-RX infrared remote control infrared receiver module NR9000-RT accessories BTicino LivingLight series (square cover) finishing cover plate; BTicino Living International series (round cover) finishing cover plate. MAINTENANCE NR9000 are suitable for mounting on a DIN rail with a quick coupling. Connections shall be in compliance with existing rules and using max 2,5mm2 cross section wires for J1 and J2 terminals and 1,5mm2 cross section wires for J3 and J4. To use wire terminals on power supply wires follow the instructions in order to prevent accidental contacts between cables at different voltages in case of wrong installation. The main power is fully isolated but we suggest to install a protection device compliant to existing national rules with a 125mA intervention threshold and a minimum 3mm contact opening. The device is not supplied with the product. To use the infrared remote control (NR9000-TC) it is necessary to connect NR9000 to the receiver module NR9000-RX through the cable supplied with the controller. The connection port of the receiver module is placed on the upper side of the NR9000 controller. The receiver can be installed in the range of the infrared remote control through the double-side tape supplied with the receiver. The infrared remote control NR9000TC is powered by 2 AAA batteries (included) and it is equipped with a support for wall mounting (further information on page 17). The controller is maintenance free. TERMINALS NR9000-RT terminals NR9000 terminals Pluggable terminals (J1 & J2) 5,08mm pitch for low voltage signals (230Vac) and 3,5mm pitch (J3 & J4) for very low voltage signals. Look at the table on the next page for details. 1st Issue rev. c 12/2015 DBL408e Page 2 CONN # pin J1 J2 J3 J4 Signal Direction Type of signal Description 1 F 2 N input 85-265Vac phase Power supply input 85-265Vac neutral Power supply 3 HOT_CL 4 HOT_COM output 24-230Vac TRIAC 4A Hot valve (Close) output 24-230Vac TRIAC COM Hot valve (COM) 5 6 HOT_OP output 24-230Vac TRIAC 4A Hot valve (Open) COLD_CL output 24-230Vac TRIAC 4A Cool valve (Close) 7 8 COLD_COM output 24-230Vac TRIAC COM Cool valve (COM) COLD_OP output 24-230Vac TRIAC 4A Cool valve (Open) 9 RA_COM output 24-230Vac COM Fan Speed COM 10 R1 output 24-230Vac RELAY 8A V1 Fan Speed 11 R2 output 24-230Vac RELAY 8A V2 Fan Speed 12 R3 output 24-230Vac RELAY 8A V3 Fan Speed 13 RB_COM output Not used 14 - N/A Not used 15 - N/A Not used 16 - N/A 40 DI1 input Not used digital 1 /24Vac Window contact 39 DI2 input digital 2 /24Vac ON-OFF contact 38 DI3 input digital 3 /24Vac Summer/Winter contact 37 DI4 input digital 4 /24Vac Comfort-economy contact 36 DI_COM input digital COM COM 35 S1 input analogue input Return sensor 34 S2 input analogue input Remote set 33 S3 input analogue input Auxiliary Loop Return Sensor 32 S4 input analogue input Remote Set Auxiliary Loop 31 S_COM input COM COM 30 OCC output COM Open Collector +12V Com Open Collector +12V 29 OC1 output Open Collector 1 Open Collector for external RELAY 1 28 OC2 output Open Collector 2 Open Collector for external RELAY 2 27 AO2 output Analogue output 2 Modulating cooling valve 2 – fan 26 AO1 output Analogue output 1 Modulating heating valve 1 – sequence 25 AOC output COM COM / Shield 24 485- Bidir BUS RS485 - Supervisor Bus (-) 23 485+ Bidir BUS RS485 + Supervisor Bus (+) 22 +12Vcc output +12V (sensor NR9000-RT) +12V (sensor NR9000-RT) 21 SDA Bidir BUS TX (sensor NR9000-RT) BUS TX (sensor NR9000-RT) 20 SCL Bidir BUS RX (sensor NR9000-RT) BUS RX (sensor NR9000-RT) 19 GND Bidir GND (sensor NR9000-RT) GND (sensor NR9000-RT) 18 TTL+ Bidir Link Bus + Bus I/O expansion + 17 TTL- Bidir Link Bus - Bus I/O expansion - 1st Issue rev. c 12/2015 DBL408e Page 3 WIRING DIAGRAMS Example of 4-pipe plant with 230V 3-point valves Example of 4-pipe plants with 230V ON/OFF valves 1st Issue rev. c 12/2015 DBL408e Page 4 Example of 4-pipe plants with 24V 3-point valves Example of 4-pipe plant with 24V ON/OFF valves 1st Issue rev. c 12/2015 DBL408e Page 5 Example of 2-pipe plant with 230V 3-point valves Example of 2-pipe plant with 230V ON/OFF valves 1st Issue rev. c 12/2015 DBL408e Page 6 Example of 2-pipe plant with 24V 3-point valves Example of 2-pipe plant with 24V ON/OFF valves 1st Issue rev. c 12/2015 DBL408e Page 7 OPERATION room 1 The internally stored parameters used by the controller during operation can be changed using NR9000-RT Remote Sensor or using a Supervisory System (MODBUS protocol). Remote Sensor NR9000-RT allows to change the operation mode, the set point and the fan speed; all other parameters can be modified only through the supervisory system or the dedicated configuration tool. The controller can operate also without the Remote Sensor using a dedicated analogue input (Return Sensor). link bus controller expansions The controller will consider the data acquired by the Sensor and by the Supervisory system (if present) and will perform a P or PI or PID regulation to drive the valves and the fan. The controller can operate also without NR9000-RT and supervisory system (Modbus). In this case the room temperature is measured by the return sensor and thanks to the remote selector it is possible to set the correction of the temperature. In this configuration, the control parameters can be changed only through a dedicated configuration tool. The controller can be controlled by an infrared remote control (NR9000-TC). The remote control is equipped with a wide display and supplied together with batteries and frame for wall mounting. It allows to set the temperature in the range 10T30°C, the programming of a daily switching on and switching off and the set of the operation mode (ventilation only, heating only, cooling only and automatic). In case both remote control and remote terminal are present together, the controller will follow the settings received by the last device. In case the last control is sent by the remote control, the information of the remote terminal will be overwritten too. • N Controllers + N Remote Sensor + Supervisor (with or without remote control) System configuration The system can be configured as shown in the following diagrams: • Controller + Remote sensor (with or without remote control) Supervisory system The supervisory system can be implemented using the following MODBUS-RTU (master) devices: • • room 1 • Controller (Stand Alone) with return sensor (with or without remote control) room 1 return sensor Operator Panel: MT-NET-PONR: it is possible to connect up to 50 controllers. PC Supervisor: configuration tool “Configuratore NR9000” downloadable from www.controlli.eu site; in this case it is possible to connect up to 250 controllers. It is possible to use also Micronet View or Touch Screen GTO series on demand getting in touch with our technical dept.; in this case it is possible to connect up to 48 controllers. ModBus - RS485 Connection The RS485 network is implemented with a 3-conductor cable, which will be later identified as “+” (pin 23), “-” (pin 24) and “GND” (pin 25). For wiring is suggested Belden®, model 8762. For “disturbed” areas is suggested a Belden®, model 3106A using the twisted pair to connect the “+” and “-“, the reference wire to connect to “GND” and the shield to connect to ground. Alternatively you can use a cable with the following electrical and mechanical characteristics: • • • • AWG 20/22; characteristic impedance of 120Ω; copper wire, “plait” type, twisted; shielded braided and insulated; The shield must be connected to controller GND (pin 25). The network must be wired only in accordance with the principle shown here, called “daisy chain” (the device is composed by a single RS485 port). Star connections are not allowed. Connections warnings • N Controllers ( with N-1 expansions) + 1 Remote Sensor (N max I/O expansions = 6) (with or without remote control) 1st Issue rev. c 12/2015 DBL408e Page 8 For proper network cabling is recommended to take the following precautions: CONTROLLER FUNCTIONS 1. Summer/Winter Changeover The summer/winter changeover is used by the controller to reverse the action (Hot/Cold) in 2-pipe systems: the temperature set in economy mode will be increased with the set correction during summer and decreased during winter. This information can be defined through a dedicated digital input or via parameter and it can be set by the supervisory system or by a configuration tool using MODBUS protocol. N.B: by default Summer/Winter changeover is set by local mode; in plants equipped with a supervisory system it has to be preconfigured by remote mode; Do not use different types of cable to achieve the same network, but always use only the same type of cable; 2. The network cable carries out safety voltage signals (SELV) and must not be wired together with dangerous voltage signals (e.g., 230Vac) or carriers of high currents, especially if in alternating current. Also avoid parallel paths to these power cables; 3. Wire the cable lying avoiding kinks, narrow bending radii and unnecessary wrapping in hanks or skeins; 4. Do not twist the cable cord around the power conductors and, if they should cross, consider an intersection at 90 ° between the cable and these conductors; 5. Keep away from sources of electromagnetic field in particular by large motors, electrical cabinet, reactors for neon, all types of antennas; 6. Do not pull the power cable exceeds 110N (11.3kg) to prevent ironing; 7. Assess in advance the route so that it will be as short as possible and note addresses of connected instruments with particular reference to its location in the orderly sequence. This can be very useful in maintenance; we recommend to note the Modbus Address on the product label. 8. Do not reverse the polarity “+” and “-” of the connection terminals; 9. Avoid short lengths of cable terminations in connection tools to make a maintenance without tearing or flues of the cables possible; 10. Identify start and ending terminations and avoid cuts “open”; Terminating transistors and network polarization The slew rate control, mutual function in our 485 transceiver and the limited baud rate to 9600 baud make the terminating resistors not necessary. RS485 network needs of polarization typically in charge of the master device; the controller doesn’t have polarization resistors. The transceiver used by the controller allows to drive up to 256 points. RS485 standards require a maximum length of 1200m and/or 32 devices on the network. It should be noted that more limits are exceeded, higher is the probability that problems in communication arise. The phenomenon is not systematic and may not occur. Conversely, in case problems should arise and none of the points mentioned in this paragraph has solved them, it is recommended to connect a repeater (CONV RS485-RIP), as shown in the picture below: Repeater R=100 - 120 Ohm N4177-07 GND Supervisory System + R=100 - 120 Ohm + - G N D Device + - G N D Device + - G N D + - G N D Device + - G N+ D G N D Device N.B.: Connect the repeater if cables length exceeds 1200m or if devices are more than 32. Operation modes NR9000 works with 3 different operation modes: • • • COMFORT: the controller will control the temperature (driving valves and fan) to satisfy the Comfort Temperature Set. ECONOMY: the controller will control the temperature to satisfy the Economy Temperature Set. FROST PROTECTION: the controller is normally OFF; just during winter operation it works with a set fixed at 8°C and heating function only. 1st Issue rev. c Initial Valve position To drive a 3-point actuator is necessary to place the actuator in a specific position. Each time the controller is powered up, the actuator will be driven in the closing position for a time equal to the overall travel time plus 33%. Cut-off This function is used to stop the control of the 3 points actuator after the overall travel time plus 33%. This function is used to ensure the correct valve closing and to reduce the noise. The function can be disabled by the supervisory system. In this case at its stroke end the actuator will be powered indefinitely. Window contact This function is used to save energy when a Normally Closed contact is opened (Open Window). In this case the controller will change the operation mode from Comfort to Economy. When the window is open, if the minimum fan speed or the air recirculation functions are enabled, the fan will be anyway turned off when the set is reached. Hot/Cold launch This function is used to avoid the introduction of cold or hot air in the ambient by delaying (for a set time) the fan start. To disable the function, set the time = 0. “Disposal” The “Disposal” function is useful both for the hot and the cold channel and it helps to take off the energy stored in the fan coil radiator by delaying the fan turning off. To disable the function, set the time = 0. Minimum speed activation This function is used to prevent air stratification, especially when using the Return Sensor, as it could be very low sensitive to temperature variation that occurs at man’s height. A continuous air movement helps to avoid /reduce air stratification and to optimize the regulation. If the fan is connected to the relay output, it is necessary to set the “minimum fan speed” parameter at 1. A system configuration with Proportional Fan requires setting the minimum speed in % of the control value (0 - 10V), therefore, if the fan is connected to the 0-10V output, it is necessary to set the “minimum fan speed” parameter at a value between 0 and 50. In both cases the 0 value disables the function. To disable this function, set 0 as minimum speed. Auxiliary regulation ON/OFF (P action) This function can be automatically enable when the sensor in position S3 is connected. If the remote set in S4 is connected, it is possible to have a set in the range 10-30°C, otherwise it can be set through the supervisory system together with the dead zone. If the supervisory system is not present , this function will be carried on at fixed point 20°C with dead zone = 1K. The output will be available in OC2 and it will exclude the management of the electrical coil. Air recirculation function This function manages the minimum fan speed. It is enabled setting a “period” and a “minimum speed” different from zero. When the “period” will be passed, the fan will be enabled at the minimum speed for the time (minutes) set. 12/2015 DBL408e Page 9 Electrical Coil Electrical Coil function can be enabled in the configuration tool as “emergency”. The output provides an open collector signal (OC2) (with reference to signal pin 30, +12V) to control an external auxiliary relay. The output is activated when the room temperature is lower than: “hot” operation set - Proportional Band - 1°C and it goes off when the room temperature is higher than: “hot” operation set - proportional band Electrical Coil in “emergency” mode: Control modes NR9000 works with 7 different control modes selectable via dip switch or by supervisory system: ON/OFF Valves and 3-speed fan (“FAST” operation mode - Operation Diagram 1). 2. ON/OFF Valves and 3-speed fan (Operation Diagram 2). 3. 3-point Valves and 3-speed fan (Operation Diagram 3). 4. ON/OFF Valves and 1-speed fan (Operation Diagram 4). 5. 3-point Valves and 1-speed fan (Operation Diagram 5). 6. ON/OFF Valves and Modulating FAN (0–10V) (Operation Diagram 6). 7a. 2-pipe plant. Proportional Valve (0-10V) and Modulating Fan (010V) (Operation Diagram 7a). 7b. 4-pipe plant: Sequence Valves 0-5/6-10V and Modulating Fan (0-10V) (Operation Diagram 7b). 1. In case of use of 3-speed fans (3 relays), the 0-10V outputs are always available and they follow the ON-OFF or 3-point valves characteristics. The diagrams of the valves and fans share the Set point, instead proportional bands and hysteresis can be set independently. Time table by remote control It is possible to program a daily switching on and switching off through the use of the optionals NR9000-TC infrared remote control and NR9000-RX infrared receiver module (for further information look at pages 17-18). 1. It is possible to enable the functions hot/cold launch, “disposal” and minimum speed activation with a priority over normal operation defined by the diagrams. ON/OFF Valves and 3 Speed FAN - “FAST” operation mode The valves are activated in ONOFF mode with a hysteresis. Speed 1 is ON when the error (E) is greater than 10%. TSET-T E % = ----------- * 100 PB Speed 2 and 3 follow to the Proportional Band as shown in the diagram aside. 2. ON/OFF Valves and 3 Speed FAN The valves are activated in ONOFF mode with a hysteresis. Speed 1, 2 and 3 follow to the Proportional Band as shown in the diagram aside. 1st Issue rev. c 12/2015 DBL408e Page 10 3. 3 point valves and 3 Speed FAN The valves are activated in Proportional mode (0-100%) using the set proportional band. Speed 1, 2 and 3 follow to the Proportional Band as shown in the diagram aside. 4. ON/OFF valves and 1 Speed FAN The valves are activated in ONOFF mode with hysteresis. Speed 1 follows to the Proportional Band as shown in the diagram aside. 5. 3 point valves and 1 Speed FAN The valves are activated in Proportional mode (0-100%) using a proportional band. Speed 1 follows to the Proportional Band as shown in the diagram aside. 1st Issue rev. c 12/2015 DBL408e Page 11 6. ON/OFF Valves and Proportional Speed Fan (0-10V) The valves are activated in ONOFF mode with hysteresis. Speed fan follow to the Proportional Band as shown in the diagram aside generating a 0-10V output control signal. 7a. Proportional Valve (0-10V) and Proportional Speed Fan (0-10V) (2-pipe plant) The valves are activated in Proportional mode (0-100%) using the set proportional band, (heating during winter, cooling during summer). Fan speeds follow the Proportional Band as shown in the diagram aside generating a 0-10V output control signal. 7b. 0-5/6-10 V Sequence Valves and Proportional Speed Fan (0-10V) (4-pipe plant) The valves are activated in sequence mode (0-5/6-10) with hysteresis. If the set is satisfied the output is 5,5V. Fan speeds follow the Proportional Band as shown in the diagram aside generating a 0-10V output control signal. Modulating valve and/or fan application example Control modes diagrams 2-pipe plant Out AO1 Out AO2 6 No --- Fan 6 Yes --- Fan 7 Yes Hot/cool valve Fan 7 No Hot/cool sequence Fan 1st Issue rev. c 12/2015 DBL408e Page 12 NR9000 CONTROLLER DIP SWITCHES AND LEDs The controller has 8 DIP switches accessible by removing the top cover and two LEDs to check operation anomalies. 1 2 3 4 5 6 7 8 ON DIP switches from 1 to 4 can be used to set MODBUS devices address (up to 14) without the use of the configuration tool and to set the controller in expansion mode duplicating the outputs. If DIP 1-4 are all ON the controller is configured as expansion, duplicating the master controller outputs connected to the remote sensor (NR9000-RT) and/or to the supervisory system. If DIP switches 1 to 4 are all OFF the default ModBus address is 1 (factory eeprom setting). In case of more than 14 devices, configuration can be carried out via supervisory system or using a configuration tool via Modbus protocol. DIP from 5 to 7 are used to select the operation diagram. If DIP 5 to 7 are OFF the default operation diagram is nr. 2 - ON/OFF Valves and 3 Speed FAN (factory eeprom setting). DIP 8 is used to select 2/4 pipe system. If DIP 8 is OFF the system is 2 pipe (factory eeprom setting). Parameters set by DIP have the priority over the supervisory system. It is possible to disable the DIP switch setting by ModBus. It is necessary to power down and power up the controller in case of any change in DIP switches configuration. DIP switches 5-7 settings DIP5 DIP6 DIP7 CONFIGURATION DIAGRAM OFF OFF OFF ON/OFF Valves and 3 FAN speed (factory setting) ON OFF OFF ON/OFF Valves and 3 FAN speed “FAST” (Operating Diagram 1) OFF ON OFF ON/OFF Valves and 3 FAN speed (Operating Diagram 2) ON ON OFF 3-point Valves and 3 FAN speed (Operating Diagram 3) OFF OFF ON ON/OFF Valves and 1 FAN speed (Operating Diagram 4) ON OFF ON 3-point Valves and 1 FAN speed (Operating Diagram 5) OFF ON ON ON/OFF Valves and Modulating FAN (0 – 10 V) (Operating Diagram 6) ON ON ON 0-5/6-10 Sequence Valves and Modulating FAN (0 – 10 V). (Operating Diagram 7) DIP switche 8 settings DIP 8 PLANT OFF 2-pipe ON 4-pipe DIP Switches 1-4 settings DIP1 DIP2 DIP3 DIP4 MODBUS ADDRESS OFF OFF OFF OFF Factory Setting (default address1) ON OFF OFF OFF 1 OFF ON OFF OFF 2 ON ON OFF OFF 3 OFF OFF ON OFF 4 ON OFF ON OFF 5 OFF ON ON OFF 6 ON ON ON OFF 7 OFF OFF OFF ON 8 ON OFF OFF ON 9 OFF ON OFF ON 10 ON ON OFF ON 11 OFF OFF ON ON 12 ON OFF ON ON 13 OFF ON ON ON 14 ON ON ON ON Controller used as IO expansion 1st Issue rev. c LEDs functionalities Controller is equipped with 2 LEDs to check its behaviour and possible anomalies as shown in the following table: RED LED GREEN LED BLINKING OFF OFF BLINKING RATE 1Hz – DUTY CYCLE 50% HOT VALVE OPENED BLINKING 1Hz - DUTY CYCLE 50% COOL VALVE OPENED BLINKING BLINKING 1Hz – DUTY CYCLE 10% ON ON DESCRIPTION ON NA BLINKING 2 Hz – DUTY CYCLE 50% HOT & COOL VALVE CLOSED REMOTE SENSOR COMUNICATION FAILURE LOCAL SENSOR ERROR Note: for a 2-pipe system the only connected 3-point or ON/OFF valve is the HOT valve and so the only operative LED for hot and cool fluid is the RED LED. 12/2015 DBL408e Page 13 DEFAULT PARAMETERS The controller is released with the DIP switches in OFF position (2-pipe, Modbus Address 1, ON / OFF valves and 3 fan speed) and with regulation parameters shown in the following table: Parameter Vmin Vmax Default Hot Loop Set Point 100 (10°C) 350 (35°C) 200 (20°C) Stroke Time for 3 Points actuators 30s 480s 60s Derivative Constant for hot loop 1s 1000s 1s Derivative Constant for cool loop 1s 1000 s 1s Dead Zone 0 (0°C) 100 (10°C) 20 (2°C) Auxiliary Loop Set 100 (10°C) 350 (35°C) 200 (20°) Set adjustment for Economy operation mode 0 (0°C) 40 (4°C) 30 (3°C) Action Type P(0), PI(1), PID(2) 0 2 0 (P) Proportional Band Hot Valve 5 (0.5°C) 80 (8°C) 10 (1°C) Proportional Band Cool Valve 5 (0.5°C) 80 (8°C) 10 (1°C) Proportional Band Hot Fan 5 (0.5°C) 80 (8°C) 30 (3°C) Proportional Band Cool Fan 5 (0.5°C) 80 (8°C) 30 (3°C) Integration Time Hot loop 1 (min) 30 (min) 5 (min) Integration Time Cool loop 1 (min) 30 (min) 5 (min) Cut Off Function with Extra stroke of 33% 0 1 1 (ENABLE) Summer/Winter Changeover 0 1 0 (WINTER) Operation Mode: COMFORT(0), Economy(1), Frost(2) 0 2 0 (COMFORT) Delay Time Fan Start 0 255 0 (DISABLE) Delay Time Fan Stop 0 255 0 (DISABLE) minimum fan speed 0 50 0 (DISABLE) Controller Modbus Address 1 250 1 Operation Diagram 1 7 2 2/4 Pipe system 0 1 0 (2-PIPE) NR9000-RT (*) “STATUS WORD” 0 8 8 (FULL ENABLE) NR9000 (**) “STATUS WORD” 0 255 0 Fan Operation Mode (STOP(0),V1(1),V2(2),V3(3),AUTO(4)) 0 4 4 (AUTO) Digital Inputs reverse action (4 BIT, N.O.(0),N.C.(1)) 0 15 1 Bit0: WINDOW CONTACT (N.C.) Bit1:REMOTE POWER OFF (N.A.) Bit2:W/S CHANGEOVER (N.A.) Bit3: COMFORT/ECONOMY (N.A.) Relay Commutation Time delay (Fixed 1 sec) 0 1 1 (ENABLE) Auxiliary loop hysteresis Auxiliary loop direct/reverse action Air recirculation function Period Air recirculation function time 0 (0.5°C) 0 0 (min) 1 (min) 80 (8.0°C) 1 60 (min) 10 (min) 10 (1.0°C) 1 0 (min) 1 (min) 1st Issue rev. c 12/2015 DBL408e Page 14 * “STATUS WORD” parameter NR9000-RT Value Default 0 Display Off “---” 1 Display “Only” Room Temperature in page 0 2 Display “Only” Temperature Set in page 0 3 Display Room Temperature in page 0 with T. Set, Fan e Mode “fixed”. 4 Display Room Temperature in page 0 with T. Set, Fan “fixed” e only Mode “editable” 5 Display Temperature Set in page 0 with Fan e Mode “fixed”. 6 Display Temperature Set in page 0 with Fan “fixed” e only Mode “editable” 7 All enabled with Set Correction (+-3K) 8 All enabled with Temperature Set 10T35°C (default) ** “STATUS WORD” parameter NR9000 BIT Description “0” “1” 0 Operation Mode 1 Ambient Temperature Remote (comes from NR9000-RT) Local (comes from “dedicated” analogue input S1) 0 2 Summer / Winter Changeover Remote (Disable digital input Summer/ Winter DI3) Local (Enable digital input Summer/Winter DI3) 1 3 Temperature Set Remote (comes from NR9000-RT) Local (comes from “dedicated” analogue input S2) 0 4 Window Contact Disable digital input DI1 Enable digital input DI1 0 5 Temperature Set Correction Mode 10-35°C ±3K 0 Remote (Disable digital input Comfort/ Local (Enable digital input Economy and Power Off) Comfort/Economy and Power Off) Default 0 6 DIP switch Enable Disable 0 7 Electrical Battery Disable Enable 0 1st Issue rev. c 12/2015 DBL408e Page 15 REMOTE SENSOR NR9000-RT NR9002-RT remote sensor mounting instructions Flush-mounting 1 2 Make wiring connections Remove the cover plate T amb 4 3 Fix to flush-mounting box 503 The remote sensor has 4 buttons and a 3 digit LCD display. The functions of the sensor are: • • • • Room Temperature Monitoring (T amb). Temperature Set (buttons 2 & 3). Fan Speed Set (Auto, OFF, V1, V2, V3 - button 1). Operation Mode Set (Button 4). Wall mounting The sensor has several configurations (enabled/disabled functions) that can be defined by the controller through the supervisory system or the configuration tool: • Set Point Disabled In this case the controller does not allow the user to change the set point from the Remote Terminal. • Fan Speed Disabled In this case the controller does not allow the user to change the fan speed from the Remote Terminal. • Operating Mode Disabled In this case the controller does not allow the user to change the operation modes from the Remote Terminal. • Remote Sensor Disabled In this case the controller does not allow the user to change all the function listed above and the remote terminal can show and send to controller only the room temperature. Distance between holes [mm] Make wiring connections Remove the cover plate It is possible to calibrate the room temperature displayed on the remote sensor of ± 3°C (label tAr) and to read and set the MODBUS address (label Add) of the controller connected to the sensor following these instructions: • • press button 4 and select the frost protection status (OFF) press for more than 10s the button 1 (FAN) Fix to wall with 2 Fisher screws All functionalities are enabled by default. The remote sensor NR9000-RT has a two-coloured LED to identify the operation mode as shown in the following tables: OPERATION MODE LED Comfort green Economy orange Frost protection (OFF) green blinking 1st Issue rev. c 12/2015 DBL408e Page 16 NR9000-TC REMOTE CONTROL The remote control is infrared type with a graphic display and programming keyboard. For a correct work, it is necessary a visual contact with the receiver fitted on board of the unit to be controlled. It is necessary that the infrared control is pointed towards the receiver and that the distance between infrared control and receiver is max 5/6 meters. The correct delivery of the information to the receiver module is signalled with an alternating blinking of the GREEN and YELLOW LED placed on the receiver module. Setting will be sent to the receiver module with a single message in the moment in which you press the button “OFF” or “ON/SEND”. Use of the infrared handset TIMER PROGRAM Start time: Press SELECT button twice, the word PROGRAM and the word START (lighting) will be displayed. Press (+) or (-) button, the word START will become fix and the hours value will start lighting. Use (+) button to increase or (-) to decrease the hours. Press SELECT button, the minutes value will light. Use (+) button to increase or (-) to decrease minutes. Stop time: Press SELECT button, the word STOP will light on the display. Press (+) or (-) button, the word STOP will become fix and the hours value will start lighting. Use (+) button to increase or (-) to decrease the hours. Press SELECT button, the minutes value will light. Use (+) button to increase or (-) to decrease the minutes. ON or OFF Timer: Press SELECT button, the TIMER icon will start lighting. Press (+) button to start the timer (dark icon) or (-) button to de-activate it (light icon). Press SELECT button to store the information. Press ON/SEND button to send information to the unit. General information on timer mode: Once set up the timer program, it will be repeated day by day until it will be cancelled (timer OFF). It is possible to by-pass manually the set automatic program by pressing ON/SEND button to switch on the unit or pressing OFF button to switch off the unit. The manual mode will be ON until the next automatic mode of the program. NR9000-TC infrared remote control mounting instructions NR9000-TC infrared remote control is supplied together with a support for wall mounting and batteries. To fix the support to the wall use screws of correct diameter and length (not supplied). 1. 2. Open the back cover and slide it outward; insert the 2 alkaline batteries (size AAA 1,5V) according to polarity; the display will power on; close the cover again. Description of the controls 3. 4. ON/SEND Switches on the unit and/or update the information. NOTE: in case of batteries replacement, after removal of the exhausted ones, wait for 10 minutes before installing the new ones. MODE Press button MODE to change between only Ventilation, Heating, Cooling and Automatic Work. Press ON/SEND button to send information to the unit. Dry function is not available. FAN Press FAN button to change between Min, Med, Max speed and Auto (A) (automatic speed). Press ON/SEND button to send information to the unit. Description of the function visualized on the display SET POINT TEMPERATURE In order to set the desired temperature inside the room (set-point temperature) in order to increase it press button (+), in order to decrease it press button (-) until the desired temperature. Press ON/SEND button to send information to the unit. SWING mode (not available) CLOCK SET UP Press SELECT button, the word CLOCK SET will light. Press (+) or (-) button, the word CLOCK SET will become fix and the hours value will start lighting. Use (+) button to increase or (-) to decrease the hours. Press SELECT button, the minutes value will light. Use (+) button to increase or (-) to decrease minutes. Press SELECT button to stop the set up. Press ON/SEND button to send information to the unit. 1st Issue rev. c 12/2015 DBL408e Page 17 NR9000-RX RECEIVER MODULE DIMENSIONS [mm] For operation with remote control NR9000-TC it is necessary to connect the receiver module NR9000-RX to the controller NR9000 through the flat cable supplied with it using the connection port placed on the upper side of the controller. NR9000 The receiver module is equipped with 2 signalling LEDs: • • GREEN LED to show the controller status (LED ON = controller ON, LED OFF = controller OFF); YELLOW LED to show the time table status (LED ON = time table enabled, LED OFF = time table disabled). The GREEN and YELLOW LED briefly blink when they receive a signal coming from the remote control. Further than the two LEDs the receiver module is equipped with a button to override the switching on and switching off of the controller. If time table are enabled, by pressing the button they will be disabled. NR9000-RT1X NR9000-RX infrared receiver module mounting instructions The receiver module is supplied together with a flat connector (80cm) to be connected to NR9000 controller and a double-side tape for fixing on smooth surfaces. In case the flat cable is not connected to the receiver, proceed as follows: 4. 5. 6. 30 44 50,4 36,3 22,4 N.B.: In case the flat cable is already connected to the receiver module, just follow the instructions on point 5 and 6. NR9000-RT2X 136,5 3. 42,5 2. unscrew the two screws on the receiver to open the back cover: a 6-terminal connector will be visible; insert one end of the cable inside the connector. The connector can be mounted in one direction only as it is polarized; close again the back cover and tighten the screws making the flat cable come out from the split you find between cover and case; in case it is necessary to place the flat cable in a duct, see the picture below for duct dimensions; connect the other end of the flat cable to the connector you can see in the split on the upper side of the controller. The connector can be mounted in one direction only as the cable is polarized; Place the double-side tape on the back side of the receiver module and pay attention not to force the flat cable. 134 1. 35 NR9000-TC 14,3 50 20 4,25 NR9000-RX 13,8 The performances stated in this sheet can be modified without any prior notice 1st Issue rev. c 12/2015 DBL408e Page 18
© Copyright 2026 Paperzz