PLAN SYMBOL LEGEND 1. CONTRACTOR SHALL CAREFULLY EXAMINE ALL DRAWINGS AND SPECIFICATIONS TO PROPERLY DETERMINE SCOPE OF WORK. SYMBOL 2. DIVISION 22 SCOPE OF WORK INCLUDES THE INSTALLATION OF ALL SERVICE FITTINGS AND PIPING AS INDICATED ON FIXTURE & EQUIPMENT SCHEDULES AND AS SHOWN ON LF- & LP- DRAWINGS (LABORATORY SERVICE FITTINGS FURNISHED BY DIVISION 11). INSTALL ALL LABORATORY SERVICE FITTINGS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND INSTRUCTIONS. FITTINGS ON LP-SERIES DRAWINGS ARE SYMBOLIC ONLY. REFER TO LF-SERIES DRAWINGS FOR ACTUAL FITTINGS, LOCATIONS AND ARRANGEMENTS. CONTRACTOR SHALL FIELD VERIFY CONDITIONS AT ALL POINTS OF CONNECTION PRIOR TO INSTALLATION. 4. EQUIPMENT AND SYSTEM INSTALLATION SHALL CONFORM WITH ALL APPLICABLE LOCAL, STATE, FEDERAL AND HEALTH AUTHORITY CODES. 5. 6. ALL PIPING SHOWN ON DRAWINGS IS DIAGRAMMATIC. ADDITIONAL OFFSETS, WHICH MAY BE REQUIRED, IN WASTE & VENT RISERS OR IN BELOW BENCH SERVICE PIPING SHALL BE PROVIDED UNDER DIVISION 22. ALL EXPOSED TO VIEW PIPING SHALL BE INSTALLED WITH SPECIAL CARE GIVEN TO UNIFORM SPACING, LEVEL AND PLUMB, CLEAN APPEARANCE FREE OF DEBRIS AND HANDLING MARKS, WITHOUT THE NEED FOR OFFSETS BELOW THE CEILING LEVEL. 8. VALVES AND CAPS AT POINTS OF CONNECTION ARE SHOWN ON LP-SERIES DRAWINGS FOR COORDINATION ONLY, REFER TO P-SERIES DRAWINGS FOR LOCATION AND SIZES. 9. LABORATORY SINK (PROVIDED UNDER DIVISION 11) CS* CUP SINK (PROVIDED UNDER DIVISION 11) FIXTURE/FITTING NO. PIPE DROP ENCLOSURE (PROVIDED UNDER DIVISION 11). FOR PIPING LAYOUT WITHIN PIPE DROP REFER TO DETAIL #5/LP-301. ARCHITECTURE • INTERIORS • PLANNING TW@DH ICW IHW PW 1/2 1/2 1/2 1 1/2 1/2 1 1/2 SKB 1/2 1/2 1/2 SKC 1/2 1/2 1/2 LG LA LV CA P-TRAP & TRAP ARM SAFETY SHOWER/RECESSED EYEWASH UNIT (PROVIDED UNDER DIVISION 11) FD FLOOR DRAIN (SHOWN FOR COORDINATION PURPOSES ONLY. REFER TO P-SERIES DRAWINGS.) FS FLOOR SINK (SHOWN FOR COORDINATION PURPOSES ONLY. REFER TO P-SERIES DRAWINGS.) SERVICE FITTING SCHEDULE SF1 TW ICW IHW PW LG LA LV CA 1/2 3/4 1/2 SF5 1/2 11. PROVIDE VALVED AND CAPPED CONNECTIONS WHERE "ROUGH-IN ONLY" OR "FUTURE SERVICES" ARE INDICATED ON DRAWINGS. PIPE TEE & ELBOW UP SF6 1/2 12. PIPE SIZES ARE INDICATED ON THESE DRAWINGS BY MEANS OF THE POINT OF CONNECTION, SERVICE DROP, FITTING, FIXTURE AND EQUIPMENT CONNECTION SCHEDULES. PIPE TEE & ELBOW DOWN SF7 15. FLOOR DRAINS AND FLOOR SINKS ARE SHOWN ON LABORATORY PLUMBING PLANS FOR GENERAL LOCATION AND REFERENCE ONLY. REFER TO PLUMBING DRAWINGS FOR ACTUAL LOCATION, SIZE AND TYPE OF DEVICE. DETAIL NUMBER DRAWING NUMBER 16. TEST ALL VALVES, SERVICE FITTINGS, EMERGENCY SHOWERS, EYEWASHES AND DRENCH HOSES AS SPECIFIED TO ENSURE SYSTEM INTEGRITY AND PROPER OPERATION. EQUIPMENT NO. ICW IHW EQ1 ( AUTOCLAVE) 1 1/2 EQ2 (GLASSWARE WASHER) 1 1 PRV LG LA LV 1 EW PRESSURE REDUCING VALVE TW ICW 1 IHW IHWR PW 1/2 3/4 LG LA LV 1/2 1/2 3/4 21. REFERENCES TO LP DETAILS ARE SHOWN FOR SPECIFIC CONDITIONS ON THE LP FLOOR PLAN DRAWINGS. IN ADDITION, REFER TO GENERAL NOTES AND PLAN SYMBOL LEGEND FOR MISCELLANEOUS DETAILS. 22. PROVIDE CLEANOUTS IN ACCORDANCE WITH PLUMBING CODE OR LOCAL, STATE, FEDERAL AND HEALTH AUTHORITY REQUIREMENTS. COORDINATE CLEANOUT ACCESS LOCATIONS WITH LABORATORY CASEWORK INSTALLATION. 23. CONNECTIONS TO HOSE EYEWASHES AND/OR DRENCH HOSES TO BE PROTECTED BY BACK FLOW PREVENTERS INSTALLED ACCORDING WITH PLUMBING CODE AND ACCEPTED BY THE LOCAL AUTHORITY HAVING JURISDICTION. 24. EMERGENCY SHOWERS, EYEWASHES AND DRENCH HOSES ARE FURNISHED UNDER DIVISION 11. INSTALL THESE DEVICES AS DETAILED AND SHOWN ON PLANS. CONNECT TO TEPID WATER SUPPLY WITHOUT ISOLATION VALVES. 25. PROVIDE BACKFLOW PREVENTERS ON EQUIPMENT CONNECTIONS TO POTABLE WATER AS REQUIRED BY LOCAL CODE AND ACCEPTED BY LOCAL AUTHORITY HAVING JURISDICTION. 3/4 1/2 A.F.C. ABOVE FINISHED CEILING BV BALL VALVE DN DOWN N.T.S. NOT TO SCALE P.O.C. POINT OF CONNECTION SIM. SIMILAR TYP. TYPICAL U.O.N. UNLESS OTHERWISE NOTED 6 1/2 3/4 3/4 1/2 ROOM NAME C 3/4 ROOM NO. CHME MINATURE CHEMICAL PILOT PLANT C:\Users\rilao\Documents\LP-NMSU-JETT HALL-2015_romelrfd.rvt 9/14/2015 1:27:02 PM FIXTURE, SERVICE FITTING AND EQUIPMENT LEGEND INDUSTRIAL HOT WATER RETURN DESIGNATES LABORATORY SINK(FURNISHED UNDER DIVISION 11 - U.O.N. REFER TO PLANS) LA LABORATORY AIR (15 psig) DESIGNATES TYPES OF PLUMBING SERVICES REQUIRED AT SINK, REFER TO FIXTURE CONNECTION SCHEDULE-LP-001 LG LABORATORY GAS LV LABORATORY VACUUM DESIGNATES CUP SINK(FURNISHED UNDER DIVISION 11 - U.O.N. REFER TO PLANS) LW LABORATORY WASTE DESIGNATES TYPES OF PLUMBING SERVICES REQUIRED AT CUPSINK, REFER TO FIXTURE CONNECTION SCHEDULE-LP-001 PW PURIFIED WATER SG1 SPECIAL GAS 1 (ARGON) SKA CSA IHW IHW PW LG LA LV CA GPM GPM GPM GPM GPM sCFH sCFM sCFM sCFM DESIGN FLOW 3 3 3 184 1.01 PIPE SIZE (IN) 3/4 3/4 3/4 NEW CHME RESEARCH LAB 289 2.01 DESIGN FLOW 23 PIPE SIZE (IN) 1 1/4 NEW CHME RESEARCH LAB 289 2.02 DESIGN FLOW 10 5 PIPE SIZE (IN) 1 3/4 280 / 289 2.03 NEW CHME RESEARCH LAB 289 2.04 GLASSWARE/AUTOCLAVE 282 2.05 BSL-2 ROOM / NEW CHME RESEARCH LAB 284 / 289 2.06 NEW CHME RESEARCH LAB 289 2.07 LASER ROOM / NEW CHME RESEARCH LAB 286 / 289 2.08 NEW CHME RESEARCH LAB 289 2.09 NEW CHME RESEARCH LAB 289 2.10 Construction Documents 1/2 4 24 4 6 * 3/4 1/2 1 1/4 2 4 1 1 * 1/2 1/2 3/4 DESIGN FLOW 23 2 1.5 PIPE SIZE (IN) 1 1/4 1/2 1/2 DESIGN FLOW 9 1.5 32 6 8 PIPE SIZE (IN) 1 1/2 3/4 1/2 1 1/4 DESIGN FLOW 10 8 8 1 PIPE SIZE (IN) 1 1 * 1/2 1/2 DESIGN FLOW 23 1.5 1.5 1 1 1 PIPE SIZE (IN) 1 1/4 1/2 1/2 * 1/2 3/4 DESIGN FLOW 9 3 2 32 6 8 PIPE SIZE (IN) 1 3/4 * 3/4 1/2 1 1/4 DESIGN FLOW 1 4 15 PIPE SIZE (IN) 1/2 1 1/2 DESIGN FLOW 6 3 PIPE SIZE (IN) 3/4 3/4 DESIGN FLOW 23 PIPE SIZE (IN) 1 1/4 1/2 1/2 4 12 2 3 * 1/2 1/2 1 B NOTES: 1. FLOW RATES REPRESENT DESIGN PEAK LABORATORY LOADS USED FOR PIPE SIZING AT POC. 2. TW- TEPID WATER FOR SAFETY SHOWER/EYEWASH SIZED FOR INSTANTANEOUS/INCIDENTAL USE. DESIGNATES SERVICE FITTING STATION (FURNISHED UNDER DIVISION 11 - U.O.N. REFER TO PLANS) 3. * PROVIDE MINIMUM 3 fps CIRCULATION VELOCITY IN LABORATORY PW LOOP. SYSTEM STATIC PRESSURE SHOULD NOT EXCEED 60 psig. VALVED SERVICE CONNECTION PER LP SCHEDULES AND DETAILS. DESIGNATES TYPES OF PLUMBING SERVICES REQUIRED, REFER TO SERVICE FITTING SCHEDULE-LP-001 TEPID WATER TW ICW SECOND FLOOR INDUSTRIAL HOT WATER LABORATORY WASTE VENT TW POC NO. FIRST FLOOR DESCRIPTION LWV 1/2 PIPING POINT OF CONNECTION SCHEDULE PIPING LEGEND IHWR 1/2 * BUILDING PW WATER SIZE NOTES: 1. BUILDING PW WATER LOOP TO EACH SERVICE DROP PER LP-SERIES DRAWINGS. B IHW N GI 9/11/15 Jett Hall and Jett Annex Renovations and Additions * 1/2 ANALYTICAL/INSTRUMENTATION / NEW CHME RESEARCH LAB ICW N AL E N New Mexico State University SG1 5 26. SEAL ALL PIPING PENETRATIONS THROUGH RATED WALLS WITH UL APPROVED SYSTEM. SEE ARCHITECTURAL & PLUMBING DETAILS. INDUSTRIAL COLD WATER CA 3/4 7 ABOVE FINISHED FLOOR S IO 1/2 3 DRENCH HOSE (EYEWASH)- TEPID WATER (FITTING FURNISHED UNDER DIVISION 11 & INSTALLED UNDER DIVISION 22) A.F.F. ES SERVICE DROP SCHEDULE PIPE SIZE IN INCHES C 20. ALL PLUMBING VENTS SHALL EXTEND SIX INCHES ABOVE FLOOD LEVEL RIM OF FIXTURE SERVED BEFORE CHANGING FROM VERTICAL TO A HORIZONTAL POSITION UNLESS OTHERWISE NOTED FOR SPECIAL VENTING ARRANGEMENTS. W 18351 4 19. PROVIDE MINIMUM SIZE OF 2" LABORATORY WASTE & 1-1/2" VENT RISER WHERE LABORATORY WASTE POINTS OF CONNECTION SYMBOL IS INDICATED ON DRAWINGS. WASTE PENETRATIONS AT LABORATORY SINKS & CUPSINKS MAY REQUIRE OFFSET TO AVOID STRUCTURAL BEAMS AND JOISTS. REFER TO DETAIL #3/LP-301. R. LEMES L U M EXI PROJECT DETAIL REFERENCE BUBBLE COORDINATES PLAN WITH DETAIL SHEETS CYLINDER MANIFOLD W SG 1/2 2 18. PROVIDE STAINLESS STEEL ESCUTCHEON PLATES FOR ALL EXPOSED PIPE PENETRATIONS IN WALLS AND CEILINGS. COMPRESSED AIR (100 pisg) CA NOTES: 1. BUILDING PW WATER LOOP TO EACH EQUIPMENT PER LP-SERIES DRAWINGS. 2. CONNECTION TO SERVICE PER LP-SERIES DRAWINGS. DROP NUMBER NO. 17. INSULATE PIPING IN ACCORDANCE WITH DIVISION 22 SPECIFICATIONS. INSULATION TO INCORPORATE ENTIRE LENGTH OF PIPE FROM POINT OF CONNECTION TO POINT OF USE. PW CO SERVICE DROP NUMBER - COORDINATES PLAN WITH SERVICE DROP SCHEDULE 1 D PIPE SIZE IN INCHES F 14. FITTING/FIXTURE INLET SIZE MAY VARY. PROVIDE APPROPRIATE CONNECTORS. EQUIPMENT CONNECTION SCHEDULE ** 50-80 PSIG (VERIFY WITH MANUFACTURER) POINT OF CONNECTION NUMBER - COORDINATES PLAN WITH POINT OF CONNECTION SCHEDULE 1 1/2 P RO 13. REFER TO THE LABORATORY PLUMBING DETAILS FOR TYPICAL PIPE ROUTING BELOW AND WITHIN THE CASEWORK. THE QUANTITY, SIZE AND MATERIAL OF PIPE WILL VARY IN ACCORDANCE WITH THE TYPE OF SERVICES. INSTALL IN ACCORDANCE WITH THE PIPING ARRANGEMENT AND ORIENTATION SHOWN ON PLANS. 1/2 E TR POINT OF CONNECTION TO VALVED AND CAPPED SERVICES (VALVES AND CAP PROVIDED UNDER DIVISION 22 P-SERIES DRAWINGS) 1/2 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 PA POINT OF CONNECTION TO 1-1/2" LABORATORY WASTE VENT RISE @ 6"A.F.C. (U.O.N.) (REFER TO P-SERIES DRAWINGS FOR CONTINUATION) STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 3/4 SF4 POINT OF CONNECTION TO 2" LABORATORY WASTE @ 6"A.F.F. & 1-1/2" LABORATORY WASTE VENT RISE @ 6"A.F.C. - U.O.N. (REFER TO P-SERIES DRAWINGS FOR CONTINUATION) SG1 1/2 SF3 PIPE ELBOW UP (OR) TEE UP & DOWN B. WHERE SERVICE DROPS ARE INDICATED, THE SERVICE DROP SCHEDULE SHALL GOVERN THE DROP AS WELL AS EACH ASSOCIATED BRANCH. THESE SERVICES SHALL EXTEND TO BELOW BENCH AND RUN HORIZONTALLY UNDIMINISHED IN SIZE UP TO THE LAST TEE SERVICING DIFFERENT FITTINGS. C. THE FIXTURE, SERVICE FITTING & EQUIPMENT CONNECTION SCHEDULE SHALL INDICATE THE SIZE FOR THE FINAL SECTION OF PIPING. CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 1 1/4 SF2 PIPE CAPPED V LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 NOTES: 1. BUILDING PW WATER LOOP TO EACH FIXTURE PER LP-SERIES DRAWINGS. 2. CONNECTION TO SERVICE PER LP-SERIES DRAWINGS. 3. ALL SERVICES TO FUME HOOD TO BE PRE-PIPED TO SINGLE POINT OF CONNECTION BY DIV. 11. FUME HOOD SERVICE FITTING LOCATION MAY VARY, REFER TO LF PLANS. SERVICE FITTING NO. PIPING BELOW FLOOR A. THE POINT OF CONNECTION SCHEDULE INDICATES PIPE SIZE ENTERING EACH LABORATORY. THE SIZE SHALL EXTEND UNDIMINISHED UP TO THE LAST TEE BRANCH OF THE CEILING DISTRIBUTION PIPING. CONSULTANTS PIPE SIZE IN INCHES PIPING BELOW BENCH W 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail [email protected] Web Site www.vhgarchitect.com E 1 1/2 PIPE ELBOW DOWN CA LW(P-TRAP) 1 1/2 10. INSTALL WATER HAMMER ARRESTORS ON LINES SERVING FIXTURES OR EQUIPMENT WITH QUICK CLOSING VALVES. PIPING/ABBREVIATION SG CSA THE FOLLOWING GUIDELINES SHALL GOVERN THE PIPE SIZES: D SK* PROVIDE REDUCERS ON POINT OF CONNECTION WHERE SIZES SHOWN ON P-SERIES DRAWINGS ARE LARGER THAN INDICATED ON LP-SERIES DRAWINGS. PROVIDE ADAPTERS/REDUCERS WHERE NECESSARY FOR CONNECTION TO PIPING SERVICES OR WASTE LINES. Van H. Gilbert Architect PC PIPE SIZE IN INCHES SKA PIPE LINES ENTERING LABORATORIES ARE SHOWN WITH WIDE SEPARATION FOR CLEAR IDENTIFICATION PURPOSES ONLY. MAINTAIN A TIGHT AND ORDERLY GROUPING OF PIPES WITHIN EACH LABORATORY. LOCATION, ROUTING AND SUPPORT OF LABORATORY PIPING SHALL BE COORDINATED WITH THE INSTALLED EQUIPMENT, OVERHEAD SERVICE CARRIERS, PIPE DROP ENCLOSURES, BUILDING STRUCTURAL ELEMENTS, DUCTWORK, ELECTRICAL CONDUITS, POWER PANELS AND LIGHT FIXTURES. 7. 6 FIXTURE CONNECTION SCHEDULE ABBREVIATION DESCRIPTION SS 3. 5 R GENERAL NOTES 4 EE 3 EW E 2 NE 1 EQ1 GAL PW WATER HOURLY CONSUMPTION 30 PW WATER 4-HOUR CONSUMPTION 120 A 14400 RI Checked By BS/PL Copyright © GPM PW WATER PEAK FLOW RATE September 11, 2015 Drawn By ESTIMATED PW WATER CONSUMPTION AND PEAK LOAD DESIGNATES TYPES OF PLUMBING SERVICES REQUIRED, REFER TO EQUIPMENT CONNECTION SCHEDULE-LP-001 Description Project Number 6. IHW HARDNESS SHOULD NOT TO EXCEED 120 MG/L (PPM) TO LABORATORY EQUIPMENT. DESIGNATES EQUIPMENT STATION (FURNISHED UNDER DIVISION 11 AND/OR OFOI. REFER TO PLANS) Date Date 5. IHWR CIRCULATED INSIDE LABORATORY AS SHOWN ON PLANS. DESIGN FLOW PER P-SERIES DRAWINGS. SF1 A Mark 4. COMPRESSED AIR DISTRIBUTED AT 100 psig TO LABORATORY POC. PROVIDE PRESSURE REGULATORS AS SHOWN ON PLANS FOR LOWER PRESSURE SERVICES. VAN H. GILBERT ARCHITECT PC SHEET TITLE LAB PLUMBING GEN. NOTES, LEGENDS & SCHEDULES 6 LP-001 1 2 3 4 5 6 SHEET 1 99 OF 187 6 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING DN DN E 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail [email protected] Web Site www.vhgarchitect.com E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 A E MAIL ME/AE OFFICE 104B SEMINAR ME/AE OFFICE ME/AE OFFICE ME/AE OFFICE ME/AE OFFICE 116 114 112 110 108 104A LOBBY H100 CHME OFFICE CHME OFFICE CHME OFFICE CHME OFFICE CHME OFFICE CHME OFFICE CHME OFFICE CHME OFFICE CHME OFFICE 150 152 154 156 158 160 162 164 166 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 CHME OFFICE 168 ME/AE OFFICE 106 ME/AE DIRECTORS OFFICE SUITE 104 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 B CHME OFFICE 163 UNISEX R101 SUPPORT CHME OFFICE SUITE 117D 159 C MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 CHME OFFICE 159G BREAK ROOM 105A VESTIBULE H117 STOR S117B ME /AE GRADUATE STUDENT OFFICE ME/AE SEMINAR 115 113 DATA ROOM T165 ME/AE SEMINAR CLASSROOM 111 109 MEN WOMEN OFFICE 105 R153 R151 CHASE CHME OFFICE 103B STOR D CHME OFFICE 159B CHME OFFICE S117A 159C DN CHME OFFICE 159D 159E DN 159F D D 17 22 10 16 14 11 26 ELECTRICAL ROOM 4 7 E167 6 1 R. LEMES L U M EXI CO W E TR DN 13 8 PA 20 23 CHME OFFICE NE OFFICE 117C CHME OFFICE 159A F ES EE P RO R 18351 DN MECHANICAL ROOM CHME COMPUTER LAB M198 177 S IO N AL E N N GI 9/11/15 PROJECT CHME STUDENT PROJECT/STUDY AREA CORRIDOR New Mexico State University 178 H103 STORAGE S180 Jett Hall and Jett Annex Renovations and Additions ME/AE WELDING 182 KITCHEN 179 STUDENT PROJECTS CENTER C C 196 CHME MINATURE CHEMICAL PILOT PLANT LP-111 ME/ AE STORAGE 184 ME/ AE OFFICE S196B ME/AE LAB ME/AE LAB 191A 191 Construction Documents 196A ME/AE ROBOTICS LAB 191C ME/AE LAB 191B B B ME/ AE HYDRAULICS LAB C:\Users\rilao\Documents\LP-NMSU-JETT HALL-2015_romelrfd.rvt 194 CHME UNDERGRADUATE LAB 193 KEY PLAN ME/ AE OFFICE 194A LAB 193A Mark Description Date DN DN September 11, 2015 Project Number 14400 Drawn By A A RI Checked By BS/PL Copyright © FLOOR PLAN 1 FIRST Scale: 3/32" = 1'-0" 0' 2' 4' VAN H. GILBERT ARCHITECT PC SHEET TITLE Project North 9/14/2015 1:27:05 PM Date LAB PLUMBING FIRST FLOOR KEYPLAN 8' LP-101 1 2 3 4 5 6 SHEET 100 OF 187 6 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING 23 22 20 17 16 14 13 11 10 26 8 7 6 4 1 E 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail [email protected] Web Site www.vhgarchitect.com E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 A CLASSROOM 216 CHME OFFICE CHME OFFICE CHME OFFICE CHME OFFICE CHME OFFICE CHME OFFICE 204 250 252 254 256 258 260 E CHME OFFICE MEETING/WAITING ROOM CHME OFFICE 262 264 268 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 CLASSROOM CLASSROOM 208 CLASSROOM ME/ AE DIRECTORS OFFICE 206 210 B STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 CORRIDOR H201 STOR S257 C CHME OFFICE 263 ME/ AE OFFICE JAN JAN 201A J255 CHME OFFICE CHME CONFERENCE ROOM 265 274 217A DATA VESTIBULE CLASSROOM H217 CLASSROOM MEN T203 207 CLASSROOM 215 CLASSROOM 213 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 259 R253 WOMEN R201 STOR S217B D D D DN ELECTRICAL ROOM ELECTRICAL ROOM E301 E267 PA CO W E TR R. LEMES L U M EXI NE PENTHOUSE M301 F ES EE P RO BIOMASS THERMOCHEMICAL PROCESSING LAB R 18351 S IO N AL E N N GI 9/11/15 278 PROJECT New Mexico State University LP-112A C Jett Hall and Jett Annex Renovations and Additions C ANALYTICAL / INSTRUMENTATION CHME RESEARCH LAB BUILD-OUT ALTERNATE #1 (REFER TO DIVISION 1 SPECIFICATIONS) 280 GLASSWARE / AUTOCLAVE 282 Construction Documents BSL-2 ROOM 284 CHME RESEARCH LAB BUILD-OUT ALTERNATE #2 (REFER TO DIVISION 1 SPECIFICATIONS) LASER ROOM 286 CHME RESEARCH LAB 289 B MICROSCOPE ROOM LP-112B B V 288 EQUIP. ROOM 9/14/2015 1:27:56 PM C:\Users\rilao\Documents\LP-NMSU-JETT HALL-2015_romelrfd.rvt 290 THIN FILMS LAB KEY PLAN 292 LAB MANAGER OFFICE 295 Mark Date Description Date September 11, 2015 Project Number Drawn By Project North A 14400 A RI Checked By BS/PL Copyright © FLOOR PLAN 1 SECOND Scale: 3/32" = 1'-0" 0' 2' 4' VAN H. GILBERT ARCHITECT PC SHEET TITLE 8' LAB PLUMBING SECOND FLOOR KEYPLAN LP-102 1 2 3 4 5 6 SHEET 2 101 OF 187 6 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING E 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail [email protected] Web Site www.vhgarchitect.com E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 W CO 1 (TYP.) LP-301 R. LEMES L U M EXI E TR PA D NE D R F ES EE P RO 1.01 CA 18351 TW ICW IHW PRV S IO N AL E N N GI 9/11/15 PROJECT W SKC LG CHME MINATURE CHEMICAL PILOT PLANT LA IHW LG ICW LA New Mexico State University TW LG 7 LA 1 LP-303 Jett Hall and Jett Annex Renovations and Additions 184 SF7@+54" C LG LA C 5 LP-302 (TYP.) LG LA LA LG SF7@+54" Construction Documents Project North FLOOR PLAN - PILOT PLANT 1 FIRST Scale: 1/4" = 1'-0" 0' 2' 4' 8' C:\Users\rilao\Documents\LP-NMSU-JETT HALL-2015_romelrfd.rvt B B KEY PLAN Mark Date Description Date September 11, 2015 Project Number 14400 Drawn By A A RI Checked By BS/PL Copyright © VAN H. GILBERT ARCHITECT PC 9/14/2015 1:27:57 PM SHEET TITLE LAB PLUMBING FIRST FLOOR LP-111 1 2 3 4 5 6 SHEET 102 OF 187 6 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING E 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail [email protected] Web Site www.vhgarchitect.com E CONSULTANTS 1 1/2" TW 1 1/4" IHW 1/2" IHWR 2" ICW 1" PW 1 1/4" LG 2" LV 3/4 CA LG SOLENOID VALVE LG SOLENOID VALVE SWITCH LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 TW D IHW TW ICW LA LV IHW PW LG CA ICW IHW IHWR SHUT- OFF & BALANCE VALVE PW W LG PA PW W ES PW F CA CSA R LV 18351 P RO CSA CO 1 W 1 R. LEMES L U M EXI E TR W W PW 2 LP-302 (TYP.) D ICW 1 ICW W IHWR CSA W SKA IHW IHW PW TW PW LA PW LV D MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 278 PW CSA LG E267 LG CA LV BIOMASS THERMOCHEMICAL PROCESSING LAB 7 LP-301 (TYP.) EE LA PW ICW IHW LG LA LV PW PRV 1 LG LV ELECTRICAL ROOM LG PW ICW ICW IHW SF1 2.01 PW 2.02 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 NE PW W PW PW W IHWR SKA SKA PW W CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 S IO N AL E N N GI 9/11/15 1 ICW 1 LG IHW LV LA PW ICW W PW LV LA LG IHW PROJECT ICW CSA IHW CSA New Mexico State University LV LG LA IHW ICW ICW IHW PW SKA 1 W CSA Jett Hall and Jett Annex Renovations and Additions CSA C W 289 CSA IHW TW W IHWR CSA CSA 2.04 LA LG LV LG LV IHW CSA PW 3 LP-302 1 1 W PW 9/14/2015 1:28:13 PM B IHWR IHW ICW LV CSA CA 1 LG ICW CSA LA LV LV LA ICW TW 1 LG GLASSWARE / AUTOCLAVE IHW 282 ICW IHW PW PW CA CA PW ICW IHWR CSA 7 LP-302 W 2.05 IHW ICW PW W W MATCHLINE CA LV 1 Mark EQ2 LG MATCHLINE LP-112B PW 8 LP-302 PW CSA KEY PLAN EQ1 PW PW IHW ICW ICW LG W CA 1 W SKA LV LA C:\Users\rilao\Documents\LP-NMSU-JETT HALL-2015_romelrfd.rvt CSA PW 6 LP-301 (TYP.) LG W SKA PW B W PW 1 W SF2 @+84" ICW W PW IHWR CSA LV PW IHW LG 280 W TW ICW ANALYTICAL / INSTRUMENTATION PW PW IHW ICW PW SKA LA 1 Construction Documents CA LG PRV ICW ICW LA ICW TYP. PW 1 ICW 2 LP-301 PW 1 LV 1 LP-301 TYP. PW CSA LV PRV ICW W LA IHWR 1 W W 1 ICW 1 IHWR SHUT- OFF & BALANCE VALVE ICW IHW IHWR PW PW LG TW IHW W SF1 ICW 2.03 IHW CHME RESEARCH LAB PW W 1 C CSA IHWR W Description Date September 11, 2015 Project Number LP-112B 14400 Drawn By A A Project North FLOOR PLAN - EAST WING - NORTH 1 SECOND Scale: 1/4" = 1'-0" Date RI Checked By BS/PL Copyright © VAN H. GILBERT ARCHITECT PC SHEET TITLE 0' 2' 4' LAB PLUMBING SECOND FLOOR NORTH 8' LP-112A 1 2 3 4 5 6 SHEET 3 103 OF 187 6 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING LP-112A ICW CSA SF1 TW 2.06 ICW PW 1 2 LP-301 LP-301 LA LV 2.07 CA 4 SF4@+54" LV LA LA LG LG 1 CA ICW LV (TYP.) CSA LA SF4 SF4 LG ICW LA LV LV LA CA LG W ICW 18351 P RO 1 W R. LEMES L U M EXI CO ICW LV LA LA E TR LV LG W SF5 @+54" PA LG 1 D 4 W CA 1 6 LP-302 ES F W R LV CSA SKA IHWR SHUT- OFF & BALANCE VALVE 2.08 LA CSA CSA D CA 289 W W TW 1 286 IHW CHME RESEARCH LAB (TYP.) MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 LASER ROOM IHWR 1 W 1 W SF5 @+54" PW ICW LV 3 LP-302 SF4 SF4 IHW PW LA CSA STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 LV LV CSA W CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 SF3 @+98" SKA PRV ICW (TYP.) EE LG LV LA NE LV ICW LA LV PW LG LV LA LA LA LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 IHW PW ICW LG 1 PW PW PW 2 LP-302 (TYP.) ICW PW 1 4 LP-302 LV W W CONSULTANTS BSL-2 ROOM 284 (TYP.) CA 3 PW PRV LV CSA CSA 1 LG W E W IHW PW PW CSA 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail [email protected] Web Site www.vhgarchitect.com MATCHLINE SKB W W W PW E 1 PW 1 IHWR MATCHLINE IHW TW LP-112A S IO N AL E N N GI 9/11/15 CSA ICW ICW LV LA 1 W W CSA CSA PW W Jett Hall and Jett Annex Renovations and Additions PW ICW LG LA 1 LG ICW LV LG 288 IHWR LA New Mexico State University IHW 1 LV MICROSCOPE ROOM TW CSA PROJECT C LG EQUIP. ROOM 290 LV CSA C 6 (TYP.) LP-301 CSA W 1 CA 1 PW LV PW ICW SKA W LG IHW LA 2 SF6 SF6 IHW IHWR PW PW PW SG1 DEWAR MANIFOLD PW LV LV W SKA W LA PW 1/2"ø SG1 9 LP-302 ICW PW LG SF2 @+84" IHWR IHW LG CA LA PRV SKA ICW Construction Documents IHWR SHUT- OFF & BALANCE VALVE 2.09 PW ICW SF6 PW SF6 LG SOLENOID VALVE SWITCH (TYP.) 7 LP-301 W THIN FILMS LAB 292 2.10 TW SF1 5 9/14/2015 1:28:28 PM C:\Users\rilao\Documents\LP-NMSU-JETT HALL-2015_romelrfd.rvt B B LAB MANAGER OFFICE 295 KEY PLAN Mark Date Description Date September 11, 2015 Project Number 14400 Drawn By A A Project North FLOOR PLAN - EAST WING - SOUTH 1 SECOND Scale: 1/4" = 1'-0" RI Checked By BS/PL Copyright © VAN H. GILBERT ARCHITECT PC SHEET TITLE 0' 2' 4' LAB PLUMBING SECOND FLOOR SOUTH 8' LP-112B 1 2 3 4 5 6 SHEET 4 104 OF 187 6 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING 1 WALL SHUT-OFF VALVES BY DIVISION 22 P-SERIES DRAWINGS 2 LABORATORY PLUMBING PIPE SERVICE, SIZES PER POINT OF CONNECTION SCHEDULE, REFER TO LP-002 PIPE SERVICES PER P-SERIES DWGS. WATER BY-PASS SHUT-OFF VALVE (NORMALLY CLOSED) MAX. DISTANCE BETWEEN FITTINGS SHALL BE THREE PIPE DIAMETERS 3 SHUT-OFF VALVES TW ICW IHW IHWR POINT OF CONNECTION TO 1-1/2" LABORATORY WASTE VENT AT 6" ABOVE FINISHED CEILING REFER TO P-SERIES DRAWINGS NOTE: WASTE PENETRATION OFFSETS MAY OCCUR AT HOODS, WALL, ISLAND, AND PENINSULA BENCH LABORATORY SINKS AND/OR CUPSINKS. LOCATIONS VARY TO AVOID STRUCTURAL BEAMS AND JOISTS. REFER TO PLANS. 1 POINT OF CONNECTION TO 2" LABORATORY WASTE AT 6" ABOVE FINISHED FLOOR, REFER TO P-SERIES DRAWINGS 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail [email protected] Web Site www.vhgarchitect.com E CONSULTANTS LABORATORY WASTE OFFSET, MAINTAINED WITHIN TOE KICK SPACE OF BASE CABINET REFER TO P-SERIES DRAWINGS FOR CONTINUATION LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 WALL PW BOTTOM OF PIPE 6"-12" PW PW LG CA LV PCWS PCWR LA - CEILING CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 WATER SHUT-OFF VALVE (NORMALLY OPEN) - TYP PRESSURE REGULATING VALVE UNISTRUT PIPE SUPPORT, REFER TO DETAIL #8/LP-301 CORRIDOR LAB ELEVATION STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 3 NOTES: 1. PROVIDE REDUCERS WHERE PIPE SIZES ON THE LABORATORY PLUMBING SIDE IS SMALLER THAN THE POINT OF CONNECTION SIZE NOTED ON THE P-SERIES DRAWINGS. PLAN VIEW 2. LOCATE VALVES IN READILY ACCESSIBLE CEILING SPACE. 3. SERVICES MAY VARY, REFER TO PLANS & POC SCHEDULE. 2 LW LAB MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 3 REFER TO PLUMBING DRAWING (P-SERIES) FOR PIPING UPSTREAM OF THIS POINT FINISHED FLOOR PLAN PW CORRIDOR A PW PW E ALIGN VALVES LOCATE AS CLOSE AS PRACTICAL TO LAB WALL LWV ALIGN VALVES REFER TO LAB PLUMBING DRAWINGS (LP-SERIES) FOR PIPING DOWNSTREAM OF THIS POINT D D SECTION A 1 PW WATER SUPPLY VALVES AT POC 2 WASTE OFFSET AT SINK LOCATION 1" = 1'-0" 3 R. LEMES L U M EXI W CO PA 3" = 1'-0" NE 1/2" = 1'-0" E TR TYPICAL POINT OF CONNECTION PIPING AT LAB ENTRY DOORS 2 SERVICE FITTINGS AS SHOWN ON LF-SERIES DRAWINGS. REFER TO SCHEDULE DRAWING LP-001 3 1-1/2 "P" TRAP 4 POINT OF CONNECTION TO 1-1/2" LABORATORY WASTE VENT AT 6" ABOVE FINISHED CEILING REFER TO P-SERIES DRAWINGS 5 LABORATORY WASTE POINT OF CONNECTION TO SINK TAILPIECE 6 1/2" DIAMETER FLEXIBLE CONNECTORS 7 FIXTURE SUPPLY STOP VALVE WITH KEY & ESCUTCHEON PLATE AT CABINET BACK RAIL. MOUNT AT HEIGHT ACCESSIBLE FROM SINK CABINET(TYP.) A 2' - 2 1/4" 3 - TW LWV TW ICW PW PW LWV IHW IHWICW IHW ICW 8 TW(EW) 2. PIPE CLAMPS AND ASSEMBLIES PROVIDED BY PIPING AND CONDUIT INSTALLERS. LV PW PW 1. SERVICES & SIZES VARY, REFER TO LABORATORY PLUMBING PLANS & DETAILS. LG 4 1/4" 2 3/8" LWV LV 1 7/8" LA NOTES: 2 2 WALL BENCH CONDITION 1 1 PIPE DROP ENCLOSURE PER DIVISION 11 PW C 2 LA WALL H UNISTRUT P4000 ANCHORED TO WALL PER DIV. 22 3 LG ONE OR TWO PIECE PIPE/CONDUIT CLAMP WITH ELASTOMERIC ISOLATION MATERIAL. SIZE TO FIT PIPE/CONDUIT BEING SUPPORTED. "STRUT" TYPE CHANNEL BRACKET (BY DIVISION 11) 11 ℄ NOTES: 1. SERVICES AND ARRANGEMENT MAY VARY REFER TO LABORATORY PLUMBING PLANS 7 18" LW 8 "STRUT" TYPE BRACKET ANCHORED TO WALL 5 9 8 FT. HIGH PRESSURE REINFORCED PVC HOSE, INSTALL WITH COIL LOOP IN SINK CABINET, FREE OF CONTACT AND BINDING WITH OBJECTS 7 10 BACK FLOW PREVENTER BY DIV 11, CLAMPED ON THE BACK BOARD BY DIV. 22 11 1/2" PW BALL VALVE BY DIV 22 10 3 LW ICW ONE OR TWO PIECE PIPE/CONDUIT CLAMP WITH ELASTOMERIC ISOLATION MATERIAL. SIZE TO FIT PIPE/CONDUIT BEING SUPPORTED. 4 6 9 LW IHW C BELOW BENCH SUPPORT RACK 1 1/2" = 1'-0" 4 TYPICAL WALL PIPE DROP ENCLOSURE 3" = 1'-0" SECTION A C Construction Documents 2. REFER TO DETAIL #9/LP-301 FOR PW VERTICAL PIPING LOOP AT LABORATORY SINK 5 TYPICAL PIPING AT LABORATORY SINK 1" = 1'-0" 6 B B 2 1-1/4" TW SUPPLY 3 SAFETY SHOWER SUPPLIED PER DIV. 11 INSTALLED PER DIV. 22 4 1 1/2" P-TRAP CONNECTED TO WASTE AND VENT SYSTEM. PROVIDE ACCESS PANEL FOR P-TRAP. 84"A.F.F. 3 4 PW TW ICW 8 4 2 1/2" TW SUPPLY TO EYEWASH 4 1 LV 1" TW SUPPLY TO SAFETY SHOWER IHWR 7 IHW REMOVABLE SHOWER VALVE ACCESS PANEL ICW 6 ℄ PW RECESSED EYEWASH AT WALL SUPPLIED PER DIV. 11 INSTALLED PER DIV. 22 7 2 A 6" 2 LA 3 1 LG 5 6 - PW 10 5 TW 1 15 9 INSTANT ACTION BALL VALVE IHWR 5 4 8 10 ESCUTCHEON PW 11 1-1/2" P-TRAP CONNECTED TO WASTE AND VENT SYSTEM. PROVIDE ACCESS PANEL FOR P-TRAP. PW 9 12 1 LA REMOVABLE DRAIN ACCESS PANEL 3" SPACING BETWEEN PIPES, TYP. LV 13 DRAIN PAN 6 A 12 15 11 POINT OF CONNECTION TO 2" LABORATORY WASTE AT 6" ABOVE FINISHED FLOOR, REFER TO P-SERIES DRAWINGS CONNECTION TO PW SERVICE MINIMIZE DEAD LEG 4 SERVICE FITTING MOUNTED ON FIXED SIDE OF PIPE DROP ENCLOSURE BY DIVISION 11/12 (REFER TO PLANS FOR LOCATIONS) Mark 2 UNISTRUT PIPE SUPPORT 3 PIPE INSULATION ℄ 2 6 2 4 PURIFIED WATER PIPING LINEAR SUPPORT 1/2" FEMALE NPT X 3/8" O.D. COMPRESSION ADAPTOR 7 POC PIPING SUPPORT DETAIL 3 3/4" = 1'-0" 4 Description Date September 11, 2015 Project Number 14400 Drawn By 3/8" O.D. COMPRESSION X 3/8" O.D. COMPRESSION ELBOW ADAPTOR A NOTE: FLOOR PW LOOP DROPPED IN PIPE DROP ENCLOSURE PER DIV. 22 P-SERIES DRAWINGS. ELEVATION 3/4" = 1'-0" Date RI Checked By BS/PL Copyright © NOTES: SERVICES MAY VARY, REFER TO PLANS & POC SCHEDULE. NOTE: DETAIL IS SHOWN DIAGRAMMATICALLY. PIPING SHALL BE MAINTAINED WITHIN WALL AND CEILING SPACE. 2 3 5 14 1 PW SHUT OFF VALVE, INSTALL WITHIN SINK CABINET FOR ACCESS 3 LABORATORY PLUMBING PIPE SERVICE, SIZES PER POINT OF CONNECTION SCHEDULE, REFER TO LP-001 PLAN VIEW POINT OF CONNECTION TO 1-1/2" LABORATORY WASTE VENT AT 6" ABOVE FINISHED CEILING REFER TO P-SERIES DRAWINGS PIPING AT SAFETY SHOWER/RECESSED EYEWASH UNIT 2 18" 14 SERVICE FITTING AS SHOWN ON LF-SERIES DRAWINGS. REFER TO SCHEDULE DRAWING LP-001 ELEVATION 4 LG 5 13 1 PW IHW - C:\Users\rilao\Documents\LP-NMSU-JETT HALL-2015_romelrfd.rvt 2 SINGLE PIPE HANGER TO STRUCTURE ABOVE PW 1 9/14/2015 1:28:37 PM N GI 9/11/15 Jett Hall and Jett Annex Renovations and Additions NOTES: 1. SERVICES MAY VARY, REFER TO PLANS & SCHEDULES ELEVATION N AL E N New Mexico State University 1 2. COORDINATE PIPING INSTALLATION WITH DIVISION 11 SHOP SUBMITTALS S IO PROJECT 4 4 ES F POINT OF CONNECTION TO 2" LABORATORY WASTE AT 6" ABOVE FINISHED FLOOR, REFER TO P-SERIES DRAWINGS EE P RO 1 R 18351 5 SHEET TITLE LAB PLUMBING DETAILS SECTION A 8 PIPING PW VERTICAL PIPING LOOP AT LABORATORY SINK 1" = 1'-0" 6 VAN H. GILBERT ARCHITECT PC 9 LP-301 SHEET 5 105 OF 187 6 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING 6 2 2 4 WALL WALL 5 1 1 2 POINT OF CONNECTION TO 2" LABORATORY WASTE AT 6" ABOVE FINISHED FLOOR. REFER TO P-SERIES DRAWINGS. 4 1 5 1 POINT OF CONNECTION TO PREPIPED HOOD SERVICES. 3 1 4 HOOD PLAN VIEW 1 2 3 LV LA LG ICW HOOD PLAN VIEW W/ 3" CHASE SPACE PRE-PIPED WET & DRY SERVICE SUPPLIES TO HOOD SERVICES MAY VARY, REFER TO PLANS FOR TYPES. 5 LABORATORY WASTE AND VENT RISER LOCATED WITHIN WALL. PIPED SERVICES LOCATED IN WALL TO FEED ADJACENT BENCH SERVICE FITTINGS. REFER TO PLANS FOR WHERE OCCURS. 4 POINT OF CONNECTION TO CUP SINK TAILPIECE. POINT OF CONNECTION TO 1-1/2" LABORATORY VENT @ 6" ABOVE FINISHED CEILING. 5 1-1/2" P-TRAP. 6 LABORATORY WASTE AND VENT RISER BEHIND HOOD IN 3" CHASE OR IN WALL. REFER TO PLANS FOR LOCATIONS. LV LA LG ICW POINT OF CONNECTION TO 2" LABORATORY WASTE AT 6" ABOVE FINISHED FLOOR. REFER TO P-SERIES DRAWINGS. 2 POINT OF CONNECTION TO PRE-PIPED HOOD SERVICES 3 POINT OF CONNECTION TO CUPSINK TAILPIECE CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 4 POINT OF CONNECTION TO 1-1/2" LABORATORY VENT @ 6" ABOVE FINISHED CEILING 5 1-1/2" P-TRAP 6 WASTE AND VENT RISER BEHIND HOOD 6 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 LV LA LG ICW 2 NOTES: 2. REFER TO SCHEDULES FOR PIPE SIZES. REFER ALSO TO DETAIL #1/LP-302 3 1 5 3. PIPING SHOWN DASHED IS PART OF PRE-PIPED FUME HOOD PER DIVISION 11. PIPED SERVICES BEHIND HOOD IN 3" CHASE TO FEED ADJACENT BENCH SERVICE FITTINGS. REFER TO PLANS FOR WHERE OCCURS. 1. SERVICES MAY VARY, REFER TO PLANS LV LA LG MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 2. REFER TO SCHEDULES FOR PIPE SIZES. FOR TYPICAL HOOD TOP PLAN, REFER TO DETAIL #1/LP-302 4. PIPING SHOWN SOLID TO BE PROVIDED UNDER DIVISION 22. 3. PIPING SHOWN DASHED TO BE PROVIDED UNDER DIVISION 11 NOTE: WASTE PENETRATION LOCATIONS MAY REQUIRE OFFSET TO AVOID STRUCTURAL BEAMS, REFER TO P-SERIES DRAWINGS. 4. PIPING SHOWN SOLID TO BE PROVIDED UNDER DIVISION 22 5. P-TRAP, P-TRAP ARM AND ELBOW BENDS TO CUPSINK TO BE LOCATED WITHIN SIDE PANEL OF FLOOR MOUNTED HOOD D 1 TYPICAL PIPING AT CHEMICAL FUME HOOD SCALE: NTS 2 TYPICAL PIPING AT FLOOR MOUNTED HOOD 1/2" = 1'-0" 3 R. LEMES L U M EXI W CO PA SCALE: NTS D E TR TYPICAL PIPING AT CHEMICAL FUME HOOD - PLAN 1 2 5 LOCATION OF LABORATORY WASTE AND VENT RISER LOCATED BEHIND HOOD IN 3" CHASE. REFER TO PLANS FOR WHERE OCCURS. 6 E NOTES: 1. SERVICES MAY VARY, REFER TO PLANS. 3 3" FILLER PANEL/CHASE PROVIDED PER DIVISION 11. REFER TO LF PLANS FOR LOCATIONS. 4 6 LV LA LG ICW NE 3 1 6" E LV LA LG ICW 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail [email protected] Web Site www.vhgarchitect.com F ES EE P RO R 18351 S IO N AL E N N GI 9/11/15 PROJECT 4 2 98" A.F.F. 1 1 BIOLOGICAL SAFETY CABINET. 2 BSC WALL MOUNTED POINT OF CONNECTION SHUT-OFF VALVE 3 4 1 3 SERVICE FITTINGS AS SHOWN ON LF-SERIES DRAWINGS. REFER TO SCHEDULE DRAWING LP-001 2 1 1 CABLE TRAY BY DIVISION 11 2 LOCATE PIPES TO DROP ON CABLE TRAY BEARING SURFACE 3 SERVICE FITTINGS AS SHOWN ON LF-SERIES DRAWINGS. REFER TO SCHEDULE DRAWING LP-001 "A" PIPING WITHIN BIOLOGICAL SAFETY CABINET CHASE TO SERVICE FITTING 2 FINISHED WALL FLEX PIPE CONNECTOR 3 FLAT BRACKET SECURED TO WALL STRUCTURE, SOLDER PIPE TO BRACKET 54" TYP. - U.O.N. C 2 1 3 NOTES: 1. NUMBER OF SERVICES MAY VARY, REFER TO PLANS. 4 New Mexico State University Jett Hall and Jett Annex Renovations and Additions UNISTRUT PIPE CLAMPS NOTE: SERVICES & ARRANGEMENTS MAY VARY REFER TO PLANS & SCHEDULES NOTE: SERVICES & ARRANGEMENTS MAY VARY REFER TO PLANS & SCHEDULES C "A" PLAN VIEW 2. OFOI BSC MAY NOT BE PRE-PIPED. FINISHED FLOOR Construction Documents 4 3 SECTION ELEVATION 1" = 1'-0" 4 PIPING AT WALL MOUNTED FITTING 1" = 1'-0" 5 PIPING @ OVERHEAD SERVICE CARRIER WITH CABLE TRAY 6 B 3 2 1 14 PW CA 1 IHW SUPPLY 2 3 UNION (TYPICAL) MPS 5 7 STEAM GENERATOR DRAIN. ROUTE TO FLOOR SINK 8 INTEGRAL STEAM GENERATOR FLOOR SINK SEE P-DRAWINGS 7 15 2 CHANGEOVER ENCLOSURE W/ HEATER AND ANNUNCIATOR 3 HIGH PRESSURE HEADER 4 BANK SHUT-OFF VALVE, TYP. 5 PIGTAIL 6 CHECK VALVE 7 GAS CYLINDERS OFOI 8 CYROGENIC CYLINDER - OFOI 9 1"ø MANIFOLD RELIEF EXHAUST PIPE, CONNECTED TO LABORATORY EXHAUST DUCTWORK 10 CYLINDER RESTRAINT BY DIV. 11 11 POWER SOURCE (IF REQUIRED) 12 ANNUNCIATOR 13 THREADED CONNECTOR ON END OF RELIEF EXHAUST PIPE 14 THREAD-O-LET FITTING WELDED TO EXHAUST DUCT 9 3 IHW ISOLATION VALVE 4 DRAIN TO FLOOR SINK. REFER TO LP AND PLUMBING PLANS 5 GLASSWARE WASHER 6 WATER GAUGE 7 ICW ISOLATION VALVE VENT TO DUCT CONNECTION DETAIL 2 6 11 7 8 TO DISTRIBUTION SYSTEM 12 11 1 4 CA SUPPLY W/ ISOLATION VALVE 2 3 9 PW PIPING LOOP BY DIV. 22. REFER TO LP-SERIES DWG FOR CONTINUATION 10 PW SUPPLY W/ ISOLATION VALVE 11 WATER PRESSURE REGULATOR 5 5 6 WATER HAMMER ARRESTER. 4 NOTES: 1. ICW & IHW SOURCE SUPPLIES PROVIDED FROM BACK FLOW PROTECTED WATER SYSTEM. 6 7 8 FLOOR SINK SEE P-DRAWINGS 3 6 11 3 FLOW DIAGRAM 2. PIPE SIZES, SERVICES AND LOCATIONS OF CONNECTIONS MAY VARY. REFER TO PLANS, SCHEDULES AND MANUFACTURER'S REQUIREMENTS. SCALE: NTS 2 Mark 3 SCALE: NTS 4 15 September 11, 2015 14400 Drawn By RELIEF EXHAUST PIPE CONNECTOR SCREWED INTO THREAD-O-LET. PROVIDE TEFLON TAPE ON CONNECTOR THREADS A RI Checked By BS/PL Copyright © NOTES: 1. NOT ALL MANIFOLD COMPONENTS ARE SHOWN. REFER TO DIVISION 22 SPECIFICATIONS. 8 CYLINDER MANIFOLD AT CRYOGENIC CYLINDERS 5 Description Project Number LAB PLUMBING DETAILS SCALE: NTS 6 VAN H. GILBERT ARCHITECT PC SHEET TITLE 3. NUMBER OF CYLINDERS MAY VARY, REFER TO PLANS. 7 PIPING AT GLASSWARE WASHER Date Date 2. PROVIDE MOUNTING/BRACKETING HARDWARE FOR AFFIXING UNIT TO WALL. 3. ROUTE STEAM RELIEF VALVE TO FLOOR SINK. PIPING AT AUTOCLAVE 1 1 ICW 5 CHAMBER DRAIN. ROUTE TO FLOOR SINK 5 6 WATER HAMMER ARRESTER 9 IHW PRESSURE REGULATOR (TYPICAL) 9 2 STRAINER (TYPICAL) 4 6 PIPE UNION (TYPICAL) PRESSURE GAUGE (TYPICAL) 10 8 SYSTEM SHUT-OFF VALVE 13 PW 8 SHUT-OFF VALVE (TYPICAL) 1 60"A.F.F. 9 CA SUPPLY A 1 EXHAUST DUCT ICW SUPPLY C:\Users\rilao\Documents\LP-NMSU-JETT HALL-2015_romelrfd.rvt 3/4" = 1'-0" 9 4 9/14/2015 1:28:40 PM SECTION "A"-"A" 3 PIPING AT BIOLOGICAL SAFETY CABINET B ELEVATION 9 LP-302 SHEET 6 106 OF 187 6 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING 8 7 1 LABORATORY GAS POINT OF CONNECTION 2 LABORATORY GAS DISTRIBUTION FROM POINT OF CONNECTION 3 GAS DISTRIBUTION PIPING TO LABORATORY SERVICES (REFER TO PLANS FOR ROUTING) 1 1 E 2 FINISHED WALL 5 5.5" WIDE x 5.5" TALL VISION PANEL 6 WALL BOARD FRAME 7 16 GAUGE STEEL VALVE BOX, BAKED WHITE ENAMEL FINISH, 12"x12"x4" DEEP 5 2-PIECE BRASS BALL VALVE WITH BRASS TRIM AND THREADED ENDS. UL LISTED AND AGA/CGA CERTIFIED FOR NATURAL GAS SERVICE. VALVE HANDLES TO BE INSTALLED HORIZONTAL TO EXTEND OUT OF VALVE BOX. 9 PIPE & VALVE TO BE MOUNTED IN CENTER OF VALVE BOX. 10 SMALL PADDLE HANDLE, NON-LOCKING 11 ENGRAVED PLASTIC LABEL. WHITE LETTERING ON BLACK LABEL. ℄ 8 LABORATORY GAS CONTROL VALVE CLOSE ONLY IN EMERGENCY 10 9 40" 11 FINISHED FLOOR MOUNTING BRACKET 3 SERVICE FITTING PER DIVISION 11 3 CMU WALL E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 4 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 (24"A.F.F.@ ICW FITTING) 8 6 2 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail [email protected] Web Site www.vhgarchitect.com 2 54" TYP.-U.O.N. 3 PIPES BRACKETED TO WALL 3 4 4 PLAN VIEW 1 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 NOTES: ALL EXPOSED PIPING TO BE FREE OF DEBRIS, OVER SPRAY PAINT AND PIPE DOPE FOR A NEAT APPEARANCE. FINISHED FLOOR ELEVATION D SECTION 1 PIPING AT WALL MOUNTED FITTING (EXPOSED) 1" = 1'-0" 2 NOT USED R. LEMES L U M EXI W CO PA 1" = 1'-0" E TR PIPING AT GAS SHUT-OFF VALVE NE D F ES EE P RO R 18351 S IO N AL E N N GI 9/11/15 PROJECT New Mexico State University Jett Hall and Jett Annex Renovations and Additions C C Construction Documents NOT USED NOT USED NOT USED C:\Users\rilao\Documents\LP-NMSU-JETT HALL-2015_romelrfd.rvt B B Mark Date Description Date A A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC 9/14/2015 1:28:41 PM SHEET TITLE LAB PLUMBING DETAILS NOT USED NOT USED 1 2 LP-303 NOT USED 3 4 5 6 SHEET 107 OF 187 6
© Copyright 2024 Paperzz