ZX-Family Gas-insulated medium voltage switchgear

Gas-insulated switchgear
Flexible combination, reliability, availability and economy are
the attributes that make it easy for our clients in industry and
utilities to decide in favor of products from the ZX series.
Together with complete conventional solutions, the use of
digital protection and control technology, sensor systems
and plug-in connections makes ZX systems unrestrictedly
fit for the future, and the primary function of reliable power
distribution is fulfilled with no ifs and buts. This is ensured by
ABB’s uncompromising approach to quality, which leaves no
customer’s wishes unfulfilled.
- Systems in metal-enclosed design
- Hermetically sealed pressure systems –
gas-tight for life!
- SF6 insulating gas for guaranteed dielectric strength
- Metal partitioning between functions where necessary
- Plug-in technology for cables, busbars and
voltage transformers
- Enclosures in stainless steel
- Vacuum circuit-breakers
- Factory tested quality
A strong family for all situations in life.
Aligned to each need, the members of
the ZX family offer a solution for each
requirement. In over 70 countries the
customers rely on gas-insulated switchgears from ABB.
Contact us
ABB AG
Calor Emag Medium Voltage Products
Oberhausener Strasse 33
40472 Ratingen, Germany
Phone: +49(0)21 02/12-0
Fax:
+49(0)21 02/12-17 77
Email: [email protected]
ABB AG
Calor Emag Medium Voltage Products
Petzower Strasse 8
14542 Werder (Havel) OT Glindow, Germany
Phone: +49(0)21 02/12-0
+49(0)21 02/12-17 77
Fax:
Email: [email protected]
Note:
We reserve the right to make technical changes or
modify the contents of this document without prior
notice. With regards to purchase orders, the agreed
particulars shall prevail. ABB does not accept any
responsibility whatsoever for potential errors or possible lack of information in this document.
We reserve all rights to this document and in the
subject matter and illustrations contained therein
Any reproduction – in whole or in parts – is forbidden
without ABB’s prior written consent.
DEABB 2435 E (03.09-1000-AMC)
ZX-Family
Gas-insulated medium voltage switchgear
Copyright© 2009 ABB AG
All rights reserved.
www.abb.com/mediumvoltage
ZX-Family
Gas-insulated medium
voltage switchgear
ZX-Family Gas-insulated medium voltage switchgear
Your ZX benefit
Minimum overall costs
Your ZX benefit
Safety first
1
14
13
2
12
3
4
10
ZX offers maximum economy
ZX ensures maximum operator safety
The compact design of the panels reduces the space required
and therefore the size of the station. Freedom from maintenance is achieved by constant conditions in the high voltage
compartments in conjunction with the selection of suitable
materials. As a rule, therefore, isolation of the switchgear to
perform maintenance work is not required. The panels are
designed for an expected service life of over 40 years. Thanks
to the plug-in technology applied in the areas of the busbars,
cables and secondary systems, extremely short installation
times are possible. No gas work is required as a rule at site.
All live components are enclosed to prevent accidental contact. As the high voltage compartments are independent of
external influences (degree of protection IP65), the probability
of a fault during operation is extremely low. As evidenced by
arc fault testing, our switchgear systems are notable for maximum operator safety. A further enhancement can be achieved
by providing pressure relief to outside the switchgear room.
9
1
17
16
9
5
8
6
7
Circuit-breaker panel 1250 A
2
3
4
5
15
14
13
Main components of ZX1.2
1 Plug-in voltage transformer
2 Isolating system for voltage transformers
3 Density sensor
4 Circuit-breaker operating mechanism
5 Multifunctional protection and control unit
6 Three-position disconnector operating mechanism
7 Three-position disconnector
8 Busbars
9 Pressure relief disk
10 Pressure relief duct
11 Cable connector
12 Cable socket
13 Measuring sockets for capacitive voltage indicator system
14 Test socket
15 Vacuum circuit-breaker
16 Combined current and voltage sensor or current transformer
17 Plasma diverter
12
ZX0 elements at a glance
1 Multifunctional protection and control unit
2 Measuring sockets for capacitive voltage indicator system
3 Three position disconnector mechanism
4 Circuit-breaker mechanism
5 Cable connector
6 Ring-type current transformer
7 Voltage transformer
8 VT isolating system
9 Pressure relief plate
10 Outer cone
11 Vacuum circuit-breaker
12 Three-position disconnector
13 Busbars
14 Plug-in busbar voltage transformers
11
Your ZX benefit
Maximum availability
11
6
7
8
10
9
Feeder 2000 A
Easy, simple and fast
10
The plug-in busbar technology without screw couplings
permits simple and therefore safe assembly. In spite of the
extremely low failure probability of the ZX switchgear systems,
replacement of components in the gas compartments and
therefore a rapid return to service after repairs is possible.
In gas-insulated switchgear, earthing of switchgear sections
is performed by a high quality vacuum circuit-breaker. The
circuit-breaker can close onto a short-circuit significantly
more frequently and reliably than a positively making earthing
switch.
1
9
7
8
6
5
13
14
3
10
9
4
15
12
11
2
Double busbar panel for 2000 A
ZX0
ZX1.2
ZX2
Compact system for distribution applications in two basic
versions: block and individual panel design. Installation
against a wall. Both local manual operation and remote
control are facilitated. Together with vacuum circuit-breakers,
there are switch-disconnectors with and without fuses.
Metal partitioned single busbar system for transformer and
distribution substations with raised cable terminations for
ultra-simple cable installation from the rear. All switching
devices can be remote controlled and optionally mechanically
interlocked.
Metal partitioned single or double busbar system for all applications – even with the highest parameters. Cables accessible
from the rear. All switching devices can be remote controlled
and optionally mechanically interlocked. Both combined protection and control devices and pure protection devices are
used.
IEC Ratings
Maximum operating voltage
kV 12 Test voltages
kV 28/75 Rated frequency
Hz 50/60 50/60
Rated busbar current
A
...1250
...1250 ...1250
Rated busbar current Rated current of feeder with CB A
...1250 ...1250 ...1250
Rated current of feeder
Rated current of feeder with load break switch A
...630 ...630 ...630
Rated peak withstand current
kA Rated peak withstand current kA ...62.5 ...62.5 ...62.5
Rated short-time current, 3s
kA Rated short-time current, 3s kA ...25 ...25 ...25
Internal Arc Classification
IAC AFL 25 kA 1s
50/60 1)
17.5 IEC Ratings
kV 1)
12 Rated voltage
Rated voltage kV
17.5 24
Maximum operating voltage kV 17.5
24
36
40.5
38/95 50/125
Test voltages kV
38/95
50/125
70/170
85/185
Rated frequency Hz
50/60
50/60
50/60
50/60
A
…2500
…2500
…2500
…2500
A
630
12/17.5
1250 ...2500
630 62.5 …80
62.5
25 …31.5
Internal Arc ClassificationIAC AFLR 31.5 kA 1s
1)
acc. to IEC 62271-200 |
2)
25
24
Special Ratings
24
1250 ...2500 …80
…31.5
36
1250 ...2500
…80
…31.5
ZX2 key elements
1 Plug-in voltage transformer - busbar
2 Plug-in voltage transformer - outgoing feeder
3 Density sensor
4 Circuit-breaker operating mechanism
5 Multifunctional protection and control unit
6 Three-position disconnector operating mechanism
7 Three-position disconnector
8 Busbars
9 Pressure relief disk
10 Pressure relief duct
11 Cable connector
12 Cable socket
13 Measuring sockets for capacitive voltage indicator system
14 Vacuum circuit-breaker
15 Combined current and voltage sensor or current transformer
IEC Ratings
Rated voltage
kV
12/17.5
24
Special Ratings
36
Maximum operating voltage
kV Test voltages
kV
Rated frequency
Hz
50/60
50/60
50/60
50/60
A
…2500
…2500
…2500
…2500
Rated busbar current 2)
A
630
24
36
40.5
50/125
70/170
85/185
1250 ...2500
630
1250 . ..2500
…80
Rated peak withstand curren
kA 62.5 …100
62.5
…100
…100
…100
…31.5
Rated short-time current, 3s
kA 25 …40
25
…40
…40
…40
1250 ..2500
Rated current of feeder 2)
17.5
38/95
Internal Arc ClassificationIAC AFLR 40 kA 1s
1) 2)
with pressure relief duct
1)
1250 ...2500 1250 ...2500
1)
acc. to IEC 62271-200 | 2) Single busbar systems up to 4000 A on request
acc. to IEC 62271-200
ZX-Family Gas-insulated medium voltage switchgear
ZX-Family Gas-insulated medium voltage switchgear
ZX-Family Gas-insulated medium voltage switchgear
Your ZX benefit
Minimum overall costs
Your ZX benefit
Safety first
1
14
13
2
12
3
4
10
ZX offers maximum economy
ZX ensures maximum operator safety
The compact design of the panels reduces the space required
and therefore the size of the station. Freedom from maintenance is achieved by constant conditions in the high voltage
compartments in conjunction with the selection of suitable
materials. As a rule, therefore, isolation of the switchgear to
perform maintenance work is not required. The panels are
designed for an expected service life of over 40 years. Thanks
to the plug-in technology applied in the areas of the busbars,
cables and secondary systems, extremely short installation
times are possible. No gas work is required as a rule at site.
All live components are enclosed to prevent accidental contact. As the high voltage compartments are independent of
external influences (degree of protection IP65), the probability
of a fault during operation is extremely low. As evidenced by
arc fault testing, our switchgear systems are notable for maximum operator safety. A further enhancement can be achieved
by providing pressure relief to outside the switchgear room.
9
1
17
16
9
5
8
6
7
Circuit-breaker panel 1250 A
2
3
4
5
15
14
13
Main components of ZX1.2
1 Plug-in voltage transformer
2 Isolating system for voltage transformers
3 Density sensor
4 Circuit-breaker operating mechanism
5 Multifunctional protection and control unit
6 Three-position disconnector operating mechanism
7 Three-position disconnector
8 Busbars
9 Pressure relief disk
10 Pressure relief duct
11 Cable connector
12 Cable socket
13 Measuring sockets for capacitive voltage indicator system
14 Test socket
15 Vacuum circuit-breaker
16 Combined current and voltage sensor or current transformer
17 Plasma diverter
12
ZX0 elements at a glance
1 Multifunctional protection and control unit
2 Measuring sockets for capacitive voltage indicator system
3 Three position disconnector mechanism
4 Circuit-breaker mechanism
5 Cable connector
6 Ring-type current transformer
7 Voltage transformer
8 VT isolating system
9 Pressure relief plate
10 Outer cone
11 Vacuum circuit-breaker
12 Three-position disconnector
13 Busbars
14 Plug-in busbar voltage transformers
11
Your ZX benefit
Maximum availability
11
6
7
8
10
9
Feeder 2000 A
Easy, simple and fast
10
The plug-in busbar technology without screw couplings
permits simple and therefore safe assembly. In spite of the
extremely low failure probability of the ZX switchgear systems,
replacement of components in the gas compartments and
therefore a rapid return to service after repairs is possible.
In gas-insulated switchgear, earthing of switchgear sections
is performed by a high quality vacuum circuit-breaker. The
circuit-breaker can close onto a short-circuit significantly
more frequently and reliably than a positively making earthing
switch.
1
9
7
8
6
5
13
14
3
10
9
4
15
12
11
2
Double busbar panel for 2000 A
ZX0
ZX1.2
ZX2
Compact system for distribution applications in two basic
versions: block and individual panel design. Installation
against a wall. Both local manual operation and remote
control are facilitated. Together with vacuum circuit-breakers,
there are switch-disconnectors with and without fuses.
Metal partitioned single busbar system for transformer and
distribution substations with raised cable terminations for
ultra-simple cable installation from the rear. All switching
devices can be remote controlled and optionally mechanically
interlocked.
Metal partitioned single or double busbar system for all applications – even with the highest parameters. Cables accessible
from the rear. All switching devices can be remote controlled
and optionally mechanically interlocked. Both combined protection and control devices and pure protection devices are
used.
IEC Ratings
Maximum operating voltage
kV 12 Test voltages
kV 28/75 Rated frequency
Hz 50/60 50/60
Rated busbar current
A
...1250
...1250 ...1250
Rated busbar current Rated current of feeder with CB A
...1250 ...1250 ...1250
Rated current of feeder
Rated current of feeder with load break switch A
...630 ...630 ...630
Rated peak withstand current
kA Rated peak withstand current kA ...62.5 ...62.5 ...62.5
Rated short-time current, 3s
kA Rated short-time current, 3s kA ...25 ...25 ...25
Internal Arc Classification
IAC AFL 25 kA 1s
50/60 1)
17.5 IEC Ratings
kV 1)
12 Rated voltage
Rated voltage kV
17.5 24
Maximum operating voltage kV 17.5
24
36
40.5
38/95 50/125
Test voltages kV
38/95
50/125
70/170
85/185
Rated frequency Hz
50/60
50/60
50/60
50/60
A
…2500
…2500
…2500
…2500
A
630
12/17.5
1250 ...2500
630 62.5 …80
62.5
25 …31.5
Internal Arc ClassificationIAC AFLR 31.5 kA 1s
1)
acc. to IEC 62271-200 |
2)
25
24
Special Ratings
24
1250 ...2500 …80
…31.5
36
1250 ...2500
…80
…31.5
ZX2 key elements
1 Plug-in voltage transformer - busbar
2 Plug-in voltage transformer - outgoing feeder
3 Density sensor
4 Circuit-breaker operating mechanism
5 Multifunctional protection and control unit
6 Three-position disconnector operating mechanism
7 Three-position disconnector
8 Busbars
9 Pressure relief disk
10 Pressure relief duct
11 Cable connector
12 Cable socket
13 Measuring sockets for capacitive voltage indicator system
14 Vacuum circuit-breaker
15 Combined current and voltage sensor or current transformer
IEC Ratings
Rated voltage
kV
12/17.5
24
Special Ratings
36
Maximum operating voltage
kV Test voltages
kV
Rated frequency
Hz
50/60
50/60
50/60
50/60
A
…2500
…2500
…2500
…2500
Rated busbar current 2)
A
630
24
36
40.5
50/125
70/170
85/185
1250 ...2500
630
1250 . ..2500
…80
Rated peak withstand curren
kA 62.5 …100
62.5
…100
…100
…100
…31.5
Rated short-time current, 3s
kA 25 …40
25
…40
…40
…40
1250 ..2500
Rated current of feeder 2)
17.5
38/95
Internal Arc ClassificationIAC AFLR 40 kA 1s
1) 2)
with pressure relief duct
1)
1250 ...2500 1250 ...2500
1)
acc. to IEC 62271-200 | 2) Single busbar systems up to 4000 A on request
acc. to IEC 62271-200
ZX-Family Gas-insulated medium voltage switchgear
ZX-Family Gas-insulated medium voltage switchgear
ZX-Family Gas-insulated medium voltage switchgear
Your ZX benefit
Minimum overall costs
Your ZX benefit
Safety first
1
14
13
2
12
3
4
10
ZX offers maximum economy
ZX ensures maximum operator safety
The compact design of the panels reduces the space required
and therefore the size of the station. Freedom from maintenance is achieved by constant conditions in the high voltage
compartments in conjunction with the selection of suitable
materials. As a rule, therefore, isolation of the switchgear to
perform maintenance work is not required. The panels are
designed for an expected service life of over 40 years. Thanks
to the plug-in technology applied in the areas of the busbars,
cables and secondary systems, extremely short installation
times are possible. No gas work is required as a rule at site.
All live components are enclosed to prevent accidental contact. As the high voltage compartments are independent of
external influences (degree of protection IP65), the probability
of a fault during operation is extremely low. As evidenced by
arc fault testing, our switchgear systems are notable for maximum operator safety. A further enhancement can be achieved
by providing pressure relief to outside the switchgear room.
9
1
17
16
9
5
8
6
7
Circuit-breaker panel 1250 A
2
3
4
5
15
14
13
Main components of ZX1.2
1 Plug-in voltage transformer
2 Isolating system for voltage transformers
3 Density sensor
4 Circuit-breaker operating mechanism
5 Multifunctional protection and control unit
6 Three-position disconnector operating mechanism
7 Three-position disconnector
8 Busbars
9 Pressure relief disk
10 Pressure relief duct
11 Cable connector
12 Cable socket
13 Measuring sockets for capacitive voltage indicator system
14 Test socket
15 Vacuum circuit-breaker
16 Combined current and voltage sensor or current transformer
17 Plasma diverter
12
ZX0 elements at a glance
1 Multifunctional protection and control unit
2 Measuring sockets for capacitive voltage indicator system
3 Three position disconnector mechanism
4 Circuit-breaker mechanism
5 Cable connector
6 Ring-type current transformer
7 Voltage transformer
8 VT isolating system
9 Pressure relief plate
10 Outer cone
11 Vacuum circuit-breaker
12 Three-position disconnector
13 Busbars
14 Plug-in busbar voltage transformers
11
Your ZX benefit
Maximum availability
11
6
7
8
10
9
Feeder 2000 A
Easy, simple and fast
10
The plug-in busbar technology without screw couplings
permits simple and therefore safe assembly. In spite of the
extremely low failure probability of the ZX switchgear systems,
replacement of components in the gas compartments and
therefore a rapid return to service after repairs is possible.
In gas-insulated switchgear, earthing of switchgear sections
is performed by a high quality vacuum circuit-breaker. The
circuit-breaker can close onto a short-circuit significantly
more frequently and reliably than a positively making earthing
switch.
1
9
7
8
6
5
13
14
3
10
9
4
15
12
11
2
Double busbar panel for 2000 A
ZX0
ZX1.2
ZX2
Compact system for distribution applications in two basic
versions: block and individual panel design. Installation
against a wall. Both local manual operation and remote
control are facilitated. Together with vacuum circuit-breakers,
there are switch-disconnectors with and without fuses.
Metal partitioned single busbar system for transformer and
distribution substations with raised cable terminations for
ultra-simple cable installation from the rear. All switching
devices can be remote controlled and optionally mechanically
interlocked.
Metal partitioned single or double busbar system for all applications – even with the highest parameters. Cables accessible
from the rear. All switching devices can be remote controlled
and optionally mechanically interlocked. Both combined protection and control devices and pure protection devices are
used.
IEC Ratings
Maximum operating voltage
kV 12 Test voltages
kV 28/75 Rated frequency
Hz 50/60 50/60
Rated busbar current
A
...1250
...1250 ...1250
Rated busbar current Rated current of feeder with CB A
...1250 ...1250 ...1250
Rated current of feeder
Rated current of feeder with load break switch A
...630 ...630 ...630
Rated peak withstand current
kA Rated peak withstand current kA ...62.5 ...62.5 ...62.5
Rated short-time current, 3s
kA Rated short-time current, 3s kA ...25 ...25 ...25
Internal Arc Classification
IAC AFL 25 kA 1s
50/60 1)
17.5 IEC Ratings
kV 1)
12 Rated voltage
Rated voltage kV
17.5 24
Maximum operating voltage kV 17.5
24
36
40.5
38/95 50/125
Test voltages kV
38/95
50/125
70/170
85/185
Rated frequency Hz
50/60
50/60
50/60
50/60
A
…2500
…2500
…2500
…2500
A
630
12/17.5
1250 ...2500
630 62.5 …80
62.5
25 …31.5
Internal Arc ClassificationIAC AFLR 31.5 kA 1s
1)
acc. to IEC 62271-200 |
2)
25
24
Special Ratings
24
1250 ...2500 …80
…31.5
36
1250 ...2500
…80
…31.5
ZX2 key elements
1 Plug-in voltage transformer - busbar
2 Plug-in voltage transformer - outgoing feeder
3 Density sensor
4 Circuit-breaker operating mechanism
5 Multifunctional protection and control unit
6 Three-position disconnector operating mechanism
7 Three-position disconnector
8 Busbars
9 Pressure relief disk
10 Pressure relief duct
11 Cable connector
12 Cable socket
13 Measuring sockets for capacitive voltage indicator system
14 Vacuum circuit-breaker
15 Combined current and voltage sensor or current transformer
IEC Ratings
Rated voltage
kV
12/17.5
24
Special Ratings
36
Maximum operating voltage
kV Test voltages
kV
Rated frequency
Hz
50/60
50/60
50/60
50/60
A
…2500
…2500
…2500
…2500
Rated busbar current 2)
A
630
24
36
40.5
50/125
70/170
85/185
1250 ...2500
630
1250 . ..2500
…80
Rated peak withstand curren
kA 62.5 …100
62.5
…100
…100
…100
…31.5
Rated short-time current, 3s
kA 25 …40
25
…40
…40
…40
1250 ..2500
Rated current of feeder 2)
17.5
38/95
Internal Arc ClassificationIAC AFLR 40 kA 1s
1) 2)
with pressure relief duct
1)
1250 ...2500 1250 ...2500
1)
acc. to IEC 62271-200 | 2) Single busbar systems up to 4000 A on request
acc. to IEC 62271-200
ZX-Family Gas-insulated medium voltage switchgear
ZX-Family Gas-insulated medium voltage switchgear
ZX-Family Gas-insulated medium voltage switchgear
Gas-insulated switchgear
Flexible combination, reliability, availability and economy are
the attributes that make it easy for our clients in industry and
utilities to decide in favor of products from the ZX series.
Together with complete conventional solutions, the use of
digital protection and control technology, sensor systems
and plug-in connections makes ZX systems unrestrictedly
fit for the future, and the primary function of reliable power
distribution is fulfilled with no ifs and buts. This is ensured by
ABB’s uncompromising approach to quality, which leaves no
customer’s wishes unfulfilled.
- Systems in metal-enclosed design
- Hermetically sealed pressure systems –
gas-tight for life!
- SF6 insulating gas for guaranteed dielectric strength
- Metal partitioning between functions where necessary
- Plug-in technology for cables, busbars and
voltage transformers
- Enclosures in stainless steel
- Vacuum circuit-breakers
- Factory tested quality
A strong family for all situations in life.
Aligned to each need, the members of
the ZX family offer a solution for each
requirement. In over 70 countries the
customers rely on gas-insulated switchgears from ABB.
Contact us
ABB AG
Calor Emag Medium Voltage Products
Oberhausener Strasse 33
40472 Ratingen, Germany
Phone: +49(0)21 02/12-0
Fax:
+49(0)21 02/12-17 77
Email: [email protected]
ABB AG
Calor Emag Medium Voltage Products
Petzower Strasse 8
14542 Werder (Havel) OT Glindow, Germany
Phone: +49(0)21 02/12-0
+49(0)21 02/12-17 77
Fax:
Email: [email protected]
Note:
We reserve the right to make technical changes or
modify the contents of this document without prior
notice. With regards to purchase orders, the agreed
particulars shall prevail. ABB does not accept any
responsibility whatsoever for potential errors or possible lack of information in this document.
We reserve all rights to this document and in the
subject matter and illustrations contained therein
Any reproduction – in whole or in parts – is forbidden
without ABB’s prior written consent.
DEABB 2435 E (03.09-1000-AMC)
ZX-Family
Gas-insulated medium voltage switchgear
Copyright© 2009 ABB AG
All rights reserved.
www.abb.com/mediumvoltage
ZX-Family
Gas-insulated medium
voltage switchgear
ZX-Family Gas-insulated medium voltage switchgear
Gas-insulated switchgear
Flexible combination, reliability, availability and economy are
the attributes that make it easy for our clients in industry and
utilities to decide in favor of products from the ZX series.
Together with complete conventional solutions, the use of
digital protection and control technology, sensor systems
and plug-in connections makes ZX systems unrestrictedly
fit for the future, and the primary function of reliable power
distribution is fulfilled with no ifs and buts. This is ensured by
ABB’s uncompromising approach to quality, which leaves no
customer’s wishes unfulfilled.
- Systems in metal-enclosed design
- Hermetically sealed pressure systems –
gas-tight for life!
- SF6 insulating gas for guaranteed dielectric strength
- Metal partitioning between functions where necessary
- Plug-in technology for cables, busbars and
voltage transformers
- Enclosures in stainless steel
- Vacuum circuit-breakers
- Factory tested quality
A strong family for all situations in life.
Aligned to each need, the members of
the ZX family offer a solution for each
requirement. In over 70 countries the
customers rely on gas-insulated switchgears from ABB.
Contact us
ABB AG
Calor Emag Medium Voltage Products
Oberhausener Strasse 33
40472 Ratingen, Germany
Phone: +49(0)21 02/12-0
Fax:
+49(0)21 02/12-17 77
Email: [email protected]
ABB AG
Calor Emag Medium Voltage Products
Petzower Strasse 8
14542 Werder (Havel) OT Glindow, Germany
Phone: +49(0)21 02/12-0
+49(0)21 02/12-17 77
Fax:
Email: [email protected]
Note:
We reserve the right to make technical changes or
modify the contents of this document without prior
notice. With regards to purchase orders, the agreed
particulars shall prevail. ABB does not accept any
responsibility whatsoever for potential errors or possible lack of information in this document.
We reserve all rights to this document and in the
subject matter and illustrations contained therein
Any reproduction – in whole or in parts – is forbidden
without ABB’s prior written consent.
DEABB 2435 E (03.09-1000-AMC)
ZX-Family
Gas-insulated medium voltage switchgear
Copyright© 2009 ABB AG
All rights reserved.
www.abb.com/mediumvoltage
ZX-Family
Gas-insulated medium
voltage switchgear
ZX-Family Gas-insulated medium voltage switchgear