TEMPERATURE INDICATOR D A TA SHEET F040

TEMPERATURE INDICATOR
DATASHEET F040 - TEMPERATURE INDICATOR
WITH VERY LARGE DIGITS
Advantages
Signal input
• Robust IP67 (NEMA Type4X) field enclosure.
It is so rugged, you can even stand on it!
• Intrinsically Safe available - ATEX, IECEx, FM and
CSA approval for gas and dust applications.
• Programming can be done by your own crew, with
the sensible menu-driven structure, saving cost
and irritation. Know one, know them all!
• Very diverse mounting possibilities: walls, pipes,
panels or directly onto outdoor sensors!
Temperature
• PT100 - 2, 3 or 4 wire.
• (0)4 - 20mA.
• 0 - 10V DC.
Applications
• The F-Series is your first and safest choice for field
mount indicators in safe and hazardous area
applications. Especially in harsh weather
conditions like rain, snow, salty atmosphers and
temperatures between -40°C up to +80°C
(-40°F up to 176°F).
• Applications where a basic temperature
measurement display is required without
temperature monitoring. More sophisticated
models: F043, F140 and F143 or the D-Series
DIN panel mount indicators.
Features
•
•
•
•
•
•
•
•
•
Displays actual temperature and measuring unit.
Very large 26mm (1") digits.
Piegraph indication: ten segments.
Number of digits for temperature: 5 1/2 .
Selectable on-screen engineering units: °C-°F-K.
Auto backup of all settings.
Explosion/flame proof available.
LED backlight option.
Loop or battery powered, 8 - 24V AC/DC or
115 - 230V AC power supply.
• Sensor supply 8.2 / 12 / 24V DC.
1
General information
Signal input
Introduction
The F040 does accept (0)4 - 20mA and 0 - 10V
input signals from any type of temperature
measurement device. Also a two, three or four wire
PT100 sensor can be used. Thermocouple inputs
are in preparation.
The F040 is a straight forward temperature
indicator, displaying the actual value with its
measuring unit. The display is typically used as a
battery powered indicator for PT100 temperature
sensors but also often used with (0)4 - 20mA input
signals. The measuring unit to be displayed is
simply selected through an alfa-numerical
configuration menu.
No adhesive labels have to be put on the outside of
the enclosure: a weather proof and user friendly
solution!
The configuration of the Span, off-set and number
of decimals is done through software functions,
without any sensitive dip-switches or trimmers.
A wide selection of options further enhances the
capabilities of this model, including Intrinsic Safety
for hazardous area applications.
Power requirements
Several power supply options are available to
power the F040 and sensor.
A battery powered version with a long life lithium
battery which will last up to five years. A 4 - 20mA
input loop powered version is available as well. A
real sensor supply is offered with the 24V AC/DC
or 115 - 230V AC power requirement options.
Hazardous area
For hazardous area applications, this model has
been ATEX, IECEx, FM and CSA certified
Intrinsically Safe for gas and dust applications,
with an allowed ambient temperature of
-40°C to +70°C (-40°F to +158°F). A flame proof
Ex d enclosure with ATEX certification is also
available.
Display
The display has very large 26mm (1”) digits which
displays the temperature and measuring unit. As
the F040 has been designed for field mounted
applications, a smart display update function has
been incorporated: related to the lower ambient
temperature, the update frequency of the LCD is
tuned automatically to achieve a readable display
even at -40°C / -40°F.
Enclosures
Various types of enclosures can be selected, all
ATEX, IECEx, FM and CSA approved. As standard
the F040 is supplied in an GRP panel mount
enclosure, which can be converted to an IP67 /
NEMA Type4X GRP field mount enclosure by the
addition of a back case. Most popular is our
rugged aluminum field mount enclosure with IP67
/ NEMA Type4X rating. Both European or U.S.
cable gland entry threads are available.
Backlight
For those applications where readability during
day and night is an issue, a white backlight is
available. The intensity can be adjusted from the
keyboard. The display is a transflective type,
which means that a high contrast reading is
guaranteed in full sunlight as well as during the
night. This backlight option is also available
Intrinsically Safe.
Overview application F040
Configuration
All configuration settings are accessed via a
simple operator menu which can be password
protected. Each setting is clearly indicated with an
alphanumerical description, which avoids
confusing abbreviations. All settings are safely
stored in EEPROM memory in the event of sudden
power failure.
Temperature
input
2
F040
Dimensions enclosures
Terminal connections analog input
Power requirement PB/PC - PD - PL - PX
Aluminum & GRP panel mount enclosure
31 mm
(1.22")
TEMPERATURE INPUT
29 mm
(1.14")
BACKLIGHT
POWER REQUIREMENTS
120 mm (4.72")
130 mm (5.12")
115 (4.53")
02
98 (3.86")
01
04
03
T: PT100
See specific terminal layout.
A: (0)4 - 20mA
HB & HC enclosures
07
08
09
Aluminum & GRP field / wall mount enclosures
+
+
U+
For analog input
(type U): voltage as
connected to terminal 5.
A - PL: 4 - 20mA
10
ZB: 20 - 30V DC
For analog input
(type A): voltage as
connected to terminal 5.
U: 0 - 10V
+
PL: input loop powered.
I+
Ø 7mm (0.27")
Ø 7mm (0.27")
06
I+
panel cut-out
130 mm (5.12")
05
PD: 16 - 30V DC
120 mm (4.72")
PX: 8 - 30V DC
60 mm (2.36")
+
75 mm (2.95")
PB / PC: battery powered
(PX is also available: if an external supply is connected,
the battery supply will be switched off / on automatically.)
112 mm (4.40")
Aluminum
PG9
GRP
22,50mm
30mm 30mm
HD
M20 x 1,5 PG9
30mm 30mm
HL
HE
/2"NPT
1
Ø16
22,50mm
30mm 30mm
HM
01
Ø16
HF
M16 x 1,5
M20 x 1,5
Ø20
02
03
04
05
BACKLIGHT
06
07
08
09
10
ZB: 20 - 30V DC
PX: 8 - 30V DC
TP: PT100 2 - wire
22,50mm (0.9")
/ "NPT
1 2
POWER
REQUIREMENTS
TEMPERATURE INPUT
22,50mm
1.18"
0.9"
1.18"
M16 x 1,5
HA
Terminal connections PT100 input
Power requirement PB/PC - PX
+
+
TP: PT100 3 - wire
Ø22 ( 7/8")
HG
Ø20
M20 x 1,5
24mm 24mm
36mm
36mm
M20 x 1,5
M20 x 1,5
14mm
17mm
12mm 12mm
24mm 24mm
36mm
36mm
HP
Terminal connections analog / PT100 input
Power requirement PF
Ø12
30mm (1.18") 30mm (1.18")
HJ
6 x M12
POWER REQUIREMENTS
0.9"
HT
00
HK
0.9"
38mm
-
03
04
05
15mm
HV
TP: PT100 2 - wire
TP: PT100 3 - wire
4 x M20 x 1.5
TP: PT100 4 - wire
HZ
F040
3
06
07
+
+
+
+
U: 0 - 10V
+
PM: 115 - 230V AC
/2"NPT
15mm
/ "NPT
PF: 24V DC
HU
1
16mm
15mm
02
A: (0)4 - 20mA
PF: 24V AC
1.18" 1.18"
1 2
01
Flat bottom, no holes available.
/ "NPT
/ "NPT
TEMPERATURE INPUT
Ø22 ( 7/8") Ø22 ( 7/8") Ø22 ( 7/8")
1 2
1 2
PB / PC: battery powered
(PX is also available: if an external supply is connected,
the battery supply will be switched off / on automatically.)
17mm
HH
14mm
HO
TP: PT100 4 - wire
Ø20
12mm 12mm
25mm
22,50mm
25mm
22,50mm
HN
22,50mm (0.9")
22,50mm
25mm 25mm
Typical wiring diagram F040-T-PB
TERMINAL CONNECTORS
F0 - series
Typical wiring diagram F040-T-PX-ZB
Type PB:
BATTERY POWERED
Type PB:
BATTERY POWERED
TERMINAL CONNECTORS
F0 - series
10
09
06
09
06
8 - 30V DC
04
03
Temperature sensor
type T: PT100
01
01
02
02
03
Temperature sensor
type T: PT100
Sensor supply: not available.
Sensor supply: not available.
Typical wiring diagram F040-A-PX-ZB
TERMINAL CONNECTORS
F0 - series
Power supply type PX:
8 - 30V DC
05
Common ground
04
05
Main supply
20 - 30V DC
-
Power supply type PX:
8 - 30V DC
(not used in this example)
Backlight option: type ZB
+
Backlight supply
Common ground
-
10
+
Backlight option: type ZB
20 - 30V DC
(not used in this example)
Typical wiring diagram F040-A-PL-ZB
Type PL:
INPUT LOOP POWERED
TERMINAL CONNECTORS
F0 - series
Type PX:
BASIC 8 - 30V DC POWER REQUIREMENT
(STANDARD)
05
Common ground
04
Backlight option: type ZB
09
10
09
Main supply
Common ground
20 - 30V DC
-
Common ground
Backlight option: type ZB
20 - 30V DC
10
+
Backlight supply
Backlight supply
02
01
Common ground
01
Circuit depends on
type of signal
Signal
8 - 30V DC
-
02
Temperature input type A - PL:
Input loop powered 4 - 20mA
+
-
Circuit depends on
type of signal
+
8 - 30V DC
Temperature input type A:
(0)4 - 20mA
Signal
Common ground
Power supply type PX:
8 - 30V DC
Sensor supply: sensor is externally powered.
* Sensor supply voltage:
Terminal 3: not available.
4
F040
Typical wiring diagram F040-A-PD-ZB
TERMINAL CONNECTORS
F0 - series
Typical wiring diagram F040-A-PF-ZB
Type PD:
16 - 30V DC POWER REQUIREMENT
TERMINAL CONNECTORS
F0 - series
Type PF:
24V AC / DC POWER REQUIREMENT
* Sensor supply voltage:
Terminal 7: 8.2 / 12 / 24V DC.
Please note:
Power supply type PD is not available for temperature sensor type T PT100
Typical wiring diagram F040-A-PM-ZB
Type PM:
115 - 230V AC POWER REQUIREMENT
07
Supply *
Temperature input type A:
(0)4 - 20mA
Common ground
Power supply type PM:
115 - 230V AC
N
L1
00
01
Main supply
05
Common ground
06
Signal
02
Circuit depends on
type of signal
Backlight option: type ZB
Internally powered.
* Sensor supply voltage:
Terminal 7: 8.2 / 12 / 24V DC.
F040
07
Common ground
* Sensor supply voltage:
Terminal 3: not available.
Terminal 6 with type PD: voltage as connected to terminal 5 (internally linked).
TERMINAL CONNECTORS
F0 - series
06
01
02
Common ground
02
Main supply
Signal
00
05
04
Temperature input type A:
(0)4 - 20mA
01
Circuit depends on
type of signal
16 - 30V DC
5
Power supply type PF:
24V AC / DC
24V DC
-
Common ground
-
Main supply
Common ground
Sensor supply type PD:
16 - 30V DC
Temperature input type A:
(0)4 - 20mA
Signal
+
06
Supply *
Supply *
05
Circuit depends on
type of signal
09
Backlight option: type ZB
Internally powered.
+
Backlight supply
Common ground
10
Backlight option: type ZB
20 - 30V DC
Hazardous area applications
The F040-PD-XI offers the input voltage to
power an analog sensor. An ATEX approved
flame proof Ex d enclosure is available as well.
Please contact your supplier for further details.
The F040-XI has been certified according ATEX
and IECEx by KEMA and according CSA c-us and
FM for use in Intrinsically Safe applications with
an ambient temperature of -40°C to +70°C
(-40°F to +158°F).
• The ATEX markings for gas and dust
applications are:
II 1 G Ex ia IIC T4 Ga
II 1 D Ex ia IIIC T100 °C Da.
• The IECEx markings for gas and dust
applications are: Ex ia IIC T4 Ga and
Ex ia IIIC T100 °C Da.
• The CSA c-us markings are: Class I/II/III,
Division 1, Groups A, B, C, D, E, F, G,
Temperature class T4 and Class I, Zone 0,
AEx ia IIC T4.
• The FM markings are: Class I/II/III, Division
1, Groups A, B, C, D, E, F, G, Temperature
class T4 and Class I, Zone 0, AEx ia IIC T4.
It is allowed to connect up to three I.S. power
supplies to power the unit, sensor and backlight. Consult the certificate for the maximum
input and output values of the circuits.
Certificate of conformity KEMA 05ATEX1168 X
• IECEx KEM 08.0006X • CSA.08.2059461 X
CERTIFICATE OF CONFORMITY
1.
HAZARDOUS (CLASSIFIED) LOCATION ELECTRICAL EQUIPMENT PER US REQUIREMENTS
2.
Certificate No:
3.
Equipment:
(Type Reference and Name)
F0 Series General Purpose Indicators
4.
Name of Listing Company:
Fluidwell BV
5.
Address of Listing Company:
Voltaweg 23
5466 AZ Veghel
Netherlands
6.
The examination and test results are recorded in confidential report number:
7.
FM Approvals LLC, certifies that the equipment described has been found to comply with the following Approval
standards and other documents:
FM16US0177X
3033306 dated 25 June 2009
FM Class 3600:2011, FM Class 3610:2015, FM Class 3810:2005,
ANSI/UL 60079-0:2013, ANSI/UL 60079-11:2014, ANSI/IEC 60529:2004
8.
If the sign ‘X’ is placed after the certificate number, it indicates that the equipment is subject to specific
conditions of use specified in the schedule to this certificate.
9.
This certificate relates to the design, examination and testing of the products specified herein. The FM
Approvals surveillance audit program has further determined that the manufacturing processes and quality
control procedures in place are satisfactory to manufacture the product as examined, tested and Approved.
10.
Equipment Ratings:
Intrinsically Safe for use in Class I / II / III, Division 1, Groups A, B, C, D, E, F and G
Class I, Zone 0, Group IIC, Hazardous (Classfied) Locations
Certificate issued by:
20 September 2016
J. E. Marquedant
Manager, Electrical Systems
Date
To verify the availability of the Approved product, please refer to www.approvalguide.com
THIS CERTIFICATE MAY ONLY BE REPRODUCED IN ITS ENTIRETY AND WITHOUT CHANGE
FM Approvals LLC. 1151 Boston-Providence Turnpike, Norwood, MA 02062 USA
T: +1 (1) 781 762 4300 F: +1 (1) 781 762 9375 E-mail: [email protected] www.fmapprovals.com
F 347 (Mar 16)
Page 1 of 3
Configuration example IIA - IIB and IIC - F040-T-PC-XI - Battery powered unit
HAZARDOUS AREA
SAFE AREA
Backlight option: type ZB
(Not used in this example).
Power supply type PX: 8 - 30V DC
(Not used in this example).
Temperature sensor
type T: PT100
01
02
03
04
05
06
09
10
TERMINAL CONNECTORS
F0 - series
* Sensor supply voltage for analog temperature sensor type A / U: not available in this example.
Please note: type PX may be used in combination with the battery (type PC). PX will power the unit; the battery will be disabled automatically till power is disconnected.
6
F040
Configuration example IIA - IIB and IIC - F040-A-PD-XI-ZB - Power requirement 16 - 30V DC
HAZARDOUS AREA
TERMINAL CONNECTORS
F0 - series
SAFE AREA
+
10
Supply backlight
Backlight option: type ZB
-
05
+
Supply *
06
09
Common ground
Main supply
Power supply type PD: 16 - 30V DC
-
Power supply
Uo = max. 30V
Io = max. 200mA
Po = max. 1,2W
Power supply
For example
MTL 5525
For example
MTL 5525
I.S. temperature sensor - input type A: (0)4 - 20mA
Signal
02
Circuit depends on
type of signal
04
Common ground
Uo = max. 30V
Io = max. 200mA
Po = max. 0,75W
01
Common ground
Note: above values are safety values.
Consult the technical specification for operational values.
* Sensor supply voltage for analog temperature sensor type A / U: Terminal 6: as input voltage terminal 5 (internally linked).
Please note: type PD may be used in combination with the battery (type PC). PD will power the unit; the battery will be disabled automatically till power is disconnected.
Configuration example IIA - IIB and IIC - F040-A-PL-XI-ZB - Input loop powered
HAZARDOUS AREA
TERMINAL CONNECTORS
F0 - series
SAFE AREA
+
10
Supply backlight
Backlight option: type ZB
-
09
02
Signal
-
Circuit depends on
type of signal
I.S. temperature sensor - input type A - PL: 4 - 20mA input loop powered
+
Common ground
01
Common ground
Uo = max. 30V
Io = max. 200mA
Po = max. 0,75W
Power supply
Uo = max. 30V
Io = max. 93mA
Po = max. 0,92W
Power supply
For example
MTL 5525
For example
MTL 5525
Note: above values are safety values.
Consult the technical specification for operational values.
Sensor supply is not available: unit is input loop powered (type PL).
Please note: type PL may be used in combination with the battery (type PC). PL will power the unit; the battery will be disabled automatically till power is disconnected.
F040
7
Directives & Standards
Technical specification
EMC
Low voltage
RoHS
ATEX / IECEx
General
Display
Type
Dimensions
Digits
Piegraph
Refresh rate
Option ZB
High intensity reflective numeric and
alphanumeric LCD, UV-resistant.
90 x 40mm (3.5" x 1.6").
51/2 very large 26mm (1") digits.
Various symbols and measuring units.
Ten segments - related to the input signal.
User definable: fast, 1sec , 3sec, 15sec, 30sec, off.
Transflective LCD with white LED-backlight.
Intensitiy can be adjusted in the configuration menu.
Good readings in full sunlight and darkness.
Also available Intrinsically Safe.
FM
CSA
IP & NEMA
Directive 2014/30/EU, FCC 47 CFR part 15.
Directive 2014/35/EU.
Directive 2011/65/EU.
Directive 2014/34/EU, IEC 60079-0, IEC 60079-11,
IEC 60079-26.
FM Class No. 3600, FM Class No. 3610.
CSA 22.2 No. 157-92.
EN 60529 & NEMA 250.
Enclosure
General
Window
Sealing
Control keys
Ambient temperature
Safe areas
-40°C to +80°C (-40°F to +176°F).
Intrinsically Safe -40°C to +70°C (-40°F to +158°F).
Polycarbonate window.
Silicone.
Three industrial micro-switch keys. UV-resistant
silicone keypad.
Aluminum wall / field mount enclosures
General
Power requirements
Type PB
Long life Lithium battery - life-time depends upon
settings and configuration - up to 5 years.
(requires PD, PL or PX)
Type PC
Intrinsically Safe long life lithium battery - life-time
depends upon settings and configuration - up to 5
years. (requires XI, and PD, PL or PX)
Type PD
16 - 30V DC. Power consumption max. 1 Watt.
Type PF
24V AC / DC ± 10%. Power consumption max. 15 Watt.
Type PL
Input loop powered from sensor signal 4 - 20mA
(type A).
Type PM
115 - 230V AC ± 10%. Power consumption max. 15 Watt.
Type PX
8 - 30V DC. Power consumption max. 0.3 Watt.
Type ZB
20 - 30V DC. Power consumption max. 1 Watt.
With type PF / PM: internally powered.
Note PB/PF/PM Not available Intrinsically Safe.
Note PF/PM
The total consumption of the sensor and backlight
type ZB may not exceed 400mA @ 24V DC.
Note
For Intrinsically Safe applications, consult the safety
values in the certificate.
Dimensions
Weight
Type HA
Type HL
Type HM
Type HN
Type HO
Type HP
Type HT
Type HU
Type HV
Type HZ
GRP wall / field mount enclosures
General
Dimensions
Weight
Type HD
Type HE
Type HF
G
Type H
Type HH
Type HJ
Type HK
Sensor excitation
Type PB/PC/PX
Type PD
Type PF / PM
Note
Not available, just suitable for PT100 sensors.
The sensor supply voltage will be according to power
supply voltage (as connected to terminal 5).
8.2 / 12 and 24V DC - max. 400mA @ 24V DC.
There is no sensor supply available for PT100 sensors.
Terminal connections
Type
Dimensions
Panel cut-out
Type HB
Password
GRP wall/field mount enclosure IP67 / NEMA Type4X,
UV-resistant and flame retardant.
130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.
600 gr.
Cable entry: no holes.
Cable entry: 2 x Ø 16mm and 1 x Ø 20mm.
Cable entry: 1 x Ø 22mm (7/8").
Cable entry: 2 x Ø 20mm.
Cable entry: 6 x Ø 12mm.
Cable entry: 3 x Ø 22mm (7/8").
Flat bottom, cable entry: no holes.
Panel mount enclosures
Removable plug-in terminal strip.
Wire max. 1.5mm2 and 2.5mm2.
Data protection
Type
Die-cast aluminum wall/field mount enclosure IP67 /
NEMA Type4X with 2-component UV-resistant coating.
130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.
1100 gr.
Cable entry: 2 x PG9 and 1 x M20.
Cable entry: 2 x 1/2" NPT.
Cable entry: 2 x M16 and 1 x M20.
Cable entry: 1 x M20.
Cable entry: 2 x M20.
Cable entry: 6 x M12.
Cable entry: 1 x 1/2" NPT.
Cable entry: 3 x 1/2" NPT.
Cable entry: 4 x M20.
Cable entry: no holes.
EEPROM backup of all settings. Data retention at
least 10 years.
Configuration settings can be password protected.
Weight
Type HC
Weight
8
130 x 120 x 60mm (5.12" x 4.72" x 2.36") - W x H x D.
115 x 98mm (4.53" x 3.86") L x H.
Die-cast aluminum panel mount enclosure IP65 /
NEMA Type4X.
600 gr.
GRP panel mount enclosure IP65 / NEMA Type4X,
UV-resistant and flame retardant.
450 gr.
F040
Hazardous area
Intrinsically Safe
ATEX
certification
IECEx
certification
CSA c-us
certification
FM certification
Ambient Ta
Accessories
Mounting accessories
II 1 G Ex ia IIC T4 Ga.
II 1 D Ex ia IIIC T100 °C Da.
Ex ia IIC T4 Ga.
Ex ia IIIC T100 °C Da.
Intrinsically Safe for Class I/II/III, Div. 1,
Groups A, B, C, D, E, F, G, Temp. class T4
and Class I, Zone 0, AEx ia IIC T4.
Intrinsically Safe for Class I/II/III, Div. 1,
Groups A, B, C, D, E, F, G, Temp. class T4
and Class I, Zone 0, AEx ia IIC T4.
-40°C to +70°C (-40°F to +158°F).
ACF02
ACF05
ACF06
ACF07
ACF08
ACF09
ACF11
Cable glands
ACF20
ACF25
ACF26
ACF27
ACF28
ACF29
ACF32
ACF33
ACF34
ACF35
ACF39
ACF40
Explosion proof
ATEX certification
Type XF
Weight
Note
Stainless steel wall mounting kit.
Stainless steel pipe mounting kit (worm gear clamps
not included).
Two stainless steel worm gear clamps Ø 44 - 56mm.
Two stainless steel worm gear clamps Ø 58 - 75mm.
Two stainless steel worm gear clamps Ø 77 - 95mm.
Two stainless steel worm gear clamps Ø 106 - 138mm.
Swivel with 25° movement from center axis for direct
flowmeter mounting: 1” NPT to 1/2” NPT.
II 2 G / Ex d IIB T5 Gb.
II 2 D / Ex t IIIB T100 °C Db.
Dimensions of enclosure: 300 x 250 x 200mm
(11.8" x 9.9" x 7.9") L x H x D.
Appr. 15kg.
IECEx available on request.
Signal inputs
Temperature
Resolution: 16 bit. Error < 0.01mA / ± 0.05% FS.
Low level cut-off programmable.
Type A
(0)4 - 20mA. Analog input signal can be scaled to
any desired range within 0 - 20mA.
Span
0.00001 - 199,999 with variable decimal position.
Offset
-99,999 / +199,999 units.
Voltage drop
Type A: max. 1V DC @ 20mA.
Voltage drop
Type A - PL (loop powered): max. 2.6V DC @ 20mA.
Update time
Four times per second.
Type T
2, 3 or 4 wire PT100 (requires PB, PC or PX).
Offset
-999.9 / +999.9 units.
Update time
Once per second.
Range
-100°C to +200°C (-148°F to 392°F).
Accuracy 0.1°C (0.2°F).
Type U
0 - 10V DC. Analog input signal can be scaled to
any desired range within 0 - 10V DC.
Span
0.00001 - 199,999 with variable decimal position.
Offset
-99,999 / +199,999 units.
Load impedance 3kOhm.
Update time
Four times per second.
Note
For signal A and U: power supply to temperature
sensor is required; e.g. PD.
Accuracy
For HA enclosure, includes O-rings.
For HE enclosure, includes locknuts and O-rings.
For HF enclosure, includes locknuts and O-rings.
For HG enclosure, includes locknuts and O-rings.
For HH enclosure, includes locknuts and O-rings.
For HJ enclosure, includes locknuts and O-rings.
For HM enclosure, includes O-rings.
For HN enclosure, includes O-rings.
For HO enclosure, includes O-rings.
For HP enclosure, includes O-rings.
For HT enclosure, includes O-rings.
For HU enclosure, includes O-rings.
Intrinsically Safe isolators
ACG01
ACG02
ACG03
ACG04
ACG05
ACG06
ACG07
MTL5511 - One channel pulse or switch output
transfer from hazardous area to safe area.
MTL5525 - One channel power supply from safe area
to hazardous area (e.g. to power the unit with PD or
to power a switching or analog device in hazardous
area).
MTL5541 - One channel 4 - 20mA repeater from
hazardous area to safe area.
MTL 5051 - Bi-direction serial-data-isolator
(for Modbus communication).
MTL5516C - Two channel pulse or switch output
transfer from hazardous area to safe area.
MTL5513 - One channel pulse or switch output
transfer from hazardous area to safe area.
MTL5546Y - One channel isolated driver bringing
4 - 20mA from safe area to hazardous area, HART
transparent, OCD.
Display example - 90 x 40mm (3.5" x 1.6")
Operational
Operator functions
Displayed
functions
• Actual temperature.
• Measuring unit.
Temperature
Digits
Units
Decimals
F040
51/2 digits.
°C, °F or K.
Type T: 1.
Type A / U: 0 - 1 - 2 - 3 - 4 or 5.
9
Ordering information
Standard configuration: F040-A-HC-PX-XX-ZX.
ordering information:
Temperature input signal
A
T
U
F040
-_
-H _
-P _
-X _
-Z _
(0)4 - 20mA input.
PT100 input - requires PX.
0 - 10V DC input.
Panel mount enclosures - IP65 / NEMA Type4X
HB
HC
Aluminum enclosure.
GRP enclosure.
GRP field / wall mount enclosures - IP67 / NEMA Type4X
HD
HE
HF
G
H
HH
HJ
HK
Cable entry: no holes.
Cable entry: 2 x Ø 16mm & 1 x Ø 20mm.
Cable entry: 1 x Ø 22mm (7/8”).
Cable entry: 2 x Ø 20mm.
Cable entry: 6 x Ø 12mm.
Cable entry: 3 x Ø 22mm (7/8”).
Flat bottom, cable entry: no holes.
Aluminum field / wall mount enclosures - IP67 / NEMA Type4X
HA
HL
HM
HN
HO
HP
HT
HU
HV
HZ
Cable entry: 2 x PG9 + 1 x M20.
Cable entry: 2 x 1/2”NPT.
Cable entry: 2 x M16 + 1 x M20.
Cable entry: 1 x M20.
Cable entry: 2 x M20.
Cable entry: 6 x M12.
Cable entry: 1 x 1/2”NPT.
Cable entry: 3 x 1/2”NPT.
Cable entry: 4 x M20.
Cable entry: no holes.
Power requirements
PD
PF
PL
PM
PX
16 - 30V DC + sensor supply.
24V AC / DC + sensor supply.
Input loop powered from sensor signal 4 - 20mA (type A).
115 - 230V AC + sensor supply.
Basic power supply 8 - 30V DC (no sensor supply for type A/U sensors).
PB
PC
Lithium battery powered - requires PD, PL or PX.
Lithium battery powered - Intrinsically Safe - requires XI, and PD, PL or PX.
Additional battery supply (optional)
Hazardous area
XI
XF
XX
Intrinsically Safe, according ATEX, IECEx, CSA c-us and FM.
Ex d enclosure - 3 keys according ATEX.
Safe area only.
Other options
ZB
ZX
Backlight.
No options.
The bold marked text contains the standard configuration.