110P-Type Terminal Block Instructions

110P-Type Terminal Block Instructions
General
The 110P-type patch panel system terminal blocks are used to terminate raw-ended cable pairs.
Ordering information is listed below:
Ordering No.
107058810
107058869
107058802
107058851
Catalog No.
110PB2-300FT
110PB2-900FT
110PA2-300FT
110PA2-900FT
Description
110 field terminated block, 4-pair, 300-pair count
110 field terminated block, 4-pair, 900-pair count
110 field terminated block, 5-pair, 300-pair count
110 field terminated block, 5-pair, 900-pair count
How to Contact Us
•
To find out more about CommScope® solutions, visit us on the web at http://www.commscope.com/
•
For customer support regarding CommScope products, contact your local account representative or call 1800-544-1948 or (828) 459-5000.
Instruction Sheet 847265295
Issue 7, May 2010
© 2010 CommScope, Inc.
All rights reserved
Page 1
5 Pages
Step 1 – Mount Terminal Block Panels
Note:
Align screw locations
horizontally and vertically
Mounting screws
Terminal block
panels
7-5/8”
7-5/8”
7-5/8”
7-5/8”
(194 mm) (194 mm) (194 mm) (194 mm)
*
*
*
Horizontal
line
Insert four
screws for
panel 1
Panel
4
Panel
2
68”
(1.73 m)
110A
brackets
68”
(1.73 m)
Horizontal
line
*
*
*
17-1/2”
(445 mm)
17-1/2”
(445 mm)
Mounting screws
* 3-3/16” (81 mm) space between panels
Wall Mounting
Bracket Mounting
7-5/8”
(194 mm)
Note:
Wall screws should be mounted
7-5/8” (194 mm) apart to accommodate
panel mounting brackets
Bottom panel
mounting brackets
Optional holes
Bottom Rear View of Terminal Block Panel
Wall Mounting
1. For 900-pair size installations, make two horizontal lines on the mounting surface, one at 68 inches
(1.73 m) and one at 17-1/2 inches (445 mm) above floor. For 300-pair size installations, make one
horizontal line on the mounting surface 60 inches (1.52 m) and one at 47-1/2 inches (1.21 m) above
floor. Mark location for screws as shown above.
2. Partially insert four No. 12 x 3/4” round head wood screws (not provided) for each terminal block
panel to be mounted. Two on the top and two on the bottom.
3. Position terminal block panel on screws and tighten screws to secure panel to wall.
Page 2
5 Pages
847265295
Instruction Sheet
Bracket Mounting
1. Attach each 110A mounting bracket to wall 68 inches (1.73 m) and 17-1/2 inches (445 mm) above the
floor using four No. 12 x 3/4” round head wood screws (not provided).
2. Position terminal block panel so that slots in hanger are seated on detents in the 110A bracket.
Step 2 – Prepare Cable
O-W Binder Group
BL-W Binder Group
1
Bond Strap
8-32 X 3/8 Screw
8-32 Nut
2
Wire
Panel
3
4
O-W
Binder
Group
BL-W
Binder
Group
Note:
Nut and screw with captive lock
washer may be substituted
1. Position cable and remove outer sheath starting above terminal block panel.
2. Install D-bond clamp as shown in the insert above and in instructions available on the
CommScope website (860370451). Attach bond strap to terminal block panel with screws, nut,
and washers supplied.
3. Separate binder groups and dress in slots from top to bottom of terminal block panel (BL-W top
left, O-W top right, etc.) in color-code sequence.
4. Secure cable to back of panel with cable ties at the top and at each group of four binder groups.
847265295
Issue 7, May 2010
Page 3
5 Pages
Step 3 – Install Wiring Blocks
Terminal
block
panel
Note: Cable not shown
for clarity.
Wiring block
1
Plastic
rivet
4
3. Place the conductors in the index strip
following the even-count color code.
Binder groups entering from the left are
terminated on the top index strip and
binder groups entering from the right
are terminated on the bottom.
3
788H1
impact
tool
2
1. Position wiring block on terminal block panel and
secure with two plastic rivets. Repeat until all
wiring blocks are in place.
2. Dress the binder groups through the cable slots
in the wiring blocks.
4. Seat and cut conductors using 788H1
Impact Tool. (Exercise care to prevent
cutting the wrong side.) Remove cut
conductor and check to make sure no
short pieces of cut conductors are
wedged in the wiring slot.
Step 4 – Install Connecting Blocks
1. Position appropriate connecting blocks
(see table) in index strip (slate down)
and seat using 788H1 tool.
Circuit
Pair
Count
2
1
3
2 or 4
Quantity of Connecting Blocks
Per Index Strip
3-Pair
4-Pair
7
1*
5-Pair
1*
5
5
1 or 5
* located at far right end of index strip
2. Position jumper trough between wiring
blocks and secure with two plastic rivets.
Page 4
5 Pages
847265295
Instruction Sheet
Step 5 – Complete Installation
188C3 or 188D3
backboard
Field terminated
terminal block
2
3
Duct assembly
Typical Layout
1.
2.
3.
4.
Continue installation of terminal blocks as required.
Mount 188C3 or 188D3 backboards as required.
Install duct assemblies at bottom of field terminated terminal blocks.
Slide the appropriate paper inserts into the designation strips and install on wiring blocks. Two
are required for each 100-pair wiring block.
5. (Not shown) Determine the proper length patch cord and place the patch cord in its appropriate
location.
Note: In locations where there are floor cables, the 3-pair cord must be placed on the first 3 pairs of the
4-pair. Floor cord is inserted into the fourth pair location.
847265295
Issue 7, May 2010
Page 5