Three Conductor SER

spec
P.O. Box 368, Union, NJ O7O83-O368, 9O8-687-781O, 8OO-327-2443, Fax: 9O8-687-886O
®
SER
THREE CONDUCTOR SER
ALUMINUM, XLPE INSULATED 600V
90°C WET OR DRY
®
APPLICATION:
SER is used as a service entrance cable, to convey power from
the service drop to the meter. It may also be used in other
branch circuits or feeders as permitted by the NEC. SER is rated
for 600V not to exceed 90°C wet and dry. Single conductors are UL Listed Types XHHW/XHHW-2. The cable is rated
Sunlight Resistant for CT Use.
CONSTRUCTION:
Three insulated conductors with a bare 8000 aluminum alloy
neutral, and a reinforcement tape.
Conductors:
Stranded aluminum alloy (AA-8176) compacted conductor
Class B stranding per ASTM B 801
Insulation:
Black thermoset flame retardant cross-linked polyethylene (XLPE)
Neutral:
Bare aluminum 8000 alloy
Jacket:
Sunlight resistant grey polyvinyl chloride (PVC)
STANDARDS:
• UL 854: Service-Entrance Cables
• UL 44: Rubber-Insulated Wires and Cables
*Also available in four conductor construction
* Ampacities shown are for general use as specified by the National Electrical Code, 2011 Edition, Article 310.15
Article 310.15All data subject to change without notice.