ABBREVIATIONS ELECTRICAL SYMBOLS LIST GENERAL NOTES

1.
THE SUBMISSION OF A BID BY THE ELECTRICAL CONTRACTOR IS NOTIFICATION THAT THE ELECTRICAL
CONTRACTOR HAS TOTALLY FAMILIARIZED HIMSELF WITH THE CONTRACT DOCUMENTS AND EXISTING SITE
CONDITIONS AND HAS AGREED TO PROVIDE THE NECESSARY LABOR AND MATERIAL FOR THE COMPLETE
INSTALLATION OF EACH SYSTEM IN A NEAT AND WORKMANLIKE MANNER IN ACCORDANCE WITH THE BEST
PRACTICES OF THE INDUSTRY AND IN COMPLIANCE WITH ALL AUTHORITIES HAVING JURISDICTION.
MANHOLE
KEY NOTE
FLOOR MOUNTED METAL SUPPORT FRAME FOR ELECTRICAL ENCLOSURES
VFD
NEW EMERGENCY CIRCUIT
30/3
2.
THESE DRAWINGS ARE PRESENTED TO THE ELECTRICAL CONTRACTOR WITH THE UNDERSTANDING THAT
THE ELECTRICAL CONTRACTOR IS AN EXPERT AND COMPETENT IN THE PREPARATION OF CONTRACT BID
PRICES ON THE BASIS OF INFORMATION SUCH AS IS CONTAINED IN THESE DOCUMENTS. IT IS THE INTENT
OF THE DRAWINGS AND SPECIFICATIONS TO CALL FOR FINISHED WORK, TESTED AND READY FOR
OPERATION AND IN COMPLETE CONFORMANCE WITH ALL APPLICABLE CODES, RULES, AND REGULATIONS.
MINOR ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT MANIFESTLY NECESSARY FOR THE PROPER
INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS, SHALL BE INCLUDED IN THE WORK AND IN THE
PROPOSAL THE SAME AS IF SPECIFIED OR SHOWN ON THE DRAWINGS. IF ANY DEPARTURES FROM THE
DRAWINGS ARE DEEMED NECESSARY, DETAILS OF SUCH DEPARTURES AND THE REASONS THEREFORE
SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT
PRIOR APPROVAL OF SEPTA.
UNFUSED DISCONNECT SWITCH
<SWITCH AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED
NEW LOW VOLTAGE/CONTROL WIRING
100/60/3
FUSED DISCONNECT SWITCH
<SWITCH AMPS>/<FUSE AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED
60/30/3
ST
ENCLOSED CIRCUIT BREAKER
<FRAME AMPS>/<TRIP AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED
ST = SHUNT TRIP
NEW GROUND CABLE
EQUIPMENT PROVIDED BY OTHERS
UNDERGROUND SECONDARY CABLE
SHOWN HERE FOR REFERENCE ONLY. SEE CIVIL PLANS
208/120V DISTRIBUTION PANELBOARD
SURFACE MOUNTED
JUNCTION BOX
MOUNTED ABOVE SUSPENDED CEILING / FLUSH WALL
INSTALLED WITHIN 2' OF EQUIPMENT AND CONNECTED
VAV = DEDICATED TO VARIABLE AIR VOLUME BOX CONTROL
SD = DEDICATED TO SMOKE DAMPER
MD = DEDICATED TO MOTORIZED VOLUME DAMPER
UH = UNIT HEATER
EWC = ELECTRIC WATER COOLER
DMO = DOOR MOTOR OPERATOR
MOTOR RATED TOGGLE SWITCH, 20A SINGLE POLE, UON
HORSEPOWER RATED WITH OVERLOAD PROTECTION.
15 or 20A, 125V QUADRUPLEX RECEPTACLE
FLUSH WALL MOUNTED @ 18" AFF, UON
480/277V PANELBOARD
FLUSH MOUNTED
RISER / SINGLE LINE SYMBOLS
460V
POWER TRANSFORMER
500KVA
VOLTAGES, WINDINGS AND SIZE AS INDICATED
208/120V
ATS
100A
480V,4P
DROP CORD RECEPTACLE
CEILING MOUNTED
SPECIAL PURPOSE RECEPTACLE. NEMA TYPE AS INDICATED
FLUSH WALL MOUNTED @ 18" AFF, UON
3 PHASE SPECIAL PURPOSE RECEPTACLE. NEMA TYPE AS INDICATED
FLUSH WALL MOUNTED @ 18" AFF, UON
JUNCTION BOX OR POKE-THRU WITH COMBINATION POWER/DATA
FLUSH FLOOR MOUNTED REFER TO DETAIL ON DRAWING E002
20A, 125V DUPLEX RECEPTACLE
FLUSH CEILING MOUNTED
CAPPED CONDUIT
CONDUIT WITH BUSHING
HOMERUN-NUMERAL WHERE USED INDICATES DESIGNATED PANEL AND CIRCUIT
NUMBER FOR REFERENCE ONLY. WHERE CONDUIT IS NOT SPECIFIED USE AC
OR MC CABLE FOR APPLICATION.
2#12, #12G, 3/4"C HOMERUN, UON
3#12, #12G, 3/4"C HOMERUN, UON
4#12, #12G, 3/4"C HOMERUN, UON
AT 120V AND OVER 100' CIRCUIT LENGTH PROVIDE #10 MINIMUM.
AT 277V AND OVER 200' CIRCUIT LENGTH PROVIDE #10 MINIMUM.
SPLICE (JUNCTION) OF PATHS OF CONDUCTORS OR CABLES.
CARD READER, PROVIDE 2"x4" JUNCTION BOX
WALL MOUNTED @ 42" AFF UON ON NON-SECURED SIDE OF DOOR
ELECTRIC DOOR STRIKE
20.
ELECTRICAL CONTRACTOR SHALL SIMILARLY NOTIFY ENGINEER OF COMPLETION OF ALL WORK,
INDICATING THE ELECTRICAL CONTRACTOR IS READY FOR THE ENGINEER TO PERFORM THE FINAL
PUNCHLIST INSPECTION.
21.
UPON COMPLETION OF ALL UNFINISHED OR FAULTY WORK NOTED IN ENGINEER FINAL PUNCH LIST, THE
ELECTRICAL CONTRACTOR SHALL SUBMIT TO THE ENGINEER IN WRITING A LETTER OF COMPLETION
CERTIFYING THAT ALL PUNCH LIST ITEMS HAVE BEEN COMPLETED AND ALL AS-BUILTS, MANUALS, ETC.
HAVE BEEN SUBMITTED.
22.
SHOULD A CONTRACTOR REQUIRE REMOVAL, RELOCATION, OR REROUTING OF ANOTHER TRADE'S WORK
THAT IS NOT INDICATED ON DRAWINGS, THE CONTRACTOR REQUIRING SUCH WORK SHALL BE
RESPONSIBLE FOR THAT WORK, AND PAY ALL REQUIRED COSTS.
23.
ALL WORK INVOLVING ALTERATIONS TO EXISTING SYSTEMS, EQUIPMENT, AND MATERIALS SHALL BE
REVIEWED WITH THE PROJECT MANAGER AND SEPTA BEFORE BEGINNING WORK.
24.
DEFINITION: UNLESS OTHERWISE NOTED, ALL WORK SPECIFIED HEREIN OR NOTED ON DRAWINGS, SHALL
BE BY THE ELECTRICAL CONTRACTOR. ALL REFERENCES TO "CONTRACTOR" OR "THIS CONTRACTOR" ON
DRAWINGS OR SPECIFICATIONS ARE ADDRESSED TO THE ELECTRICAL CONTRACTOR. THE TERM
"PROVIDE" WHENEVER ENCOUNTERED ON DRAWINGS OR IN THESE SPECIFICATIONS, SHALL MEAN
"FURNISH AND INSTALL."
25.
CODES AND STANDARDS: ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE NATIONAL
ELECTRIC CODE, ALL APPLICABLE CODES, SPECIFICATIONS, LOCAL ORDINANCES, INDUSTRY STANDARDS,
UTILITY COMPANY REGULATIONS AND FIRE INSURANCE CARRIER'S REQUIREMENTS.
26.
MATERIALS: ALL MATERIALS FURNISHED BY THIS CONTRACTOR, SHALL BE NEW AND BEAR THE LABEL OR
LISTING OF A NATIONALLY RECOGNIZED INDEPENDENT TESTING LABORATORY.
ELECTRICAL CONTRACTOR SHALL SECURE AND PAY ALL FEES, LICENSES, INSPECTIONS, AND PERMITS
PERTAINING TO THE CONTRACT. SUBMIT TO SEPTA DUPLICATE CERTIFICATES OF INSPECTION FROM
APPROVED INSPECTION AGENCY.
27.
OUTLET AND SWITCH BOXES: PROVIDE AND INSTALL OUTLET BOXES OF PROPER TYPE AND SIZE AS
REQUIRED AT ALL OUTLETS WHERE SHOWN. SECURED FIRMLY IN PLACE AND SET TRUE AND SQUARE AND
FLUSH WITH THE FINISHED SURFACE.
8.
ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER'S WRITTEN
INSTRUCTIONS.
28.
INSTALLATION OF RACEWAYS: ALL RACEWAYS SHALL BE INSTALLED CONCEALED. NO SURFACE RACEWAY
WILL BE ACCEPTED IN FINISHED AREAS.
9.
ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WORKMEN'S IDENTIFICATION AND BADGING,
SAFETY AND FIRE PROTECTION, BARRICADES, WARNING SIGNS, TRASH REMOVAL, CUTTING AND
PATCHING.
29.
WIRING: WIRING OF BRANCH CIRCUITS SHALL BE TYPE THHN/THWN IN RIGID GALVANIZED STEEL CONDUIT
RACEWAYS ARE SHOWN DIAGRAMMATICALLY, EXACT LOCATION TO BE DETERMINED ON THE JOB. EXACT
LOCATION OF OUTLETS TO BE DETERMINED BY SEPTA. CONTRACTOR SHALL ARRANGE ALL NEW CIRCUITS
IN PANELS SO AS TO BALANCE THE LOAD ON ALL PHASES. EXPOSED CONDUIT IN UNFINISHED AREAS
SHALL BE EMT. CONDUIT DIRECTLY BURIED UNDERGROUND SHALL BE SCHEDULE 40 PVC WITH RGS
ELBOWS AND STUB UPS.
10.
ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL RIGGING, HANDLING, AND PROTECTION OF
MATERIALS. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND WITHOUT BLEMISH OR DEFECT. ALL
EQUIPMENT INSTALLED SHALL BEAR THE LABEL OF AN APPROVED AGENCY.
11.
ELECTRICAL CONTRACTOR SHALL PROVIDE LABOR TO RECEIVE, UNLOAD, STORE, PROTECT, AND
TRANSFER TO POINT OF INSTALLATION FOR ALL FURNISHED ITEMS.
30.
A TYPED DIRECTORY CARD SHALL BE PROVIDED IN EACH PANEL WITH ADDED CIRCUITS TO INDICATE THE
LOADS ACTUALLY SERVED.
12.
WHERE CONDUIT, CABLES, DUCTWORK, OR PIPING PASSES THROUGH FIRE RATED FLOORS OR WALLS, THE
PENETRATION SHALL BE COMPLETELY SEALED WITH A FIRE STOP MATERIAL THAT IS UL LISTED, FM
GLOBAL APPROVED (WWW.FMGLOBAL.COM/PAGE.ASPX?ID=50030000) AND ACCEPTED BY THE BUILDING
DEPARTMENT AND FIRE DEPARTMENT AS BEING SUITABLE FOR THIS SERVICE. THIS MATERIAL SHALL BE
INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER TO MAINTAIN THE UL
LISTED FIRE RATING OF THE PENETRATED WALL OR FLOOR.
31.
PROVIDE NEW FIXTURES AS SPECIFIED ON LIGHTING FIXTURE SCHEDULE. ALL NEW LED LAMPS SHALL BE
3500K.
32.
GROUNDING: SHALL BE IN STRICT ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE ARTICLE 250.
PROVIDE GROUND WIRES AS REQUIRED AND RESIZE CONDUIT IF NECESSARY.
33.
DEMONSTRATION OF COMPLETE ELECTRICAL SYSTEMS: UPON COMPLETION OF THE WORK THIS
CONTRACTOR SHALL OBTAIN A CERTIFICATE OF APPROVAL FROM ALL RECOGNIZED AGENCIES
CONCERNED WITH THE WORK. CONTRACTOR SHALL NOTIFY AND MAKE ALL THE NECESSARY
ARRANGEMENTS WITH THE INSPECTING AGENCY AND LOCAL AUTHORITIES SO THAT INSPECTION MAY BE
CARRIED OUT AT THE PROPER TIME.
34.
PROJECT MUST MEET FM GLOBAL STANDARDS (WWW.FMGLOBAL.COM/)
CURRENT TRANSFORMER
13.
ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SLAB OPENINGS, WALL OPENINGS, BEAM
PENETRATIONS, AND CORING AS IT RELATES TO HIS WORK. ELECTRICAL CONTRACTOR SHALL SUBMIT SIZE
AND LOCATION FOR REVIEW AND APPROVAL.
14.
ALL EXTERIOR WALL OPENINGS SHALL BE SLEEVED, PROPERLY CAULKED, AND SEALED WITH A HIGH
QUALITY SEALANT TO PREVENT INFILTRATION OF MOISTURE AND OUTSIDE AIR.
15.
CONTRACTOR SHALL SUBMIT SCHEDULE OF SUBMITTALS PRIOR TO SUBMITTING ANY SHOP DRAWINGS,
ETC. TO BE SUBMITTED FOR THIS PROJECT, INCLUDING THE ANTICIPATED DATE OF EACH SUBMISSION.
CONTRACTORS SHALL SUBMIT (6) SETS OF COMPLETE SHOP DRAWINGS AND CATALOG CUTS, WIRING
DIAGRAMS AND ASSOCIATED DATA TO THE PROJECT MANAGER FOR APPROVAL PRIOR TO PURCHASING
EQUIPMENT OR STARTING ANY WORK. ANY WORK INSTALLED OR EQUIPMENT PURCHASED PRIOR TO
RECEIPT OF PROJECT MANAGER APPROVED SHOP DRAWINGS THAT REQUIRES CHANGES SHALL BE
REPLACED AT CONTRACTOR'S EXPENSE.
16.
SUBMIT CATALOG INFORMATION, FACTORY ASSEMBLY DRAWINGS AND FIELD INSTALLATION DRAWINGS AS
REQUIRED FOR A COMPLETE EXPLANATION AND DESCRIPTION OF ALL ITEMS TO BE PROVIDED. THE
ELECTRICAL CONTRACTOR SHALL REVIEW AND APPROVE ALL SHOP DRAWINGS. NO SUBMISSION WILL BE
ACCEPTED WITHOUT THE SIGNED APPROVAL OF THE ELECTRICAL CONTRACTOR. THE ELECTRICAL
CONTRACTOR SHALL CHECK AND VERIFY ALL FIELD MEASUREMENTS.
17.
UPON COMPLETION OF CONSTRUCTION, CONTRACTOR SHALL SUPPLY THE PROJECT MANAGER WITH (1)
METER
ELECTRICALLY HELD UL LISTED RELAY FOR EMERGENCY LIGHTING.
LIGHTING SHALL BE CONTROLLED BY SWITCH UNDER NORMAL POWER
CONDITION FROM NORMAL SOURCE. IN EMERGENCY MODE THE RELAY
SHALL ENABLE THE DEDICATED LIGHTING TO BE SWITCHED TO THE
EMERGENCY SOURCE FOR FULL OPERATION. PROVIDE BODINE BALLAST
#GTD OR SIMILIAR.
VOICE / DATA SYMBOLS
VOICE/DATA OUTLET
FLUSH WALL MOUNTED @ 18" AFF UON, WITH 3/4" CONDUIT IN DEMISING WALL,
LIGHTING SYMBOLS
LIGHTING FIXTURES. REFER TO "LIGHTING FIXTURE SCHEDULE".
ABBREVIATIONS
CB
CIRCUIT BREAKER
FLEX
FLEXIBLE
CCTV
CLOSED CIRCUIT TELEVISION
FMC
FLEXIBLE METAL CONDUIT
(NOT ALL ABBREVIATIONS ARE NECESSARILY
USED ON THIS PROJECT)
CD
CANDELA
G
GROUND
PNL
PANEL
CL
CEILING MOUNT
GFI
GROUND FAULT INTERRUPTER
PVC
POLYVINYL CHLORIDE CONDUIT
CKT
CIRCUIT
GRC
GALVANIZED RIGID CONDUIT
PWR
POWER
PB
PULL BOX
PHASE
+
MOUNTING HEIGHT ABOVE FINISHED FLOOR
COORDINATE WITH ARCHITECTURAL PLANS
CONT
CONTINUATION
HP
HORSE POWER
REC
RECEPTACLE
(E)
EXISTING TO REMAIN
CU
COPPER
HZ
HERTZ
RMC
RIGID METAL CONDUIT
(ER)
EXISTING TO BE REMOVED
DEG
DEGREE
IG
ISOLATED GROUND
SPD
SURGE PROTECTION DEVICE
(ERR)
REMOVED & RELOCATED
DIA
DIAMETER
IMC
INTERMEDIATE METAL CONDUIT
SPEC
SPECIFICATION
(ERRO)
REMOVED & RETURNED TO OWNER
DISC
DISCONNECT
JB
JUNCTION BOX
SW
SWITCH
(N)
NEW
DIV
DIVISION
KCMIL
THOUSAND CIRCULAR MILS
SWBD
SWITCHBOARD
(RE)
RELOCATED EXISTING
EA
EACH
KV
KILOVOLT
SYS
SYSTEMS
1P
SINGLE POLE
EC
ELECTRICAL CONTRACTOR
KVA
KILOVOLT AMPERE
TVSS
TRANSIENT VOLTAGE SURGE SUPPRESSION
2P
TWO POLE
ELEC
ELECTRICAL
KW
KILOWATT
TYP
TYPICAL
CEILING MOUNTED
3P
THREE POLE
EM
EMERGENCY
KWH
KILOWATT HOUR
UON
UNLESS OTHERWISE NOTED
PHOTOCELL CONTROL SWITCH
WALL MOUNTED @ 10" BELOW FINISHED CEILING
A
AMPERE
EMT
ELECTRICAL METALLIC TUBING
LTG
LIGHTING
UPS
UNINTERRUPTED POWER SUPPLY
AF
AMPERE FRAME
DEGREE FAHRENHEIT
MCB
MAIN CIRCUIT BREAKER
V
VOLTS
AFF
ABOVE FINISHED FLOOR
FA
FIRE ALARM
MCC
MOTOR CONTROL CENTER
VIF
VERIFY IN FIELD
AIC
AMPERE INTERRUPTING CAPACITY
FACP
FIRE ALARM CONTROL PANEL
MCM
THOUSAND CIRCULAR MILS
VFD
VARIABLE FREQUENCY DRIVE
AT
AMPERE TRIP
FAAP
FIRE ALARM ANNUNCIATOR PANEL
MI
MINERAL INSULATED CABLE
WP
WEATHERPROOF
ATS
AUTOMATIC TRANSFER SWITCH
FATC
FIRE ALARM TERMINATION CABINET
MTD
MOUNTED
XFMR
TRANSFORMER
DWG. NO.:
OF
AWG
AMERICAN WIRE GAUGE
FC
FOOT CANDLE
N
NEUTRAL
Y
WYE
SHT. NO.:
OF
EMERGENCY LIGHTING FIXTURES. REFER TO "LIGHTING FIXTURE SCHEDULE".
SINGLE POLE SWITCH
FLUSH WALL MOUNTED @ 48" AFF, UON
3 = THREE-WAY
4 = FOUR-WAY
D = INTEGRAL DIMMER
OS = INTEGRATED OCCUPANCY SENSOR
PHOTOCELL CONTROL SWITCH
CEILING MOUNTED
ELECTRICALLY HELD UL LISTED RELAY FOR EMERGENCY LIGHTING.
LIGHTING SHALL BE CONTROLLED BY SWITCH UNDER NORMAL POWER
CONDITION FROM NORMAL SOURCE. IN EMERGENCY MODE THE RELAY
SHALL ENABLE THE DEDICATED LIGHTING TO BE SWITCHED TO THE
EMERGENCY SOURCE FOR FULL OPERATION. PROVIDE BODINE BALLAST
#GTD OR SIMILIAR.
ADA ACCESS BUTTON, MAKE ALL FINAL CONNECTIONS TO DOOR CONTROLLER
TIME CLOCK
DOOR CONTROLLER
INSTALLED SYSTEMS SHALL OPERATE UNDER ALL CONDITIONS OF LOAD WITHOUT SOUND OR VIBRATION
THAT IS OBJECTABLE TO THE PROJECT MANAGER, OR SEPTA. OBJECTABLE SOUND OR VIBRATION
CONDITIONS DUE TO WORKMANSHIP SHALL BE CORRECTED IN APPROVED MANNER BY THE ELECTRICAL
CONTRACTOR AT HIS EXPENSE.
7.
CIRCUIT BREAKER - MOLDED CASE TYPE
<FRAME AMPS>/<TRIP AMPS>/<POLES>
CONDUIT OR RACEWAY TURNING UP
CONDUIT OR RACEWAY TURNING DOWN
ELECTRICAL CONTRACTOR SHALL SCHEDULE HIS WORK IN ACCORDANCE WITH THE CONSTRUCTION
SCHEDULE SO THAT ALL OF HIS WORK CAN BE INSTALLED WITHOUT DELAYING THE PROJECT. ALL WORK
RELATED TO SHUTDOWN OF EXISTING SERVICES SHALL BE PERFORMED AT THE HOURS DESIGNATED BY
SEPTA WITH ALL ASSOCIATED COSTS BORNE BY THE ELECTRICAL CONTRACTOR AT NO COST TO SEPTA.
PROVIDE ANY TEMPORARY FACILITIES REQUIRED TO PERMIT SEPTA'S USE OF EXISTING FACILITIES AND
SYSTEMS TO REMAIN UNDISTURBED. COORDINATE ALL WORK, INCLUDING ALL SHUTDOWNS THAT AFFECT
SYSTEMS AND/OR PORTIONS OF THE BUILDING THAT MUST REMAIN IN OPERATION, WITH SEPTA.
GROUND CONNECTION
20A, 125V QUADRUPLEX RECEPTACLE
FLUSH CEILING MOUNTED
SPECIAL PURPOSE RECEPTACLE. NEMA TYPE AS INDICATED
FLUSH CEILING MOUNTED
6.
19.
GENERATOR
100/90/3
15 or 20A, 125V SURGE SUPPRESSION DUPLEX RECEPTACLE
FLUSH WALL MOUNTED @ 18" AFF, UON
TRANSFER SWITCH
ATS = AUTOMATIC TRANSFER
MTS = MANUAL TRANSFER
POLES AND RATING AS NOTED
MOTOR
15 or 20A, 125V SINGLE RECEPTACLE, W/ ISOLATED GROUND
FLUSH WALL MOUNTED @ 18" AFF, UON
15 or 20A, 125V DUPLEX RECEPTACLE CONTROLLED BY WALL SWITCH
FLUSH WALL MOUNTED @ 48" AFF, UON
LAYOUT OF EQUIPMENT INDICATED ON THE DRAWINGS SHALL BE CHECKED AND COMPARED AGAINST ALL
DRAWINGS AND SPECIFICATIONS OF ALL TRADES AND EXACT LOCATIONS DETERMINED USING APPROVED
SHOP DRAWINGS OF SUCH EQUIPMENT. WHERE PHYSICAL INTERFERENCES OCCUR, CONSULT WITH THE
PROJECT MANAGER AND PREPARE DATED, DIMENSIONED DRAWINGS COORDINATED WITH ALL OTHER
TRADES WORKING IN THIS AREA AND CORRECTING SUCH INTERFERENCE.
TAPBOX, SPLICE BOX
15 or 20A, 125V EMERGENCY QUADRUPLEX RECEPTACLE
FLUSH WALL MOUNTED @ 18" AFF, UON
20A, 125V, 2P W/G. SINGLE RECEPTACLE
FLUSH WALL MOUNTED @ 18" AFF, UON
EWC = ELECTRIC WATER COOLER
5.
480/277V DISTRIBUTION PANELBOARD
SURFACE MOUNTED
15 or 20A, 125V EMERGENCY DUPLEX RECEPTACLE
FLUSH WALL MOUNTED @ 18" AFF, UON
15 or 20A, 125V QUADRUPLEX RECEPTACLE, W/ ISOLATED GROUND
FLUSH WALL MOUNTED @ 18" AFF, UON
NUMBER INDICATES QUANTITIES OF IG TYPE RECEPTACLES.
1 = ONE DUPLEX IG TYPE & ONE DUPLEX STANDARD G. RECEPTACLE
2 = QUADRUPLEX IG TYPE RECEPTACLES
THE DRAWINGS INDICATE ARRANGEMENTS AND APPROXIMATE SIZES AND RELATIVE LOCATIONS OF
PRINCIPAL APPARATUS, EQUIPMENT, DEVICES, AND SERVICES TO BE PROVIDED. DRAWINGS ARE
DIAGRAMMATIC AND ARE A GRAPHIC REPRESENTATION OF CONTRACT REQUIREMENTS TO THE BEST
AVAILABLE STANDARDS AT THE SCALE INDICATED.
480/277V PANELBOARD
SURFACE MOUNTED
15 or 20A, 125V DUPLEX RECEPTACLE, GFI TYPE
FLUSH WALL MOUNTED @ 18" AFF, UON
WP = WEATHER PROOF
15 or 20A, 125V DUPLEX RECEPTACLE, W/ ISOLATED GROUND
FLUSH WALL MOUNTED @ 18" AFF, UON
4.
208/120V PANELBOARD
FLUSH MOUNTED
POWER SYMBOLS
15 or 20A, 125V DUPLEX RECEPTACLE
FLUSH WALL MOUNTED @ 18" AFF, UON
C = GRAY COLORED RECEPTACLE FOR COMPUTERS
T = TAMPER PROOF
XP = EXPLOSION PROOF
ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL DIMENSIONS IN THE FIELD, AND SHALL
ADVISE THE PROJECT MANAGER AND THE OWNER OF ANY DISCREPANCIES BEFORE PERFORMING THE
WORK.
208/120V PANELBOARD
SURFACE MOUNTED
UNDERGROUND TELEPHONE CABLE
SHOWN HERE FOR REFERENCE ONLY. SEE CIVIL PLANS
20/1
3.
ALL WORK FURNISHED UNDER THE CONTRACT SHALL BE GUARANTEED AGAINST ANY AND ALL DEFECTS IN
WORKMANSHIP AND/OR MATERIALS FOR A PERIOD OF NOT LESS THAN (1) YEAR FROM THE DATE OF FINAL
ACCEPTANCE OF THE INSTALLATION. ANY DEFECTS OF WORKMANSHIP DEVELOPING DURING THIS PERIOD
SHALL BE REMEDIED AND ANY DEFECTIVE MATERIAL REPLACED WITHOUT ADDITIONAL COST TO SEPTA.
1
NEW UNDERGROUND/UNDER SLAB CONDUIT
COMBINATION MOTOR CONTROLLER / DISCONNECT SWITCH
<SWITCH AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED
VFD = VARIABLE FREQUENCY DRIVE
100/3
18.
CWT
ANNOTATION SYMBOLS
SEPTA AT CONTRACTOR'S EXPENSE. CONTRACTOR SHALL INSTRUCT SEPTA'S PERSONNEL WITH REGARD
TO THE PROPER OPERATION OF ALL SYSTEMS TO THE SATISFACTION OF SEPTA.
MAN CWT
TRANSFORMER
ADDENDUM 1
(NOT ALL SYMBOLS ARE NECESSARILY USED ON THIS PROJECT)
NEW CONDUIT/CIRCUIT/EQUIPMENT
COMPLETE SET OF CAD AS-BUILT DRAWINGS IN AUTOCAD 2000 AT CONTRACTOR'S EXPENSE AND (3)
GENERAL NOTES
4/17/15
ELECTRICAL SYMBOLS LIST
SCALE:
SCALE FACTOR:
DATE:
DRAWN BY:
CHECKED BY:
WORK ORDER NO.:
SHEET NUMBER
ARCHIVE NO.:
BLDG
BUILDING
FDR
FEEDER
NC
NORMALLY CLOSED
C
CONDUIT
FL
FLOOR
NO
NORMALLY OPEN
DEGREE CELSIUS
FLA
FULL LOAD AMPERES
P
POLE
DELTA
COMPUTER FILE NO.:
REV. NO.:
KEY NOTES
DATA ROOM'S AIR CONDITIONER & CONDENSING UNIT
POWERED THROUGH SINGLE POINT AT CONDENSING UNIT.
EXTEND CONDUIT/WIRE TO AIR CONDITIONER.
HANDS-FREE SINK REQUIRES 120V RECEPTACLE. SINK
PROVIDED BY OTHERS WITH LOW-VOLTAGE PLUG-IN
TRANSFORMER.
HANDS-FREE SINKS REQUIRES 120V. MOUNT JUNCTION BOX
BELOW SINK. SINK PROVIDED BY OTHERS WITH
LOW-VOLTAGE 100VA TRANSFORMER.
HANDS-FREE TOILET REQUIRES 120V. MOUNT IN LOCATION
RECOMMENDED BY MANUFACTURER. TOILET PROVIDED BY
OTHERS WITH LOW-VOLTAGE TRANSFORMER.
DEDICATED RECEPTACLE FOR ELECTRIC WATER HEATER TO
BE MOUNTED UNDER SINK. LABEL FACEPLATE "FOR WATER
HEATER".
PROVIDE 120V:24V TRANSFORMER FOR LOW VOLTAGE
DAMPER.
PROVIDE 120V:24V TRANSFORMER FOR LOW VOLTAGE
DAMPER.
PROVIDE SECURITY PANEL, TYCO INTEGRATED SECURITY
ACE8/SWH-1 OR SEPTA APPROVED EQUAL
4
2
LP2
TROUGH
HP1ABOVE CB-1
LP2
LP1
LP2
6
19
UH-1
LP1
LP2
C
14
13
12
VAV
+
1"C FOR DATA
3/4"C FOR POWER
PUMP P-1
SD
LP1
LP1
+
LP2
+
VAV
+
+
12
SINKS
100VA, 120V
LP1
LP1
15
29
HAND DRYER
1500VA, 120V
HAND DRYER
1500VA, 120V
LP2
14
18
VAV
1"C FOR POWER
1"C FOR DATA
CEILING FAN
LP2
LP2
REFRIGERATOR
120V
20
LP1 23
22
26
28 30
EWC
+
1
+
LP1
18
REF. REF. REF.
CR
+
24
STANDARD OUTLET MOUNTING HEIGHT SHALL BE THE SAME
AS ELECTRICAL HEIGHT, U.O.N. EXACT LOCATION OF
OUTLETS SHALL BE AS INDICATED ON THE ARCHITECTURAL
DRAWINGS.
LP1 CEILING FAN
LP2 LP2
17
27
REF.
+
LP2 LP2 LP2
EQUIPMENT AND/OR CABLE LOCATED AT THIS STAGE OF THE
TELECOMMUNICATIONS CABLING CONFIGURATION IS EITHER
EXISTING OR NOT COVERED UNDER THIS CONTRACT AND
WILL BE FURNISHED BY OTHERS.
OUTLET IDENTIFICATION NUMBERING SHALL BE AS DIRECTED
BY OWNER'S M.I.S. DEPARTMENT INSTALLATION SHALL
COMPLY WITH SPECIFICATIONS. EACH CABLING SHALL BE
TAGGED AT ALL TERMINATIONS POINTS.
25
LP2
LP2
EWC
LP2
C
32
33
ELECTRIC WH-2
1.5KVA, 120V
16
+
WP
LP1 31
TOILET (TYP 11)
50VA, 120V
VAV
10
VAV
VIDEO MONITORS, +48" (TYP 9)
120V & DATA
LP2
LP1
27 LP1
LP1 LP1
LP2
LABEL ALL RACKS, FRAMES, CABINETS, BLOCKS, CABLES,
CABLE SUPPORTS, ETC. IN ACCORDANCE WITH EIA/TIA 606.
+
LP1
10
LP1
6
TOILET (TYP 3)
50VA, 120V
16
MD
PUMP P-2
SINK
35VA,120V
ELECTRIC WH-2
1.5KVA, 120V
MD
TELECOMMUNICATIONS INSTALLATION SHALL COMPLY WITH
ALL CURRENT APPLICABLE CODES, INCLUDING
PHILADELPHIA ELECTRICAL CODES, THE NATIONAL ELECTRIC
CODE, AND ALL APPLICABLE LOCAL CODES HAVING
JURISDICTION.
SINKS
100VA, 120V
LP2
REC
ON
ROOF
UH-2
4
PROVIDE FIRESTOPPING FOR ALL SLEEVE AND CONDUIT
PENETRATIONS THROUGH RATED PARTITIONS OR FLOORS IN
ACCORDANCE WITH THE SPECIFICATIONS.
11
21
LP2
LP2
8
TELECOMMUNICATION NOTES
T75K
VAV
VAV
MDP
MD
BMS PANEL
120V
BOILER CONTROLS
120V
LP1
HP1 HP1
3
2
1
MD
LP1
7
LP1
5
CWT
MD CT
MD
WIRE ALL ADA ACCESS BUTTONS TO CIRCUIT LP1#34
WP
MAN CWT
LP1
LP1
TRAP PRIMER TP-1
120V
GAS WATER HEATER
RE-CIRC PUMP 120V
EF-4
1/25HP,120V
ADDENDUM 1
WP
EF-3
1/30HP,120V
4/17/15
LP1
1 LP1
PROVIDE TWO CAT 6 CABLES IN A 1" EMT CONDUIT HOMERUN
BACK TO THE SECURITY PANEL IN THE COMM ROOM AND
SAFE OFF BOTH ENDS.
LP2
SECURITY
PANEL
7
C
19
LP2
LP2
VAV
2 LP2
LP2
C
LP2
VAV
UP TO
CU-1
21
LP1
KIOSK & PRINTER
LP2
ELECTRIC WH-2
1.5KVA, 120V
34
23
1
TELEPHONE
4'x4' PLYWOOD
LP2
26
3
AC-1
VAV
5
LP2
15
C
CONDESATE PUMP
120V
LP2
LP2
29
LP2
PRINTER/COPIER
CR
VAV
17
CEILING FAN
LP1
C
VAV
30
28
DMO
CR
TYP
BURIED CONDUIT FOR TELE/DATA
REFER TO DRAWING E102 FOR CONTINUATION
25
LP1
LP1
TYP
DMO
WP
CR
DMO
CR
LP1
CEILING FAN (TYP 4)
5.7A,120V
32
TYP
TYP
SCALE:
SCALE FACTOR:
DATE:
DRAWN BY:
CHECKED BY:
WORK ORDER NO.:
SHEET NUMBER
DWG. NO.:
OF
SHT. NO.:
OF
ARCHIVE NO.:
COMPUTER FILE NO.:
REV. NO.:
KEY NOTES
EXHAUST FAN PROVIDED WITH DISCONNECT AND OVERLOAD
PROTECTION BY OTHERS.
DATA ROOM'S AIR CONDITIONER & CONDENSING UNIT
POWERED THROUGH SINGLE POINT AT CONDENSING UNIT.
EXTEND CONDUIT/WIRE TO AIR CONDITIONER.
EXHAUST FAN EF-1
1/4HP, 120V
ROOFTOP UNIT RTU-1
15HP SUPPLY FAN
(3)11.2A COMPRESSORS
(3)2A CONDENSORS
WALKING PAD, TYP.
9
LP1
MECHANICAL EQUIPMENT PAD
100/100/3
WP
WP
REC CIRCUIT
LP2#2 BELOW
3
MDP
SKYLIGHT
SKYLIGHT
SKYLIGHT
SKYLIGHT
SKYLIGHT
SKYLIGHT
CU-1
DOWN TO AC
WALKING PAD, TYP.
SCALE:
SCALE FACTOR:
DATE:
DRAWN BY:
CHECKED BY:
WORK ORDER NO.:
SHEET NUMBER
DWG. NO.:
OF
SHT. NO.:
OF
ARCHIVE NO.:
COMPUTER FILE NO.:
REV. NO.:
PANEL: MDP
LOCATION: ELECTRICAL ROOM 130
480/277
MOUNTING:
BUILDING: FRANKFORD ADMINISTRATION BUILDING
FED FROM: REFER TO SINGLE LINE ON DRAWING E002
BUS:
GROUND
3
5
7
9
11
20
20
-
-
-
COPPER
ALUMINUM NEUTRAL: 100%
DESCRIPTION OF LOAD
(KVA)
LOAD
FEED THRU
TOP
A
B
C
MLO
BOTTOM
SHUNT TRIP
DESCRIPTION OF LOAD
LOAD
P
AIC: 32,000 AMPS
TRIP CKT.
AMPS NO.
ROOFTOP UNIT RTU-1
SPACE
FCU-1
20
FCU-4
SPACE
20
SPACE
SPACE
-
SPACE
SPACE
125
-
FCU-2
FCU-3
BUS:
GROUND
-
SPACE
-
2
4
6
8
10
12
14
15
MAIN BRK: MLO AMPS 3
SURFACE
FLUSH
COPPER
ALUMINUM NEUTRAL: 100%
ARC FLASH HAZARD CATEGORY: 2
DESCRIPTION OF LOAD
(KVA)
LOAD
FEED THRU
TOP
A
B
C
MLO
BOTTOM
SHUNT TRIP
DESCRIPTION OF LOAD
LOAD
KEY NOTES
P
AIC: 14,000 AMPS
PER PHASE
CKT. TRIP
NO. AMPS
1
MAIN BUS: 150 AMPS
ISOLATED GROUND LUGS:
1
FEED:
NEMA ENCLOSURE TYPE:
FEEDER SIZE: REFER TO SINGLE LINE ON DRAWING E002
MANUFACTURER/MODEL:REFER TO SPECIFICATIONS
(KVA)
PANEL LP1 VIA TRANSFORMER
VOLTS, 3 PHASE, 4 WIRE
MOUNTING:
BUILDING: FRANKFORD ADMINISTRATION BUILDING
FED FROM: REFER TO SINGLE LINE ON DRAWING E002
(KVA)
PANEL HP1
480/277
REFER TO SINGLE LINE DIAGRAM ON DRAWING E002 FOR
FEEDER SIZE.
PROVIDE 3#12, #12G, 3/4"C
TRIP CKT.
AMPS NO.
(KVA)
PUMP P-1 (1.5HP)
PUMP P-2 (1.5HP)
15
2
3
4
5
6
7
20
LIGHTING
SPARE
20
8
9
20
LIGHTING
SPARE
20
10
11
20
LIGHTING
SPARE
20
12
13
20
LIGHTING
SPARE
20
14
15
20
LIGHTING
SPARE
20
16
17
20
SPARE
SPARE
20
18
19
20
SPARE
SPACE
-
20
21
20
SPARE
SPACE
-
22
23
20
SPARE
SPACE
-
24
25
-
SPACE
SPACE
-
26
27
-
SPACE
SPACE
-
28
29
-
SPACE
SPACE
-
30
31
-
SPACE
SPACE
-
32
33
-
SPACE
SPACE
-
34
35
-
SPACE
SPACE
-
36
37
-
SPACE
SPACE
-
38
39
-
SPACE
SPACE
-
40
41
-
SPACE
SPACE
-
42
MAN CWT
CWT
13
100
FLUSH
ARC FLASH HAZARD CATEGORY: 2
(KVA)
150
MAIN BRK: 400 AMPS 3
SURFACE
PER PHASE
CKT. TRIP
NO. AMPS
PANEL: HP1
LOCATION: ELECTRICAL ROOM 130
MAIN BUS: 400 AMPS
ISOLATED GROUND LUGS:
1
FEED:
NEMA ENCLOSURE TYPE:
FEEDER SIZE: REFER TO SINGLE LINE ON DRAWING E002
MANUFACTURER/MODEL:REFER TO SPECIFICATIONS
1
VOLTS, 3 PHASE, 4 WIRE
SURFACE
BUILDING: FRANKFORD ADMINISTRATION BUILDING
FED FROM: REFER TO SINGLE LINE ON DRAWING E002
BUS:
GROUND
COPPER
MAIN BUS: 250 AMPS
MAIN BRK: 250 AMPS 3 P
FLUSH
ALUMINUM NEUTRAL: 200% AIC: 10,000 AMPS
ISOLATED GROUND LUGS:
1
FEED:
NEMA ENCLOSURE TYPE:
FEEDER SIZE: REFER TO SINGLE LINE ON DRAWING E002
MANUFACTURER/MODEL:REFER TO SPECIFICATIONS
ARC FLASH HAZARD CATEGORY: 1
FEED THRU
TOP
SHUNT TRIP
PER PHASE
CKT. TRIP
NO. AMPS
DESCRIPTION OF LOAD
(KVA)
LOAD
(KVA)
DESCRIPTION OF LOAD
LOAD
A
B
C
MLO
BOTTOM
TRIP CKT.
AMPS NO.
PANEL: LP2
LOCATION: ELECTRICAL ROOM 130
MOUNTING:
SURFACE
BUILDING: FRANKFORD ADMINISTRATION BUILDING
FED FROM: REFER TO SINGLE LINE ON DRAWING E002
BUS:
GROUND
COPPER
208/120 VOLTS, 3 PHASE, 4 WIRE
MAIN BUS: 250 AMPS
MAIN BRK: MLO AMPS 3 P
ALUMINUM NEUTRAL: 200% AIC: 10,000 AMPS
FLUSH
ISOLATED GROUND LUGS:
1
FEED:
NEMA ENCLOSURE TYPE:
FEEDER SIZE: REFER TO SINGLE LINE ON DRAWING E002
MANUFACTURER/MODEL:REFER TO SPECIFICATIONS
ARC FLASH HAZARD CATEGORY: 1
FEED THRU
TOP
DESCRIPTION OF LOAD
(KVA)
(KVA)
LOAD
(KVA)
DESCRIPTION OF LOAD
LOAD
A
B
C
MLO
BOTTOM
SHUNT TRIP
PER PHASE
CKT. TRIP
NO. AMPS
ADDENDUM 1
MOUNTING:
208/120 VOLTS, 3 PHASE, 4 WIRE
TRIP CKT.
AMPS NO.
4/17/15
PANEL: LP1
LOCATION: ELECTRICAL ROOM 130
(KVA)
20
BMS PANEL
TELEPHONE BOARD REC
20
2
1
20
REC SERVER ROOM
REC MECH RM, EXTERIOR
20
2
3
20
BOILER CONTROLS
FIRE ALARM CONTROL PANEL
20
4
3
20
REC SERVER ROOM
REC 112A, ELEC RM, C102
20
4
5
20
TRAP PRIMER TP-2
SMOKE DAMPERS
20
6
5
20
REC SERVER ROOM
REC 108, 110
20
6
7
20
RE-CIRC PUMP
DAMPERS, EF-5, EF-6
20
8
7
20
REC SERVER ROOM
COMPUTER REC 102, 104, 106, 108, 110
20
8
9
20
EXHAUST FAN EF-1 (1/4HP)
HANDS-FREE MENS RESTROOM
20
10
9
20
SPARE
REC 102, 104, 106
20
10
11
20
EXHAUST FAN EF-2 (1/6HP)
HANDS-FREE WOMENS RESTROOM
20
12
11
20
REC RESTROOMS 122, 124
REC RESTROOMS 111, 113
20
12
13
20
WATER HEATER WH-2
HANDS-FREE RESTROOMS 111 & 113
20
14
13
20
SPARE
REC KITCHEN
20
14
15
20
WATER HEATER WH-2
ELECTRIC WATER COOLER KITCHEN
20
16
15
20
REC C101, 100, EXTERIOR
REC KITCHEN
20
16
17
20
WATER HEATER WH-2
ELECTRIC WATER COOLER LOUNGE
20
18
17
20
REC 101
REC KITCHEN
20
18
19
20
VAV CONTROLLERS
20
20
19
20
REC 101
REFRIGERATOR 109
20
20
21
20
VAV CONTROLLERS
AIR CONDITIONER & CONDENSING UNIT
DATA ROOM
22
21
20
REC 101
REFRIGERATOR 120
20
22
23
20
CEILING FANS 120
HEATERS 130,131, DAMPERS
20
24
23
20
REC 120
REFRIGERATOR 120
20
24
25
20
CEILING FANS 120
CONDESATE PUMP
20
26
25
20
REC 120, 125, 126, C103
REFRIGERATOR 120
20
26
27
20
HAND DRYER WOMENS RESTROOM
DOOR CONTROLLER
20
28
27
20
REC 101A, 101B, 107, EXTERIOR
REC 120
20
28
29
20
HAND DRYER WOMENS RESTROOM
DOOR CONTROLLER
20
30
29
20
PRINTER/COPIER
REC 120
20
30
31
20
HAND DRYER MENS RESTROOM
DOOR CONTROLLER
20
32
31
20
SPARE
VIDEO MONITORS 120
20
32
33
20
HAND DRYER MENS RESTROOM
ADA DOOR ASSIST BUTTONS
20
34
33
20
SPARE
VIDEO MONITORS 120
20
34
35
20
SPARE
SPARE
20
36
35
20
SPARE
SPARE
20
36
37
20
SPARE
SPARE
20
38
37
20
SPARE
SPARE
20
38
39
20
SPARE
SPARE
20
40
39
20
SPARE
SPARE
20
40
41
20
SPARE
SPARE
20
42
41
20
SPARE
SPARE
20
42
1
1
SCALE:
SCALE FACTOR:
DATE:
DRAWN BY:
CHECKED BY:
WORK ORDER NO.:
SHEET NUMBER
DWG. NO.:
OF
SHT. NO.:
OF
ARCHIVE NO.:
COMPUTER FILE NO.:
REV. NO.: