1. THE SUBMISSION OF A BID BY THE ELECTRICAL CONTRACTOR IS NOTIFICATION THAT THE ELECTRICAL CONTRACTOR HAS TOTALLY FAMILIARIZED HIMSELF WITH THE CONTRACT DOCUMENTS AND EXISTING SITE CONDITIONS AND HAS AGREED TO PROVIDE THE NECESSARY LABOR AND MATERIAL FOR THE COMPLETE INSTALLATION OF EACH SYSTEM IN A NEAT AND WORKMANLIKE MANNER IN ACCORDANCE WITH THE BEST PRACTICES OF THE INDUSTRY AND IN COMPLIANCE WITH ALL AUTHORITIES HAVING JURISDICTION. MANHOLE KEY NOTE FLOOR MOUNTED METAL SUPPORT FRAME FOR ELECTRICAL ENCLOSURES VFD NEW EMERGENCY CIRCUIT 30/3 2. THESE DRAWINGS ARE PRESENTED TO THE ELECTRICAL CONTRACTOR WITH THE UNDERSTANDING THAT THE ELECTRICAL CONTRACTOR IS AN EXPERT AND COMPETENT IN THE PREPARATION OF CONTRACT BID PRICES ON THE BASIS OF INFORMATION SUCH AS IS CONTAINED IN THESE DOCUMENTS. IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS TO CALL FOR FINISHED WORK, TESTED AND READY FOR OPERATION AND IN COMPLETE CONFORMANCE WITH ALL APPLICABLE CODES, RULES, AND REGULATIONS. MINOR ITEMS NOT USUALLY SHOWN OR SPECIFIED, BUT MANIFESTLY NECESSARY FOR THE PROPER INSTALLATION AND OPERATION OF THE VARIOUS SYSTEMS, SHALL BE INCLUDED IN THE WORK AND IN THE PROPOSAL THE SAME AS IF SPECIFIED OR SHOWN ON THE DRAWINGS. IF ANY DEPARTURES FROM THE DRAWINGS ARE DEEMED NECESSARY, DETAILS OF SUCH DEPARTURES AND THE REASONS THEREFORE SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL. NO DEPARTURES SHALL BE MADE WITHOUT PRIOR APPROVAL OF SEPTA. UNFUSED DISCONNECT SWITCH <SWITCH AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED NEW LOW VOLTAGE/CONTROL WIRING 100/60/3 FUSED DISCONNECT SWITCH <SWITCH AMPS>/<FUSE AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED 60/30/3 ST ENCLOSED CIRCUIT BREAKER <FRAME AMPS>/<TRIP AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED ST = SHUNT TRIP NEW GROUND CABLE EQUIPMENT PROVIDED BY OTHERS UNDERGROUND SECONDARY CABLE SHOWN HERE FOR REFERENCE ONLY. SEE CIVIL PLANS 208/120V DISTRIBUTION PANELBOARD SURFACE MOUNTED JUNCTION BOX MOUNTED ABOVE SUSPENDED CEILING / FLUSH WALL INSTALLED WITHIN 2' OF EQUIPMENT AND CONNECTED VAV = DEDICATED TO VARIABLE AIR VOLUME BOX CONTROL SD = DEDICATED TO SMOKE DAMPER MD = DEDICATED TO MOTORIZED VOLUME DAMPER UH = UNIT HEATER EWC = ELECTRIC WATER COOLER DMO = DOOR MOTOR OPERATOR MOTOR RATED TOGGLE SWITCH, 20A SINGLE POLE, UON HORSEPOWER RATED WITH OVERLOAD PROTECTION. 15 or 20A, 125V QUADRUPLEX RECEPTACLE FLUSH WALL MOUNTED @ 18" AFF, UON 480/277V PANELBOARD FLUSH MOUNTED RISER / SINGLE LINE SYMBOLS 460V POWER TRANSFORMER 500KVA VOLTAGES, WINDINGS AND SIZE AS INDICATED 208/120V ATS 100A 480V,4P DROP CORD RECEPTACLE CEILING MOUNTED SPECIAL PURPOSE RECEPTACLE. NEMA TYPE AS INDICATED FLUSH WALL MOUNTED @ 18" AFF, UON 3 PHASE SPECIAL PURPOSE RECEPTACLE. NEMA TYPE AS INDICATED FLUSH WALL MOUNTED @ 18" AFF, UON JUNCTION BOX OR POKE-THRU WITH COMBINATION POWER/DATA FLUSH FLOOR MOUNTED REFER TO DETAIL ON DRAWING E002 20A, 125V DUPLEX RECEPTACLE FLUSH CEILING MOUNTED CAPPED CONDUIT CONDUIT WITH BUSHING HOMERUN-NUMERAL WHERE USED INDICATES DESIGNATED PANEL AND CIRCUIT NUMBER FOR REFERENCE ONLY. WHERE CONDUIT IS NOT SPECIFIED USE AC OR MC CABLE FOR APPLICATION. 2#12, #12G, 3/4"C HOMERUN, UON 3#12, #12G, 3/4"C HOMERUN, UON 4#12, #12G, 3/4"C HOMERUN, UON AT 120V AND OVER 100' CIRCUIT LENGTH PROVIDE #10 MINIMUM. AT 277V AND OVER 200' CIRCUIT LENGTH PROVIDE #10 MINIMUM. SPLICE (JUNCTION) OF PATHS OF CONDUCTORS OR CABLES. CARD READER, PROVIDE 2"x4" JUNCTION BOX WALL MOUNTED @ 42" AFF UON ON NON-SECURED SIDE OF DOOR ELECTRIC DOOR STRIKE 20. ELECTRICAL CONTRACTOR SHALL SIMILARLY NOTIFY ENGINEER OF COMPLETION OF ALL WORK, INDICATING THE ELECTRICAL CONTRACTOR IS READY FOR THE ENGINEER TO PERFORM THE FINAL PUNCHLIST INSPECTION. 21. UPON COMPLETION OF ALL UNFINISHED OR FAULTY WORK NOTED IN ENGINEER FINAL PUNCH LIST, THE ELECTRICAL CONTRACTOR SHALL SUBMIT TO THE ENGINEER IN WRITING A LETTER OF COMPLETION CERTIFYING THAT ALL PUNCH LIST ITEMS HAVE BEEN COMPLETED AND ALL AS-BUILTS, MANUALS, ETC. HAVE BEEN SUBMITTED. 22. SHOULD A CONTRACTOR REQUIRE REMOVAL, RELOCATION, OR REROUTING OF ANOTHER TRADE'S WORK THAT IS NOT INDICATED ON DRAWINGS, THE CONTRACTOR REQUIRING SUCH WORK SHALL BE RESPONSIBLE FOR THAT WORK, AND PAY ALL REQUIRED COSTS. 23. ALL WORK INVOLVING ALTERATIONS TO EXISTING SYSTEMS, EQUIPMENT, AND MATERIALS SHALL BE REVIEWED WITH THE PROJECT MANAGER AND SEPTA BEFORE BEGINNING WORK. 24. DEFINITION: UNLESS OTHERWISE NOTED, ALL WORK SPECIFIED HEREIN OR NOTED ON DRAWINGS, SHALL BE BY THE ELECTRICAL CONTRACTOR. ALL REFERENCES TO "CONTRACTOR" OR "THIS CONTRACTOR" ON DRAWINGS OR SPECIFICATIONS ARE ADDRESSED TO THE ELECTRICAL CONTRACTOR. THE TERM "PROVIDE" WHENEVER ENCOUNTERED ON DRAWINGS OR IN THESE SPECIFICATIONS, SHALL MEAN "FURNISH AND INSTALL." 25. CODES AND STANDARDS: ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE, ALL APPLICABLE CODES, SPECIFICATIONS, LOCAL ORDINANCES, INDUSTRY STANDARDS, UTILITY COMPANY REGULATIONS AND FIRE INSURANCE CARRIER'S REQUIREMENTS. 26. MATERIALS: ALL MATERIALS FURNISHED BY THIS CONTRACTOR, SHALL BE NEW AND BEAR THE LABEL OR LISTING OF A NATIONALLY RECOGNIZED INDEPENDENT TESTING LABORATORY. ELECTRICAL CONTRACTOR SHALL SECURE AND PAY ALL FEES, LICENSES, INSPECTIONS, AND PERMITS PERTAINING TO THE CONTRACT. SUBMIT TO SEPTA DUPLICATE CERTIFICATES OF INSPECTION FROM APPROVED INSPECTION AGENCY. 27. OUTLET AND SWITCH BOXES: PROVIDE AND INSTALL OUTLET BOXES OF PROPER TYPE AND SIZE AS REQUIRED AT ALL OUTLETS WHERE SHOWN. SECURED FIRMLY IN PLACE AND SET TRUE AND SQUARE AND FLUSH WITH THE FINISHED SURFACE. 8. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER'S WRITTEN INSTRUCTIONS. 28. INSTALLATION OF RACEWAYS: ALL RACEWAYS SHALL BE INSTALLED CONCEALED. NO SURFACE RACEWAY WILL BE ACCEPTED IN FINISHED AREAS. 9. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WORKMEN'S IDENTIFICATION AND BADGING, SAFETY AND FIRE PROTECTION, BARRICADES, WARNING SIGNS, TRASH REMOVAL, CUTTING AND PATCHING. 29. WIRING: WIRING OF BRANCH CIRCUITS SHALL BE TYPE THHN/THWN IN RIGID GALVANIZED STEEL CONDUIT RACEWAYS ARE SHOWN DIAGRAMMATICALLY, EXACT LOCATION TO BE DETERMINED ON THE JOB. EXACT LOCATION OF OUTLETS TO BE DETERMINED BY SEPTA. CONTRACTOR SHALL ARRANGE ALL NEW CIRCUITS IN PANELS SO AS TO BALANCE THE LOAD ON ALL PHASES. EXPOSED CONDUIT IN UNFINISHED AREAS SHALL BE EMT. CONDUIT DIRECTLY BURIED UNDERGROUND SHALL BE SCHEDULE 40 PVC WITH RGS ELBOWS AND STUB UPS. 10. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL RIGGING, HANDLING, AND PROTECTION OF MATERIALS. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND WITHOUT BLEMISH OR DEFECT. ALL EQUIPMENT INSTALLED SHALL BEAR THE LABEL OF AN APPROVED AGENCY. 11. ELECTRICAL CONTRACTOR SHALL PROVIDE LABOR TO RECEIVE, UNLOAD, STORE, PROTECT, AND TRANSFER TO POINT OF INSTALLATION FOR ALL FURNISHED ITEMS. 30. A TYPED DIRECTORY CARD SHALL BE PROVIDED IN EACH PANEL WITH ADDED CIRCUITS TO INDICATE THE LOADS ACTUALLY SERVED. 12. WHERE CONDUIT, CABLES, DUCTWORK, OR PIPING PASSES THROUGH FIRE RATED FLOORS OR WALLS, THE PENETRATION SHALL BE COMPLETELY SEALED WITH A FIRE STOP MATERIAL THAT IS UL LISTED, FM GLOBAL APPROVED (WWW.FMGLOBAL.COM/PAGE.ASPX?ID=50030000) AND ACCEPTED BY THE BUILDING DEPARTMENT AND FIRE DEPARTMENT AS BEING SUITABLE FOR THIS SERVICE. THIS MATERIAL SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER TO MAINTAIN THE UL LISTED FIRE RATING OF THE PENETRATED WALL OR FLOOR. 31. PROVIDE NEW FIXTURES AS SPECIFIED ON LIGHTING FIXTURE SCHEDULE. ALL NEW LED LAMPS SHALL BE 3500K. 32. GROUNDING: SHALL BE IN STRICT ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE ARTICLE 250. PROVIDE GROUND WIRES AS REQUIRED AND RESIZE CONDUIT IF NECESSARY. 33. DEMONSTRATION OF COMPLETE ELECTRICAL SYSTEMS: UPON COMPLETION OF THE WORK THIS CONTRACTOR SHALL OBTAIN A CERTIFICATE OF APPROVAL FROM ALL RECOGNIZED AGENCIES CONCERNED WITH THE WORK. CONTRACTOR SHALL NOTIFY AND MAKE ALL THE NECESSARY ARRANGEMENTS WITH THE INSPECTING AGENCY AND LOCAL AUTHORITIES SO THAT INSPECTION MAY BE CARRIED OUT AT THE PROPER TIME. 34. PROJECT MUST MEET FM GLOBAL STANDARDS (WWW.FMGLOBAL.COM/) CURRENT TRANSFORMER 13. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SLAB OPENINGS, WALL OPENINGS, BEAM PENETRATIONS, AND CORING AS IT RELATES TO HIS WORK. ELECTRICAL CONTRACTOR SHALL SUBMIT SIZE AND LOCATION FOR REVIEW AND APPROVAL. 14. ALL EXTERIOR WALL OPENINGS SHALL BE SLEEVED, PROPERLY CAULKED, AND SEALED WITH A HIGH QUALITY SEALANT TO PREVENT INFILTRATION OF MOISTURE AND OUTSIDE AIR. 15. CONTRACTOR SHALL SUBMIT SCHEDULE OF SUBMITTALS PRIOR TO SUBMITTING ANY SHOP DRAWINGS, ETC. TO BE SUBMITTED FOR THIS PROJECT, INCLUDING THE ANTICIPATED DATE OF EACH SUBMISSION. CONTRACTORS SHALL SUBMIT (6) SETS OF COMPLETE SHOP DRAWINGS AND CATALOG CUTS, WIRING DIAGRAMS AND ASSOCIATED DATA TO THE PROJECT MANAGER FOR APPROVAL PRIOR TO PURCHASING EQUIPMENT OR STARTING ANY WORK. ANY WORK INSTALLED OR EQUIPMENT PURCHASED PRIOR TO RECEIPT OF PROJECT MANAGER APPROVED SHOP DRAWINGS THAT REQUIRES CHANGES SHALL BE REPLACED AT CONTRACTOR'S EXPENSE. 16. SUBMIT CATALOG INFORMATION, FACTORY ASSEMBLY DRAWINGS AND FIELD INSTALLATION DRAWINGS AS REQUIRED FOR A COMPLETE EXPLANATION AND DESCRIPTION OF ALL ITEMS TO BE PROVIDED. THE ELECTRICAL CONTRACTOR SHALL REVIEW AND APPROVE ALL SHOP DRAWINGS. NO SUBMISSION WILL BE ACCEPTED WITHOUT THE SIGNED APPROVAL OF THE ELECTRICAL CONTRACTOR. THE ELECTRICAL CONTRACTOR SHALL CHECK AND VERIFY ALL FIELD MEASUREMENTS. 17. UPON COMPLETION OF CONSTRUCTION, CONTRACTOR SHALL SUPPLY THE PROJECT MANAGER WITH (1) METER ELECTRICALLY HELD UL LISTED RELAY FOR EMERGENCY LIGHTING. LIGHTING SHALL BE CONTROLLED BY SWITCH UNDER NORMAL POWER CONDITION FROM NORMAL SOURCE. IN EMERGENCY MODE THE RELAY SHALL ENABLE THE DEDICATED LIGHTING TO BE SWITCHED TO THE EMERGENCY SOURCE FOR FULL OPERATION. PROVIDE BODINE BALLAST #GTD OR SIMILIAR. VOICE / DATA SYMBOLS VOICE/DATA OUTLET FLUSH WALL MOUNTED @ 18" AFF UON, WITH 3/4" CONDUIT IN DEMISING WALL, LIGHTING SYMBOLS LIGHTING FIXTURES. REFER TO "LIGHTING FIXTURE SCHEDULE". ABBREVIATIONS CB CIRCUIT BREAKER FLEX FLEXIBLE CCTV CLOSED CIRCUIT TELEVISION FMC FLEXIBLE METAL CONDUIT (NOT ALL ABBREVIATIONS ARE NECESSARILY USED ON THIS PROJECT) CD CANDELA G GROUND PNL PANEL CL CEILING MOUNT GFI GROUND FAULT INTERRUPTER PVC POLYVINYL CHLORIDE CONDUIT CKT CIRCUIT GRC GALVANIZED RIGID CONDUIT PWR POWER PB PULL BOX PHASE + MOUNTING HEIGHT ABOVE FINISHED FLOOR COORDINATE WITH ARCHITECTURAL PLANS CONT CONTINUATION HP HORSE POWER REC RECEPTACLE (E) EXISTING TO REMAIN CU COPPER HZ HERTZ RMC RIGID METAL CONDUIT (ER) EXISTING TO BE REMOVED DEG DEGREE IG ISOLATED GROUND SPD SURGE PROTECTION DEVICE (ERR) REMOVED & RELOCATED DIA DIAMETER IMC INTERMEDIATE METAL CONDUIT SPEC SPECIFICATION (ERRO) REMOVED & RETURNED TO OWNER DISC DISCONNECT JB JUNCTION BOX SW SWITCH (N) NEW DIV DIVISION KCMIL THOUSAND CIRCULAR MILS SWBD SWITCHBOARD (RE) RELOCATED EXISTING EA EACH KV KILOVOLT SYS SYSTEMS 1P SINGLE POLE EC ELECTRICAL CONTRACTOR KVA KILOVOLT AMPERE TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION 2P TWO POLE ELEC ELECTRICAL KW KILOWATT TYP TYPICAL CEILING MOUNTED 3P THREE POLE EM EMERGENCY KWH KILOWATT HOUR UON UNLESS OTHERWISE NOTED PHOTOCELL CONTROL SWITCH WALL MOUNTED @ 10" BELOW FINISHED CEILING A AMPERE EMT ELECTRICAL METALLIC TUBING LTG LIGHTING UPS UNINTERRUPTED POWER SUPPLY AF AMPERE FRAME DEGREE FAHRENHEIT MCB MAIN CIRCUIT BREAKER V VOLTS AFF ABOVE FINISHED FLOOR FA FIRE ALARM MCC MOTOR CONTROL CENTER VIF VERIFY IN FIELD AIC AMPERE INTERRUPTING CAPACITY FACP FIRE ALARM CONTROL PANEL MCM THOUSAND CIRCULAR MILS VFD VARIABLE FREQUENCY DRIVE AT AMPERE TRIP FAAP FIRE ALARM ANNUNCIATOR PANEL MI MINERAL INSULATED CABLE WP WEATHERPROOF ATS AUTOMATIC TRANSFER SWITCH FATC FIRE ALARM TERMINATION CABINET MTD MOUNTED XFMR TRANSFORMER DWG. NO.: OF AWG AMERICAN WIRE GAUGE FC FOOT CANDLE N NEUTRAL Y WYE SHT. NO.: OF EMERGENCY LIGHTING FIXTURES. REFER TO "LIGHTING FIXTURE SCHEDULE". SINGLE POLE SWITCH FLUSH WALL MOUNTED @ 48" AFF, UON 3 = THREE-WAY 4 = FOUR-WAY D = INTEGRAL DIMMER OS = INTEGRATED OCCUPANCY SENSOR PHOTOCELL CONTROL SWITCH CEILING MOUNTED ELECTRICALLY HELD UL LISTED RELAY FOR EMERGENCY LIGHTING. LIGHTING SHALL BE CONTROLLED BY SWITCH UNDER NORMAL POWER CONDITION FROM NORMAL SOURCE. IN EMERGENCY MODE THE RELAY SHALL ENABLE THE DEDICATED LIGHTING TO BE SWITCHED TO THE EMERGENCY SOURCE FOR FULL OPERATION. PROVIDE BODINE BALLAST #GTD OR SIMILIAR. ADA ACCESS BUTTON, MAKE ALL FINAL CONNECTIONS TO DOOR CONTROLLER TIME CLOCK DOOR CONTROLLER INSTALLED SYSTEMS SHALL OPERATE UNDER ALL CONDITIONS OF LOAD WITHOUT SOUND OR VIBRATION THAT IS OBJECTABLE TO THE PROJECT MANAGER, OR SEPTA. OBJECTABLE SOUND OR VIBRATION CONDITIONS DUE TO WORKMANSHIP SHALL BE CORRECTED IN APPROVED MANNER BY THE ELECTRICAL CONTRACTOR AT HIS EXPENSE. 7. CIRCUIT BREAKER - MOLDED CASE TYPE <FRAME AMPS>/<TRIP AMPS>/<POLES> CONDUIT OR RACEWAY TURNING UP CONDUIT OR RACEWAY TURNING DOWN ELECTRICAL CONTRACTOR SHALL SCHEDULE HIS WORK IN ACCORDANCE WITH THE CONSTRUCTION SCHEDULE SO THAT ALL OF HIS WORK CAN BE INSTALLED WITHOUT DELAYING THE PROJECT. ALL WORK RELATED TO SHUTDOWN OF EXISTING SERVICES SHALL BE PERFORMED AT THE HOURS DESIGNATED BY SEPTA WITH ALL ASSOCIATED COSTS BORNE BY THE ELECTRICAL CONTRACTOR AT NO COST TO SEPTA. PROVIDE ANY TEMPORARY FACILITIES REQUIRED TO PERMIT SEPTA'S USE OF EXISTING FACILITIES AND SYSTEMS TO REMAIN UNDISTURBED. COORDINATE ALL WORK, INCLUDING ALL SHUTDOWNS THAT AFFECT SYSTEMS AND/OR PORTIONS OF THE BUILDING THAT MUST REMAIN IN OPERATION, WITH SEPTA. GROUND CONNECTION 20A, 125V QUADRUPLEX RECEPTACLE FLUSH CEILING MOUNTED SPECIAL PURPOSE RECEPTACLE. NEMA TYPE AS INDICATED FLUSH CEILING MOUNTED 6. 19. GENERATOR 100/90/3 15 or 20A, 125V SURGE SUPPRESSION DUPLEX RECEPTACLE FLUSH WALL MOUNTED @ 18" AFF, UON TRANSFER SWITCH ATS = AUTOMATIC TRANSFER MTS = MANUAL TRANSFER POLES AND RATING AS NOTED MOTOR 15 or 20A, 125V SINGLE RECEPTACLE, W/ ISOLATED GROUND FLUSH WALL MOUNTED @ 18" AFF, UON 15 or 20A, 125V DUPLEX RECEPTACLE CONTROLLED BY WALL SWITCH FLUSH WALL MOUNTED @ 48" AFF, UON LAYOUT OF EQUIPMENT INDICATED ON THE DRAWINGS SHALL BE CHECKED AND COMPARED AGAINST ALL DRAWINGS AND SPECIFICATIONS OF ALL TRADES AND EXACT LOCATIONS DETERMINED USING APPROVED SHOP DRAWINGS OF SUCH EQUIPMENT. WHERE PHYSICAL INTERFERENCES OCCUR, CONSULT WITH THE PROJECT MANAGER AND PREPARE DATED, DIMENSIONED DRAWINGS COORDINATED WITH ALL OTHER TRADES WORKING IN THIS AREA AND CORRECTING SUCH INTERFERENCE. TAPBOX, SPLICE BOX 15 or 20A, 125V EMERGENCY QUADRUPLEX RECEPTACLE FLUSH WALL MOUNTED @ 18" AFF, UON 20A, 125V, 2P W/G. SINGLE RECEPTACLE FLUSH WALL MOUNTED @ 18" AFF, UON EWC = ELECTRIC WATER COOLER 5. 480/277V DISTRIBUTION PANELBOARD SURFACE MOUNTED 15 or 20A, 125V EMERGENCY DUPLEX RECEPTACLE FLUSH WALL MOUNTED @ 18" AFF, UON 15 or 20A, 125V QUADRUPLEX RECEPTACLE, W/ ISOLATED GROUND FLUSH WALL MOUNTED @ 18" AFF, UON NUMBER INDICATES QUANTITIES OF IG TYPE RECEPTACLES. 1 = ONE DUPLEX IG TYPE & ONE DUPLEX STANDARD G. RECEPTACLE 2 = QUADRUPLEX IG TYPE RECEPTACLES THE DRAWINGS INDICATE ARRANGEMENTS AND APPROXIMATE SIZES AND RELATIVE LOCATIONS OF PRINCIPAL APPARATUS, EQUIPMENT, DEVICES, AND SERVICES TO BE PROVIDED. DRAWINGS ARE DIAGRAMMATIC AND ARE A GRAPHIC REPRESENTATION OF CONTRACT REQUIREMENTS TO THE BEST AVAILABLE STANDARDS AT THE SCALE INDICATED. 480/277V PANELBOARD SURFACE MOUNTED 15 or 20A, 125V DUPLEX RECEPTACLE, GFI TYPE FLUSH WALL MOUNTED @ 18" AFF, UON WP = WEATHER PROOF 15 or 20A, 125V DUPLEX RECEPTACLE, W/ ISOLATED GROUND FLUSH WALL MOUNTED @ 18" AFF, UON 4. 208/120V PANELBOARD FLUSH MOUNTED POWER SYMBOLS 15 or 20A, 125V DUPLEX RECEPTACLE FLUSH WALL MOUNTED @ 18" AFF, UON C = GRAY COLORED RECEPTACLE FOR COMPUTERS T = TAMPER PROOF XP = EXPLOSION PROOF ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL DIMENSIONS IN THE FIELD, AND SHALL ADVISE THE PROJECT MANAGER AND THE OWNER OF ANY DISCREPANCIES BEFORE PERFORMING THE WORK. 208/120V PANELBOARD SURFACE MOUNTED UNDERGROUND TELEPHONE CABLE SHOWN HERE FOR REFERENCE ONLY. SEE CIVIL PLANS 20/1 3. ALL WORK FURNISHED UNDER THE CONTRACT SHALL BE GUARANTEED AGAINST ANY AND ALL DEFECTS IN WORKMANSHIP AND/OR MATERIALS FOR A PERIOD OF NOT LESS THAN (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE OF THE INSTALLATION. ANY DEFECTS OF WORKMANSHIP DEVELOPING DURING THIS PERIOD SHALL BE REMEDIED AND ANY DEFECTIVE MATERIAL REPLACED WITHOUT ADDITIONAL COST TO SEPTA. 1 NEW UNDERGROUND/UNDER SLAB CONDUIT COMBINATION MOTOR CONTROLLER / DISCONNECT SWITCH <SWITCH AMPS>/<POLES>, VOLTAGE RATING AS REQUIRED VFD = VARIABLE FREQUENCY DRIVE 100/3 18. CWT ANNOTATION SYMBOLS SEPTA AT CONTRACTOR'S EXPENSE. CONTRACTOR SHALL INSTRUCT SEPTA'S PERSONNEL WITH REGARD TO THE PROPER OPERATION OF ALL SYSTEMS TO THE SATISFACTION OF SEPTA. MAN CWT TRANSFORMER ADDENDUM 1 (NOT ALL SYMBOLS ARE NECESSARILY USED ON THIS PROJECT) NEW CONDUIT/CIRCUIT/EQUIPMENT COMPLETE SET OF CAD AS-BUILT DRAWINGS IN AUTOCAD 2000 AT CONTRACTOR'S EXPENSE AND (3) GENERAL NOTES 4/17/15 ELECTRICAL SYMBOLS LIST SCALE: SCALE FACTOR: DATE: DRAWN BY: CHECKED BY: WORK ORDER NO.: SHEET NUMBER ARCHIVE NO.: BLDG BUILDING FDR FEEDER NC NORMALLY CLOSED C CONDUIT FL FLOOR NO NORMALLY OPEN DEGREE CELSIUS FLA FULL LOAD AMPERES P POLE DELTA COMPUTER FILE NO.: REV. NO.: KEY NOTES DATA ROOM'S AIR CONDITIONER & CONDENSING UNIT POWERED THROUGH SINGLE POINT AT CONDENSING UNIT. EXTEND CONDUIT/WIRE TO AIR CONDITIONER. HANDS-FREE SINK REQUIRES 120V RECEPTACLE. SINK PROVIDED BY OTHERS WITH LOW-VOLTAGE PLUG-IN TRANSFORMER. HANDS-FREE SINKS REQUIRES 120V. MOUNT JUNCTION BOX BELOW SINK. SINK PROVIDED BY OTHERS WITH LOW-VOLTAGE 100VA TRANSFORMER. HANDS-FREE TOILET REQUIRES 120V. MOUNT IN LOCATION RECOMMENDED BY MANUFACTURER. TOILET PROVIDED BY OTHERS WITH LOW-VOLTAGE TRANSFORMER. DEDICATED RECEPTACLE FOR ELECTRIC WATER HEATER TO BE MOUNTED UNDER SINK. LABEL FACEPLATE "FOR WATER HEATER". PROVIDE 120V:24V TRANSFORMER FOR LOW VOLTAGE DAMPER. PROVIDE 120V:24V TRANSFORMER FOR LOW VOLTAGE DAMPER. PROVIDE SECURITY PANEL, TYCO INTEGRATED SECURITY ACE8/SWH-1 OR SEPTA APPROVED EQUAL 4 2 LP2 TROUGH HP1ABOVE CB-1 LP2 LP1 LP2 6 19 UH-1 LP1 LP2 C 14 13 12 VAV + 1"C FOR DATA 3/4"C FOR POWER PUMP P-1 SD LP1 LP1 + LP2 + VAV + + 12 SINKS 100VA, 120V LP1 LP1 15 29 HAND DRYER 1500VA, 120V HAND DRYER 1500VA, 120V LP2 14 18 VAV 1"C FOR POWER 1"C FOR DATA CEILING FAN LP2 LP2 REFRIGERATOR 120V 20 LP1 23 22 26 28 30 EWC + 1 + LP1 18 REF. REF. REF. CR + 24 STANDARD OUTLET MOUNTING HEIGHT SHALL BE THE SAME AS ELECTRICAL HEIGHT, U.O.N. EXACT LOCATION OF OUTLETS SHALL BE AS INDICATED ON THE ARCHITECTURAL DRAWINGS. LP1 CEILING FAN LP2 LP2 17 27 REF. + LP2 LP2 LP2 EQUIPMENT AND/OR CABLE LOCATED AT THIS STAGE OF THE TELECOMMUNICATIONS CABLING CONFIGURATION IS EITHER EXISTING OR NOT COVERED UNDER THIS CONTRACT AND WILL BE FURNISHED BY OTHERS. OUTLET IDENTIFICATION NUMBERING SHALL BE AS DIRECTED BY OWNER'S M.I.S. DEPARTMENT INSTALLATION SHALL COMPLY WITH SPECIFICATIONS. EACH CABLING SHALL BE TAGGED AT ALL TERMINATIONS POINTS. 25 LP2 LP2 EWC LP2 C 32 33 ELECTRIC WH-2 1.5KVA, 120V 16 + WP LP1 31 TOILET (TYP 11) 50VA, 120V VAV 10 VAV VIDEO MONITORS, +48" (TYP 9) 120V & DATA LP2 LP1 27 LP1 LP1 LP1 LP2 LABEL ALL RACKS, FRAMES, CABINETS, BLOCKS, CABLES, CABLE SUPPORTS, ETC. IN ACCORDANCE WITH EIA/TIA 606. + LP1 10 LP1 6 TOILET (TYP 3) 50VA, 120V 16 MD PUMP P-2 SINK 35VA,120V ELECTRIC WH-2 1.5KVA, 120V MD TELECOMMUNICATIONS INSTALLATION SHALL COMPLY WITH ALL CURRENT APPLICABLE CODES, INCLUDING PHILADELPHIA ELECTRICAL CODES, THE NATIONAL ELECTRIC CODE, AND ALL APPLICABLE LOCAL CODES HAVING JURISDICTION. SINKS 100VA, 120V LP2 REC ON ROOF UH-2 4 PROVIDE FIRESTOPPING FOR ALL SLEEVE AND CONDUIT PENETRATIONS THROUGH RATED PARTITIONS OR FLOORS IN ACCORDANCE WITH THE SPECIFICATIONS. 11 21 LP2 LP2 8 TELECOMMUNICATION NOTES T75K VAV VAV MDP MD BMS PANEL 120V BOILER CONTROLS 120V LP1 HP1 HP1 3 2 1 MD LP1 7 LP1 5 CWT MD CT MD WIRE ALL ADA ACCESS BUTTONS TO CIRCUIT LP1#34 WP MAN CWT LP1 LP1 TRAP PRIMER TP-1 120V GAS WATER HEATER RE-CIRC PUMP 120V EF-4 1/25HP,120V ADDENDUM 1 WP EF-3 1/30HP,120V 4/17/15 LP1 1 LP1 PROVIDE TWO CAT 6 CABLES IN A 1" EMT CONDUIT HOMERUN BACK TO THE SECURITY PANEL IN THE COMM ROOM AND SAFE OFF BOTH ENDS. LP2 SECURITY PANEL 7 C 19 LP2 LP2 VAV 2 LP2 LP2 C LP2 VAV UP TO CU-1 21 LP1 KIOSK & PRINTER LP2 ELECTRIC WH-2 1.5KVA, 120V 34 23 1 TELEPHONE 4'x4' PLYWOOD LP2 26 3 AC-1 VAV 5 LP2 15 C CONDESATE PUMP 120V LP2 LP2 29 LP2 PRINTER/COPIER CR VAV 17 CEILING FAN LP1 C VAV 30 28 DMO CR TYP BURIED CONDUIT FOR TELE/DATA REFER TO DRAWING E102 FOR CONTINUATION 25 LP1 LP1 TYP DMO WP CR DMO CR LP1 CEILING FAN (TYP 4) 5.7A,120V 32 TYP TYP SCALE: SCALE FACTOR: DATE: DRAWN BY: CHECKED BY: WORK ORDER NO.: SHEET NUMBER DWG. NO.: OF SHT. NO.: OF ARCHIVE NO.: COMPUTER FILE NO.: REV. NO.: KEY NOTES EXHAUST FAN PROVIDED WITH DISCONNECT AND OVERLOAD PROTECTION BY OTHERS. DATA ROOM'S AIR CONDITIONER & CONDENSING UNIT POWERED THROUGH SINGLE POINT AT CONDENSING UNIT. EXTEND CONDUIT/WIRE TO AIR CONDITIONER. EXHAUST FAN EF-1 1/4HP, 120V ROOFTOP UNIT RTU-1 15HP SUPPLY FAN (3)11.2A COMPRESSORS (3)2A CONDENSORS WALKING PAD, TYP. 9 LP1 MECHANICAL EQUIPMENT PAD 100/100/3 WP WP REC CIRCUIT LP2#2 BELOW 3 MDP SKYLIGHT SKYLIGHT SKYLIGHT SKYLIGHT SKYLIGHT SKYLIGHT CU-1 DOWN TO AC WALKING PAD, TYP. SCALE: SCALE FACTOR: DATE: DRAWN BY: CHECKED BY: WORK ORDER NO.: SHEET NUMBER DWG. NO.: OF SHT. NO.: OF ARCHIVE NO.: COMPUTER FILE NO.: REV. NO.: PANEL: MDP LOCATION: ELECTRICAL ROOM 130 480/277 MOUNTING: BUILDING: FRANKFORD ADMINISTRATION BUILDING FED FROM: REFER TO SINGLE LINE ON DRAWING E002 BUS: GROUND 3 5 7 9 11 20 20 - - - COPPER ALUMINUM NEUTRAL: 100% DESCRIPTION OF LOAD (KVA) LOAD FEED THRU TOP A B C MLO BOTTOM SHUNT TRIP DESCRIPTION OF LOAD LOAD P AIC: 32,000 AMPS TRIP CKT. AMPS NO. ROOFTOP UNIT RTU-1 SPACE FCU-1 20 FCU-4 SPACE 20 SPACE SPACE - SPACE SPACE 125 - FCU-2 FCU-3 BUS: GROUND - SPACE - 2 4 6 8 10 12 14 15 MAIN BRK: MLO AMPS 3 SURFACE FLUSH COPPER ALUMINUM NEUTRAL: 100% ARC FLASH HAZARD CATEGORY: 2 DESCRIPTION OF LOAD (KVA) LOAD FEED THRU TOP A B C MLO BOTTOM SHUNT TRIP DESCRIPTION OF LOAD LOAD KEY NOTES P AIC: 14,000 AMPS PER PHASE CKT. TRIP NO. AMPS 1 MAIN BUS: 150 AMPS ISOLATED GROUND LUGS: 1 FEED: NEMA ENCLOSURE TYPE: FEEDER SIZE: REFER TO SINGLE LINE ON DRAWING E002 MANUFACTURER/MODEL:REFER TO SPECIFICATIONS (KVA) PANEL LP1 VIA TRANSFORMER VOLTS, 3 PHASE, 4 WIRE MOUNTING: BUILDING: FRANKFORD ADMINISTRATION BUILDING FED FROM: REFER TO SINGLE LINE ON DRAWING E002 (KVA) PANEL HP1 480/277 REFER TO SINGLE LINE DIAGRAM ON DRAWING E002 FOR FEEDER SIZE. PROVIDE 3#12, #12G, 3/4"C TRIP CKT. AMPS NO. (KVA) PUMP P-1 (1.5HP) PUMP P-2 (1.5HP) 15 2 3 4 5 6 7 20 LIGHTING SPARE 20 8 9 20 LIGHTING SPARE 20 10 11 20 LIGHTING SPARE 20 12 13 20 LIGHTING SPARE 20 14 15 20 LIGHTING SPARE 20 16 17 20 SPARE SPARE 20 18 19 20 SPARE SPACE - 20 21 20 SPARE SPACE - 22 23 20 SPARE SPACE - 24 25 - SPACE SPACE - 26 27 - SPACE SPACE - 28 29 - SPACE SPACE - 30 31 - SPACE SPACE - 32 33 - SPACE SPACE - 34 35 - SPACE SPACE - 36 37 - SPACE SPACE - 38 39 - SPACE SPACE - 40 41 - SPACE SPACE - 42 MAN CWT CWT 13 100 FLUSH ARC FLASH HAZARD CATEGORY: 2 (KVA) 150 MAIN BRK: 400 AMPS 3 SURFACE PER PHASE CKT. TRIP NO. AMPS PANEL: HP1 LOCATION: ELECTRICAL ROOM 130 MAIN BUS: 400 AMPS ISOLATED GROUND LUGS: 1 FEED: NEMA ENCLOSURE TYPE: FEEDER SIZE: REFER TO SINGLE LINE ON DRAWING E002 MANUFACTURER/MODEL:REFER TO SPECIFICATIONS 1 VOLTS, 3 PHASE, 4 WIRE SURFACE BUILDING: FRANKFORD ADMINISTRATION BUILDING FED FROM: REFER TO SINGLE LINE ON DRAWING E002 BUS: GROUND COPPER MAIN BUS: 250 AMPS MAIN BRK: 250 AMPS 3 P FLUSH ALUMINUM NEUTRAL: 200% AIC: 10,000 AMPS ISOLATED GROUND LUGS: 1 FEED: NEMA ENCLOSURE TYPE: FEEDER SIZE: REFER TO SINGLE LINE ON DRAWING E002 MANUFACTURER/MODEL:REFER TO SPECIFICATIONS ARC FLASH HAZARD CATEGORY: 1 FEED THRU TOP SHUNT TRIP PER PHASE CKT. TRIP NO. AMPS DESCRIPTION OF LOAD (KVA) LOAD (KVA) DESCRIPTION OF LOAD LOAD A B C MLO BOTTOM TRIP CKT. AMPS NO. PANEL: LP2 LOCATION: ELECTRICAL ROOM 130 MOUNTING: SURFACE BUILDING: FRANKFORD ADMINISTRATION BUILDING FED FROM: REFER TO SINGLE LINE ON DRAWING E002 BUS: GROUND COPPER 208/120 VOLTS, 3 PHASE, 4 WIRE MAIN BUS: 250 AMPS MAIN BRK: MLO AMPS 3 P ALUMINUM NEUTRAL: 200% AIC: 10,000 AMPS FLUSH ISOLATED GROUND LUGS: 1 FEED: NEMA ENCLOSURE TYPE: FEEDER SIZE: REFER TO SINGLE LINE ON DRAWING E002 MANUFACTURER/MODEL:REFER TO SPECIFICATIONS ARC FLASH HAZARD CATEGORY: 1 FEED THRU TOP DESCRIPTION OF LOAD (KVA) (KVA) LOAD (KVA) DESCRIPTION OF LOAD LOAD A B C MLO BOTTOM SHUNT TRIP PER PHASE CKT. TRIP NO. AMPS ADDENDUM 1 MOUNTING: 208/120 VOLTS, 3 PHASE, 4 WIRE TRIP CKT. AMPS NO. 4/17/15 PANEL: LP1 LOCATION: ELECTRICAL ROOM 130 (KVA) 20 BMS PANEL TELEPHONE BOARD REC 20 2 1 20 REC SERVER ROOM REC MECH RM, EXTERIOR 20 2 3 20 BOILER CONTROLS FIRE ALARM CONTROL PANEL 20 4 3 20 REC SERVER ROOM REC 112A, ELEC RM, C102 20 4 5 20 TRAP PRIMER TP-2 SMOKE DAMPERS 20 6 5 20 REC SERVER ROOM REC 108, 110 20 6 7 20 RE-CIRC PUMP DAMPERS, EF-5, EF-6 20 8 7 20 REC SERVER ROOM COMPUTER REC 102, 104, 106, 108, 110 20 8 9 20 EXHAUST FAN EF-1 (1/4HP) HANDS-FREE MENS RESTROOM 20 10 9 20 SPARE REC 102, 104, 106 20 10 11 20 EXHAUST FAN EF-2 (1/6HP) HANDS-FREE WOMENS RESTROOM 20 12 11 20 REC RESTROOMS 122, 124 REC RESTROOMS 111, 113 20 12 13 20 WATER HEATER WH-2 HANDS-FREE RESTROOMS 111 & 113 20 14 13 20 SPARE REC KITCHEN 20 14 15 20 WATER HEATER WH-2 ELECTRIC WATER COOLER KITCHEN 20 16 15 20 REC C101, 100, EXTERIOR REC KITCHEN 20 16 17 20 WATER HEATER WH-2 ELECTRIC WATER COOLER LOUNGE 20 18 17 20 REC 101 REC KITCHEN 20 18 19 20 VAV CONTROLLERS 20 20 19 20 REC 101 REFRIGERATOR 109 20 20 21 20 VAV CONTROLLERS AIR CONDITIONER & CONDENSING UNIT DATA ROOM 22 21 20 REC 101 REFRIGERATOR 120 20 22 23 20 CEILING FANS 120 HEATERS 130,131, DAMPERS 20 24 23 20 REC 120 REFRIGERATOR 120 20 24 25 20 CEILING FANS 120 CONDESATE PUMP 20 26 25 20 REC 120, 125, 126, C103 REFRIGERATOR 120 20 26 27 20 HAND DRYER WOMENS RESTROOM DOOR CONTROLLER 20 28 27 20 REC 101A, 101B, 107, EXTERIOR REC 120 20 28 29 20 HAND DRYER WOMENS RESTROOM DOOR CONTROLLER 20 30 29 20 PRINTER/COPIER REC 120 20 30 31 20 HAND DRYER MENS RESTROOM DOOR CONTROLLER 20 32 31 20 SPARE VIDEO MONITORS 120 20 32 33 20 HAND DRYER MENS RESTROOM ADA DOOR ASSIST BUTTONS 20 34 33 20 SPARE VIDEO MONITORS 120 20 34 35 20 SPARE SPARE 20 36 35 20 SPARE SPARE 20 36 37 20 SPARE SPARE 20 38 37 20 SPARE SPARE 20 38 39 20 SPARE SPARE 20 40 39 20 SPARE SPARE 20 40 41 20 SPARE SPARE 20 42 41 20 SPARE SPARE 20 42 1 1 SCALE: SCALE FACTOR: DATE: DRAWN BY: CHECKED BY: WORK ORDER NO.: SHEET NUMBER DWG. NO.: OF SHT. NO.: OF ARCHIVE NO.: COMPUTER FILE NO.: REV. NO.:
© Copyright 2026 Paperzz