Thermostat Sub. Set. LC204

Thermostat Submittal Data
Contractor:
P.O.:
Engineer:
ATP32H01S/ASUB01
Project Name:
Unit Tag:
Three Heat/Two Cool
ACO/MCO Programmable
Print Form
Clear Form
6-3/4 (172)
1/16 (2)
3-1/4 (82)
1-3/8 (35)
Specifications:
Electrical Rating:
1-7/8
(47)
• 24 Vac, 50/60 Hz. nominal
20 to 30 Vac, 50/60 Hz.
4-1/8
(105)
Minimum Stage Operation Time:
4-3/4
(121)
• Minimum On (Heat and Cool): factory setting 2 minutes;
option 0 minutes.
• Minimum Off (Cool and Heat Pump): factory setting 4
minutes; option 0, 1, 3, 5 minutes.
1-11/16
(43)
7-5/16 (186)
Humidity Ratings:
• 5% to 90% RH, noncondensing.
7/8
(22)
Clock Accuracy:
• +/-1 minute per month.
Wiring:
R
G
G
Y1
X
R
O
X1
C
Y1
AL1
Y2
Y1
O
O/W2
Y2
R
Application:
DXM Control
The ATP32H01S Thermostat and ASUB01 Subbase provide 3
stages heating, 2 stages cooling, and programmable temperature
control of 24V WSHP equipment.
Y
O
W
A
9/16
(14)
AL2
Fan
W1
System
G
Copy
Continous
Unoccupied
ASUB01
ASUB01
Heat/Cool
Settings
G
Day
X
Clear
Start Time
Change
Time/Temp
R
Set Current
Day/Time
Unoccupied
Temp
X1
Temporary
Occupied
Occupied
Temp
C
Unoccupied
Start Time
AL1
Occupied
Start Time
4-5/8
(117)
X4
Run
Program
Set Temperature
X4
5 (127)
Set Program
CXM Control
* Note: Install jumper between X4 and X to power thermostat LED's from transformer in heat
pump control box.
Features:
• 7-day programming.
• Two Occupied and two Unoccupied periods per day.
• Individual heat and cool setpoints available for
Occupied and Unoccupied periods.
• Proportional plus Integral (P+I) control eliminates
temperature fluctuations.
• Intelligent Recovery® control automatically optimizes
equipment start times based on building load.
• Intelligent Fan™ feature energizes fan continuously in the
Occupied periods. Fan can also be configured for auto
operation.
• Automatic or manual changeover.
• Convenient overrides allow temporary setpoint changes.
• Keypad lockout available.
• Set points are permanently held in memory (no
batteries used) and retained during power outages.
• Fault LED on subbase.
*LC204*
LC204
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as
described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other
information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.
The latest version of this document is available at www.climatemaster.com.
Rev.: 09/09/02