RS Room Sensors Technical Instructions

RS Room Sensors
Technical Instructions
What are RS Room Sensors?...................................................................................... 2
RS Standard features ................................................................................................ 3
Local access port........................................................................................... 3
To address an RS Standard ............................................................................ 3
RS Plus features........................................................................................................ 4
Slide potentiometer....................................................................................... 4
MANUAL ON button ....................................................................................... 4
OCCUPIED LED.............................................................................................. 4
Local access port........................................................................................... 4
RS Pro features ......................................................................................................... 5
Display.......................................................................................................... 5
MANUAL ON button ....................................................................................... 5
WARMER and COOLER buttons ...................................................................... 6
INFO button................................................................................................... 6
Local access port........................................................................................... 6
RS Pro-F features ...................................................................................................... 7
MANUAL ON button ....................................................................................... 7
INFO button................................................................................................... 7
MODE button................................................................................................. 7
FAN button .................................................................................................... 7
To mount an RS sensor .............................................................................................. 8
Wiring an RS sensor................................................................................................... 9
Rnet wiring specifications .............................................................................. 9
To wire an RS sensor...................................................................................... 9
To communicate through the local access port .......................................................... 11
To set up a Local Access connection in WebCTRL ..........................................11
Troubleshooting ...................................................................................................... 13
RS Standard or RS Plus ...............................................................................13
RS Pro or RS Pro-F ......................................................................................13
Automated Logic Corporation • 1150 Roberts Blvd. • Kennesaw, GA 30144 • 770/429-3000 • Fax 770/429-3001 •
www.automatedlogic.com • © 2006 Automated Logic Corporation. All rights reserved throughout the world. Automated Logic Corporation,
the Automated Logic logo, WebCTRL, EIKON, BACview, SuperVision, and InterOp are registered trademarks, and Alert is a trademark of
Automated Logic Corporation. BACnet® is a registered trademark of ASHRAE. All other brand and product names are trademarked by their
respective companies.
What are RS Room Sensors?
RS sensors are thermistor-based temperature sensors used with any control module that
connects to the Rnet such as an LGR, ME-LGR, SE line, ME line, ZN line, or WebZone
control module. The four types of RS sensors are RS Standard, RS Plus, RS Pro, and RS
Pro-F.
An Rnet can consist of any of the following combinations of devices wired in a daisy-chain
or star configuration:
•
1 RS Plus, RS Pro, or RS Pro-F
•
1–4 RS Standards
•
1–4 RS Standards, and 1 RS Plus, RS Pro, or RS Pro-F
•
Any of the above combinations, plus up to 2 BACview's, but no more than 6 devices
total
NOTES
○
If you use two BACview's, one can be powered by the Rnet, but the other must be
externally powered.
○
ZN line control modules do not support BACview6’s.
RSRoom
RoomSensors
Sensors••Rev.
Rev.9/7/2006
9/7/2006
RS
22
2006Automated
AutomatedLogic
LogicCorporation
Corporation
©©2006
RS Standard features
2.75 in.
(6.9 cm)
4.75 in.
(12.1 cm)
Setscrew
Local access port
Local access port
See To communicate through the local access port (page 11).
To address an RS
Standard
The default address of an RS Standard is 1. The first RS Standard retains this address. To
change the address of each additional RS Standard on the network:
1
Pull the back plate off the sensor, pulling from the bottom first.
2
Remove the two hexagonal screws that attach the circuit board to the cover plate.
3
Remove the cover plate.
4
On the circuit board, set the address jumper to 2, 3, or 4. Each sensor must have a
unique address on the Rnet.
5
Attach the circuit board to the cover plate with the hexagonal screws.
RSRoom
RoomSensors
Sensors••Rev.
Rev.9/7/2006
9/7/2006
RS
33
2006Automated
AutomatedLogic
LogicCorporation
Corporation
©©2006
RS Plus features
2.75 in.
(6.9 cm)
4.75 in.
(12.1 cm)
Slide
potentiometer
Setscrew
Local access port
Slide
potentiometer
To raise or lower the zone's setpoint, move the slide potentiometer to WARMER or
COOLER. The maximum you can adjust the setpoint is defined in the Max Adjust field on
the RS sensor microblock's Properties page in WebCTRL.
MANUAL ON
button
Press the MANUAL ON button one time to override the schedule and set the zone to
occupied for the amount of time defined in the Each pulse field on the RS sensor
microblock's Properties page in WebCTRL. Press the button again to incrementally
increase the time. For example, if the Each pulse field is set at five minutes, press the
button once for an occupancy of five minutes, twice for ten minutes, and so on. The
maximum length of time you can override the schedule is defined in the Max Accum field
on the Properties page.
To cancel the override, hold down the MANUAL ON button until the OCCUPIED LED turns
off.
OCCUPIED LED
The OCCUPIED LED lights when the zone is occupied from a regular schedule or a manual
override.
Local access port
See To communicate through the local access port (page 11).
RSRoom
RoomSensors
Sensors••Rev.
Rev.9/7/2006
9/7/2006
RS
44
2006Automated
AutomatedLogic
LogicCorporation
Corporation
©©2006
RS Pro features
2.75 in.
(6.9 cm)
4.75 in.
(12.1 cm)
Setscrew
Local access port
Display
The display shows occupancy, zone temperature, and an alarm bell icon. Celsius values
are to the nearest 0.5 degree; Fahrenheit values are to the nearest full degree.
The display shows Occupied when the zone is occupied from a regular schedule or from a
manual override.
MANUAL ON
button
Press the MANUAL ON button one time to override the schedule and set the zone to
occupied for the amount of time defined in the Each pulse field on the RS sensor
microblock's Properties page in WebCTRL. Press the button again to incrementally
increase the time. For example, if the Each pulse field is set at five minutes, press the
button once for an occupancy of five minutes, twice for ten minutes, and so on. The
maximum length of time you can override the schedule is defined in the Max Accum field
on the Properties page.
The display shows the duration of the override in minutes. If the override time exceeds
199 minutes, the display shows the time in hours.
To cancel the override, hold the button down until 0 displays. Wait five seconds for the
display to show the current zone temperature again.
RSRoom
RoomSensors
Sensors••Rev.
Rev.9/7/2006
9/7/2006
RS
55
2006Automated
AutomatedLogic
LogicCorporation
Corporation
©©2006
WARMER and
COOLER buttons
To raise or lower the zone's setpoint:
1
Press WARMER or COOLER to display the current average setpoint (the average
between the heating and cooling setpoints).
2
Press WARMER or COOLER again to raise or lower the setpoint. You can adjust the
setpoint by no more than the amount defined in the Max Adjust field on the RS sensor
microblock's Properties page in WebCTRL.
NOTE Pressing WARMER or COOLER will override an unoccupied schedule and set the
zone to occupied for the amount of time defined in the Each pulse field on the RS sensor
microblock's Properties page in WebCTRL.
INFO button
Press the INFO button to cycle through:
•
•
•
•
•
Local access port
the zone temperature
the outside air temperature, if enabled in the control program
the override time, in minutes
the heating setpoint
the cooling setpoint
See To communicate through the local access port (page 11).
RSRoom
RoomSensors
Sensors••Rev.
Rev.9/7/2006
9/7/2006
RS
66
2006Automated
AutomatedLogic
LogicCorporation
Corporation
©©2006
RS Pro-F features
2.75 in.
(6.9 cm)
4.75 in.
(12.1 cm)
Setscrew
Local access port
The RS Pro-F has all the features of the RS Pro (page 5) plus the additional functionality
described for the following four buttons.
NOTE Much of the RS Pro-F's functionality depends on the setup of the RS Zone Sensor
with Fan Control microblock in EIKON for WebCTRL. See the system engineer for
instructions on using these four buttons.
MANUAL ON
button
The Timed Local Override section of the microblock dialog box determines if pressing the
MANUAL ON button sets the zone to occupied for a set amount of time in the same
manner as the RS Pro or sets the zone to continuously occupied.
INFO button
This button cycles through the same information as the RS Pro and up to 4 additional
inputs defined in the Optional Inputs section of the microblock dialog box in EIKON for
WebCTRL.
MODE button
The MODE button lets you cycle through up to 4 operational modes defined with custom
programming in EIKON for WebCTRL. The sensor displays various information for each
mode based on the setup in the Mode section of the microblock dialog box.
FAN button
Press the FAN button to select the controlled equipment's fan speed. A fan icon on the
left side of the display indicates when the fan is on.
RSRoom
RoomSensors
Sensors••Rev.
Rev.9/7/2006
9/7/2006
RS
77
2006Automated
AutomatedLogic
LogicCorporation
Corporation
©©2006
To mount an RS sensor
1
Pull the backplate off the RS sensor. You may need to turn the setscrew in the bottom
of the sensor clockwise until you can remove the backplate.
2
Pull the Rnet communication cable through the wire guide in the backplate.
3
Use 2 screws to mount the backplate to the wall or outlet box.
4
Wire the RS sensor to a control module or another RS sensor. See Wiring an RS
sensor (page 9).
5
Attach the sensor's cover and circuit board to the mounted backplate, inserting the
top first.
6
Turn the setscrew one full turn counterclockwise so that the cover cannot be
removed.
RSRoom
RoomSensors
Sensors••Rev.
Rev.9/7/2006
9/7/2006
RS
88
2006Automated
AutomatedLogic
LogicCorporation
Corporation
©©2006
Wiring an RS sensor
The Rnet communicates at a rate of 115 kbps and should be wired in a daisy-chain, star,
or hybrid configuration.
Rnet wiring
specifications
To wire an RS
sensor
NOTE Use the specified type of wire and cable for maximum signal integrity.
Description
4 conductor, overall shielded, CMP, 18 AWG (7x0152),
plenum rated cable
Conductor
18 AWG (7x0152) bare copper if using BACview on Rnet.
22 AWG (7x0152) bare copper if only RS sensors on Rnet.
Maximum length
500 feet (152 meters)
Insulation
Low-smoke PVC (or equivalent)
Color Code
Black, white, green, red
Shielding
Aluminum/Mylar shield (100% coverage) with TC drain wire
Jacket color
White
UL temperature rating
32–167°F (0–75°C)
Voltage
300 Vac, power limited
Listing
UL: NEC CL2P, or better
1
Turn off the control module's power.
2
Remove the sensor's cover. See To mount an RS sensor (page 8).
3
Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick
the inner insulation.
Outer jacket
.25 in.
(.6 cm)
Foil shield
Inner insulation
4
Strip about .25 inch (.6 cm) of the inner insulation from each wire.
5
If wiring 1 cable to the RS sensor, cut the shield wire off at the outer jacket, then wrap
the cable with tape at the outer jacket to cover the end of the shield wire.
If wiring 2 cables in a daisy-chain configuration, twist together the shield wires, then
wrap the shield wires with tape.
RSRoom
RoomSensors
Sensors••Rev.
Rev.9/7/2006
9/7/2006
RS
99
2006Automated
AutomatedLogic
LogicCorporation
Corporation
©©2006
6
Insert the other 4 wires into the RS sensor's screw terminal connector. If wiring 2
cables, insert like-colored wires into each terminal.
CAUTION Allow no more than .06 inch (1.5 mm) bare communication wire to
protrude. If bare communication wire contacts the cable's foil shield, shield wire, or a
metal surface other than the terminal block, the sensor may not communicate
correctly.
.06 in.
(1.5 mm)
Correct
Correct
Incorrect
Incorrect
7
Connect the other end of the cable to the control module's Rnet port or to another RS
sensor.
NOTES
○
Insert the shield wire with the ground wire into the control module's GND
terminal.
○
Use the same polarity throughout the Rnet.
8
Turn on the control module's power.
9
Reattach the sensor's cover and circuit board to the backplate, inserting the top first.
RSRoom
RoomSensors
Sensors••Rev.
Rev.9/7/2006
9/7/2006
RS
10
10
2006Automated
AutomatedLogic
LogicCorporation
Corporation
©©2006
To communicate through the local access port
You can connect to the Local Access port of an RS Room Sensor to perform test and
balance or to make changes to any device on the network.
PREREQUISITES
•
A computer with an EIA-232 port
•
An APT with cables. See the APT Technical Instructions
(http://info.automatedlogic.com).
NOTE Contact your Automated Logic Corporation dealer for details and availability of
the APT and cables.
1
Connect the computer to the sensor's Local Access port.
NOTE To insert the cable connector into the sensor's Local Access port, first insert
the connector’s prongs into the port, then tilt the connector downward to insert the
rest of the connector into the port.
Rnet
adapter
cable
9-pin
APT cable
8-pin
APT cable
To set up a Local
Access
connection in
WebCTRL
2
Set the APT's Mode Select switch to 485.
3
Set the APT's Exec. 4 Relay switch to Network.
1
On WebCTRL's CFG tree, select Connections.
2
On the Configure tab, click Add.
3
From the Type drop-down list, select BACnet Local Access.
4
Optional: Edit the Description.
5
Type the computer's Port number that the APT is connected to.
6
Set the Baud rate to 115200.
RSRoom
RoomSensors
Sensors••Rev.
Rev.9/7/2006
9/7/2006
RS
11
11
2006Automated
AutomatedLogic
LogicCorporation
Corporation
©©2006
7
Click Accept.
8
On the View tab, click the drop-down arrow next to your device's network Connection,
then select BACnet Local Access.
9
Click Accept.
10 On the Configure tab, select BACnet Local Access, then click Start.
11 On the NET tree, select the control module that you are connected to.
T
12 Click the menu button
, then select Manual Command.
13 Type rnet here in the dialog box, then click OK.
14 Repeat step 12, type modstat in the dialog box, then click OK. If WebCTRL
displays a modstat report, WebCTRL is communicating with the control module.
RSRoom
RoomSensors
Sensors••Rev.
Rev.9/7/2006
9/7/2006
RS
12
12
2006Automated
AutomatedLogic
LogicCorporation
Corporation
©©2006
Troubleshooting
Use the following tables to troubleshoot your RS sensor.
RS Standard or
RS Plus
RS Pro or
RS Pro-F
If LED on back of circuit board...
Then sensor...
Is not lit
Has no power
Blinks 1 time per second
Has power, but is not communicating
Blinks 2.5 times per second
Is correctly wired and communicating
If display shows...
Then sensor...
Nothing
Has no power
All display elements
Has power, but is not communicating
Only the temperature and current status
Is correctly wired and communicating
RSRoom
RoomSensors
Sensors••Rev.
Rev.9/7/2006
9/7/2006
RS
13
13
2006Automated
AutomatedLogic
LogicCorporation
Corporation
©©2006