Coordination tables between circuit breaker and Canalis electrical busbar trunking Complementary technical information Enhanced discrimination through cascading Rated current of the upstream busbar trunking: 315 and 400 A Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Discrimination limit between upst. and downst. circuit breakers (kA) Reinforced breaking capacity of the downstream circuit breaker (kA) Reinforced protection of the downstream busbar trunking (kA) Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Discrimination limit between upst. and downst. circuit breakers (kA) Reinforced breaking capacity of the downstream circuit breaker (kA) Reinforced protection of the downstream busbar trunking (kA) NSX400N Micrologic 2.0/5.0/6.0 KSA/KVA/KVC 315 and 400 A 45 NSX400H Micrologic 2.0/5.0/6.0 KSA/KVA/KVC 315 and 400 A 70 NSX400L Micrologic 2.0/5.0/6.0 KSA/KVA/KVC 315 and 400 A 150 NSX100F NSX160F TMD/Micrologic 2.0/5.0/6.0 KSA KSA 100 A 160 A NSX100N NSX160N TMD/Micrologic 2.0/5.0/6.0 KSA KSA 100 A 160 A NSX100N NSX160N TMD/Micrologic 2.0/5.0/6.0 KSA KSA 100 A 160 A 45 45 70 70 150 150 45 45 70 70 150 150 45 45 70 70 70 70 NSX400N Micrologic 2.0/5.0/6.0 KSA/KVA/KVC 315 and 400 A 45 NSX400H Micrologic 2.0/5.0/6.0 KSA/KVA/KVC 315 and 400 A 70 NSX400L Micrologic 2.0/5.0/6.0 KSA/KVA/KVC 315 and 400 A 150 NSX100N TMD/Micrologic 2.0/5.0/6.0 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A NSX100N TMD/Micrologic 2.0/5.0/6.0 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A NSX100N/H TMD/Micrologic 2.0/5.0/6.0 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A 45 45 45 70 70 70 150 150 150 45 45 45 70 70 70 150 150 150 45 45 45 50 50 50 50 50 50 Rated current of the upstream busbar trunking: 200 and 250 A Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Discrimination limit between upst. and downst. circuit breakers (kA) Reinforced breaking capacity of the downstream circuit breaker (kA) Reinforced protection of the downstream busbar trunking (kA) Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Discrimination limit between upst. and downst. circuit breakers (kA) Reinforced breaking capacity of the downstream circuit breaker (kA) Reinforced protection of the downstream busbar trunking (kA) NSX250N TDM/Micrologic 2.0/5.0/6.0 KSA/KVA/KVC 200 and 250 A 36 NSX250H TDM/Micrologic 2.0/5.0/6.0 KSA/KVA/KVC 200 and 250 A 70 NSX250L TDM/Micrologic 2.0/5.0/6.0 KSA/KVA/KVC 200 and 250 A 150 NSX100F TMD/Micrologic 2.0/5.0/6.0 KSA-10 100 A NSX100N TMD/Micrologic 2.0/5.0/6.0 KSA-10 100 A NSX100H TMD/Micrologic 2.0/5.0/6.0 KSA-10 100 A 36 36 36 36 70 150 36 70 70 NSX250N TDM/Micrologic 2.0/5.0/6.0 KSA/KVA/KVC 200 and 250 A 36 NSX250H TDM/Micrologic 2.0/5.0/6.0 KSA/KVA/KVC 200 and 250 A 70 NSX250L TDM/Micrologic 2.0/5.0/6.0 KSA/KVA/KVC 200 and 250 A 150 NSX100F TMD/Micrologic 2.0/5.0/6.0 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A NSX100N TMD/Micrologic 2.0/5.0/6.0 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A NSX100N/H TMD/Micrologic 2.0/5.0/6.0 40 A 63 A 100 A KN KN KN 40 A 63 A 100 A 36 36 36 36 36 36 36 36 36 36 36 36 70 70 70 150 150 150 36 36 36 50 50 50 70 50 50 256 Book.indb 256 09/12/2008 14:33:05
© Copyright 2026 Paperzz