Product/Technical Issue Date MS4PMUHVT 09/30/02 MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack The MS4PMUHVT Multi-Stage Electronic Temperature Control is intended for multi-stage temperature control applications. The MS4PMUHVT control is specifically designed for the control of applications with up to four stages in the following configurations: • four cooling stages with common setpoint • four heating stages with common setpoint • four stages with deadband (two heating stages and two cooling stages with common setpoint) • two independent sets of two dependent stages (two heating stages and two cooling stages with independent setpoints) Figure 1: MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Features and Benefits ❑ Single Package Provides the functionality of multiple control components at a cost-effective price. ❑ Easily Readable Display Displays main sensor or evaporator sensor temperatures; Helps troubleshoot control, Provides alarm codes. ❑ Accurate, Interchangeable Provides accurate control performance with up to 300 feet (91 m) of sensor wiring. (An offset is provided for longer wiring.) Temperature Sensor ❑ Nonvolatile Memory Retains user-programmed settings in event of power loss ❑ Heavy-Duty Relays Allow direct control of equipment; Reduce installation time. © 2002 Johnson Controls, Inc. Part No. 24-8782-5, Rev. C Code No. LIT-125195 1 www.johnsoncontrols.com FCC Compliance Statement This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense. Canadian Compliance Statement Operation Mode Selection Mode Selection allows selection of one of several modes: • Direct mode for cooling applications • Reverse mode for heating applications • Deadband mode for applications requiring cooling and heating with a common setpoint and a deadband • Independent Setpoint mode for applications requiring cooling and heating with one setpoint for heating and a second (independent) setpoint for cooling This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Stage Control Several settings define the control functions for the stages: • Setpoints and Differentials setting establish the temperature-control ranges. Application • Cycle Delays establish a set time interval between heating or cooling cycle restarts to avoid excessive cycling. • Soft Start controls the rate at which temperature approaches the Setpoint on power-up or when Binary Input Option 3 is selected. This feature is useful when starting equipment where merchandise in the controlled space needs to be slowly brought to the desired temperature (Setpoint). If this feature is used, the control activates up to four stages in succession to slowly bring the sensed temperature to the desired temperature (Setpoint) at the user-selected rate. IMPORTANT: The MS4PMUHVT Multi-Stage Temperature Control is intended to control equipment under normal operating conditions. Where failure or malfunction of the MS4PMUHVT control could lead to an abnormal operating condition that could cause personal injury or damage to the equipment or other property, other devices (limit or safety controls) or systems (alarm or supervisory systems) intended to warn of, or protect against, failure or malfunction of the MS4PMUHVT control must be incorporated into and maintained as part of the control system. The MS4PMUHVT control provides direct control in many applications: Alarm Management Several settings define the control functions for alarms: • cooling tower pump and/or fan control • • rooftop heating or cooling units • High and Low Temperature Alarms provide notification of temperatures that exceed user-designated high and low limits. boiler or pump control • • space temperature control Alarm Time Delay keeps short-duration temperature changes from triggering an alarm. • compressor or chiller staging • Alarm Differential keeps the alarm from cycling rapidly on and off due to minor temperature fluctuations. • Alarm Codes assist in troubleshooting. The MS4PMUHVT control has four heavy-duty relays. See electrical ratings in Table 6 for more information. 2 MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin Binary Input Response Binary Input Function allows the user to select how the control responds to a binary input (switch) if the binary input contacts are open for a time (minutes) longer than the Binary Input Time Delay. Installation See Mounting and Wiring for installation information. Dimensions 1-3/4 (44) Additional Features The MS4PMUHVT control uses several other settings to control specific features: • 1-5/8 (42) Keyboard Locking disables/enables change of the setpoint and other functions, reducing accidental or unauthorized changes of the control settings. • Self-test Procedure initiates a cycle of all outputs and tests all LEDs. See Initiating a Manual Self-Test. • Dual Sensor Temperature Reset resets the setpoint based on the difference between the Auxiliary Temperature Sensor (ATS) and the Setpoint to provide energy savings. See Temperature Reset. For additional information about control functions and how to program them, see Programming the Control and Control Functions. 7-15/16 (202) 3 (76) 3-5/8 (92) 2-3/8 (61) Figure 3: Relay Pack with Mounting Bracket Dimensions, in. (mm) 2-3/4 (70) Control Module Front Panel The control module has an LED display and buttons for entering programming information and activating various features. 2-5/16 (58) The display has three LED digits and a minus indicator. It displays a temperature range from -40 to 176°F (-40 to 80°C) in increments of 1F° or C°. The display also features three relay status LEDs. • LED 1 indicates that the Stage 1 Relay is energized. • LED 2 indicates that the Stage 2 Relay is energized. • LED 3 indicates that the Stage 3 Relay is energized. 6 (152) 3 (75) 2-11/16 (68) 1-1/8 (28) 1-3/8 (35) Figure 4: Control Module Dimensions, in. (mm) 1/4 (6) 2 (50) 78-3/4 (2000) Relay Status LEDs Up Button Enter Button Figure 5: A99BB-200C Sensor Dimensions, in. (mm) Down Button Figure 2: Control Module Front Panel and Display MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin 3 Mounting The MS4PMUHVT control is not position-sensitive but should be mounted for convenient wiring and adjustment. The MS4PMUHVT control may be mounted as a single unit or the control module and relay pack may be separated and mounted individually. Mounting the MS4PMUHVT Control as a Single Unit Before mounting the relay pack, ensure that there is sufficient space. Follow these steps to mount the relay pack: 1. Hold the MS4PMUHVT control against the surface and use it as a template to trace the mounting slots. 2. Drill holes for mounting screws in the holes indicated. 3. Use three screws (No. 8 or No. 10 size) to mount the MS4PMUHVT control. Mounting the Control Module and Relay Pack Separately Mount the relay pack and the control module within 18 in. (46 cm) of each other. 2. Drill holes for mounting screws in the slots indicated. 3. Use three screws (No. 8 or No. 10 size) to mount the relay pack. Mounting the Control Module Before mounting the control module, ensure that there is sufficient free space [at least 2-3/4 inches (70 mm)] behind the mounting surface. Follow these steps to mount the control module: 1. Cut a hole 1-3/16 x 2-13/16 inches (29 x 71 mm). 2. Remove the mounting clip from the control module. 3. Insert the control module into the hole. 4. Install the retaining clip and slide forward to adjust for tightness. 5. Reconnect the wires on the terminals in the relay pack to the corresponding terminals on the control module. See Figures 7-9. Control Module Mounting Clip Removing the Control Module from the Relay Pack Follow these steps to separate the control module and the relay pack. See Figures 6-7. 1. Locate the mounting clip that holds the control module to the mounting bracket on the relay pack. Figure 6: Removing the Mounting Clip and Control Module V2 2. Squeeze the forward portion of the mounting clip together and slide the mounting clip back to remove the mounting clip from the back of the control module. V1 3. Pull the control module out of the mounting bracket on the relay pack. 4. Disconnect the wiring from the control module and the relay pack terminals V1, V2, O1, and O2. See Figures 7-9. Mounting the Relay Pack Before mounting the relay pack, ensure that there is sufficient space. Follow these steps to mount the relay pack: 4 D3 D4 1. Hold the relay pack with mounting bracket against the surface and use as a template to trace the mounting slots. O1 O2 Figure 7: Relay Pack Terminal Positions on the Circuit Board MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin Wiring ! Table 1: Sensor Wire Size and Length Wire Size and Length 18 AWG 20 AWG 22 AWG WARNING: Risk of Electric Shock. To avoid electric shock or damage to equipment, disconnect all power supplies before wiring any connections. More than one disconnect may be necessary to completely de-energize equipment. Wiring Sensors and Binary Inputs Wire the sensors and binary input (if used) as shown in Figures 8-9. The Sensor (S1 or S2) and Sensor Common (SC) wires are interchangeable when using the A99B temperature sensors. The binary input shares a common terminal with the sensors. 12VAC V1 V2 D BLK WHT RED GRN O1 O2 V1 V2 O1 O2 Binary Input (Switch) S2 SC S1 Sensor Common Auxiliary Temperature Sensor Main Temperature Sensor 300-599 ft 190-374 ft 120-239 ft 1 F° 600-899 ft 375-564 ft 240-349 ft 2 F° 900+ ft 565+ ft 350+ ft 3 F° 165-329 m 105-204 m 65-129 m 1 C° 330-495 m 205-310 m 130-195 m 2 C° Wiring the Relay Pack ! Note: Black boxes indicate unused terminals. Internal to Control Offset WARNING: Risk of Electric Shock. To avoid electric shock or damage to equipment, disconnect all power supplies before wiring any connections. More than one disconnect may be necessary to completely de-energize equipment. See Figure 10 for arrangement of terminals on the terminal block in the relay pack. See Figures 11-12 for sample wiring diagrams. Follow these wiring guidelines: • All wiring must conform to the National Electrical Code and local regulations. Figure 8: Wiring the Control Module MS • Use 14 AWG copper wire for motor loads up to 12 FLA and non-inductive loads up to 15 A. Loosen screw to open terminal; tighten screw to secure wiring. • Use 12 AWG copper wire with an insulation rating of 75°C (minimum) for motor loads up to 16 FLA and non-inductive loads up to 20 A. • Use wire no longer than 50 feet (15 m). • All circuits must have a common disconnect and be connected to the same pole of the disconnect. V1 V2 O1 O2 D S2 SC S1 V1 V2 O1 O2 D S2 SC S1 Relay Pack Terminal Block Insert wiring here. Note: Black boxes indicate unused terminals. Figure 9: Rear View of the Control Module Use Temperature Sensor Offset to compensate for sensor leads longer than 300 ft (if °F is used) or 165 m (if °C is used). See Table 1 and Temperature Management Functions: Temperature Sensor Offset. Terminal Labels on Circuit Board NO1 CM1 L2 120 (Not NO2 CM2 NO4 Used) NO3 NC1 CM3 NC3 240 NC2 CM4 NC4 Figure 10: Relay Pack Terminal Block MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin 5 Note: All circuits must have a common disconnect and be connected to the same pole of the disconnect. L1 L2 Internal to Relay Pack Control Relay 1 240 120 NO1 CM1 NC1 Load 1 Control Relay 2 NO2 CM2 NC2 Load 2 Control Relay 3 NO3 CM3 NC3 Load 3 Control Relay 4 NO4 CM4 NC4 Load 4 Figure 11: Typical 240 VAC Relay Pack Wiring Connections 120 VAC Neutral Note: All circuits must have a common disconnect and be connected to the same pole of the disconnect. Internal to Relay Pack Control Relay 1 240 120 NO1 CM1 Load 1 NC1 Control Relay 2 NO2 Load 2 CM2 NC2 Control Relay 3 NO3 Load 3 CM3 NC3 Control Relay 4 NO4 CM4 NC4 Load 4 Figure 12: Typical 120 VAC Relay Pack Wiring Connections 6 MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin Modes of Operation The MS4PMUHVT control performs temperature management for multi-stage applications. It can automatically adjust the setpoint to save energy, based on readings from the auxiliary temperature sensor and the function settings. Temperature Interstage Time Delay The illustrations on the following pages show the modes of operation available on the MS4PMUHVT control. Interstage Time Delay In Reverse Mode (heating applications), when Setpoint is reached on a temperature rise the N.O. relay contacts open, ending the On cycle of Stage 1. Differential is the operational range of Stage 1. Setpoint 2 is the offset from Setpoint that activates Stage 2. Differential 2 is the operational range of Stage 2. Setpoint 3 is the offset from Setpoint that activates Stage 3. Differential 3 is the operational range of Stage 3. Setpoint 4 is the offset from Setpoint that activates Stage 4. Interstage Time Delay is the minimum amount of time between two successive stages when multiple stages are called for in rapid sequence. Off Stage 2 Differential 2 Off On Stage 1 Differential Off Differential 4 Off Stage 3 Differential 3 On Setpoint is the desired temperature. In Direct Mode (cooling applications), when Setpoint is reached on a temperature drop, the Normally Open (N.O.) relay contacts open, ending the On cycle of Stage 1. On Interstage Time Delay Direct Mode (Cooling) and Reverse Mode (Heating) Direct mode is used for cooling applications. (See Figure 13.) Reverse mode is used for heating applications. (See Figure 14.) Where desirable, stages may overlap or have space between them. Stage 4 Setpoint 2 (Offset from Setpoint) Setpoint 4 (Offset from Setpoint) Setpoint 3 (Offset from Setpoint) Setpoint Time Figure 13: Direct Mode (Cooling) Temperature Off Setpoint Setpoint 2 Stage Differential (Offset from 1 Setpoint) Setpoint 3 Off (Offset from On Setpoint) Stage Differential 2 Setpoint 4 2 (Offset from Setpoint) On Off Interstage Time Delay Stage Differential 3 3 Off On Stage Differential 4 4 Interstage Time Delay On Interstage Time Delay Time Figure 14: Reverse Mode (Heating) MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin 7 Deadband Mode Deadband mode is used for applications requiring cooling and heating. Where desirable, stages may overlap or have space between them. See Figure 15. Differential is the operational range of Stage 1. Setpoint is the desired temperature. Setpoint 3 is the offset from the low end of the deadband that activates Stage 3. Setpoint 2 is width of the deadband, which is centered on Setpoint. Differential 3 is the operational range of Stage 3. Differential 2 is the operational range of Stage 2. Setpoint 4 is the offset from the high end of the deadband that activates Stage 4. In Direct Mode (cooling applications), the N.O. relay contacts open, ending the On cycle when Setpoint + (1/2 Setpoint 2) is reached on a temperature drop. Differential 4 is the operational range of Stage 4. In Reverse Mode (heating applications), the N.O. relay contacts open, ending the On cycle when Setpoint (1/2 Setpoint 2) is reached on a temperature rise. Interstage Time Delay is the minimum amount of time between two successive stages when multiple stages are called for in rapid sequence. Temperature Interstage Time Delay On Cooling Stage 4 Differential 4 On Off Differential 2 Stage 2 Setpoint 4 (Offset from Stage 2) Off Setpoint + (1/2 Setpoint 2) Setpoint 2 (Deadband) (Centered on Setpoint) Setpoint Setpoint - (1/2 Setpoint 2) Off Setpoint 3 (Offset from Stage 1) Differential Stage 1 Off On Differential 3 Stage 3 Heating On Interstage Time Delay Time Figure 15: Deadband Mode 8 MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin Independent Setpoint Mode Independent Setpoint mode is used for applications requiring cooling and heating. Where desirable, stages may overlap or have space between them. See Figure 16. Setpoint is the desired heating temperature. It is the basis for the reverse stages. In Reverse mode (heating applications), when Setpoint is reached on a temperature rise, the N.O. relay contacts open, ending the On cycle. Setpoint cannot be set higher than Setpoint 2, nor can Setpoint 2 be set lower than Setpoint. If overlapping adjustment is attempted, the setting that is not being adjusted will adopt the value of the setting that is being adjusted. Differential is the operational range of Stage 1. Setpoint 2 the desired cooling temperature programmed by the user. It is the basis for the direct stages. In Direct mode (cooling applications), when Setpoint is reached on a temperature drop, the N.O. relay contacts open, ending the On cycle. Differential 2 is the operational range of Stage 2. Setpoint 3 is the offset from Setpoint that activates Stage 3. Differential 3 is the operational range of Stage 3. Setpoint 4 is the offset from Setpoint 2 that activates Stage 4. Differential 4 is the operational range of Stage 4. Interstage Time Delay is the minimum amount of time between two successive stages when multiple stages are called for in rapid sequence. Temperature Interstage Time Delay Cooling Stage 4 Stage 2 Differential 4 Setpoint 4 Differential 2 Setpoint Stage 1 Differential Setpoint 3 Stage 3 Differential 3 Heating Interstage Time Delay Time Figure 16: Independent Setpoint Mode MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin 9 Programming the Control Use this section to program the control module. After programming, the control module retains its programmed settings, even in the event of a power failure or power-down. Using the Control Module During normal operation, the display shows the main sensor temperature. See Figure 2. • Press Up or Down repeatedly to display the main sensor temperature, auxiliary sensor temperature and the binary input status. • Press Enter to display the Setpoint value. After 15 seconds of inactivity, the display returns to main sensor temperature. Unlocking or Locking Access to Programming 1. 2. 3. In sequence, press and hold Enter, Up, and Down. Hold these buttons until “- - -” displays. Continue holding until the main sensor temperature displays (approximately 10 seconds). Selecting the Mode of Operation 1. At the same time, press and hold Enter and Down for approximately three seconds. 2. Press Up or Down until the display code for the desired mode displays: 4d = Direct mode (cooling) 4r = Reverse mode (heating) 4b = Deadband mode (both) 4i = Independent Setpoint mode (both) Press Enter to save the new setting. 3. Changing the Setpoint in Independent Setpoint Mode and Changing Other Function Settings in All Modes 1. 2. 3. Press and hold Enter for about 10 seconds. The display changes to HY. (The display shows S1 if in Mode 4i.) Press Up or Down until the desired function displays. See Table 4 and Control Functions. Press Enter. The function’s existing value displays. 4. Press Up or Down until the desired setting value displays. 5. Press Enter to save the new value. After 10 seconds of inactivity, the display returns to normal operation. Note: If Enter is not pressed, the new value is not saved, and the control reverts to the previous saved value. Initiating a Manual Self-Test IMPORTANT: Disconnect controlled loads before running the self-test procedure. Reconnect controlled loads and cycle power to resume normal operation. 1. 2. In sequence, press and hold Up and then Down. Hold for five seconds. Note: If Enter is not pressed, the new mode of operation is not saved, and the control reverts to the previous mode of operation. Changing the Setpoint in Direct, Reverse, and Deadband Modes 1. 2. 3. 4. Press and hold Enter for approximately three seconds. Release Enter when the new Setpoint value displays. Press Up or Down to display the new Setpoint value. Press Enter to save the new setting. Note: If Enter is not pressed, the new Setpoint value is not saved, and the control reverts to the previous Setpoint value. 10 MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin Control Functions Temperature Management Functions SI (Displays in Mode 4i only) Setpoint is the primary temperature setting (°F or °C) programmed by the user. For information on function in each mode, see Modes of Operation. Temperature Setpoint Sensed Temperature 30oF S2, S3, S4 Setpoint 2, Setpoint 3, Setpoint 4 depend on the mode used. For information on function in each mode, see Modes of Operation. HI, H2, H3, H4 Differentials are the difference (F° or C°) between the value at which an output is switched Off and the value at which an output is switched On (relay contacts closing and opening, initiating or ending an On cycle). For information on function in each mode, see Modes of Operation. HL, LL High and Low Setpoint Stops are temperature values (°F or °C) that define how high or low the primary Setpoint may be adjusted. Setpoint stops deter unauthorized or accidental overadjustment of Setpoint. On Load Demand Off On Output Status Off Cycle Delay Time Figure 17: Cycle Delay Cc Cycle Delay, Cooling establishes the minimum time in minutes between two subsequent On cycles of cooling (direct) stages. See Figure 17. CH Cycle Delay, Heating establishes the minimum time in minutes between two subsequent On cycles of heating (reverse) stages. See Figure 17. iS Interstage Time Delay is the minimum amount of time between two successive stages when multiple stages are called for in rapid sequence. rt Soft Start controls the rate at which the controlled temperature is allowed to approach Setpoint on power up, both initially and when the binary input is configured as remote shutoff. The setting is minutes/temperature units, such as minutes/F°. See Figure 18. Output Status (up to four stages) 20oF On Off Time (Minutes) 2 4 6 8 10 12 14 16 18 20 Figure 18: Soft Start Soft Start Example: Temperature = 20° Setpoint = 30° Soft start = 2 minutes Rate of Increase = Soft start x (setpoint – sensor reading) Controlled temperature increases by 1° every two minutes, until the setpoint temperature is reached. To go from 20° to 30° takes 20 minutes. So Temperature Sensor Offset allows compensation for temperature differences between actual and displayed temperature, such as when using long sensor leads. See Table 1 to determine the temperature value to compensate for long sensor lead extensions. Un Temperature Units Used allows selection of Fahrenheit or Celsius temperature scale. PU Display Refresh Rate establishes the time delay (seconds) between updates of the temperature display. Lc, Uc Heating Reset and Cooling Reset are automatic shifts of the setpoint, based on the temperature at the Auxiliary Temperature Sensor (ATS). See Temperature Reset for more information. NC Non-compensated Band establishes the temperature range (F° or C°) over which reset does not take place. MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin 11 Alarm Management Functions AH High Temperature Alarm establishes the temperature relative to Setpoint (F° or C°) at which the control goes into a high temperature alarm condition. (The temperature value is added to the Setpoint.) AL Low Temperature Alarm establishes the temperature relative to Setpoint (F° or C°) at which the control goes into a low temperature alarm condition. (The temperature value is subtracted from the Setpoint.) AH, AL High and Low Temperature Alarms are disabled during defrost and for 20 minutes after the defrost cycle. These alarms are also disabled for 20 minutes after startup. Ad Alarm Differential establishes the difference (F° or C°) between the alarm activation temperature and the alarm deactivation temperature. Alarm Differential Example - Cooling Applications: Setpoint = 40°F High Temperature Alarm = 15F° Alarm Differential = 2F° When the room temperature exceeds 55°F (40+15=55°F) for a time greater than the alarm time delay setting, the alarm message is displayed; however, it will reset after the temperature drops below 53°F (40+15-2=53°F). At Alarm Time Delay establishes the time delay (minutes) between reaching a high or low temperature alarm condition and displaying an alarm message on the display. This function reduces alarm oscillation and nuisance alarms caused by temperatures that temporarily exceed alarm setpoint temperatures. 12 Binary Input Functions iF Binary Input Mode allows selection of how the Normally Closed (N.C.) binary input activates the stage control contacts. Binary Input Mode can be disabled or can provide one of three predetermined responses to the binary input. (If a set of stage control contacts are used to control an external alarm, this function should be disabled.) • Shutoff and Alarm Signaling - If the binary input contact is open for a time longer than that set through the Binary Input Time Delay, the stage control contacts are switched Off, and an alarm message (A1) is displayed. • Setback - If the binary input contact is open for a time longer than that set through the Binary Input Time Delay, the setpoints are shifted by Setback. Reverse setpoints (heating) decrease. Direct setpoints (cooling) increase. • Remote Shutoff of the outputs. - If the binary input contact is open for a time longer than that set through the Binary Input Time Delay, the stage control contacts are switched Off. id Binary Input Time Delay establishes the time delay (minutes) between the binary input signal reaching the control and activation of the response selected by Binary Input Mode. Sb Setback determines the value of the Setpoint shift when the binary input is open and Setback is the response selected by Binary Input Mode. MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin Temperature Reset The control module uses non-compensated band and heating reset or cooling reset to automatically adjust the setpoint. These functions appear only when the Auxiliary Temperature Sensor (ATS) is connected. If the ATS is connected after the control module is powered up, the control module must be powered down and then powered up for these functions to appear. Non-Compensated Band Non-Compensated Band (NCB) is a temperature differential from setpoint. Within the range of this differential, variations in the ATS temperature do not cause a temperature reset. See Heating Reset and Cooling Reset for more information. Note: When Deadband mode or Independent Setpoint mode are used, NCB is the same for heating stages and cooling stages. Heating Reset When (Setpoint – ATS Temperature) > NCB, the control adjusts the heating setpoint by the following amount: [ATS Temp. – (Setpoint – NCB)] / Heating Reset Heating reset only affects the setpoint for heating stages. Cooling Reset When (ATS Temperature - Setpoint) > NCB, the control adjusts the cooling setpoint by the following amount: [ATS – (Setpoint + NCB)] / Cooling Reset Cooling reset only affects the setpoint for cooling stages. Cooling Setpoint = 70°F Reset ATS Temperature= 92°F Example NCB = 10F° Cooling Reset = 2F° Step 1 ATS Temperature – (setpoint + NCB) / cooling reset = [92 – (70 + 10)] / 2 = 6 Step 2 setpoint + reset 70 + 6 = 76 Setpoint is reset to 76°F to save energy. See Figure 20. Process Temperature Sensor 76° 70° Setpoint NonCompensated Band NCB = 10° 70° Heating Reset Example Setpoint = 70°F ATS Temperature = 42°F NCB = 20F° Heating Reset = 2F° Step 1 [ATS Temperature – (setpoint–NCB)] / heating reset = [42 – (70 – 20)]/2 = -4 Step 2 setpoint + reset 70 + (-4) = 66 1° Cooling Reset 80° 92° Auxiliary Temperature Sensor (ATS) Figure 20: Cooling Reset Setpoint is reset to 66°F to save energy. See Figure 19. 1° Heating Reset Process Temperature Sensor Setpoint 70° 66° NonCompensated Band NCB = 20° 42° 50° 70° Auxiliary Temperature Sensor (ATS) Figure 19: Heating Reset MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin 13 Table 2: Function Settings in Order of Programming in Control Module Display Code Function Useable Setting Range and Unit Value Factory-Set Values 4d = Direct 4r = Reverse 4b = Deadband 4i = Independent setpoints Modes of Operation 4d = Direct 4r = Reverse 4b = Deadband 4i = Independent setpoints 4d SI (Mode 4i only) Setpoint 4d, 4r, 4b = -40 to 99°F (-40 to 80°C) 4i = Low Setpoint Stop to High Setpoint Stop — HI Differential 1 1 to 9F° (1 to 9C°) 5 (F°) S2 ∆ Setpoint 2 4d, 4r = 1 to 40F° (1 to 40C°) 4b = 2 to 40F° (2 to 40C°) 4i = Low Setpoint Stop to High Setpoint Stop 5 (F°) H2 Differential 2 1 to 9F° (1 to 9C°) 5 (F°) S3 ∆ Setpoint 3 1 to 40F° (1 to 40C°) 5 (F°) H3 Differential 3 1 to 9F° (1 to 9C°) 5 (F°) S4 ∆ Setpoint 4 1 to 40F° (1 to 40C°) 5 (F°) H4 Differential 4 1 to 9F° (1 to 9C°) 5 (F°) LL Low Setpoint Stop -40°F (-40°C) to High Setpoint Stop 32 (°F) HL High Setpoint Stop Low Setpoint Stop to 99°F (80°C) 90 (°F) Cc Cycle Delay, Cooling 0 to 9 minutes 2 (minutes) CH Cycle Delay, Heating 0 to 9 minutes 0 (minutes) rt Soft Start 0 to 99 minutes/degrees 10 AH High Temperature Alarm 0 to 50F° (0 to 50C°) 15 (F°) AL Low Temperature Alarm -50 to 0F° (-50 to 0C°) -15 (F°) Ad Alarm Differential 1 to 9F° (1 to 9C°) 5 (F°) At Alarm Time Delay 0 to 99 minutes 15 (minutes) So Temperature Sensor Offset -20 to 20F° (-20 to 20C°) 0 (F°) Un Temperature Units Used 0 = °C 1 = °F 1 (°F) PU Display Refresh Rate 1 to 99 seconds 1 (second) iF Binary Input Mode 0 = No Response to Binary Input 1 = Shutoff and Alarm Signaling 2 = Setback Mode 3 = Remote Shutoff 0 (no response) Sb Setback -20 to 20F° (-20 to 20C°) 10 (F°) id Binary Input Time Delay 0 to 99 minutes 0 (minutes) iS Interstage Time Delay 3 to 90 seconds 3 (seconds) Lc Heating Reset 0 to 6°/ ° 4 Uc Cooling Reset 0 to 6°/ ° 4 NC Non-Compensated Band 0 to 20F° (0 to 20C°) 8 Note: Temperature Reset Functions (Heating Reset, Cooling Reset, Non-compensated Band) are only enabled after the auxiliary sensor is installed and power is cycled. 14 MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin Alarm and Fault Display Codes These alarm and fault codes flash on the LED display when the control detects the following faults: Table 3: Alarm Display Codes (Flashing) Display Code Meaning System Status F1 Indicates an open or shorted main temperature sensor. Alarm message displays. Correct problem and cycle power to reset control. A1 Binary input is open for longer than the Binary Input Time Delay and Binary Input Mode Option 1 is selected. Control output is switched off; alarm message displays. Correct the condition to reset. OF Binary input is open and Binary Input Mode Option 3 selected. Control output is switched off. Close the digital input to reset. HI Main sensor temperature has reached or exceeded the High Temperature Alarm value. Alarm message displays. Correct the condition to reset. LO Main sensor temperature has reached or fallen below the Low Temperature Alarm value. Alarm message displays. Correct the condition to reset. EE Program failure Alarm message displays, other outputs off. Replace control. Table 4: Status Codes (Steady) Status Code Indicates: On Auxiliary temperature sensor (S2) is not connected or, if it is connected, the sensor (or binary input) is open or shorted. OF Binary input is closed. Ordering Information Table 5: Ordering Information Item Code Description Shipping weight MS4PMUHVT-11C Relay pack temperature control with two A99B sensors 2.9 lb (1320 g) MS4PM12C-11C Replacement control module for use in relay pack only 1.6 lb (726 g) RP4MSUHV-1C Relay pack without control module 2.3 lb (1060 g) A99BB-200C Sensor, cable length: 6-1/2 ft (2 m) 0.13 lb (60 g) Repair and Replacement Relay Electrical Ratings Field repair of the control should not be made. In case of a defective or improperly functioning control, please check with your nearest Johnson Controls/PENN representative. Relay Ratings in Table 6 are for ambient temperatures in the range -40 to 111°F (-40 to 44°C). Derate electrical ratings 3.45% per 1F° in the range 111 to 140°F. Derate electrical ratings 6.25% per 1C° in the range 44 to 60°C. MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin 15 Table 6: SPDT Relay Electrical Ratings 24 VAC Single-Phase Ratings 120 VAC 208 VAC 240 VAC Horsepower Rating — AC Full Load Amperes — 7.2 7.6 8 AC Locked Rotor Amperes — 43.2 45.6 48 1/3 3/4 1 Non-Inductive Amperes — 8 8 8 Pilot Duty (VA) 50 325 625 750 Technical Specifications Product Electrical Ratings Frequency MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack See Table 6. 60 Hz Power Requirements 120/240 VAC ±10% Power Consumption 10 VA @ 120/240 VAC Accuracy ±1.8F° (±1C°) Sensor Input Range -40 to 158°F (-40 to +70°C) A99B Sensor Cable 6-1/2 ft (2 m) Ambient Operating Conditions MS4PMUHVT-11C: +14 to +140°F (-10 to +60°C); 0 to 95 % RH (noncondensing) MS4PM12C-11C: +14 to +140°F (-10 to +60°C); 0 to 95 % RH (noncondensing) RP4MSUHV-1C: -40 to +140°F (-10 to +60°C); 0 to 95 % RH (noncondensing) Ambient Storage Conditions Dimensions (H x W x D) Agency Listings Emissions Compliance Shipping Weight MS4PMUHVT-11C: -22 to +176°F (-30 to +80°C); 0 to 95 % RH (noncondensing) MS4PM12C-11C: -22 to +176°F (-30 to +80°C); 0 to 95 % RH (noncondensing) RP4MSUHV-1C: -40 to +185°F (-40 to +85°C); 0 to 95 % RH (noncondensing) See Figures 3-5. UL Listed (US), File SA516, CCN SDFY UL Listed (Canada), File SA516, CCN SDFY7 FCC (US) DOC (Canada) See Table 5. The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult Johnson Controls/Penn Application Engineering at 1-800-275-5676. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 16 Published in U.S.A. www.johnsoncontrols.com MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin
© Copyright 2026 Paperzz