Description
150 psi (10 bar) Working Pressure, 300 psi (20 bar) Working Pressure, Magnetic Drive Sealed Gear Housing,
Sizes 4” through 36” (DN 100mm—DN 900mm)
Sensus Propeller Meters are intended for
accountability measurement of potable or
non-potable cold (to 100°F/38°C) water
where flow is in only one direction. The
meters can be installed at any convenient
angle from horizontal to vertical; in
discharge, suction or pressurized lines;
within stated pressure ratings. For accurate
measurement, a full flow of water through
the meter and stated minimum flow rates
are required. Because all appropriate parts
are sealed for protection, the meters can be
used with water containing particulate solids
(as sand), without causing undue wear.
Model 111
Standard Sealed Register
E-ROFI Register
Features
CONSTRUCTION
REGISTERS
The meters are produced of fabricated
steel and protected internally by an epoxy
paint.
Sensus Propeller Meters are available with
a standard sealed mechanical register
(Model 111) or a sealed Electronic Rate
of Flow Instrument and Transmitter—EROFI (Model 112).
MAGNETIC DRIVE
Eliminates mechanical packings and
stuffing boxes. A sleeve-type ceramic
magnet in the propeller assembly drives a
follower magnet located within the sealed
gear box.
RIGHT ANGLE GEARING
The brass bevel gears, which drive the
register shaft, operate within a factorysealed, oil-filled, one-piece cast bronze
gear box, providing lubrication for the life
of the meter.
CERAMIC BEARING AND SHAFT
The double land ceramic bearing retained
in the propeller assembly rotates on a
ceramic sleeved shaft. The high purity
ceramic provides exceptionally good wear
characteristics, even in water containing
entrained solids.
INSTRUMENTATION CAPABILITIES
The E-ROFI or High-Speed Pickup Registers are available for interfacing with Sensus Act-Pak Instruments. Refer to Bulletin
E-1116 for HSPU and Bulletin E-1110 for
E-ROFI Register.
INSTALLATION
The meter is installed in the pipeline
similar to placing a short length of plain
end pipe in the line either by welding,
brazing or using pipe couplings, such as
Smith-Blair #411 flexible couplings. The
meter must have a full flow of liquid to
assure proper registration. Valves, fittings
and other equipment which may create a
flow disturbance, should be positioned at
least five pipe diameters upstream, and
three to five diameters downstream from
the meter.
GASKETS
A flat gasket is used at the connection
of the meter head to the body on 4” (DN
100mm) through 8” (DN 200mm). An
“O” ring is used on 10” (DN 250mm) and
larger sizes.
MAINTENANCE
Should maintenance or testing be eeded,
the meter head can be removed without
disturbing the tube body in the pipeline.
Cover plates are available for maintaining
service or flushing of lines when the meter
head is removed.
DS-W-PRP-00-00-0612-03-A
Page 2 of 2
A
K
D
Model 112
Model 111
3.50"
4.25"
H
B
Meter
Size
4”
DN 100mm
6”
DN 150mm
8”
DN 200mm
1
Low Flow
GPM m3/h
Normal Range
GPM m3/h
1
2
82
125-500
18.2
28-114
160
220-1200
36.3
50-273
190
250-1650
43.2
57-375
10”
DN 250mm
260
330-2500
59.0
75-568
12”
DN 300mm
257
350-3500
62.4
80-795
14”
DN 350mm
350
450-4500
79.5
102-1022
16”
DN 400mm
450
550-5500
102.2
125-1249
18”
DN 450mm
550
725-7250
124.9
165-1647
20”
DN 500mm
700
850-9000
159.0
193-2044
24”
DN 600mm
1000
1300-1300
227.1
295-2952
30”
DN 750mm
1600
2100-18600
363.4
477-4224
36”
DN 900mm
2400
3000-2400
545.0
681-5450
A
in mm
B
in mm
D
in mm
H
in mm
K
in mm
Shipping
Weight
Pounds kg
17”
432mm
4-1/2”
114mm
6-1/2”
165mm
3-7/8”
99mm
7-1/2”
190mm
45 lbs.
20 kg
21”
533mm
6-1/2”
168mm
8”
203mm
5”
127mm
9”
229mm
75 lbs.
34 kg
23”
584mm
8-5/8”
219mm
8”
203mm
6”
152mm
9”
229mm
100 lbs.
45 kg
25”
635mm
10-3/4”
273mm
9-1/2”
241mm
7-3/8”
187mm
11”
279mm
120 lbs.
54 kg
27”
686mm
12-3/4”
324mm
9-1/2”
241mm
8-3/8”
213mm
11”
279mm
160 lbs.
73 kg
41”
1041mm
14”
356mm
11-1/2”
292mm
9-1/4”
235mm
13-1/2”
343mm
275 lbs.
125 kg
47”
1194mm
16”
406mm
11-1/2”
292mm
10-1/4”
260mm
13-1/2”
343mm
340 lbs.
154 kg
53”
1346mm
18”
457mm
14-1/2”
368mm
11-5/8”
295mm
13-1/2”
343mm
400 lbs.
181 kg
59”
1499mm
20”
508mm
14-1/2”
368mm
12-5/8”
321mm
13-1/2”
343mm
500 lbs.
227 kg
71”
1803mm
24”
610mm
17-1/2”
445mm
12-5/8”
321mm
13-1/2”
343mm
675 lbs.
306 kg
83”
2108mm
30”
762mm
17-1/2”
445mm
12-5/8”
321mm
13-1/2”
343mm
950 lbs.
431 kg
95”
2413mm
36”
914mm
19-1/2”
495mm
12-5/8”
321mm
13-1/2”
343mm
1250 lbs.
567 kg
SPECIFICATIONS
SERVICE
Where fluid flow is in one direction only.
ACCURACY
100 ± 2% of actual flow within specified normal and
intermittent flow ranges. 95% minimum at low flow rate.
PRESSURE
RATING
9150 psi (10 bar) maximum working pressure;
300 psi (20 bar) maximum working pressure.
TEMPERATURE
100°F (38°C) maximum.
MAXIMUM
FLOW
Maximum normal flow rates listed are for continuous
service. See bulletin PM-725 for details.
INTERMITTENT
FLOW
25% overrated capacity for 10% to 15% of the total
operating time of the meter.
STANDARD
REGISTER
Six-digit straight reading type with full 3” (75mm)
diameter, 100-division dial and center sweep test hand.
Registration available in gallons, cubic feet, acre feet,
litres, cubic meters, miners inch hours, barrels and other
standard units.
ELECTRONIC
RATE OF FLOW
INSTRUMENT/
TRANSMITTER
The electronic rate of flow instrument (E-ROFI) registers
are used to display and transmit volume and flow rate
data from a Sensus Propeller Meter to various Sensus
Act-Pak Electronic Instruments which are used to
monitor, control, record volume, and rate of flow. ActPaks are normally located apart from the meter. The
instrument is mounted on Sensus Propeller Meter Head
Assemblies using the sealed register type adapter plate
assemblies.
MATERIALS
Tube Bodies: 4” (DN 100mm) through 36” (DN 900mm)
Sizes: Fabricated steel body and straightening vanes
coated internally and externally with epoxy paint.
Meter Head: Ductile Iron
Propeller and Nut: Polypropylene
Propeller Spindle: Ceramic-Coated Stainless Steel
Rotor Bearings: Ceramic
Magnets: Permanent, Ceramic Sleeve Type
Gear Housing: One-Piece Cast Bronze
Shafts and Bolts: Stainless Steel
OPTIONAL
EQUIPMENT
Blank covers, E-ROFI Registers and HSPU for use with
Sensus Act-Pak Instruments.
Low Flow — 95% minimum accuracy 2 Intermittent Flow — 25% over maximum rated capacity
© All products purchased and services performed are subject to Sensus’ terms of sale, available at either; http://na.sensus.com/TC/TermsConditions.pdf or 1-800-METER-IT. Sensus reserves the right to modify
these terms and conditions in its own discretion without notice to the customer.
This document is for informational purposes only, and SENSUS MAKES NO EXPRESS WARRANTIES IN THIS DOCUMENT. FURTHERMORE, THERE ARE NO IMPLIED WARRANTIES, INCLUDING
WITHOUT LIMITATION, WARRANTIES AS TO FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY. ANY USE OF THE PRODUCTS THAT IS NOT SPECIFICALLY PERMITTED HEREIN
IS PROHIBITED.
8601 Six Forks Road, Suite 700
Raleigh, NC 27615
1-800-638-3748
www.sensus.com/water