LEGEND SYMBOL: DESCRIPTION PANELBOARD, MOUNT TOP 6'-0" AFF, REFER TO PANELBOARD SCHEDULES FOR REQUIREMENTS TELEPHONE/COMMUNICATIONS TERMINAL BOARD. PROVIDE 3/4"x 4'x 4' PLYWOOD BACKBOARD PAINTED WITH GRAY FIRE RETARDANT PAINT. MOUNT TOP 8'-0" AFF. PROVIDE GROUND BAR SIMILAR TO HUBBELL COMPANY MODEL NUMBER HBBB14416G, 4" BY 16". EXTEND #4 AWG BARE COPPER FROM GROUND BAR TO SERVICE ENTRANCE PANEL/DISCONNECT AND BOND TO GROUNDING SYSTEM. TTB A-1 HOME RUN TO PANEL WITH CIRCUIT SHOWN, CROSS MARKS INDICATE NUMBER OF CONDUCTORS WHERE MORE THAN TWO, NOT INCLUDING GROUND, MINIMUM #12 AWG. OVERHEAD WIRING UNDERGROUND WIRING A b b FLUORESCENT LIGHTING FIXTURE; "A" INDICATES TYPE, REFER TO LIGHTING FIXTURE SCHEDULE. "b" CORRESPONDS TO CONTROLLING SWITCH. HID, INCANDESCENT OR COMPACT FLUORESCENT LIGHTING FIXTURE; "A" INDICATES TYPE, REFER TO LIGHTING FIXTURE SCHEDULE. "b" CORRESPONDS TO CONTROLLING SWITCH. A LAMP POST STYLE FIXTURE, REFER TO SITE LIGHT FIXTURE SCHEDULE EXIT SIGN; SHADED QUADRANTS INDICATE NUMBER OF FACES, PROVIDE DIRECTIONAL ARROWS AS SHOWN. WHERE WALL MOUNTED, INSTALL 96" AFF. UNIT SHALL BE EQUIPPED WITH INTEGRAL BATTERY BACK-UP. REFER TO TYPE EX IN LIGHTING FIXTURE SCHEDULE. COMBINATION EMERGENCY LIGHT/EXIT SIGN; SHADED QUADRANTS INDICATE NUMBER OF FACES, PROVIDE DIRECTIONAL ARROWS AS SHOWN. WHERE WALL MOUNTED, INSTALL 96" AFF. UNIT SHALL BE EQUIPPED WITH INTEGRAL BATTERY BACK-UP. REFER TO TYPE CEX IN LIGHTING FIXTURE SCHEDULE. BINDING EDGE EMERGENCY LIGHT; WHERE WALL MOUNTED, INSTALL 96" AFF. UNIT SHALL BE EQUIPPED WITH INTEGRAL BATTERY BACK-UP. REFER TO TYPE EM IN LIGHTING FIXTURE SCHEDULE. EXIT DISCHARGE EMERGENCY LIGHT; UNIT SHALL BE WET LOCATION LISTED AND EQUIPPED WITH INTEGRAL BATTERY BACK-UP. REFER TO TYPE ED IN LIGHTING FIXTURE SCHEDULE. ED Sa LIGHT SWITCH, TOGGLE, 20 AMP. 277V, MTD 48" AFF, UNO. "a" CORRESPONDS TO FIXTURES CONTROLLED BY SWITCH. S3 3-WAY LIGHT SWITCH, 20 AMP, 277V, MTD 48" AFF, UNO. S4 4-WAY LIGHT SWITCH, 20 AMP, 277V, MTD 48" AFF, UNO. LIGHTING NOTES: 1. CONTRACTOR SHALL FURNISH AND INSTALL LIGHT SWITCHES/CONTROLS FOR ALL LIGHTING AT LOCATIONS AS SHOWN ON THE DRAWINGS. 2. CONFIRM EXACT LIGHT FIXTURE LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLAN. 3. CONNECT ALL EXIT AND EMERGENCY LIGHTS TO UNSWITCHED LIGHTING CIRCUITS. UNITS SHALL OPERATE AUTOMATICALLY UPON LOSS OF POWER. LIGHT SWITCH, DIMMING, 120VOLT, MTD 48" AFF, UNO. COMPATIBLE WITH FIXTURES, VERIFY WITH MANUFACTURER. OS OCCUPANCY SENSOR, DUAL TECHNOLOGY, CEILING MOUNTED OR 9' AFF WALL MOUNTED IN ROOMS WITH CEILINGS 10' OR ABOVE, WATTSTOPPER DT-200 OR EQUAL, PROVIDE BZ-50 POWER PACK POWER NOTES: 1. CONTRACTOR SHALL FURNISH AND INSTALL FUSED DISCONNECTS FOR ALL HVAC EQUIPMENT WITH FUSES AS PER MANUFACTURER RECOMMENDATIONS. AMPACITY, POLES, AND TYPE NEMA ENCLOSURE OF DISCONNECT SWITCHES AS REQUIRED. FURNISH AND INSTALL A WEATHERPROOF, GFCI DUPLEX RECEPTACLE OUTLET WITHIN 25 FEET OF EACH HVAC PIECE OF EQUIPMENT. 2. MOUNT ALL SWITCHES AND OTHER ELECTRICAL EQUIPMENT IN COMPLIANCE WITH APPLICABLE PROVISIONS OF THE APPLICABLE ACCESSIBILITY CODE. 3. ALL RESTROOM, EXTERIOR, COUNTER TOP, AND ROOF TOP HVAC SERVICE RECEPTACLES SHALL BE GFCI. 4. ALL EXTERIOR RECEPTACLES SHALL HAVE APPROVED WEATHERPROOF COVERS AS PER NEC 406.8 (B). 5. ALL DAMP AND WET LOCATION DEVICES SHALL BE WEATHER RESISTANT. OCCUPANCY SENSOR, DUAL TECHNOLOGY, WALL MOUNTED, WATTSTOPPER DW-100 OR EQUAL, INSTALL 48" AFF OCCUPANCY SENSOR, MULTI-WAY, DUAL TECHNOLOGY, WALL MOUNTED, WATTSTOPPER DW-103 OR EQUAL, INSTALL 48" AFF OM PHOTOCELL SENSOR PS J JUNCTION BOX, SIZE AND USE AS REQUIRED 20A, 125V, 2 POLE, 3 WIRE, GROUNDING DUPLEX RECEPTACLE MTD. 42" AFF, UNO. COMMUNICATIONS NOTES: 1. CONTRACTOR SHALL FURNISH AND INSTALL ALL COMBINATION TELEPHONE AND DATA CONDUITS, BOXES, PLYWOOD TERMINAL BOARD, ETC. ACTIVE EQUIPMENT AND CABLING TO BE PROVIDED/INSTALLED BY OTHERS. 2. PROVIDE APPROPRIATE NYLON PULLSTRING/ROPE IN ALL EMPTY CONDUITS. 20A, 125V, 2 POLE, 3 WIRE, GROUNDING DUPLEX RECEPTACLE, MTD 18" AFF, UNO. 20A, 125V, 2 POLE, 3 WIRE, GROUNDING USB DUPLEX RECEPTACLE MTD. 42" AFF, UNO. HUBBELL MODEL USBP20 SERIES OR EQUAL. U FIRE ALARM DEVICE LEGEND SYMBOL: DESCRIPTION OF DEVICE: HEIGHT: F "FACP" FIRE ALARM CONTROL PANEL TOP @ 6'-0" RA REMOTE ANNUNCIATOR PANEL TOP @ 6'-0" P MANUAL PULL STATION 48" S SMOKE DETECTOR CLG DD DUCT MOUNTED SMOKE DETECTOR DUCT MOUNTED R REMOTE TEST STATION FOR DD 5'-6" HS 15cd HORN/STROBE UNIT, 15cd, RED 7'-6" HS 75cd HORN/STROBE UNIT, 75cd, RED 7'-6" HS 110cd HORN/STROBE UNIT, 110cd, RED 7'-6" WEATHER PROOF HORN/STROBE UNIT 7'-6" STROBE UNIT, 15cd, RED 7'-6" HS S S WP 15cd 75cd S 110cd SS 15cd SS 75cd SS 110cd STROBE UNIT, 75cd, RED 7'-6" STROBE UNIT, 110cd, RED 7'-6" FIRE ALARM SYSTEM NOTES: 1. FURNISH AND INSTALL A COMPLETE ADDRESSABLE FIRE DETECTION AND EVACUATION SYSTEM AS DESCRIBED HEREIN AND AS SHOWN ON THE PLANS; TO BE WIRED, CONNECTED, TESTED, AND LEFT IN FIRST-CLASS OPERATING CONDITION. THE SYSTEM SHALL USE ADDRESSABLE TRUEALARM INITIATING DEVICE CIRCUITS WITH REQUIRED SUPERVISION. ALL EQUIPMENT SHALL BE UL LISTED AND LABELED. HEREIN SPECIFIED IS THAT OF SIMPLEX AND DEPICTS THE TYPE AND QUALITY OF EQUIPMENT TO BE FURNISHED. THE ENTIRE INSTALLATION SHALL CONFORM TO THE APPLICABLE SECTIONS OF NFPA 72, NATIONAL FIRE ALARM CODE; NFPA 101, LIFE SAFETY CODE; NFPA 70, NATIONAL ELECTRICAL CODE; THE AMERICANS WITH DISABILITIES ACT; AND LOCAL AUTHORITIES HAVING JURISDICTION TO MEET THE COMPLETE FUNCTIONALITY REQUIREMENTS AS SET FORTH IN THESE SPECIFICATIONS. 2. COORDINATE AND INSTALL REQUIRED ANCILLARY ALARM FUNCTIONS WHERE SHOWN ON THE PLANS. EXAMPLES ARE MONITORING OF SPRINKLER SYSTEMS AND HVAC SHUTDOWN. 3. ADDRESSABLE FIRE ALARM CONTROL PANEL - SIMPLEX MODEL 4010 OR EQUAL WITH A MINIMUM OF 250 ACTIVE POINTS, CAPABLE OF SUPPORTING ALARM INITIATING APPLIANCES AND ALARM INDICATING APPLIANCES AS REQUIRED ON THE PLANS. THE CONTROL PANEL SHALL BE PROGRAMMABLE VIA THE FRONT PANEL FOR INPUT/OUTPUT FUNCTIONS AND SHALL CONTAIN A HISTORICAL EVENT LOG, 80 CHARACTER LCD DISPLAY, AND A SYSTEM WALK TEST OPTION. 4. CONTROL PANEL REMOTE REPORTING - THE SYSTEM SHALL HAVE AN INTERNALLY MOUNTED DIGITAL ALARM COMMUNICATING TRANSMITTER (DACT), CAPABLE OF BEING PROGRAMMED FOR COMMUNICATIONS WITH A MINIMUM OF TWO TELEPHONE CIRCUITS AND WITH PROGRAMMABLE LOCAL AC POWER FAIL TIME DELAY REPORTING. 24 VDC OPERATING VOLTAGE AND BATTERY BACKUP SHALL BE PROVIDED BY THE FIRE ALARM CONTROL PANEL. DACT SHALL REPORT TO MANUFACTURER'S, UL LISTED, CENTRAL STATION MONITORING FACILITY. 5. PROVIDE BATTERY CALCULATIONS TO SHOW THAT THE PROPER QUANTITY OF BATTERIES ARE SUPPLIED THAT UPON LOSS OF 120 VAC POWER WILL PROVIDE A MINIMUM OF 24 HOURS OF NORMAL SUPERVISORY MODE FOLLOWED BY 5 MINUTES OF ALARM INDICATION. 6. PROVIDE SUBMITTALS CONTAINING COMPLETE DESCRIPTIVE DATA AND CADD DRAWING SHOWING CONDUIT LAYOUT, WIRE COUNT, AND DEVICE LOCATIONS. 7. SYSTEM SHALL BE FULLY TESTED BY A NICET CERTIFIED TECHNICIAN IN THE PRESENCE OF THE OWNER'S REPRESENTATIVE AND BE WARRANTED FOR ONE YEAR. 8. ALL REQUIRED DOCUMENTATION REGARDING THE DESIGN OF FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS AND THE PROCEDURES FOR MAINTENANCE, INSPECTION, AND TESTING OF FIRE DETECTION, ALARM AND COMMUNICATIONS SYSTEMS SHALL BE MAINTAINED AT AN APPROVED, SECURED LOCATION FOR THE LIFE OF THE SYSTEM. 9. THE FIRE ALARM CONTRACTOR MUST BE CERTIFIED IN ACCORDANCE WITH THE TENNESSEE ALARM CONTRACTORS LICENSING ACT OF 1991, TCA TITLE 62, AND CHAPTER 32 (CALL 615-741-9771 FOR ADDITIONAL INFORMATION.) 10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT THE FIRE ALARM SYSTEM IS ACCEPTABLE TO THE LOCAL FIRE OFFICIAL HAVING JURISDICTION. ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY FOR AN OPERATING AND FULLY FUNCTIONAL SYSTEM IS INCLUDED IN THIS CONTRACT. 11. ALL REQUIRED DOCUMENTATION REGARDING THE DESIGN OF FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS AND THE PROCEDURES FOR MAINTENANCE, INSPECTION, AND TESTING OF THE FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS SHALL BE MAINTAINED AT AN APPROVED, SECURED LOCATION FOR THE LIFE OF THE SYSTEM. 12. THE FIRE ALARM CONTROL PANEL CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT." THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT. 7'-6" SPEAKER/STROBE UNIT, 15cd, RED SPEAKER/STROBE UNIT, 75cd, RED ELECTRICAL ABBREVIATIONS 7'-6" 7'-6" SPEAKER/STROBE UNIT, 110cd, RED ABBREVIATIONS A D OS GENERAL ELECTRICAL NOTES: 1. THE CONTRACTOR SHALL VISIT THE JOB SITE AND CAREFULLY EXAMINE THOSE PORTIONS OF THE SITE AFFECTED BY THIS WORK SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS THAT WILL AFFECT EXECUTION OF THE WORK. 2. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL NECESSARY PERMITS AND PAYING ALL UTILITY CO. AID TO CONSTRUCTION FEES. 3. ALL WORK SHALL BE IN ACCORDANCE WITH THE CURRENT/APPLICABLE NATIONAL ELECTRICAL CODE, NFPA 70, LOCAL CODES/ORDINANCES AND THE APPLICABLE ACCESSIBLITY CODE. SHOULD PLANS AND CODES CONFLICT, THE CODE TAKES PRECEDENCE. MAKE NO CHANGES, EVEN IN THE CASE OF CONFLICT, WITHOUT FIRST OBTAINING APPROVAL OF THE ARCHITECT/ENGINEER. 4. "PROVIDE" AS USED HERE AND ON THE DRAWINGS, IS AN ALL-INCLUSIVE TERM REQUIRING CONTRACTOR TO FURNISH, INSTALL, WIRE, AND CONNECT ALL SPECIFIED EQUIPMENT AS WELL AS COMPONENTS, ACCESSORIES, AND MOUNTING HARDWARE TO INSURE THAT SPECIFIED EQUIPMENT FUNCTIONS TO MEET SYSTEM REQUIREMENTS. 5. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROTECT OTHER FACILITIES AND EQUIPMENT FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSE FOR REPAIR OR REPLACEMENT OF FACILITIES, EQUIPMENT, OR OTHER PROPERTY DAMAGED BY OPERATIONS IN CONJUNCTION WITH THE COMPLETION OF THIS WORK. ELECTRICAL CONTRACTOR SHALL GIVE ADEQUATE NOTIFICATION TO TENNESSEE ONE CALL, (800) 351-1111, PRIOR TO COMMENCEMENT OF ANY EXCAVATION. 6. PROVIDE SPECIFIED EQUIPMENT, AS NOTED ON DRAWINGS, OR APPROVED EQUAL. ADDITIONAL EQUIPMENT AND MATERIAL MAY BE REQUIRED OTHER THAN THAT SHOWN ON DRAWINGS TO INSTALL THE SPECIFIED EQUIPMENT SUCH AS HANGERS, SUPPORTS, ETC. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL MATERIAL, LABOR, AND EQUIPMENT REQUIRED. 7. THE CONTRACTOR SHALL VERIFY THAT THE ACTUAL EQUIPMENT SUPPLIED HAS THE SAME ELECTRICAL SPECIFICATIONS AS THE EQUIPMENT USED AS THE BASIS OF DESIGN. IF THE EQUIPMENT IS DIFFERENT, THE CONTRACTOR SHALL MAKE ADJUSTMENTS TO THE PANELS AND CIRCUITS AND INCLUDE THEM IN SUBMITTALS. 8. ALL MATERIALS SHALL BE LISTED AND LABELED BY UNDERWRITERS LABORATORY, INC. 9. THE CONTRACTOR IS DIRECTED TO VERIFY THE SERVICE ARRANGEMENT WITH THE LOCAL ELECTRIC UTILITY BEFORE ORDERING EQUIPMENT. DESIGN IS BASED ON A 480Y/277 VOLT, THREE PHASE, FOUR WIRE, SOLIDLY GROUNDED WYE SERVICE. THIS DESIGN ASSUMES AN UNDERGROUND SERVICE WITH SERVICE CONDUITS AND CONDUCTORS BY ELECTRICAL CONTRACTOR. ELECTRICAL CONTRACTOR SHALL INSTALL PRIMARY CONDUITS AND CONCRETE TRANSFORMER PAD AS SPECIFIED BY THE LOCAL ELECTRIC UTILITY. 10. ALL WIRES SHALL BE TERMINATED AND LABELED. ALL JUNCTION BOXES SHALL BE LABELED TO INDICATED THE CIRCUITS CONTAINED IN THE BOX. 11. PANELBOARD LEGENDS SHALL BE TYPED. LABEL ALL PANELBOARDS/SWITCHGEAR INDICATING LOCATION OF BREAKER SERVING PANEL IN ACCORDANCE WITH N.E.C. 12. ALL FEEDERS #4 AND LARGER SHALL BE MEGGER TESTED AFTER INSTALLATION. 13. UNLESS OTHERWISE NOTED, ALL CONDUCTORS SHALL BE COPPER AND #12 AWG MINIMUM WITH THHN/THWN, 600 VOLT INSULATION. 14. PROVIDE A DEDICATED NEUTRAL, COLOR CODED, FOR EACH UNGROUNDED CONDUCTOR. SHARING OF NEUTRALS IS PROHIBITED. 15. DO NOT INSTALL MORE THAN THREE CIRCUITS (SIX CURRENT CARRYING CONDUCTORS) IN A CONDUIT. 16. THE MINIMUM CONDUIT SIZE SHALL BE 1/2". INTERIOR CONDUITS SHALL BE EMT; UNDERGROUND CONDUIT AND CONCRETE ENCASED CONDUIT SHALL BE SCHEDULE 40 PVC. EXTERIOR EXPOSED CONDUIT SHALL BE SCHEDULE 40 PVC., UNLESS NOTED OTHERWISE. 17. MC CABLE SHALL NOT BE USED. 18. A GREEN, COPPER GROUND WIRE SHALL BE INSTALLED IN ALL CONDUIT SYSTEMS AND SHALL BE BONDED TO ALL ENCLOSURES, BOXES, AND EQUIPMENT. 19. BONDING JUMPERS SHALL BE USED TO BOND CONDUIT TO ENCLOSURES, BOXES, AND EQUIPMENT WHERE KNOCKOUTS ARE USED. 20. ALL DIMENSIONS ARE MEASURED TO THE CENTER OF THE DEVICE. 21. THE CONTRACTOR SHALL PROVIDE FIRESTOPPING OF ALL RATED PENETRATIONS PER DETAILS. ELECTRICAL BOXES INSTALLED ON OPPOSITE SIDES OF A FIRE RATED WALL SHALL HAVE A TWO FOOT MINIMUM HORIZONTAL SEPARATION. 22. THE CONTRACTOR SHALL PROVIDE ADEQUATE TEMPORARY POWER AND LIGHT. EQUIVALENT TO ONE 150-WATT INCANDESCENT LAMP PER 200 SQ. FT. 23. THE CONTRACTOR SHALL GUARANTY ALL WORK TO BE FREE OF DEFECTS IN WORKMANSHIP AND MATERIALS FOR ONE YEAR AFTER SUBSTANTIAL COMPLETION. 20A, 125V, 2 POLE, 3 WIRE, GROUNDING QUAD RECEPTACLE, TWO GANG BOX, MTD 42" AFF, UNO. FLOOR BOX, USE HUBBELL MODEL NO. 24GCCVR??UC WITH COVER, PROVIDE DUPLEX RECEPTACLE AND APPROPRIATE BRACKETS FOR DATA JACKS. SINGLE BOX IS SHOWN ON BOTH PLANS FOR WIRING REQUIREMENTS. PT POKE THROUGH. PROVIDE TWO 20 AMP DUPLEX RECEPTACLES AND FOUR DATA/VOICE JACK LOCATIONS, USE HUBBELL MODEL SIR6PTFIT SERIES OR EQUAL. SINGLE BOX IS SHOWN ON BOTH PLANS FOR WIRING REQUIREMENTS. TAMPER SWITCH AS REQUIRED FS FLOW SWITCH AS REQUIRED PS PRESSURE SWITCH AS REQUIRED EP EXPANSION POWER SUPPLY, 120V AS REQUIRED PW NAC POWER, 4 POINT AS REQUIRED BA 12 VOLT BATTERY 10 AH (2) AS REQUIRED RL IAM RELAY, IDNET H 190 HEAT DETECTOR 190° FIXED TEMP. H 135 HEAVY DUTY FUSED DISCONNECT SWITCH, PROVIDE FUSES AS RECOMMENDED BY EQUIPMENT MFGR. USE NEMA CONFIGURATION AS REQUIRED DH DOOR HOLDER M MINI HORN ELECTRIC MOTOR TV TELEVISION OUTLET. PROVIDE 1" CONDUIT FROM BOX TO LOCATION ABOVE ACCESSIBLE CEILING. PROVIDE BUSHING ON OPEN END OF CONDUIT. PROVIDE ONE CAT 6 AND ONE HDMI TO A/V ROOM ON RESPECTIVE FLOOR. MTD AT 7'-6" AFF AMPERE AFF ABOVE FINISHED FLOOR - MEASURED FROM FLOOR TO CENTER OF DEVICE, EXCEPT AS OTHERWISE SPECIFICALLY NOTED. ADA AMERICANS WITH DISABILITIES ACT OF 1990 AFG ABOVE FINAL GRADE BP INDICATES FIXTURE TO BE EQUIPPED WITH INTEGRAL BATTERY BACK-UP. FIXTURE SHALL ILLUMINATE AUTOMATICALLY UPON LOSS OF NORMAL POWER. REFER TO TYPE BP IN THE LIGHTING FIXTURE SCH. C CONDUIT CM INDICATES DEVICE TO BE CEILING MOUNTED EM INDICATES FIXTURE TO BE CONNECTED TO BUILDING EMERGENCY POWER SYSTEM. EUH ELECTRIC UNIT HEATER 15012 1. Wall Assembly - The 1, 2, 3 or 4 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs (max 2 hr fire rated assemblies) or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC with nom 2 by 4 in. (51 by 102 mm) lumber end plates and cross braces. Steel studs to be min 3-5/8 in. (92 mm) wide by 1-3/8 in. (35 mm) deep channels spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Nom 1/2 or 5/8 in. (13 or 16 mm) thick, 4 ft. (122 cm) wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 26 in. (660 mm). 2. Through Penetrant - One metallic pipe, conduit or tubing installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be min of 0 in. (0 mm) (point contact) to max 2 in. (51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 24 in. (610 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 24 in. (610 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 12 in. (305 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe. C. Conduit - Nom 6 in. (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing D. Copper Tubing - Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. F. Through Penetrating Product* - Flexible Metal Piping - The following types of steel flexible metal gas piping may be used: 1. Nom 2 in. (51 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. OMEGA FLEX INC 2. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. TITEFLEX CORP A BUNDY CO 3. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. WARD MFG INC NATIONAL ELECTRICAL CODE INDICATES RECEPTACLE TO BE ISOLATED GROUND TYPE F Rating Hr 1 or 2 0+, 1 or 2 1 (25) 3 or 4 3 or 4 4 (102) 1 or 2 0 N NEUTRAL NL INDICATES FIXTURE TO BE CONNECTED UNSWITCHED TO SERVE AS A "NIGHT" LIGHT. 6 (152) 3 or 4 0 PH PHASE 12 (305) 1 or 2 0 TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR, LEVITON 57277 SERIES OR EQUAL. WG INDICATES ITEM IS SUBJECT TO PHYSICAL DAMAGE: PROVIDE WIRE GUARD PROTECTION. +When copper pipe is used, T Rating is 0 hr. WP INDICATES DEVICE TO HAVE WEATHERPROOF COVER 3M COMPANY - CP 25WB+ caulk or FB-3000 WT sealant, BINDING EDGE W CF CABLE FIRESTOPPING SLEEVE, 4" SQ BY 10" LONG, 3M CO. 98-0400-5514-1 EQUAL. (865) 544-2000 FACSIMILE: (865) 544-0402 INTERNET: mhminc.com PROJECT INFORMATION SBC - 166/005-02-2013 CONTRACT: NEW FOOTBALL STADIUM - EAST TENNESSEE STATE UNIVERSITY £ SCHEMATIC DESIGN £ DESIGN DEVELOPMENT £ REDI-CHECK £ CONSTRUCTION BIDDING PHASE SEAL: * NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. © McCarty Holsaple McCarty, Inc. Do NOT scale drawings, use given dimensions only. If not shown, verify correct dimension with ARCHITECT. Contractor shall check and verify all dimensions and conditions at job site. 4 A 3 2 4 1 CONSULTANT INFORMATION 4 System No. C-AJ-1044 March 15, 2007 F Ratings - 2, 3, and 4 Hr (See Items 2A and 4) T Rating - 0 Hr L Rating At Ambient - 2 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft W Rating - Class I (See Item 4) 1 2 3 A SECTION A-A INTERCOM SPEAKER, CEILING RECESSED WIRELESS ACCESS POINT. EXTEND 1" CONDUIT FROM BOX AS INDICATED ON DRAWINGS. LOCATEON STRUCTURE IN OPEN CEILING AREAS AND 12" ABOVE CEILING IN AREAS WITH LAY-IN CEILING.PROVIDE TWO CAT 6 CABLES FROM OUTLET AND TERMINATE IN NETWORK RACK ON RESPECTIVEFLOOR. TELEPHONE: ACTIVE DESIGN PHASE *Bearing the UL Classification Marking INTERCOM SPEAKER, WEATHERPROOF, WALL MOUNT 7'6" AFF. CAMERA, PROVIDE SINGLE GANG JUNCTION BOX. STUB 1" CONDUIT FROM BOX TO ABOVE LAY-IN CEILING, PROVIDE ONE CAT 6 CABLE. [email protected] NASHVILLE , TENNESSEE 37614 T Rating Hr 1 (25) KEY PAD, PROVIDE FLUSH SINGLE GANG BOX +48"AFF. EXTEND 1/2" CONDUIT AS INDICATED ON DRAWINGS U DOUG McCARTY EMAIL: AS-BUILT RECORDS Max Pipe or Conduit Diam in. (mm) INTERCOM SPEAKER, WALL MOUNT 7'6" AFF. SP CONTACT: CONSTRUCTION DOCUMENTS CONSTRUCTION DOCUMENTS COMBINATION PHONE AND DATA OUTLET. PROVIDE 4" SQUARE BOX WITH SINGLE GANG DEVICE RING. STUB 1" CONDUIT WITH PULLSTRING FROM BOX TO LOCATION ABOVE ACCESSIBLE CEILING AS INDICATED ON DRAWINGS. PROVIDE BUSHING ON OPEN END OF CONDUIT. MTD 42" AFF, UNO. STUB UP 12" ABOVE CEILING. PROVIDE TWO CAT 6 CABLES FROM OUTLET AND TERMINATE IN NETWORK RACK ON RESPECTIVE FLOOR. WP KNOXVILLE, TENNESSEE 37902 1415 MURFREESBORO ROAD, SUITE 664 3. Fill,Void or Cavity Material* - Caulk or Sealant - Min 5/8. 1-1/4,1-7/8 and 2-1/2 in. (16, 32, 48 and 64 mm) thickness of caulk for 1, 2, 3 and 4 hr rated assemblies, respectively, applied within annulus, flush with both surfaces of wall. Min 1/4 in. (6 mm) diam bead of caulk applied to gypsum board/penetrant interface at point contact location on both sides of wall. The hourly F Rating of the firestop system is dependent upon the hourly fire rating of the wall assembly in which it is installed, as shown in the following table. The hourly T Rating of the firestop system is dependent upon the type or size of the pipe or conduit and the hourly fire rating of the wall assembly in which it is installed, as tabulated below: COMBINATION PHONE AND/OR DATA OUTLET. PROVIDE 4" SQUARE BOX WITH SINGLE GANG DEVICE RING. STUB 1" CONDUIT WITH PULLSTRING FROM BOX TO LOCATION ABOVE ACCESSIBLE CEILING AS INDICATED ON DRAWINGS. PROVIDE BUSHING ON OPEN END OF CONDUIT. MTD 18" AFF, UNO. STUB UP 12" ABOVE CEILING. PROVIDE TWO CAT 6 CABLES FROM OUTLET AND TERMINATE IN NETWORK RACK ON RESPECTIVE FLOOR. KP 550 W. MAIN STREET, SUITE 300 £ NEC 2 #14 SECTION A-A £ X Kcmil (THOUSAND CIRCULAR MILS) 24 VDC MAPNET/IDNET POWER ARCHITECTS & INTERIOR DESIGNERS INDICATES RECEPTACLE OR CIRCUIT BREAKER, AS APPLICABLE, TO HAVE GROUND FAULT PROTECTION MCM 2 #14 1B A GF JOHNSON CITY POWER BOARD STROBE CIRCUIT, HORN/STROBE CIRCUIT 2 GROUND JCPB 2 #18 TWISTED/SHIELDED Mc C A R T Y H O LSAPLE Mc C A R T Y G 7'-6" MAPNET/IDNET CIRCUIT, COMMUNICATION/DATA LINE 3 FUSE IG WIRE QUANTITY, SIZE, AND TYPE 3 F AS REQUIRED DEVICE TYPE NOTES: FIRE ALARM SYSTEM WIRING SHALL BE INSTALLED IN CONDUIT. M CJG FIRE ALARM WIRING SCHEDULE EXHAUST FAN, PROVIDE 120 VOLT CONNECTION PER NEC. PULLBOX, FIBERGLASS, SIZE AS INDICATED ON DRAWINGS. CJG HEAT DETECTOR 135° FIXED TEMP. 3 20A, 125V, 2 POLE 3 WIRE GROUNDING, CEILING MOUNTED, DUPLEX RECEPTACLE OUTLET, PROVIDE DROP CORD WITH STRAIN RELIEF GRIPS ON BOTH ENDS IN KITCHENS. PB AS REQUIRED NOTES: MODEL NUMBERS ARE SIMPLEX GRINNELL UNLESS OTHERWISE NOTED 20A, 125V, 2 POLE, 3 WIRE, GROUNDING QUAD RECEPTACLE, TWO GANG BOX, MTD 18" AFF, UNO. FB TS DESCRIPTION 1A A System No.W-L-1001 June 15, 2005 F Ratings - 1, 2, 3 and 4 Hr (See Items 2 and 3) T Ratings - 0, 1, 2, 3, and 4 Hr (See Item 3) L Rating At Ambient - less than 1 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft 3 1. Floor or Wall Assembly - Lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Except as noted in table under Item 4, min thickness of solid concrete floor or wall assembly is 4-1/2 in. (114 mm). Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow core Precast Concrete Units*. When floor is constructed of hollow core precast concrete units, packing material (Item 3) and caulk fill material (Item 4) to be installed symmetrically on both sides of floor, flush with floor surface. Wall assembly may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is in solid lightweight or normal weight concrete. Floor is 32 in. (813 mm). Max diam of opening in floor constructed of hollow-core precast concrete units is 7 in. (178 mm). See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. 1A. Steel Sleeve (Optional, not shown) - Max 15 in. (381 mm) ID (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 2 in. (51 mm) above top of floor or beyond either surface of wall. Max 16 in. (406 mm) ID (or smaller) min 0.028 (0.71 mm) wall thickness (or heavier) galvanized steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 1/2 in. (13 mm) beyond either surface of floor or wall. CODES OFFICIAL REVIEW 2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. Max annular space between pipe, conduit or tubing and edge of through opening or sleeve is dependent on the parameters shown in Item 4. Min annular space between pipe or conduit and edge of through opening is 0 in. (0 mm) (point contact). Pipe conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit. D. Conduit - Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing. E. Copper - Tubing Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tube. F. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. 3. Packing Material - Polyethylene backer rod or nom 1 in. (25 mm) thickness of tightly-packed mineral wool batt or glass fiber insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of caulk fill material (Item 4). 4. Fill,Void or Cavity Material* - Caulk or Sealant - Applied to fill the annular space flush with top surface of floor. In wall assemblies, required caulk thickness to be installed symmetrically on both sides of wall, flush with wall surface. At point contact location between penetrant and sleeve or between penetrant and concrete, a min 1/4 in. (6 mm) diam bead of caulk shall be applied at top surface of floor and at both surfaces of wall. The hourly F Ratings and the min required caulk thicknesses are dependent upon a number of parameters, as shown in the following table: Nom Pipe Tube or Conduit Diam in. (mm) Max Annular Space in. (mm) Min Caulk Thkns in. (mm) F Rating Hr 2-1/2 (64) 1/2-12 (13-305) 1-3/8 (35) 1/2 (13) 2 2-1/2 (64) 1/2-12 (13-305) 3-1/4 (83) 1 (25) 2 4-1/2 (114) 1/2-6 (13-152) 1-3/8 (35) 1/4 (6) (a) 2 4-1/2 (114) 1/2-12 (13-305) 1-1/4 (32) 1/2 (13) 3 4-1/2 (114) 1/2-20 (13-508) 2 (51) 1 (25) 3 4-1/2 (114) 1/2-20 (13-508) 2 (51) 1 (25) 3 4-1/2 (114) 1/2-12 (13-305) 3-1/4 (83) 1 (25) 3 4-1/2 (114) 22-30 (558-762) 2 (51) 2 (51) 3 5-1/2 (140) 1/2-6 (13-152) 1-3/8 (35) 1 (25) (b) 4 BINDING EDGE Min Floor or Wall Thkns In. (mm) (a)Min 2 in. (51 mm) thickness of mineral wool batt insulation required in annular space. (b)Min 1 in. (25 mm) thickness of mineral wool batt insulation required in annular space on both sides of floor or wall assembly. Min 1 in. (25 mm) thickness of caulk to be installed flush with each surface of floor or wall assembly. KEY PLAN: REVISION INFORMATION No. 1 2 3 4 Date 2/12/2016 2/12/2016 4/8/2016 1/10/2017 Description SFMO Revisions MISC. Revisions Addendum 12 A/V REVISION 3M COMPANY - CP 25WB+ caulk or FB-3000 WT sealant. (Note: W Rating applies only when FB-3000 WT sealant is used.) *Bearing the UL Classification Marking * NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2004 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. DRAWING INFORMATION SCALE: 1/8" = 1'-0" SCALE GUIDE: DWG ISSUED: PRJ MGR: PA / PC: TIME / DATE: 1/10/2017 2:46:59 PM DRAWN BY: CHECKED BY: 12.30.2015 S. WEBB S. BUTCHER / C. MOELLENDICK JAC LTH DRAWING TITLE: ELECTRICAL LEGEND AND NOTES DRAWING NO: E001
© Copyright 2026 Paperzz