SIPROTEC Motor Protection SIPROTEC Motor protection Protection functions for various types of motor faults Fault Protection ANSI - No. n Stator thermal n Stator thermal overload 49 overload n Rotor thermal overload during start n too long or blocked n too frequent n 2 Protection principles for the n Earth-fault n Short-circuit rotor overload protection n Motor starting time supervision n Restart inhibit 48 66 49R n Earth-fault protection (I0>;U0>; (U0, I0)) 50G 64G n Overcurrent time protection 51 n Current differential protection 50 87 n Loss of phase n Negative sequence protection (I2/IN) 46 n Bearing overload n Temperature sensors (RTDs) 38 n Overheating of plant on unloaded drives n Undercurrent protection, Active power protection (P<) 37 32U n Undervoltage n Undervoltage protection 27 n Asynchronous operation n Underexcitation protection 40 (Pumps, compressors) (Starting torque not reached M ~ U2 or start too long) (of a synchronous motor) 2 protection 67G Scope of motor protection functions provided by SIPROTEC devices. Protection functions ANSI 7SJ60 7SJ61 7SJ62 7SJ63/64 7UM61 7UM62 Stator overload protection 49 X X X X X X Starting time supervision 48 X X X X X X Locked rotor protection 48 X X X X X X Restart inhibit 66, 49R X X X X X X 64G X 1) X X X X 50G X X X X X 67G X 1) X X X X Earth-fault protection non-directional directional Overcurrent time protection 50, 51 X X X X X X X X X X X X X X X X X X X X X X X X X X X Current differential protection 87 Negative sequence protection 46 X 38 X 1) Undercurrent protection 37 X 1) Active power protection (P<) 32U (37) Undervoltage protection 27 Underexcitation protection 40 Frequency protection 81 Breaker failure protection 50BF Temperature supervision (via RTD - module) nn X X1) Freely programmable logic (PLC) Control functions X X X X X X X X X X X X X X X X X X X X X X X Measuring transducers Flexible serial interfaces 1) 1 2 2 2/3 X 2 3 in preparation (7SJ602) A device that best suits your requirement can be selected 3 Motor protection selection table Asynchronous Motor < 2MW 100 kW - 500 kW 7SJ60 Basic device 7SJ61 + more I/O´s + control functions + flexible serial interfaces + better local HMI (4line display; digital keyboard) 500 kW - (1-2) MW 7SJ62 Basic device + control functions Synchronous Motor 7UM61 (Option: Generator Basic) < 10 MW 7UM61 + more I/O´s (7UM612) + control functions + high accuracy + high sensitivity + operating range in a wide frequency band (11Hz - 68Hz) 7UM62 (Option: Generator Basic) or with control functions via bay mimic diagram in graphic display 7SJ63 Basic device 7SJ64 + synchro check function + high sensitivity + extensive control function + 1 serial interface more > 10 MW > 2 MW 7UM62 + differential protection + control functions + high accuracy + high sensitivity + operating range in a wide frequency band (11Hz - 68Hz) + 7UM62 (Option: Generator Basic) or with control functions via bay mimic diagram in graphic display + 4 7UM61 (Option: Generator Basic) 7SJ64 (Option: Maximum functionality + Synchro check) Application example: Protection of a small motor 100 kW - 500 kW A (L 1) B (L 2) C (L 3) ANSI 52 A (L 1) B (L 2) C (L 3) N 7SJ600/602 n Stator thermal overload protection 49 n Starting time supervision 48 n Earth-fault protection 50G n Overcurrent time protection 50, 51 n Negative sequence protection 46 Motor 5 Application example: Protection of a medium sized motor 500 kW - (1-2) MW A (L 1) B (L 2) C (L 3) A B C ANSI 52 A (L 1) B (L 2) C (L 3) N 7SJ62/63 n Stator thermal overload protection IEE n Restart inhibit (rotor protection) VE C (L 3) A (L 1) 49 66, 49R n Starting time supervision 48 n Earth-fault protection 50G (non-directional, 64G directional) 67G n Overcurrent time protection 50, 51 n Negative sequence Motor 6 protection 46 n Undervoltage protection 27 n Undercurrent protection 37 n Breaker failure protection 50BF n external RTD - module 38 Application example: Protection of a large motor > 2 MW A (L 1) B (L 2) C (L 3) ANSI 52 e 7UM62 n VE R 13 R 14 R 15 VA(L1) R 17 VB(L2) VC(L3) R 18 R 16 J1 J2 J3 J4 J5 R J6 k IA(L1)S2 IB(L2)S2 IC(L3)S2 Q8 IEE2 Q7 K 13 + RTD module 7XV5662 (6 meas. junctions) Measuring transducer for injection of any analog signal e.g. speed, vibration, pressure To serial interface TD2 K 16 K 17 + TD3 K 18 J7 IEE1 J8 Q1 Q2 Q3 Q4 Q5 Q6 From RTD module n Stator thermal overload protection 49 n Restart inhibit (rotor protection) 66, 49R n Starting time supervision 48 n Earth-fault protection 50G TD1 K 14 K 15 + 7UM62 IA(L1)S2 IB(L2)S2 IC(L3)S2 Port C or D (non-directional, directional) 64G 67G n Differential protection 87M n Overcurrent time protection 50, 51 n Negative sequence protection 46 n Undervoltage protection 27 n Undercurrent protection 37 n Active power protection 32U n Frequency protection 81 n Breaker failure protection 50BF 7 Siemens AG Power Transmission and Distribution Power Automation Division P.O. Box 48 06 90026 Nuremberg Germany www.siprotec.com Editor and Layout: Dept. Marketing Services Power Automation Division
© Copyright 2026 Paperzz