Installation, Operation,
and Maintenance Manual
ELECTRA-flo
Thermal Air Flow Measurement Transmitter
Version 1.4X & 1.5X
Installation, Operation & Maintenance
Air Monitor Corporation provides complete
technical support between the hours of
7 a.m. and 5 p.m. PST, M-F
Contact our Service Department
Toll Free: 1-800-AIRFLOW
or fax us at 1-707-526-2825
Air Monitor Corporation
116-053-13.P65 (2/28/12)
ELECTRA-flo - IO&M Manual
PAGE LEFT INTENTIONALLY BLANK
TABLE OF CONTENTS
ELECTRA-flo
TABLE OF CONTENTS
INSTRUMENT WARRANTY .................................................................................................................... i
SECTION 1 – GENERAL INFORMATION
1.1
1.2
DESCRIPTION ............................................................................................................................... 1
THEORY OF OPERATION ............................................................................................................. 1
SECTION 2 – PERFORMANCE SPECIFICATIONS
2.1
2.2
2.3
2.4
2.5
ACCURACY ................................................................................................................................... 2
RANGE ........................................................................................................................................... 2
PROBE ASSEMBLY ....................................................................................................................... 2
TRANSMITTER .............................................................................................................................. 2
POWER .......................................................................................................................................... 2
SECTION 3 – FEATURES
3.1
3.2
3.3
3.4
3.5
OPERATOR MENU ........................................................................................................................ 3
DATA DISPLAY ............................................................................................................................... 3
LARGE OPERATION RANGE ........................................................................................................ 3
ENCLOSURE ................................................................................................................................. 3
MULTIPLE OPERATING POWER SELECTIONS .......................................................................... 3
SECTION 4 – INSTALLATION
4.1
4.2
4.3
4.4
4.5
4.6
RECEIVING AND INSPECTION ..................................................................................................... 4
LOCATION ..................................................................................................................................... 4
MOUNTING .................................................................................................................................... 5
PROCESS CONNECTIONS ........................................................................................................... 5
POWER/SIGNAL CONNECTIONS ............................................................................................. 6-8
DISPLAY CONTRAST ADJUSTMENT ........................................................................................... 8
SECTION 5 – OPERATION
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10
5.11
5.12
5.13
5.14
5.15
5.16
5.17
5.18
INTRODUCTION ............................................................................................................................ 9
START-UP ...................................................................................................................................... 9
NORMAL OPERATION ................................................................................................................ 10
CONFIGURATION ........................................................................................................................ 10
PUSHBUTTON DEFINITION ........................................................................................................ 11
CONFIGURATION PROGRAMMING ...................................................................................... 12-13
OPERATOR PASSWORD SELECTION ....................................................................................... 14
FLOW CONFIGURATION ....................................................................................................... 15-16
DISPLAY CONFIGURATION ................................................................................................... 17-19
OUTPUT 2 PARAMETER SELECTION ........................................................................................ 20
LOW PASS FILTER ...................................................................................................................... 21
OUTPUT SIGNAL TYPE SELECTION ......................................................................................... 22
TRANSMITTER OUTPUT CALIBRATION ............................................................................... 23-25
K-FACTOR CONFIGURATION ................................................................................................ 26-27
MENU INACTIVITY TIMEOUT SELECTION ................................................................................ 27
NETWORK CONFIGURATION .................................................................................................... 28
FLOW ALARM CONFIGURATION .......................................................................................... 29-30
TEMPERATURE ALARM CONFIGURATION .......................................................................... 31-32
Air Monitor Corporation
116-053-13.P65 (2/28/12)
ELECTRA-flo - IO&M Manual
TABLE OF CONTENTS
ELECTRA-flo
TABLE OF CONTENTS
SECTION 6 – SUPERVISOR MENU
6.1
6.2
6.3
6.4
6.5
6.6
INTRODUCTION .......................................................................................................................... 33
SUPERVISOR PASSWORD SELECTION ................................................................................... 34
SENSOR MANAGEMENT ....................................................................................................... 35-37
DIAGNOSTIC DISPLAY SELECTION .......................................................................................... 38
DIAGNOSTIC ALERT DETERMINATION ................................................................................ 39-41
POWER CYCLE SENSOR NETWORK........................................................................................ 42
SECTION 7 – MAINTENANCE
7.1
7.2
7.3
CLEANLINESS ............................................................................................................................. 43
MECHANICAL .............................................................................................................................. 43
ELECTRICAL ............................................................................................................................... 43
SECTION 8 – TROUBLESHOOTING ................................................................................................... 44
SECTION 9 – PARTS LIST ................................................................................................................... 45
SECTION 10 – CUSTOMER SERVICE
8.1
8.2
8.3
8.4
8.5
CUSTOMER SERVICE / TECHNICAL SUPPORT ....................................................................... 46
REPAIRS / RETURNS .................................................................................................................. 46
WARRANTY REPAIRS / RETURNS............................................................................................. 46
NON-WARRANTY REPAIRS / RETURNS ................................................................................... 46
FIELD SERVICE ........................................................................................................................... 46
APPENDIX A .................................................................................................................................... 47-50
Air Monitor Corporation
116-053-13.P65 (2/28/12)
ELECTRA-flo - IO&M Manual
ELECTRA-flo
INSTRUMENT WARRANTY
INSTRUMENT WARRANTY
Air Monitor Corporation (hereinafter referred to as “Seller”)
warrants that at the time of shipment, products sold
pursuant to this contract will be free from defects in
materials and workmanship, and will conform to the
specifications furnished or approved in writing by Seller.
No warranty is given that delivered products will conform
to catalog sheets, data sheets, and the like, which are
subject to change without notice.
product which has been repaired or altered by persons
not expressly approved by Seller. Nor does Seller warrant
equipment against normal deterioration due to
environment; nor items such as lamps, glass, and similar
items subject to wear or burnout through usage.
Adjustments for items or equipment not manufactured
by Seller shall be made to the extent of any warranty of
the manufacturer or supplier thereof.
Seller will repair or replace, at its option, any products
listed under this warranty which is returned freight prepaid
to Seller within the earlier of three (3) years after start-up
or thirty-nine (39) months after shipment that, upon test
and examination, proves defective within the terms of
this warranty. The warranty period for any item repaired
or replaced shall be for the time remaining on the warranty
period of the original components. Purchaser shall notify
Seller in writing of such defect within sixty (60) days of
discovery of the defect.
Seller shall not be liable for any special or consequential
damages or for loss of damage, directly or indirectly
arising from the use of the products. Seller's warranty
shall be limited to replacement of defective equipment
and shall not include field removal and installation
expenses.
The warranty set forth above is in lieu of all other
warranties either express or implied and constitutes the
full extent of Air Monitor Corporation’s liability to the
customer, or any other party for breach of warranty.
This warranty does not extend to any product sold by
Seller which has been the subject of misuse, neglect,
accident, damage or malfunction caused by
interconnection with equipment manufactured by others,
improper installation or storage, or used in violation of
instructions furnished by Seller, nor does it extend to any
THERE ARE NO EXPRESS WARRANTIES EXCEPT AS
SET FORTH HEREIN AND THERE ARE NO IMPLIED
WARRANTIES OF MERCHANTABILITY OF FITNESS
FOR ANY PARTICULAR PURPOSE, WHICH ARE
PARTICULARLY DISCLAIMED.
NOTICE OF PROPRIETARY RIGHTS
This document contains confidential technical data, including trade
secrets and proprietary information which are the sole property of
Air Monitor Corporation. The use of said data is solely limited to
use as specified herein. Any other use is strictly prohibited without
the prior written consent of Air Monitor Corporation.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
i
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 1 – GENERAL INFORMATION
1 – GENERAL INFORMATION
1.1 – DESCRIPTION
The ELECTRA-flo Thermal Air Flow Transmitter is used in conjunction with ELECTRA-flo Probe(s). One Transmitter
can receive up to 32 individual flow sensors measuring a single ducted airflow or fan.
The Transmitter's microprocessor averages flow and temperature signals from all sensors and outputs an analog
signal and local display of these averages. The Transmitter serves as the interface for all configuration and diagnostic
functions.
1.2 – THEORY OF OPERATION
The ELECTRA-flo utilizes thermal dispersion
technology to measure airflow. As air moves across
the surface of an elevated temperature sensor, heat
is transferred from the sensor to the airflow in a
mathematically defined relationship between heat
transfer rate and airflow velocity.
Each ELECTRA-flo sensing node utilizes a pair of
precision matched thermistors. One functions as a
reference sensor measuring the ambient air
temperature at the sensing node location, and the
other thermistor is heated to a preset temperature
differential (T) above the ambient air temperature.
Airflow velocity is determined using the measured
ambient air temperature, the known heat transfer
characteristics of the heated thermistor, and the
power consumed to maintain the T between the two
thermistors.
Using a combination of Computational Fluid
Dynamics (CFD) modeling and extensive full-scale
wind tunnel verification, the aerodynamically
optimized cross section of the sensing node aperture
prevents error inducing turbulence typical of sharp
edged sensing tubes.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
The aperture’s injection molded shape has been
engineered to minimize the angular flow effects
naturally present in any duct. The flared aperture
captures a representative sample of the ducted
airflow, while the contoured leading edges prevent
the creation of vortices. The center cross section of
the aperture functions in the same manner as a
venturi. It stabilizes and flattens the velocity profile
at the point of measurement ensuring the airflow
maintains full contact with the sensing thermistors.
The flow conditioning characteristic of the aperture
compensates for turbulent airflow with pitch and/or
yaw angles up to ±30 degrees and produces an
accuracy of ±2% of reading for each ELECTRA-flo
sensor.
1
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 2 – PERFORMANCE SPECIFICATIONS
2 – PERFORMANCE SPECIFICATIONS
2.1 – ACCURACY
2.4 – TRANSMITTER
Sensor Accuracy.
Velocity:
±2% of Reading
Temperature: ±0.1ºF
Display.
3 line, backlit graphical display. Flow on Line 1 is
double height and width for improved visibility. Lines
2 and 3 are standard size and are user selectable.
Overall System Accuracy.
Flow:
±2-3% of Actual Flow
Temperature: ±0.1ºF of Air Temperature
Output.
Dual analog outputs (0-5VDC, 0-10VDC, 4-20mA)
user selectable and configurable.
Configuration.
Via cover mounted membrane keypad
2.2 – RANGE
Velocity Calibration Range.
Low Range
(0 to 5,000 FPM)
High Range
(0 to 10,000 FPM)
Custom Range (consult Factory)
Filter.
Analog outputs filtered via user selectable digital low
pass filter.
Temperature Limits.
–20ºF to 180ºF Storage
–20ºF to 140ºF Operating
2.3 – PROBE ASSEMBLY
Mounting.
4" x 4" aluminum plate with four 0.25" holes for
fasteners and neoprene gasket.
Humidity Limits.
0 to 95% RH, non-condensing
Length.
8" up to 120"
2.5 – POWER
Sensors Per Probe.
Maximum of 16
Power Supply.
24VAC or 24VDC.
Connection.
Probe to Probe via RJ-45 cable for signal and power.
Probe to Transmitter via shielded cable with RJ-45
connection. 10' length standard with optional 50' and
100' lengths.
Power Consumption.
16 to 90VA dependent on number of sensor nodes (1
to 32 maximum)
Circuit Protection.
Power input is isolated, fused, and reverse polarity
protected. Earth Ground must be connected to the
terminal labeled "G".
Temperature Limits.
–20ºF to 180ºF Storage
–20ºF to 140º Operating
Humidity Limits.
0 to 95% RH, non-condensing.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
2
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 3 – FEATURES
3 – FEATURES
3.1 – OPERATOR MENU
The microprocessor program contains a Operator menu system for selecting parameters.
Four pushbuttons UP, DN, ENT, and ESC allow the operator access to the menu for setting configuration modes and
values. Refer to the Configuration Programming (Section 5.6) instructions for operation details.
Also contained in the Operator menu is an output calibration feature. The calibration method is completely digital and
contains no analog potentiometer adjustments which are susceptible to drift. Non-volatile memory is used for storing
all setup parameters and calibration values, and will remain unchanged after set, even when power to the unit is off.
3.2 – DATA DISPLAY
The ELECTRA-flo Thermal Air Flow Transmitter utilizes a high visibility backlit graphical LCD. 3/4" x 2-1/2" display
with three lines of process data, selectable for U.S. or S.I. units. Also used for configuration interface.
3.3 – LARGE OPERATION RANGE
The ELECTRA-flo Thermal Air Flow System can maintain accurate and linear output of flows from 0 to 5,000 FPM
(Low Range) and 0 to 10,000 FPM (High Range). Consult Factory for Custom Range.
3.4 – ENCLOSURE
The ELECTRA-flo Thermal Air Flow Transmitter is housed in an aluminum NEMA 1 enclosure with hinged front cover
for access to power and signal terminals for field connection.
3.5 – MULTIPLE OPERATING POWER SELECTIONS
The ELECTRA-flo Thermal Air Flow Transmitter can be powered by either 24VAC or 24VDC.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
3
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 4 – INSTALLATION
4 – INSTALLATION
4.1 – RECEIVING AND INSPECTION
• Carefully remove the ELECTRA-flo Probe(s) or Station, and Transmitter from the shipping container and inspect for
any damage. If any damage has occurred in transit, contact freight carrier.
• Review the Factory Set-Up Information Sheet provided separately and verify the W.O. # and Serial # match those
on the ELECTRA-flo. Verify that the configuration recorded on the Factory Set-Up Information Sheet is correct for
your application. If not, contact Air Monitor's Customer Service Department at 1-800-AIRFLOW for further guidance.
Note:
The ELECTRA-flo has been configured to customer provided parameters (see "Factory Setup
Information Sheet" provided separately), and requires no field calibration/verification prior to installation.
4.2 – LOCATION
• The standard version of the ELECTRA-flo Transmitter is a NEMA 1 enclosure suitable for most clean indoor locations.
If additional protection is required, mount the Transmitter in an enclosure with adequate NEMA rating.
• The ambient temperature of the selected mounting location must be between -20ºF to 140ºF. Consideration should
be given to units exposed to direct sunlight.
• The selected mounting location should be rigid and free of vibration.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
4
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 4 – INSTALLATION
4.3 – MOUNTING
Probes. See separate Installation Instructions for the installation/mounting of ELECTRA-flo Probes and Stations.
Transmitter. This section may be skipped if the unit is an ELECTRA-flo/CM or ELECTRA-flo/M, and the Transmitter
was ordered Factory mounted to the Station.
– Tools Required: Electric drill; #25 (0.1495") bit; screwdriver or nutdriver; and four #8-32 self-tapping machine screws.
– The ELECTRA-flo can be mounted in any position provided it is secured using all four mounting holes.
– Reasonable consideration should be given to clearances for electrical connections.
– Once a suitable location is found, use the unit as a template to mark the centers of the four mounting holes.
– Drill four pilot holes at the marked locations. With the unit in position, install the four #8-32 screws.
ELECTRA-flo
Thermal Mass Flow Transmitter
A IR MONITOR
C ORPORATION
OFF
ON
Figure 4.1
4.4 – PROCESS CONNECTIONS
See separate Installation Instructions provided with the ELECTRA-flo Probes or Station for information on
connecting cables from the Probes or Station to the Transmitter.
If the ELECTRA-flo/CM and ELECTRA-flo/M have been purchased with a factory mounted transmitter, all
connector cabling has already been installed.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
5
ELECTRA-flo - IO&M Manual
SECTION 4 – INSTALLATION
ELECTRA-flo
4.5 – POWER/SIGNAL CONNECTIONS
Power wiring is done at terminal strip P8, and signal wiring is done at terminal strip P7. Both P7 and P8 are located
in the lower portion of the transmitter and are accessible by opening the front cover. See Figure 4.2 for location of P7
and P8. Two conduit openings are provided in the bottom of the transmitter for the power and signal wiring.
Figure 4.2
WIRING. It is recommended that power wiring be 14 awg to 18 awg, and signal wiring should be 14 awg to 22 awg.
14 awg is the maximum wire gauge that the terminals can accommodate. No more than two wires should be
connected to any one terminal. To aid in the wiring of both power and signal wires, P7 and P8 are removable by
pulling the terminal strip straight up and off the circuit board. Once wiring has been completed, replace the terminal
strip by aligning with receptacle and pressing firmly.
POWER 24 VAC/DC (Terminals L, N and G, P8). Power required by the ELECTRA-flo must be connected to the two
terminals labeled L(+) and N(–). Earth ground must be connected to the terminal labeled G. Power Supply must
be 20-28VAC or 20-40VDC.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
6
ELECTRA-flo - IO&M Manual
SECTION 4 – INSTALLATION
ELECTRA-flo
4.5 – POWER/SIGNAL CONNECTIONS (con't)
OUTPUT #1 (Terminals 1(+) and 2(-), P7). This output represents the measured airflow and is sourced (powered)
by the ELECTRA-flo. Output can be configured for 0-5VDC, 0-10VDC, or 4-20mADC. Review Factory Set-Up
Information Sheet for your configuration.
If output is to be 0-5VDC:
If output is to be 0-10VDC:
If output is to be 4-20mADC:
Position both jumpers on J3. See Figure 4.2.
Position both jumpers on J2. See Figure 4.2.
Position both jumpers on J4. See Figure 4.2.
In addition to positioning the jumpers for the desired output type, the corresponding output type must be selected in
the Operator Menu (see Section 5.12).
OUTPUT #2 (Terminals 3(+) and 4(-), P7). This output can represent the measured flow (0 - Design Full Range) or
temperature (0 to 140ºF / -18 to 60ºC) and is sourced (powered) by the ELECTRA-flo. Output can be configured for
0-5VDC, 0-10VDC, or 4-20mADC. Review Factory Set-Up Information Sheet for your configuration.
If output is to be 0-5VDC:
If output is to be 0-10VDC:
If output is to be 4-20mADC:
Position both jumpers on J6. See Figure 4.2.
Position both jumpers on J5. See Figure 4.2.
Position both jumpers on J7. See Figure 4.2.
In addition to positioning the jumpers for the desired output type, the corresponding output type must be selected in
the Operator Menu (see Section 5.12).
Network Connection (Terminals 5, 6 & 7, P7). This serial output is available with optional LonWorks or BACnet
(Version 1.5X only) communication.
For LonWorks, connections are as follows:
Terminal 5 – LonWorks B
Terminal 6 – LonWorks A
Terminal 7 – Ground
Two output variables are provided, flow volume and temperature.
SNVT
SNVT Index
Measurement
Units
Type Category
Type Size
SNVT_flow_f
53
Flow Volume
Liters/Sec
Floating Point
4 bytes
SNVT_temp_p
105
Temperature
°C x 100
Signed Long
2 bytes
Air Monitor Corporation
116-053-13.P65 (2/28/12)
7
ELECTRA-flo - IO&M Manual
SECTION 4 – INSTALLATION
ELECTRA-flo
4.5 – POWER/SIGNAL CONNECTIONS (con't)
For BACnet, connections are as follows:
Terminal 5 – Net A or Net +
Terminal 6 – Net B or Net Terminal 7 – Network Ground
For BACnet objects, see Appendix A.
Set the S1 Termination switches on the BACnet module as follows:
S1 Switch Position
Note:
Termination Type
1
2
3
No Termination
OFF
OFF
OFF
End of Line
ON
OFF
OFF
Fail-safe Bias
ON
ON
ON
The Fail-safe Bias termination includes End of Line termination.
4.6 – DISPLAY CONTRAST ADJUSTMENT
To compensate for different ambient lighting conditions and viewing angles, the ELECTRA-flo display's contrast can
be adjusted for optimum visibility. Contrast is adjusted using potentiometer R13. Turn R13 clockwise to increase
contrast (darken characters relative to background) or counterclockwise to decrease contrast.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
8
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5 – OPERATION
5.1 – INTRODUCTION
The ELECTRA-flo has been configured at the Factory to customer specified parameters which are recorded on the
ELECTRA-flo Factory Information Set-Up Sheet, provided separately. Review this information and verify that the
ELECTRA-flo set-up is correct for your application. If any problems or discrepancies are detected, contact Air Monitor's
Customer Service Department at 1-800-AIRFLOW prior to proceeding.
5.2 – START-UP
1. After Installation has been verified in accordance with Section 4, turn power switch located at the lower front side
to the ON position (see Figure 4.1).
2. Display will briefly indicate:
ELECTRA-flo
-------------------Thanks for Choosing
AIR MONITOR
Followed by:
1
8
16
24
32
The number of active sensors will be
represented by the bar graph and
listed below. There are 8 active
sensors in this example.
Sensors Found: 8
Total Sensors: 8
After 5 seconds, display will indicate:
1
8
16
24
32
The number of enabled sensors will be
represented by the bar graph and
listed below. There are 8 active
sensors in this example.
Enabled Sensors: 8
Total Sensors: 8
After 5 seconds, display will indicate:
ELECTRA-flo
-------------------Sensors Warming Up
with the
progressing from left to right.
after 20 seconds the display will return to Normal display mode, and the dot in the upper right of the display
indicating CPU Activated will blink rapidly (4 times per second). This is Normal operation mode and no further
user interface is required. If, however, user would like to verify configuration or change user selectable parameters,
continue to Section 5.4 entitled "CONFIGURATION".
TEMP
VELO
0 ACFM
68.0ºF
0 AFPM
*
*Dot flashes 4 times a second, indicating
that CPU is active. If ALERT flashes
instead of Dot, see section for
Diagnostics.
Normal display mode
Air Monitor Corporation
116-053-13.P65 (2/28/12)
9
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.3 – NORMAL OPERATION
Under Normal operation, the ELECTRA-flo Transmitter will continuously display flow and velocity, or temperature.
5.4 – CONFIGURATION
The ELECTRA-flo onboard microprocessor controls Configuration: Operating parameter selection; input/output
activation and scaling, and display scaling.
The customer can verify configuration and change certain parameters (within defined ranges) by entering the ELECTRAflo Configuration mode. This is accomplished using the four membrane pushbuttons located on the ELECTRA-flo
cover. See Figure 4.1 for location of pushbuttons.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
10
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.5 – PUSHBUTTON DEFINITION
The four pushbuttons used to interface with the ELECTRA-flo are as follows: UP
DN
ENT
ESC
In addition to use during Configuration programming, pushbuttons can be used for certain functions when in the
Normal operation mode. The following list describes the pushbutton function when in the Normal operation mode
and in the User Setup (programming).
When in Normal Operation Mode.
ENT then ESC then UP then ENT
Activates the Operator menu.
ENT then ESC then DN then ENT
Activates the Supervisor menu.
ENT
Activates Password selection menu.
ENT then UP then DN then ENT
Displays ID, ESID, and WO#. Press UP and software version and maximum
velocity will be displayed. Press ESC and the display will go back to the
Normal operation mode.
When in User Setup.
UP or DN
Use to scroll to the desired Main Menu item.
Use to scroll to the value or mode within a parameter.
ENT
Enters user into specific selection sub-menu from Main Menu Selection.
Displays current setting of selected Parameter. Enters the selected value or setting into memory.
ESC
Use as an escape key to exit back to Main Menu selection to avoid scrolling to Return to MAIN MENU
The following pushbutton combinations can be used to more quickly set user selected values (i.e. Process Min and
Max Values, etc.).
UP* + ESC
Increases the second column digit.
DN* + ESC
Decreases the second column digit.
UP* + DN
Increases the third column digit.
DN* + UP
Decreases the third column digit.
UP* + ESC + DN
Increases the fourth column digit.
DN* + ESC + UP
Decreases the fourth column digit.
XXXXX
2nd Column
3rd Column
4th Column
*Must be pressed and held before other button(s) are pressed.
Note: Pushbuttons are momentary type and should be quickly pressed and released to initiate desired
change, unless otherwise instructed to press and hold.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
11
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.6 – CONFIGURATION PROGRAMMING
1. With power ON and initialization complete (see Section 5.2), press ENT then ESC then UP then ENT to
activate the Operator menu. The display will indicate:
ENTER PASSWORD FOR
OPERATOR MENU
XXXX
Note: If Operator Menu password has been bypassed (see Section 5.7), the display will indicate as shown in
Step 3 below.
2. Using UP and ENT, scroll to the numeric password for the Operator Menu. From the Factory, password is set
for 1,111.
3. Once password is displayed, press ENT and display will indicate:
4. Press ENT and display will indicate:
OPERATOR MENU
OPERATOR PASSWORD
By using UP and DN, the user can scroll through the following selections:
MAIN MENU SELECTION
DESCRIPTION
Operator Password Selection
Allows for the selection of password for the Operator Menu, and the bypassing of
the password.
Flow Configuration
Allows for the configuration of process variable such as: Duct size and shape,
process type, process maximum/units, and percent lockdown.
Display Configuration
Allows the selection of parameter to be displayed on Lines 2 & 3, and display filter.
Output 2 Parameter Selection
Allows the selection Output 2 parameter.
Low Pass Filter Selection
Selects amount of filtering applied to the output and to the display.
Output Signal Type Selection
Allows the selection of signal type for Output 1 and 2.
Transmitter Output Calibration
Allows for the zeroing and spanning of transmitter analog Outputs 1 and 2.
K-factor Configuration
Turns K-factor ON or OFF and allows for the calculation or selection of exponent and
gain values.
Menu Inactivity Timeout
Selection
Allows for the selection a time after which the unit returns to normal operation if no
activity in the Operator Menu.
Network Configuration
Turns the Network ON or OFF, and allows BACnet configuration.
Flow Alarm Configuration
(available only with BACnet
Network Option)
Turns each alarm ON or OFF, select High and Low Setpoints, Deadband selection,
and Alarm Delay.
Temperature Alarm
Configuration (available only
with BACnet Network Option)
Turns each alarm ON or OFF, select High and Low Setpoints, Deadband selection,
and Alarm Delay.
Operator Menu Exit
Returns display to Normal operation.
5. Once the desired selection is displayed, press ENT to enter its sub-menu.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
12
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.6 – CONFIGURATION PROGRAMMING (con't)
Once the desired Selection is displayed, its sub-menu can be entered by pressing ENT.
At any time while in the Operator Menu, User can return to Normal operation mode by pressing ESC or scrolling to:
OPERATOR MENU
EXIT
and pressing ENT.
To better understand the process of Configuration Programming, arrows with pushbutton designations have been
included on the following flow chart of Display Configuration. This will aid in the navigation of the Configuration
Programming Process.
Operator Menu
ENT
ENT
Display Filter
Selection
Display Configuration
ESC
Display Filter
0 (None)
UP or DN will scroll
between 0 and 5
ENT or ESC
UP
DN
ENT
ESC
Line 2 Parameter
Selection
Line 2 Parameter
VELOCITY
UP or DN wil scroll
between VELOCITY,
TEMPERATURE, &
CUSTOM TEXT
Line 2 Parameter
TEMPERATURE
UP or DN wil scroll
between
VELOCITY,
TEMPERATURE, &
CUSTOM TEXT
ENT or ESC
UP
DN
UP
DN
ENT
Line 3 Parameter
Selection
ENT or ESC
UP
DN
ENT or ESC
Return to
MAIN MENU
Output 2 Parameter
Selection
This example of navigation is similar for all Operator Menu selections.
Note:
All selections that are available for further configuration programming will have an "arrow" symbol displayed in the right side of the display field. Those that are not available for further configuration programming will not have the "arrow" symbol displayed and will display Not Installed beneath the selection description. Example:
Network option is
Not Installed
The remainder of this Section details steps to verify or change Configuration Programming of all Operator Menu
Selections.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
13
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.7 – OPERATOR PASSWORD SELECTION
Allows the selection of an Operator Menu password, and the option of bypassing the password.
Operator Menu
Password Menu
- OPERATOR MENU EXIT
Operator Password Select
- Flow Configuration
Default selection shown.
- Password Selection
- Bypass Password? Selection
- Return to MAIN MENU
Available selections:
Password
1,111
0 to 9,999
Bypass Password?
NO
NO or YES
Return to
MAIN MENU
Note: The Operator Password menu can be accessed directly following start-up (power ON) by pressing:
UP then DN then UP then ESC.
1. While in Operator Menu, use UP or DN to scroll to:
Operator Password
Selection
2. Press ENT to enter Operator password menu. Display will indicate:
Password
Selection
3. Press ENT and display will indicate current password.
Note: From the Factory, password is set for 1,111
4. Use UP or DN to change password. Once desired password is displayed, press ENT. New password will be
stored in memory and display will return to previous menu (see Step 2).
Caution: If password is changed, write it down, and retain in case it is forgotten.
Note: If user desires not to change password and return to password menu, press ESC. Unit will remain
programmed as it was originally.
5. Use UP to select Bypass Password if desired.
6. Follow Steps 3 and 4 to make changes.
CAUTION: If YES is selected, this will eliminate the need to enter any password when accessing the Operator
Menu.
7. To return to Main Menu, select Return to MAIN MENU in the Operator Password Selection menu, and press
ENT.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
14
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.8 – FLOW CONFIGURATION
This Operator Menu selection is where all application specific data is entered to configure the ELECTRA-flo for a
unique application. Typical data includes: Units of Measure, Duct Type and Size, Flow Type, Units and Conditions,
and Output Lockdown.
Note:
The Factory has entered data in this section based on customer supplied information. Data can be reviewed
and verified by scrolling through the individual menu items or reviewing the Factory Set-Up Information sheet
provided separately. Review this information BEFORE making any changes as it can have a significant
effect on the operation of the ELECTRA-flo.
Operator Menu
Flow Configuration Menu
- Operator Password Selection
Flow Configuration
- Display Configuration
- Dimensional Units Selection
- Temperature Units Selection
- Duct Shape Selection
- Duct Height Selection 1
- Duct Width Selection 1
- Duct Diameter Selection 2
- Duct Area Selection 3
- Actual or Standard Selection
- Site Elevation Selection
- Volume Units Selection
- Design Full Range Selection
- Ouput Lockdown Selection
- Return to MAIN MENU
1 Available only if RECTANGULAR or OVAL is
Default selection shown.
Available selections:
Dimensional Units
U.S.
U.S. or METRIC
Temperature Units
°F
°F or °C
Duct Shape
RECTANGULAR
RECTANGULAR,
ROUND, OVAL, FAN
INLET-SINGLE, FAN
INLET-DOUBLE or
OTHER
Duct Height
XX.XX in.
0.00 to 300.00 in.
0 to 10,000 mm.
Duct Width
XX.XX in.
0.00 to 300.00 in.
0 to 10,000 mm.
Duct Diameter
XX.XX in.
0.00 to 300.00 in.
0 to 10,000 mm.
Duct Area
XX.XX Sq. Ft.
0.00 to 325.00 Sq.Ft.
0.000 to 35.500 Sq.M.
Actual or Standard
ACTUAL
Actual or
Standard
Site Elevation
0 Feet
0 to 15,000 Feet
0 to 4,572 Meters
Volume Units
ACFM
See UNITS list for
available
selections
Design Full Range
XX,XXX ACFM
Maximum Full Range
XX,XXX ACFM 4
Design value
adjustable up to
maximum value.
Ouput Lockdown
200 AFPM
0 to 5000 AFPM
selected as Shape.
2 Available only if ROUND is selected as Shape.
3 Available only if OTHER is selected as Shape.
4 Maximum Full Range is
Return to
MAIN MENU
Air Monitor Corporation
116-053-13.P65 (2/28/12)
15
based on the duct area.
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.8 – FLOW CONFIGURATION (con't)
Flow
Configuration
1. While in Operator Menu, use UP or DN to scroll to:
Dimensional Units
Selection
2. Press ENT to enter Flow Configuration menu. Display will indicate:
3. Press ENT and display will indicate current setting of Units (U.S. or METRIC).
4. Use UP or DN to change setting. Once desired setting is displayed, press ENT, new setting will be stored in
memory and display will return to Flow Configuration menu as in Step 2.
Note: If user desires not to change the setting and return to the Flow Configuration menu, press ESC. Unit will
remain programmed as it was originally.
5. Use UP or DN to select remaining parameters to be changed within the Flow Configuration menu.
6. Follow Step 4 to make any changes to parameters.
See the following Units List for the available selections for the appropriate Flow Type.
UNITS LIST
for Volume
UNIT OF MEASUREMENT
DISPLAY
Actual cubic feet per minute
ACFM
Actual cubic feet per hour
ACFH
Actual liters per second
Al/s
Actual liters per minute
Al/m
Actual cubic meters per hour
Am3/h
Standard cubic feet per minute
SCFM
Standard cubic feet per hour
SCFH
Standard liters per second
Sl/s
Standard liters per minute
Sl/m
Standard cubic meters per hour
Sm3/h
7. To return to the Main Menu, select Return to MAIN MENU in the Flow Configuration menu and press ENT.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
16
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.9 – DISPLAY CONFIGURATION
Allows selection of display parameter for lines 2 and 3. Also, the level of filtering, 0 through 5 (5 is maximum) can be
selected by User.
Operator Menu
Display Configuration Menu
- Flow Configuration
Display Configuration
- Output 2 Parameter Selection
- Display Filter Selection
- Line 2 Parameter Selection
- Line 2 Custom Text Selection 1
- Line 3 Parameter Selection
- Line 3 Custom Text Selection 1
- Return to MAIN MENU
Default selection shown.
Available selections:
Display Filter
0 (None)
0 (None) to
5 (Maximum)
Line 2 Parameter
TEMPERATURE
TEMPERATURE,
CUSTOM TEXT,
or VELOCITY
Line 2 Custom Text
_
see ASCII
Character Chart for
selection
Line 3 Parameter
VELOCITY
TEMPERATURE,
CUSTOM TEXT,
or VELOCITY
Line 3 Custom Text
_
see ASCII
Character Chart for
selection
1 Available only if Parameter is CUSTOM TEXT.
Return to
MAIN MENU
Air Monitor Corporation
116-053-13.P65 (2/28/12)
17
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.9 – DISPLAY CONFIGURATION (con't)
1. While in Operator Menu, use UP or DN to scroll to:
Display
Configuration
2. Press ENT to enter Display Configuration menu. Display will indicate:
Display Filter
Selection
3. Press ENT and display will indicate current setting of the filter [0 (None), 1 (Minimum), 2, 3, 4, or 5 (Maximum)].
4. Use UP or DN to change setting. Once desired setting is displayed, press ENT, new setting will be stored in
memory and display will return to Display Configuration menu as in Step 2.
Note: If user desires not to change the setting and return to the Display Configuration menu, press ESC. Unit
will remain programmed as it was originally.
5. Use UP and display will indicate:
Line 2 Parameter
Selection
6. Press ENT and display will indicate current parameter selected to display on Line 2 (VELOCITY,
TEMPERATURE, or CUSTOM TEXT).
7. Use UP or DN to scroll to desired parameter. Press ENT, and parameter will be stored in memory and display
will indicate as in Step 5.
Note: If user desires not to change the setting and return to the Setup menu, press ESC. Unit will remain
programmed as it was originally.
8. If CUSTOM TEXT was selected and ENT pressed in Step 7, proceed to Step 13. For other parameters,
continue with Step 9.
9. Press UP and display will indicate:
Line 3 Parameter
Selection
10. Repeat Steps 6 through 8 for Line 3. The only differences being the change of Line # in the display.
11. After Line 3 has been set, Step 9 will yield a display:
Return to
MAIN MENU
12. Press ENT to return to Main Menu.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
18
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.9 – DISPLAY CONFIGURATION (con't)
13. If Custom Text was selected and ENT pressed in Step 7 (or for Line 3), press UP and display will indicate:
Line 2 Custom Text
Selection
14. Press ENT and display will indicate:
Cursor indicates position to be
set. There are 20 positions
available to hold custom text.
Line 2 Custom Text
15. Use UP or DN to scroll through available characters (see ASCII Chart at the end of this Section for available
characters).
16. When desired character is displayed, press ENT, character will be stored and cursor will advance one position to
the right.
17. Repeat Steps 15 and 16 for all 20 positions. When position 20 is entered, user will be exited back to display as in
Step 13.
In "Set Custom Text" mode, the pushbuttons can be used in the following combinations to facilitate programming.
ESC + UP
Moves position cursor to the right, one position at a time.
ESC + DN
Moves position cursor to the left, one position at a time.
ESC + ENT
Exits "Set Custom Text". Does not enter any changes to the display since the last time ENT was pressed.
UP + DN
Jumps up five characters at a time, to the desired character.
DN + UP
Jumps down five characters at a time, to the desired character.
ASCII Character Chart
!
"
#
$
%
&
'
(
)
Air Monitor Corporation
116-053-13.P65 (2/28/12)
*
+
'
.
/
0
1
2
3
4
5
6
7
8
9
:
;
<
=
>
?
@
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
19
W
X
Y
Z
[
¥
]
^
-
`
a
b
c
d
e
f
g
h
i
j
k
l
m
n
o
p
q
r
s
t
u
v
w
x
y
z
{
|
}
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.10 – OUTPUT 2 PARAMETER SELECTION
Allows the selection of which process variables Output 2 represents.
Process variables available for output are: Flow, Temperature, or None.
If Flow is selected, output will represent 0 to Design Full Range (see Section 5.8).
If Temperature is selected, output will represent 0º to 140ºF (-18ºC to 60ºC).
Operator Menu
Default selection shown.
- Display Configuration
Output 2 Parameter Select
- Low Pass Filter Selection
Output 2 Parameter
TEMPERATURE
1. While in Operator Menu, use UP or DN to scroll to:
Available selections:
FLOW, NONE
TEMPERATURE
Output 2 Parameter
Selection
2. Press ENT and display will indicate current setting of Output #2 (Flow, Temperature or None).
3. Use UP or DN to change setting. Once desired setting is displayed, press ENT. New setting will be stored in
memory and display will return as in Step 1.
Note: If user desires not to change the setting and return to Output 2 Parameter menu, press ESC. Unit will
remain programmed as it was originally.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
20
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.11 – LOW PASS FILTER
Allows selection of level of Process filtering applied to the output. Levels are 0 to 10, with 0 representing no filtering
and 10 representing maximum filtering. Display Filter is an additional filter selection applied only to the display.
This filtering affects all subsequent outputs and displays.
Operator Menu
Default selection shown.
- Output 2 Parameter Selection
Low Pass Filter Selection
- Output Signal Type Selection
Low Pass Filter
1 (Minimum)
1. While in Operator Menu, use UP or DN to scroll to:
Available selections:
0 (None) to
10 (Maximum)
Low Pass Filter
Selection
2. Press ENT and display will indicate current setting of Process filter; (0 (none) to 10 (maximum).
3. Use UP or DN to change setting. Once desired setting is displayed, press ENT. New setting will be stored in
memory and display will return as in Step 1.
Note: If user desires not to change the setting and return to Output 2 Parameter menu, press ESC. Unit will
remain programmed as it was originally.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
21
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.12 – OUTPUT SIGNAL TYPE SELECTION
User can select signal type for Output 1 and 2.
The output types selected below must correspond to the types selected via jumpers J3 through J7 (see Section 4.5).
Operator Menu
Output Signal Menu
- Low Pass Filter Selection
Output Signal Type Select
- Transmitter Output Calibration
Default selection shown.
- Output 1 Signal Type Selection
- Output 2 Signal Type Selection
- Return to MAIN MENU
Available selections:
Output 1 Signal Type
4-20 mA
4-20 mA,
0-10 Vdc, 0-5 Vdc
Output 2 Signal Type
4-20 mA
4-20 mA,
0-10 Vdc, 0-5 Vdc
Return to
MAIN MENU
1. While in Main Menu, use UP or DN to scroll to:
Output Signal Type
Selection
2. Press ENT to enter Output Signal Type menu. Display will indicate:
Output Signal Type
Selection
3. Press ENT and display will indicate current signal type (4-20mA).
4. Use UP or DN to change signal type. Once desired signal type is displayed, press ENT. New signal type will be
stored in memory and display will return to Output Signal Type Selection menu as in Step 2.
Note: If user desired not to change the signal type and return to Output Signal Type Selection menu, press ESC.
Unit will remain programmed as it was originally.
5. Use UP or DN to select remaining parameters to be changed.
6. Follow Step 4 to make any changes to parameters.
7. To return to Main Menu, select Return to MAIN MENU in Output Signal Type Selection menu and press ENT.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
22
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.13 – TRANSMITTER OUTPUT CALIBRATION
Allows for the calibration of the ELECTRA-flo analog outputs.
Operator Menu
Output Calibration Menu
- Output Signal Type Selection
Transmitter Output Calib.
- K-Factor Configuration
- Output 1 Zero Selection
- Output 1 Span Selection
- Output 2 Zero Selection
- Output 2 Span Selection
- Return to MAIN MENU
See Calibration
Instructions
Note: Unit is supplied Factory calibrated.
This section can be accomplished with the ELECTRA-flo mounted in its operating location or at a test bench in a
calibration lab.
Required Equipment.
1. Digital Multimeter
Preparation.
1. Turn Power switch OFF on the ELECTRA-flo (see Figure 4.1).
2. Open cover of the ELECTRA-flo.
3. Remove all wires connected to terminals 1 through 4 (see Figure 4.2).
4. Turn Power switch ON.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
23
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.13 – TRANSMITTER OUTPUT CALIBRATION (con't)
1. While in Operator Menu, use UP or DN to scroll to:
Transmitter Output
Calibration
2. Press ENT to enter Display Configuration menu. Display will indicate:
Output 1 Zero
Selection
Type is 4-20mA
3. Press ENT. Display will indicate:
Output 1 Zero
Perform Calibration
Type is 4-20mA
4. Connect a DMM set for type and scale of Transmitter Output 1 (as indicated on display) across terminals 1 and
2 on the ELECTRA-flo (see Figure 4.2).
Note: If the output is 4-20mA, a load resistance should be in series with the DMM. This can be accomplished
by connecting the actual process load or a resistor of similar value to the actual process load.
DMM should be reading a minimum value; 0.00 ± 0.01 volts or 4.00 ± 0.01mA.
5. If DMM is reading out of tolerance, use UP or DN to adjust the ELECTRA-flo output for an acceptable DMM
reading.
Depending on DMM's selected range, the UP or DN button may need to be pressed and held for a period of
time before any change occurs in the DMM's display. To speed up changes in output, pushbutton combinations
can be used. The following chart lists these combinations along with the associated change in output type.
4-20mA
OUTPUT TYPE
0-5VDC
UP only
+0.001mA
+0.3mV
+0.6mV
DN only
-0.001mA
-0.3mV
-0.6mV
UP* + ESC
+0.01mA
+0.003V
+0.006V
DN* + ESC
-0.01mA
-0.003V
-0.006V
UP* + DN
+0.1mA
+0.03V
+0.06V
DN* + UP
-0.1mA
-0.03V
-0.06V
UP* + ESC* and DN
+1.0mA
+0.3V
+0.6V
DN* + ESC* and UP
-1.0mA
-0.3V
-0.6V
PUSHBUTTON COMBINATION
0-10VDC
*Must be pressed and held before other button(s) are pressed.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
24
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.13 – TRANSMITTER OUTPUT CALIBRATION (con't)
6. Once an acceptable zero reading is obtained, press ENT and then UP and display will indicate:
Output 1 Span
Selection
Type is 4-20mA
7. Press ENT. Display will indicate:
Output 1 Span
Perform Calibration
Type is 4-20mA
8. With DMM still connected as in Step 4, reading should be at maximum value; 10.00 ± 0.01 volts, 5.00 ± 0.01
volts, or 20.00 ± 0.1mA.
9. If DMM is reading out of tolerance, use UP or DN to adjust the ELECTRA-flo's output for an acceptable DMM
reading.
10. Once an acceptable span reading is obtained, press ENT and then UP and display will indicate:
Output 2 Zero
Selection
Type is 4-20mA
11. Repeat Steps 3 through 10 for Transmitter Output 2. For Transmitter Output 2, connect DMM across terminals 3
and 4.
12. Press UP and display indicates:
Return to
MAIN MENU
Air Monitor Corporation
116-053-13.P65 (2/28/12)
25
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.14 – K-FACTOR CONFIGURATION
Caution
In the majority of applications, the use of a K-Factor is neither required nor desirable.
Before using the K-Factor feature, contact the Service Department (see Section 8) to review
the application and obtain assistance in determining the K-Factor exponent and gain values.
Turns K-factor function ON or OFF, calculate a K-Factor exponent and gain from measured data, or select a K-Factor
exponent value and K-Factor gain value.
Note: If K-Factor is ON, Process displays will have an asterisk (KFon) to the right of the flow value.
Operator Menu
K- Factor Menu
- Transmitter Output Calibration
K - Factor Configuration
- Menu Inactivity Timeout Select
- K - Factor Off/On Selection
- Calculate K-Factor? Selection
- Numbr of Data Points Selection 1
- Measured Point 1 Selection 1
- Measured Point 2 Selection 1,2
- Measured Point 3 Selection 1,2
- Reference Point 1 Selection 1
- Reference Point 2 Selection 1,2
- Reference Point 3 Selection 1,2
- Perform Calculation Selection 1
- K - Factor Exponent Selection3
- K - Factor Gain Selection 3
- Return to MAIN MENU
Default selection shown.
Available selections:
K- Factor Off / On
OFF
OFF or ON
CalculateK-Factor?
NO
NO or YES
Numbr of Data Points
One Point
One Point
Two Points
Three Points
Measured Point 1
1,000 ACFM
Uses Process Units
& Format Selected
in Process Config.
Measured Point 2
5,000 ACFM
Uses Process Units
& Format Selected
in Process Config.
1 Available only if YES is selected in Calculate
K-Factor?
2 Depends on the number of Data Points selected.
3 Available only if NO is selected in Calculate
K-Factor?
Measured Point 3
9,000 ACFM
Uses Process Units
& Format Selected
in Process Config.
Reference Point 1
1,000 ACFM
Uses Process Units
& Format Selected
in Process Config.
Reference Point 2
5,000 ACFM
Uses Process Units
& Format Selected
in Process Config.
Reference Point 3
9,000 ACFM
EXPO:
GAIN:
1.0000
1.000
116-053-13.P65 (2/28/12)
26
& Format Selected
in Process Config.
Calculated from
data entered
above.
K-Factor Exponent
1.0000
0.5000 to 2.0000 *
K- Factor Gain
1.000
0.000 to 32.750 *
Return to
MAIN MENU
Air Monitor Corporation
Uses Process Units
0.0001 increments
0.001 increments
*Available range depends
on operating span versus
natural span.
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.14 – K-FACTOR CONFIGURATION (con't)
1. While in Operator Menu, use UP or DN to scroll to:
K-Factor
Configuration
2. Press ENT to enter K-Factor Configuration menu. Display will indicate:
K-Factor Off/On
Selection
3. Press ENT and display will indicate current setting of K-Factor (OFF or ON).
4. Use UP or DN to change setting. Once desired setting is displayed, press ENT. New setting will be stored in
memory and display will return to K-Factor Configuration menu as in Step 2.
Note: If user desires not to change the setting and return to K-Factor Configuration menu, press ESC. Unit will
remain programmed as it was originally.
5. Use UP or DN to select remaining parameters to be changed.
6. Follow Step 4 to make any changes to parameters.
7. To return to Main Menu, select Return to MAIN MENU in parameter menu and press ENT.
5.15 – MENU INACTIVITY TIMEOUT SELECTION
Allows user to select a time (minutes) after which the unit returns to Normal operation if no activity in the Operator
Menu.
Ope rator Me nu
Default selection shown.
- K-Factor Conf iguration
Menu Inactivity Timeout Select
- Network Selection
Me nu Inactivity
2 Minute s
1. While in Main Menu, use UP or DN to scroll to:
Available selections:
OFF to 30 minutes,
1 minute increments
Menu Inactivity
Timeout Selection
2. Press ENT and display will indicate current timeout value (1 to 30 minutes or OFF).
3. Use UP or DN to change timeout value. Once desired value is displayed, press ENT. New setting will be
stored in memory and display will return to Main Menu.
Note: If user desires not to change the setting and return to Main Menu, press ESC. Unit will remain
programmed as it was originally.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
27
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.16 – NETWORK CONFIGURATION
Allows user to turn network ON or OFF, and configure parameters based on Network type. BACnet available only
with version 1.5X.
Operator Menu
- Menu Inactivity Timeout Select
Network Configuration
- Flow Alarm Configuration
Network Configuration Menu 1
- Network ON / OFF Selection
- BACnet Instance ID Selection 2
- BACnet Address Selection 2
- BACnet MaxMasters Selection 2
- BACnet Baud Rate Selection 2
- Return to MAIN MENU
Default selection shown.
Available selections:
Network Off / On
OFF
OFF or ON
BACnet Instance ID
0
0 to 4,194,303
BACnet Address
1
1 to 127
BACnet Max Masters
1
1 to 127
BACnet Baud Rate
9600
9600, 19200,
38400, or 76800
1 Available only with Network option.
2 Available only with BACnet.
Return to
MAIN MENU
1. While in Main Menu, use UP or DN to scroll to:
Network
Configuration
2. Press ENT to enter Network Configuration menu. Display will indicate:
Network Off/On
Selection
3. Press ENT and display will indicate current setting of Network (OFF or ON).
4. Use UP or DN to change setting. Once desired setting is displayed, press ENT and new setting will be stored in
memory and display will return to Network Configuration menu as in Step 2.
Note: If user desires not to change the setting and return to Network Configuration menu, press ESC. Unit will
remain programmed as it was originally.
5. Use UP or DN to select remaining parameters to be changed.
6. Follow Step 4 to make any changes to parameters.
7. To return to Main Menu, select Return to MAIN MENU in Network Configuration menu and press ENT.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
28
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.17 – FLOW ALARM CONFIGURATION
Available only with BACnet Network option.
User can turn each Alarm ON or OFF, select type of alarm and set the following values:
Alarm 1 Setpoint (this is Low, Low1, or High1 depending on Alarm Type): Selected value of flow below (for Low and
Low1) or above (for High 1) which an alarm condition will exist.
Alarm 2 Setpoint (this is High, Low2, or High2, depending on Alarm Type): Selected value of flow below (for Low2)
or above (for High and High2) which an alarm condition will exist.
Alarm Deadband: Value that transmitter signal has to reach above (for Low, Low1, or Low2) or below (for High,
High1, or High2) before an activated alarm will reset. Value is selected in same units as transmitter span.
Alarm Delay: Time between an alarm condition existing and alarm activation. Adjustable between 0.0 and 10.0
minutes in 0.1 minute increments.
Ope rator M e nu
- Network Conf iguration
Flow Alarm Configuration
- Temperature Alarm Conf ig
1
Flow Alarm Configuration Menu
-
Alarm 1 Of f / On Selection
Alarm 2 Of f / On Selection
Alarm 1 Setpoint Selection
Alarm 2 Setpoint Selection
Alarm 1 Dead Band Selection
Alarm 2 Dead Band Selection
Alarm Delay Selection
Return to MAIN MENU
1 Available only with BACnet.
Default selection shown.
Available selections:
Alarm 1 Off / On
OFF
OFF or ON
Alarm 2 Off / On
OFF
OFF or ON
Alarm 1, Low Setpt
250 [units]
Depends on Flow
Alarm 2, High Setpt
250 [units]
Depends on Flow
Alarm 1 Dead Band
50 [units]
Depends on Flow
Alarm 2 Dead Band
50 [units]
Depends on Flow
Alarm Delay
0.0 M in.
0.0 to 10.0 Min.
Units
Units
Units
Units
in 0.1 increments
Retur n to
MAIN M ENU
Air Monitor Corporation
116-053-13.P65 (2/28/12)
29
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.17 – FLOW ALARM CONFIGURATION (con't)
1. While in Main Menu, use UP or DN to scroll to:
Flow Alarm
Configuration
2. Press ENT to enter Alarm Configuration menu. Display will indicate:
Alarm 1 Off/On
Selection
3. Press ENT and display will indicate current setting of Alarm 1 (OFF or ON).
4. Use UP or DN to change setting. Once desired setting is displayed, press ENT. New setting will be stored in
memory and display will return to Alarm Configuration menu as in Step 2.
Note: If user desires not to change the setting and return to Alarm Configuration menu, press ESC. Unit will
remain programmed as it was originally.
5. Use UP or DN to select remaining parameters to be changed.
6. Follow Step 4 to make any changes to parameters.
7. To return to Main Menu, select Return to MAIN MENU in Alarm Configuration menu and press ENT .
Air Monitor Corporation
116-053-13.P65 (2/28/12)
30
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.18 – TEMPERATURE ALARM CONFIGURATION
Available only with BACnet Network option.
User can turn each Alarm ON or OFF, select type of alarm and set the following values:
Alarm 1 Setpoint (this is Low, Low1, or High1 depending on Alarm Type): Selected value of temperature below (for
Low and Low1) or above (for High 1) which an alarm condition will exist.
Alarm 2 Setpoint (this is High, Low2, or High2, depending on Alarm Type): Selected value of temperature below (for
Low2) or above (for High and High2) which an alarm condition will exist.
Alarm Deadband: Value that transmitter signal has to reach above (for Low, Low1, or Low2) or below (for High,
High1, or High2) before an activated alarm will reset. Value is selected in same units as transmitter span.
Alarm Delay: Time between an alarm condition existing and alarm activation. Adjustable between 0.0 and 10.0
minutes in 0.1 minute increments.
Ope rator M enu
- Flow Alarm Conf iguration
Temperature Alarm Config
- OPERATOR MENU EXIT
1
Tem p Alarm Configuration Menu
-
Alarm 1 Of f / On Selection
Alarm 2 Of f / On Selection
Alarm 1 Setpoint Selection
Alarm 2 Setpoint Selection
Alarm 1 Dead Band Selection
Alarm 2 Dead Band Selection
Alarm Delay Selection
Return to MAIN MENU
1 Available only with BACnet.
Default selection shown.
Available selections:
Alarm 1 Off / On
OFF
OFF or ON
Alarm 2 Off / On
OFF
OFF or ON
Alarm 1, Low Setpt
250 [units]
Depends on Temp
Alarm 2, High Setpt
250 [units]
Depends on Temp
Alarm 1 Dead Band
50 [units]
Depends on Temp
Alarm 2 Dead Band
50 [units]
Depends on Temp
Alarm Delay
0.0 M in.
0.0 to 10.0 Min.
Units
Units
Units
Units
in 0.1 increments
Return to
MAIN M ENU
Air Monitor Corporation
116-053-13.P65 (2/28/12)
31
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
5.18 – TEMPERATURE ALARM CONFIGURATION (con't)
1. While in Main Menu, use UP or DN to scroll to:
Temperature Alarm
Configuration
2. Press ENT to enter Alarm Configuration menu. Display will indicate:
Alarm 1 Off/On
Selection
3. Press ENT and display will indicate current setting of Alarm 1 (OFF or ON).
4. Use UP or DN to change setting. Once desired setting is displayed, press ENT. New setting will be stored in
memory and display will return to Alarm Configuration menu as in Step 2.
Note: If user desires not to change the setting and return to Alarm Configuration menu, press ESC. Unit will
remain programmed as it was originally.
5. Use UP or DN to select remaining parameters to be changed.
6. Follow Step 4 to make any changes to parameters.
7. To return to Main Menu, select Return to MAIN MENU in Alarm Configuration menu and press ENT .
Air Monitor Corporation
116-053-13.P65 (2/28/12)
32
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 6 – CALIBRATION
6 – SUPERVISOR MENU
6.1 – INTRODUCTION
The Supervisor menu allows individual sensors to be enabled or disabled, scan all sensors for status, and perform
diagnostics on any alert conditions.
1. To enter the Supervisor Menu, press ENT then ESC then DN then ENT at the same time.
The display will indicate:
ENTER PASSWORD FOR
SUPERVISOR MENU
XXXXX
Note: If Supervisor Menu password has been bypassed, display will indicate as shown in Step 3 below.
2. Using UP or DN scroll to the numeric password for the Supervisor Menu. From the Factory, password is set to
2,222.
3. Once password is displayed, press ENT, and the display will indicate:
4. Press ENT, and the display will indicate:
SUPERVISOR MENU
SUPERVISOR PASSWORD
SELECTION
By using UP or DN, supervisor can scroll through the following selections.
MENU SELECTION
DESCRIPTION
Supervisor Password Selection
Allows for the selection of password for the Supervisor menu, and
the option to bypass the password.
Sensor Management
Allows for the scanning of the sensor network for active and/or
enabled sensors. Also allows for the enabling/disabling of individual
sensors.
Diagnostic Display Selection
Displays each sensor's current reading of velocity and temperature.
Diagnostic ALERT Determination
Displays any sensor or average that currently has an ALERT
condition and the ALERT code.
Power Cycle Sensor Network
Allows for the cycling of power to the sensors.
Supervisor Menu Exit
Returns display to Normal operation.
Once the desired selection is displayed, press ENT to enter its sub-menu.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
33
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 5 – OPERATION
6.2 – SUPERVISOR PASSWORD SELECTION
Allows the selection of an Supervisor Menu password, and the option of bypassing the password.
Supervisor Menu
Password Menu
- SUPERVISOR MENU EXIT
Supervisor Password Select
- Sensor Management
Default selection shown.
- Password Selection
- Bypass Password? Selection
- Return to MAIN MENU
Available selections:
Password
2,222
0 to 9,999
Bypass Password?
NO
NO or YES
Return to
MAIN MENU
1. While in Supervisor Menu, use UP or DN to scroll to:
2. Press ENT to enter Supervisor password menu. Display will indicate:
Supervisor Password
Selection
Password
Selection
3. Press ENT and display will indicate current password.
Note: From the Factory, password is set for 1,111
4. Use UP or DN to change password. Once desired password is displayed, press ENT. New password will be
stored in memory and display will return to previous menu (see Step 2).
Caution: If password is changed, write it down, and retain in case it is forgotten.
Note: If user desires not to change password and return to password menu, press ESC. Unit will remain
programmed as it was originally.
5. Use UP to select Bypass Password if desired.
6. Follow Steps 3 and 4 to make changes.
7. To return to Main Menu, select Return to MAIN MENU in the Supervisor Password Selection menu, and
press ENT.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
34
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 6 – CALIBRATION
6.3 – SENSOR MANAGEMENT
Supervisor Menu
- Supervisor Password Select
Sensor Management
- Diagnostic Display Selection
Sensor Management Menu
- Scan Network For Sensors
- Disp Enabled Sensors
- Enable Sensor Selection
- Disable Sensor Selection
- Ping Sensor Selection
- Return to MAIN MENU
1
8
16
24
32
IIIIIII_______________________
Sensors Found: 6
Xmitter Total: 1
1
8
16
24
32
IIIIIII_______________________
Enabled Sensors: 6
Xmitter Total: 1
Available selections:
Enable Sensor: 1
1
8
16
24
32
IIIIIII_______________________
Enabled Sensors: 6
1 to 32 1
Disable Sensor: 1
1
8
16
24
32
IIIIIII_______________________
Enabled Sensors: 6
1 to 32 1
Ping Sensor
1
SENSOR FOUND
Return to
MAIN MENU
SENSOR FOUND
or
SENSOR NOT FOUND
1 to 32 1 , EXIT
1 Depends on # of sensors installed.
1. While in Operator Menu, use UP or DN to scroll to:
Sensor
Management
2. Press ENT to enter Sensor Management menu. Display will indicate:
3. Press ENT to enter Sensor Management menu. Display will indicate:
*The number of Active Sensors is unique to each application.
Scan Network
For Sensors
1
8
16
24
32
Sensors Found: 8
Total Sensors: 8
4. Press ESC or ENT to return to previous menu (Step 2).
Air Monitor Corporation
116-053-13.P65 (2/28/12)
35
ELECTRA-flo - IO&M Manual
*
ELECTRA-flo
SECTION 6 – CALIBRATION
6.3 – SENSOR MANAGEMENT (con't)
5. Press UP. Display will indicate:
Display Enabled
Sensors
6. Press ENT. Display will indicate:
1
8
16
24
32
Enabled Sensors: 8
Total Sensors:
8
Display will indicate all enabled sensors on the bar graph by darkened area under their respective #, and total
number of enabled sensors will be displayed at the bottom.
7. Press ESC to return to previous menu (see Step 5).
8. Press UP and display will indicate:
Enable Sensor
Selection
9. Press ENT. Display will indicate:
1
This display will indicate which sensors are enabled.
Enable Sensor: 1
8
16
24
32
Enabled Sensors: 8
Only enabled sensors will be indicated on bar graph by darkened area under their respective #, and total
number of enabled sensors will be displayed at the bottom.
If any active sensors have been previously disabled, they can be enabled by scrolling (using UP and DN), to
their #, and pressing ENT.
10. Press ESC to return to previous menu (see Step 8).
11. Press UP and display will indicate.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
Disable Sensor
Selection
36
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 6 – CALIBRATION
6.3 – SENSOR MANAGEMENT (con't)
12. Press ENT. Display will indicate:
1
Disable Sensor: 1
8
16
24
32
Enabled Sensors: 8
13. To disable a sensor, use UP and DN to scroll to that sensor's # and press ENT. Display will respond by removing the darkened area under the sensor's # on the bar graph and reducing the number of enabled sensors by
1.
14. When done disabling sensors, press ESC and display will return to previous menu (see Step 11).
15. Press UP . Display will indicate:
Ping Sensor
Selection
16. Press ENT. Display will indicate:
Ping Sensor
1
17. Use UP and DN to scroll to desired sensor.
18. Once desired sensor # is displayed, press ENT and display will indicate either:
Ping Sensor
1
SENSOR FOUND
Ping Sensor
1
SENSOR NOT FOUND
19. Use UP and DN to scroll to all desired sensors, and press ENT to view results.
20. Either scroll to exit (after #32) or press ESC to return to previous menu (see Step 15).
21. Press UP and display will indicate.
Return to
MAIN MENU
22. Press ENT and display will return to Main Menu.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
37
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 6 – CALIBRATION
6.4 – DIAGNOSTIC DISPLAY SELECTION
Supervisor Menu
Diagnostic Display
Diagnostic Display
Sensor Number: 1
VELO
XXX SFPM
TEMP
XX.X °F
- Sensor Management
Diagnostic Display Selection
- Diagnostic ALERT Determin
Available selections:
1 to 321
1Depends on # of
Velocity & temperature units depend on
selections made in Flow Configuration in
Operator Menu.
1. While in Main Menu, use UP and DN to scroll to:
sensors installed.
Diagnostic Display
Selection
2. Press ENT. Display will indicate:
Diagnostic Display
Sensor Number: 1
VELO
XXX SFPM
TEMP
XX.X ºF
3. Use UP and DN to scroll through all enabled sensors.
4. When done, press ESC and display will return to previous menu (see Step 1).
Air Monitor Corporation
116-053-13.P65 (2/28/12)
38
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 6 – CALIBRATION
6.5 – DIAGNOSTIC ALERT DETERMINATION
Supervisor Menu
Diagnostic ALERT Menu
- Diagnostic Display Selection
Diagnostic ALERT Determination
- Power Cycle Sensor Network
- ALERT for Sensors
- ALERT for Averages
- Turn Off/On ALERT
For Missing Sensors
- Return to MAIN MENU
ALERT For Sensors
NO ALERT EXISTS
See table below for
Sensor ALERT
code & definition
ALERT For Averages
NO ALERT EXISTS
See table below for
Averages ALERT
code & definition
Turn Off/On ALERT
ON
ON or OFF
Return to
MAIN MENU
1. While in Main Menu, use UP or DN to scroll to:
Diagnostic ALERT
Determination
2. Press ENT. Display will indicate:
ALERT for Sensors
3. Press ENT. Display will indicate:
ALERT for Sensors
NO ALERT EXISTS
or if an ALERT does exist, display will indicate:
Sensor Number: 1
ALERT CODE: 1
Sensor has not
responded
Definitions of individual sensor ALERT codes are found at the end of this Section.
4. Use UP or DN to scroll through all sensors that have an alert.
Note: Only sensors with an existing alert will be displayed with its alert code.
5
When done, press ESC and display will return to previous menu (see Step 2).
6. Press UP. Display will indicate:
Air Monitor Corporation
116-053-13.P65 (2/28/12)
ALERT for Averages
39
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 6 – CALIBRATION
6.5 – DIAGNOSTIC ALERT DETERMINATION (con't)
7. Press ENT. Display will indicate:
ALERT for Averages
NO ALERT EXISTS
or if an ALERT does exist, display will indicate:
Averages Signal
ALERT CODE: 4
Average Velocity is out
of device range
Definitions of individual averages ALERT codes are found at the end of this Section.
8. Use UP or DN to scroll through all average alerts.
9. When done, press ESC and display will return to previous menu (see Step 6).
10. Press UP. Display will indicate:
Turns Off/On ALERT
for Missing Sensors
11. Press ENT. Display will indicate current setting (ON or OFF).
12. Use UP or DN to change setting if desired, press ENT.
13. Press UP. Display will indicate:
Return to
MAIN MENU
14. Press ENT and display will return to Main Menu.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
40
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 6 – CALIBRATION
6.5 – DIAGNOSTIC ALERT DETERMINATION (con't)
Sensor Alert Code
Definition
1
Sensor has not responded
2
Sensor response address incorrect
3
Sensor response command incorrect
4
Sensor signals are out of range
Definition
Averages Alert Code
Air Monitor Corporation
116-053-13.P65 (2/28/12)
4
Average Velocity is out of device range
5
Average Volume is out of design range
6
Avg. Velo. & Volu. are out of range
7
Average Temperature out of device range
8
Avg. Velo. & Temp. are out of range
9
Avg. Volu. & Temp. are out of range
10
Velo, Volu, & Temp are out of range
41
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 6 – CALIBRATION
6.6 – POWER CYCLE SENSOR NETWORK
Supervisor Menu
Power Cycle Display
Available selections:
- Diagnostic ALERT Determination
Power Cycle Sensor Network
- SUPERVISOR MENU EXIT
Power Cycle
Are you sure?
NO
1. While in Main Menu, use UP or DN to scroll to:
YES or NO
Power Cycle
Sensor Network
2. Press ENT. Display will indicate:
Power Cycle
Are you sure?
NO
3. Use UP or DN to scroll to YES if it is desired to cycle Power.
4. With YES displayed, press ENT and Transmitter will cycle power and scan active sensors and enabled
sensors, similar to when power is first turned on (see Section 5.2).
5. Press ESC to return to previous menu (see Step 1).
Air Monitor Corporation
116-053-13.P65 (2/28/12)
42
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 7 – MAINTENANCE
7 – MAINTENANCE
The ELECTRA-flo is a solid state device having few mechanical parts requiring special periodic maintenance. The
following maintenance steps are not requirements, but guidelines for establishing a maintenance program for your
specific installation.
Operating experience should be used to set frequency of specific types of maintenance.
7.1 – CLEANLINESS
– Verify condensation (or other sources of liquids) are not present inside the ELECTRA-flo.
7.2 – MECHANICAL
– Verify CABLE connections between probes and transmitter are secure.
– Verify mounting hardware is secure.
7.3 – ELECTRICAL
– Periodically inspect all wiring to the ELECTRA-flo for good connections and absence of corrosion.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
43
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 8 – TROUBLESHOOTING
8 – TROUBLESHOOTING
Personnel should be familiar with the operation of the ELECTRA-flo (see Section 5) before performing any
troubleshooting.
Problem
Solution
Display blank; with backlight
and outputs
– Check the display's ribbon cable for proper seating in transmitter circuit board
– Bad display or transmitter board
Display blank; no backlight
with outputs
– Check the display's ribbon cable for proper seating in transmitter circuit board
– Defective display
Display blank with backlight
and no outputs
– Defective display
– Defective transmitter board
– Check the CPU LED flashing on transmitter board (located to the right of the display on the
transmitter board. Figure 4.2, Page 6)
Display blank without
backlight and no outputs
– Check for proper supply voltage at P8 terminals 1 & 2 (see Figure 4.2, Page 6)
– Check F1 fuse
– Defective transmitter board
– Check the CPU LED flashing on transmitter board (located to the right of the display on the
transmitter board. Figure 4.2, Page 6)
Normal Operation with
Extremely Low or High Flow
displayed
– Check F2 Fuse
– Verify upon powering up transmitter that all sensors are "Found" and "Enabled" (Section
5.2, Page 8)
– Verify Factory Set Up data is correct in Operator Menu under "Flow Configuration" (Section
5.8, Page 14)
– Enter Supervisor Menu (Section 6, Page 28), "Diagnostic Display Selection" (Section 6.4,
Page 33). Scroll through all sensors, log data, and contact the Factory.
Display reading "0" flow with
NO "Alert" message
– Ensure Flow is above lockdown (see Section 5.8)
– Check cable connections
Display reading "0" flow with
"Alert" message
– Indicated there is a fault with one or more sensors
– Perform "Diagnostic Alert Determination" in the "Supervisor Menu; determine if "Sensor" or
"Average" alert (Section 6.5, Page 34)
– Perform "Diagnostic Display Selection" in the Supervisor Menu; determine which sensor
has a failure (Section 6.4, Page 33)
If after following the Troubleshooting steps the ELECTRA-flo continues to operate improperly,
contact the Service Department for further assistance (see Section 10).
Air Monitor Corporation
116-053-13.P65 (2/28/12)
44
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 9 – PARTS LIST
9 – PARTS LIST
The following drawing with part numbers lists components of the ELECTRA-flo that are easily replaced by the Operator.
When contacting the Customer Service Department about parts, please have the applicable Factory Set-Up Information
sheet available for reference. To inquire about price and availability of a specific part number, please contact the
Customer Service Department at:
Phone: 707-544-2706
800-AIRFLOW
Air Monitor Corporation
116-053-13.P65 (2/28/12)
Fax: 707-526-2825
45
ELECTRA-flo - IO&M Manual
ELECTRA-flo
SECTION 8 – CUSTOMER SERVICE
10 – CUSTOMER SERVICE
10.1 – CUSTOMER SERVICE/TECHNICAL SUPPORT
Air Monitor Corporation provides in-house technical support for our products:
Monday through Friday
7 am to 5 pm (pst)
Phone: 707-544-2706 or 1-800-AIRFLOW
Fax: 707-526-2825
Additionally, on-site technical assistance is available. Before contacting the Customer Service Department, please
ensure any applicable troubleshooting steps outlined in Section 8 have been performed.
10.2 – REPAIRS/RETURNS
If after contacting the Customer Service Department it is determined that equipment will require return to Air Monitor
Corporation for further repair, a Return Authorization number will be issued by the Customer Service Department. A
Confirmation of Return Authorization with shipping instructions will be sent via facsimile or e-mail.
Equipment to be returned to Air Monitor should be returned in its original shipping container if possible. If this is not
possible, ensure equipment is packaged sufficiently to protect it during shipment.
CAUTION
All damage occurring during transit is the Customer's responsibility.
List the Return Authorization (R/A) number on the packing list and clearly mark this number on the outside of each
shipping container.
Costs associated with return of equipment to Air Monitor are the customer's responsibility regardless whether the
repair/return is under warranty.
10.3 – WARRANTY REPAIRS/RETURNS
Once the Customer Service Department determines that the equipment repair is under warranty, the item will be
repaired and returned to the customer at no charge.
10.4 – NON-WARRANTY REPAIRS/RETURNS
Customer will be invoiced for all parts and labor required for the repair of equipment. Return shipping charges will
also be added to invoice.
10.5 – FIELD SERVICE
Requests for field service should be made to the Customer Service Department, who will coordinate sending a
technician to customer's site.
Phone: 707-544-2706 or 1-800-AIRFLOW
Fax: 707-526-2825
Upon completion of work, technician completes a Field Service Report and gives a copy to the customer. Field
service is charged on a daily basis and all travel expenses are also added to customer's invoice.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
46
ELECTRA-flo - IO&M Manual
ELECTRA-flo
APPENDIX A
APPENDIX A
PRODUCT DESCRIPTION – THERMAL AIRFLOW MEASURING STATION
BACnet Standardized Device Profile (Annex L)
X
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
List of all BACnet Interoperability Building Blocks supported (see Annex K in BACnet Addendum 135d)
– DS-RP-B .............
– DS-WP-B ............
– DM-DDB-B .........
– DM-DOB-B .........
– DM-DCC-B .........
– DS-RPM-B ..........
– DM-RD-B ............
Read Property
Write Property
Dynamic Device Binding
Dynamic Object Binding
Device Communicattion Control
Read Property Multiple
Reinitialize Device
Which of the following device binding methods does the product support? (check one or more)
X
X
Send Who-Is, receive I-Am (BIBB DM-DDB-A)
Receive Who-Is, send I-Am (BIBB DM-DDB-B)
Send Who-Has, receive I-Have (BIBB DM-DOB-A)
Receive Who-Has send I-Have (BIBB DM-DOB-B)
Manual configuration of recipient device's network number and MAC address
None of the above
Air Monitor Corporation
116-053-13.P65 (2/28/12)
47
ELECTRA-flo - IO&M Manual
ELECTRA-flo
APPENDIX A
STANDARD OBJECT TYPES SUPPORTED
ANALOG INPUT OBJECT TYPE
No
No
Dynamically creatable using BACnet's CreateObject Service?
Dynamically deletable using BACnet's DeleteObject Service?
List of "Required" Properties Supported
X
X
X
X
X
X
X
X
PROP_OBJECT_IDENTIFIER
PROP_OBJECT_NAME
PROP_OBJECT_TYPE
PROP_PRESENT_VALUE
PROP_STATUS_FLAGS
PROP_EVENT_STATE
PROP_OUT_OF_SERVICE
PROP_UNITS
List of "Optional" Properties Supported
X
PROP_DESCRIPTION
The Air Monitor BACnet stack supports the optional property “PROP_DESCRIPTION”. This is used to
indicate the type of information in the object. For example, for an ELECTRA-flo system, the description will
indicate as “AF0” for average flow, or “AT0” for average temperature. If the object belongs to a sensor in the
system, it will be indicated as “STn” or “SFn”, where n is the sensor address. The Air Monitor Device which
supports BACnet will determine the amount of AI objects available. For an ElectraFLO system, the amount
of AI objects is determined by the total number of sensors in the system x 2 with an additional 2 AI objects
for system average flow and system average temperature. So an ElectraFLO system with 8 sensors will
have a total of 18 AI objects. These are for average Flow and average DP. This object does not support
intrinsic reporting, so the event state is always “NORMAL”.
Usage of the Status Field.
–
Each object supports status bits IN_ALARM, FAULT, and OUT_OF_SERVICE.
–
OVERRIDDEN is not supported as it makes no sense to override a value with no reasonable substitute.
–
The OOS property indicates the physical input to the object is not in service. In the case of an ElectraFLO
system, this will be set by the transmitter if someone intentionally removes the sensor from the network.
If the transmitter determines there is a problem with any sensor in question, the OOS bit is set along
with the FAULT bit. If the OOS property is set, data from the physical device will not be used in any
calculation.
–
IN_ALARM is set for values which exceed the predetermined values set in the transmitter memory.
Sensor analog objects will not typically have this flag set. This will be done at the transmitter level
indicating the average flow or temperature are out of range.
Air Monitor Corporation
116-053-13.P65 (2/28/12)
48
ELECTRA-flo - IO&M Manual
ELECTRA-flo
APPENDIX A
STANDARD OBJECT TYPES SUPPORTED (con't)
ANALOG INPUT OBJECT TYPE (con't)
None List of all properties that are writable where not otherwise required by this standard.
None List of proprietary properties.
None List of any property value range restrictions.
List of non-dynamic object identifiers and their meaning in this device
– Analog Input AF0 ............. Total System Flow (always present)
– Analog Input AT1/DP1 ...... Total System Temperature
– Analog Input SF1 ............. Sensor 1 Flow (guaranteed to be present)
– Analog Input ST1 ............. Sensor 1 Temperature (guaranteed to be present)
– Analog Input SF2 ............. Analog Inputs 2-32 are only present if there is more than 1 sensor in system
– Analog Input ST2 .............
– Analog Input SF32 ...........
– Analog Input ST32 ...........
DEVICE OBJECT TYPE
No
No
Dynamically creatable using BACnet's CreateObject Service?
Dynamically deletable using BACnet's DeleteObject Service?
List of "Optional" Properties Supported
X
PROTOCOL_CONFORMANCE_CLASS
List of all properties that are writable where not otherwise required by this standard
X
X
X
X
X
Property Description set by AMC Firmware
Device_Name set via ELECTRA-flo transmitter menu
Max_Master set via ELECTRA-flo transmitter menu
Max_Info_Frames set via ELECTRA-flo transmitter menu
Instance ID set via ELECTRA-flo transmitter menu
List of proprietary properties
– Property Identifier ..................... 38400
– Property Datatype ..................... Unsigned
– Meaning .................................... Baud Rate (set via ELECTRA-flo transmitter menu)
List of any property value range restrictions
– Object_Name ........................... <32 bytes
– Object_Identifier ....................... Device Type only
– Number_Of_APDU_Retries ...... 0-255
– APDU_Timeout ......................... 0-65535 milliseconds
– Vendor_Identifier ...................... 0-65535 milliseconds
– System_Status
Air Monitor Corporation
116-053-13.P65 (2/28/12)
49
ELECTRA-flo - IO&M Manual
ELECTRA-flo
APPENDIX A
STANDARD OBJECT TYPES SUPPORTED (con't)
DATA LINK LAYER OPTIONS (check all that are supported)
X
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s):
MS/TP Master (Clause 9), baud rates: 9600, 19200, 38400 (default), 57600, 76800
MS/TP Slave (Clause 9), baud rate(s):
Point-to-Point, EIA 232 (Clause 10), baud rate(s):
Point-to-Point, Modem (Clause 10), baud rate(s):
LonTalk (Clause 11), medium:
Other:
NETWORKING OPTIONS (check all that are supported)
Router, Clause 6 - List all routing configurations (e.g. ARCNET-Ethernet, Ethernet-MS/TP, etc.)
Annex H.3, BACnet Tunneling Router over UDP/IP
BACnet/IP Broadcast Management Device (BBMD)
BBMD supports registrations by Foreign Devices
SEGMENTATION CAPABILITY (check all that apply)
Segmented requested supported .................Window Size:
Segmented responses supported ................Window Size:
CHARACTER SETS SUPPORT (check all that apply)
Indicating support for multiple character sets does not imply they can all be supported simultaneously.
X
ANSI X3.4
IBMTM/MicrosoftTM DBCS
ISO 8859-1
ISO 10646 (UCS-2)
ISO 10646 (ICS-4)
JIS C 6226
If this product is a communication gateway, describe the non-BACnet equipment/network(s) the gateway supports.
- Not applicable
Include any additional information about the product's BACnet capabilities relevant to interoperability:
Air Monitor Corporation
116-053-13.P65 (2/28/12)
50
ELECTRA-flo - IO&M Manual
© Copyright 2026 Paperzz