to PDF

Thermographic
Inspection
At
Date:
2010
P S Electrical Services (1998) Ltd
Tel: 01299 251758
Fax: 01299 251308
Email [email protected]
Thermographic Survey
P S Electrical Svs (1998) Ltd
Page 1 / 34
Thermogram 14/05/2010
Photo
67.9 °C
60
Sp2
40
20
Li1
11.5
Sp1
Location Generator House
Equipment Generator No2
Sp1 Temperature 35.5 °C
Sp2 Temperature 31.4 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 2 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
2010
Photo
76.1 °C
Sp2
60
Li1
40
20
13.2
Sp1
Location Generator House
Equipment Generator No2
Sp1 Temperature 41.5 °C
Sp2 Temperature 58.4 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 3 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
2010
Photo
102.2 °C
100
80
Sp2
Li1
60
40
20
11.6
Sp1
Location Generator House
Equipment Generator No6
Sp1 Temperature 58.6 °C
Sp2 Temperature 64.0 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 4 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
2010
Photo
62.0 °C
60
Sp2
50
Mk
Li1
40
33.0
Sp1
Location Pump Room
Equipment Pump Bearings
Sp1 Temperature 59.6 °C
Sp2 Temperature 35.1 °C
Analysis and recommended actions:
Heat in main Bearings
P S Electrical Svs (1998) Ltd
Page 5 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
64.2 °C
60
Sp2
50
Li1
40
30
25.0
Sp1
Location Transformer Room5
Equipment Transformer 5
Sp1 Temperature 30.8 °C
Sp2 Temperature 27.7 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 6 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
32.5 °C
30
Sp2
Li1
25
21.8
Sp1
Location Transformer Room5
Equipment UPS input
Sp1 Temperature 27.6 °C
Sp2 Temperature 30.8 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 7 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
39.9 °C
Sp2
35
Li1
30
25
22.6
Sp1
Location East Corridor
Equipment Lighting & Power PDU
Sp1 Temperature 28.6 °C
Sp2 Temperature 25.0 °C
Analysis and recommended actions:
Check connections and clamp for load
P S Electrical Svs (1998) Ltd
Page 8 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
48.0 °C
Sp2
40
Sp1
Li1
30
21.2
Location
east Corridor
Equipment Downflow PDU 1
Component CRAC3-10
Sp1 Temperature 44.4 °C
Sp2 Temperature 30.7 °C
Analysis and recommended actions:
Check connections and clamp for load PDU out of balance
P S Electrical Svs (1998) Ltd
Page 9 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
32.9 °C
Sp2
Li1
30
25
22.1
Sp1
Location
East Corridor
Equipment Source Change over PDU
Component Outgoing load No1
Sp1 Temperature 23.1 °C
Sp2 Temperature 23.8 °C
Analysis and recommended actions:
Check connections and clamp for load PDU out of balance
P S Electrical Svs (1998) Ltd
Page 10 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
41.4 °C
40
Sp2
30
Li1
20.7
Sp1
Location
East Corridor
Equipment Down Flow PDU No3
Component CRAC-16
Sp1 Temperature 26.6 °C
Sp2 Temperature 30.2 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 11 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
25.9 °C
24
Sp2
Li1
22
20
18.2
Sp1
Location UPS Room M1
Equipment Transformer 6B
Sp1 Temperature 18.9 °C
Sp2 Temperature 19.2 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 12 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
39.5 °C
35
Sp2
Li1
30
25
21.6
Sp1
Location UPS Room 4
Equipment Unit 6D
Sp1 Temperature 23.0 °C
Sp2 Temperature 29.3 °C
Analysis and recommended actions:
Poor cable connection
P S Electrical Svs (1998) Ltd
Page 13 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
26.5 °C
26
Sp2
24
Li1
22
21.9
Sp1
Location UPS Room No1
Equipment Unit 4E
Sp1 Temperature 23.1 °C
Sp2 Temperature 24.0 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 14 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
53.4 °C
50
Sp2
Li1
40
29.8
Sp1
Location Pump Room
Equipment Pump No6
Sp1 Temperature 30.2 °C
Sp2 Temperature 31.3 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 15 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
60.4 °C
60
Sp2
50
40
Li1
30
24.4
Sp1
Location Pump Room
Equipment Pump 4
Sp1 Temperature 44.9 °C
Sp2 Temperature 33.1 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 16 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
31.3 °C
30
Sp2
28
Mk
Li1
Sp1
26
24
23.2
Location East Corridor 1st Floor
Equipment Lighting & Power 2
component 10 B connection
Sp1 Temperature 29.8 °C
Sp2 Temperature 27.3 °C
Analysis and recommended actions:
Check connections and clamp for load
P S Electrical Svs (1998) Ltd
Page 17 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
35.5 °C
35
Sp2
30
Sp1
Mk
25
Li1
23.8
Location
East Corridor 1st Floor
Equipment PDU 5
Component
Sp1 Temperature 36.2 °C
Sp2 Temperature 25.9 °C
Analysis and recommended actions:
Check connections and clamp for load
P S Electrical Svs (1998) Ltd
Page 18 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
63.8 °C
60
Sp2
Li1
40
20.5
Sp1
Location Area 1
Equipment PDU 1F
Sp1 Temperature 33.3 °C
Sp2 Temperature 50.5 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 19 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
68.7 °C
60
Sp2
Li1
40
21.6
Sp1
Location Area 1
Equipment PDU 1E
Sp1 Temperature 28.8 °C
Sp2 Temperature 30.0 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 20 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
65.0 °C
60
Sp2
Li1
40
20.0
Sp1
Location Area 1
Equipment PDU 1D
Sp1 Temperature 34.8 °C
Sp2 Temperature 54.9 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 21 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
23.5 °C
Li1
22
Sp2
20
18
16.2
Sp1
Location
Area 1
Equipment Distribution Board 1J/1
Component Terminals
Sp1 Temperature 14.9 °C
Sp2 Temperature 17.4 °C
Analysis and recommended actions:
PDU out of balance
P S Electrical Svs (1998) Ltd
Page 22 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
26.9 °C
Li1
25
Sp2
20
15.8
Sp1
Location
Area 1
Equipment Distribution Board 1T/1
Component Terminals
Sp1 Temperature 17.3 °C
Sp2 Temperature 20.7 °C
Analysis and recommended actions:
PDU out of balance
P S Electrical Svs (1998) Ltd
Page 23 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
33.7 °C
Li1
32
Sp2
30
28
26
24
23.7
Sp1
Location Area 1
Equipment Feeder to DB 1J/1
component Cables
Sp1 Temperature 31.0 °C
Sp2 Temperature 27.7 °C
Analysis and recommended actions:
Out of balance
P S Electrical Svs (1998) Ltd
Page 24 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
62.2 °C
60
Sp2
Li1
40
20
15.8
Sp1
Location Area 1
Equipment PDU 1A
Sp1 Temperature 27.6 °C
Sp2 Temperature 29.3 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 25 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
87.0 °C
80
Sp2
Li1
60
40
24.9
Sp1
Location Area 3
Equipment PDU 3D
Sp1 Temperature 64.0 °C
Sp2 Temperature 25.9 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 26 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
75.7 °C
Sp2
60
Li1
40
26.7
Sp1
Location Area 2
Equipment PDU 2F
Sp1 Temperature 56.8 °C
Sp2 Temperature 55.3 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 27 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
27.1 °C
26
Sp2
24
Li1
22
21.6
Sp1
Location Area 6
Equipment PDU 6E
Sp1 Temperature 22.8 °C
Sp2 Temperature 23.2 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 28 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
67.5 °C
60
Sp2
Li1
40
25.2
Sp1
Location Area 6
Equipment PDU 6A
Sp1 Temperature 38.5 °C
Sp2 Temperature 37.0 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 29 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
54.3 °C
50
40
Li1
Sp2
30
23.4
Sp1
Location Transformer Room 3
Equipment Capacitors
Sp1 Temperature 33.9 °C
Sp2 Temperature 55.4 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 30 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
84.8 °C
80
60
Li1
Sp2
40
32.9
Sp1
Location Transformer room 4
Equipment Transformer 4
Sp1 Temperature 39.8 °C
Sp2 Temperature 85.6 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 31 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
46.7 °C
Li1
Sp2
40
30
21.6
Sp1
Location Transformer room 7
Equipment Transformer 7
Sp1 Temperature 24.8 °C
Sp2 Temperature 26.1 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 32 / 34
Thermographic
Inspection
At
Thermogram 14/05/2010
Date:
14/05/2010
Photo
48.6 °C
Li1
Sp2
40
30
23.1
Sp1
Location Transformer room 6
Equipment Transformer 6
Sp1 Temperature 27.6 °C
Sp2 Temperature 46.1 °C
Analysis and recommended actions:
Image taken for reference only
P S Electrical Svs (1998) Ltd
Page 33 / 34
Thermographic
Inspection
At
Date:
14/05/2010
Images that Require your Attention
Page
Number
8
9
10
13
17
18
22
23
24
P S Electrical Svs (1998) Ltd
Page 34 / 34