Energy Efficient Variable Speed EC Motor Fan Coil Unit Solutions

BUILDING EFFICIENCY
Energy Efficient Variable Speed EC Motor
Fan Coil Unit Solutions
Model YECAH
Product Introduction
INTRODUCTION
Johnson Controls YORK® YECAH ceiling mounted compact cabinet fan coil units are
high airflow and high static pressure air-conditioning units using high efficiency 355 mm
diameter EC plug fan(s).
YECAH fan coil units have been designed incorporating variable speed EC motor
technology to meet the needs of today's sustainable building designs and to exceed
the stringent European ErP 2015 energy standard . They are the ideal HVAC solution
for both new construction and revovation projects for hotels, retail centers, office
buildings, and education facilities. The 355 mm diameter EC plug fans operate at lower
RPM , lower noise , and higher efficiency levels when compared to ceiling concealed
units incorporating multiple fans with smaller diameter impellers.
YECAH fan coils are available in 4 models with integral EC fan(s) incorporate fully
variable 0-10v speed control, and are suitable for a wide range of chilled water and hot
water flow rates, including wide delta T applications to maximize pump energy savings.
YECAH fan coil units are available with multiple coil options for each model (the 2 pipe
system has 4 or 6 rows, and the 4 pipe system has 4+1, 6+1, 4+2 or 6+2 rows). The air
flow ranges from nominal 750 L/s to 1500 L/s, while the external static pressure ranges
from 175 Pa to 375 Pa.
large removable access panels to the fan
section.
Cooling and heating coil use copper tubes
with corrugated aluminium fins, mounted
above a full stainless steel drain pan. The
EC plug fan(s) feature EC technology and
with a wide RPM range, can satisfy variable
Each YECAH unit is made of galvanized steel with 15 mm thick non-combustible
airflow and pressure from a 0 - 10 vdc
thermal insulation. It contains built-in cooling & heating coils, single or dual EC variable control signal. A MODBUS high level data
speed plug fan assemblies, a removable inspection panel with sash catches, and
connection is provided as standard.
4R Cooling Coil Only
Coils
6R Cooling Coil Only
1R/ 2R Heating Coil
GENERAL
Motor Protection
IP 54 - 50 Hz
Fin Protection
Hydrophilic Fin
Drain Pan
Stainless Steel Drain Pan
Coil header
Copper
G1(Nylon) filter
Filters & Rails
G1(Aluminium mesh) filter
G3 Plate filter
G4 Plate filter
Lengend
Thermostat
Lengend:
Standard
Option
2
ENERGY EFFICIENT EC MOTOR AHU SOLUTIONS MODEL YECAH
Nomenclature & Feature
NOMENCLATURE
YECAH 03
D
4
0
0
0
L
A
York EC Fan Ceiling-mounted AHU
Series
Unit Size:
03: 750l/s
04: 1000l/s
05: 1250l/s
06: 1500l/s
Connection Type:
L:Left
R:Right
0: Mixed air condition
X: Fresh air condition
Direct drive
0: no filter
A:G1(nylon)
B:G1(AL.)
C:G3
D:G4
No. of Rows:
4:4Row cooling
6:6Row cooling
0: no heating coil
1: 1R heating coil
2: 2R heating coil
FEATURES AND BENEFITS
Energy saving
Low noise level
Coil is made of expanded copper tubes and corrugated fins to achieve
high exchange efficiency.
355mm diameter EC plug fans fans provide high efficiency and static
capability over wide operation range
Each fan and motor assembly has been dynamically and statically
balanced
Variable speed, low noise, directly driven EC fan
Significant energy savings
Fan and motor performance rating exceeds the 2015 ErP (European
Energy- related Products Directive)
Whisper quiet comfort condition results in satisfied occupants.
Easy drainage
Full Drain pan allows quick and easy drainage of condensation. Drain
pan is made of high quality stainless steel.
Full drain pan design provides superior condensate management.
Compact size & low
height
Ceiling concealed unit is restricted to 508 mm height to fit within
commercial building ceiling spaces
Suits many ducted HVAC applications
Easy of installation
Threaded Brass connector is provided for easy piping connection. Purge
valves are provided on all coils to assist in commissioning.
Reduces installation and commissioning time and cost.
Easy maintenance
EC fans are direct drive with sealed for life bearings. Inspection panel
allows fast and easy periodic inspection of coil and drain tray. Optional
unit mounted filter track
Reduced maintenance time and cost.
3
Technical Specifications
MODEL
Performance
Nominal Air Flow
Nominal External Static Pressure
COIL
Face Area
Face Velocity
Header Material
Max Working Pressure
COOLING COIL
Water Flow Rate
Water Pressure Drop
Water Content
Air Pressure Drop
Nominal Capacity
YECAH03
YECAH04
YECAH05
YECAH06
L/S
Pa
750
175
1000
175
1250
175
1500
175
sq.m
m/s
0.284
2.64
0.508
1.97
0.508
2.46
0.610
2.46
Copper
1600
kPa
4 Rows
6 Rows
4 Rows
6 Rows
4 Rows
6 Rows
4 Rows
6 Rows
4 Rows
6 Rows
L/S
kPa
L
Pa
kW
0.31
0.40
17.2
18.0
3.0
4.6
130
205
9.1
11.7
0.45
0.59
20.2
26.5
3.8
5.7
75
115
13.2
17.4
0.48
0.66
10.3
23.9
3.8
5.7
105
165
14.0
19.3
0.62
0.82
25.8
18.4
4.6
6.8
105
165
18.2
23.8
0.12
0.27
2.0
2.5
0.8
1.5
25
55
9.9
21.6
0.19
0.42
7.5
9.3
0.9
1.9
15
30
15.5
34.2
0.21
0.47
8.8
11.7
0.9
1.9
20
45
16.9
38.6
0.25
0.58
15.0
19.7
1.1
2.3
20
45
20.6
47.0
HEATING COIL
Water Flow Rate
Water Pressure Drop
Water Content
Air Pressure Drop
Nominal Capacity
1 Row
2 Rows
1 Row
2 Rows
1 Row
2 Rows
1 Row
2 Rows
1 Row
2 Rows
MOTOR
Type
No. of Motor
Nameplate Rating Input
Control Signal Input
Nameplate Amps (220V / 1 Ph. / 50 - 60 Hz.)
Nameplate Power Supply
FAN
Type
Quantity
UNIT DIMENSIONS
Length
Width
Height
Weight(4R Coil)
Weight (6R+2R Coil)
L/S
kPa
L
Pa
kW
W
V
A
-
1
750
3.3
Electronically Commutated
1
2
750
750×2
0~10VDC
3.3
3.3×2
230V / 1 Ph. / 50 - 60 Hz
2
750×2
3.3×2
BC SWSI Plug
mm
mm
mm
kg
kg
1
1
2
2
940
950
508
151
168
940
1500
508
186
210
940
1500
508
201
225
940
1750
508
220
250
Note: 1. Standard mixed air cooling conditions: air inlet at 23°C DB/17°C WB; chilled water inlet/outlet at 6°C/13°C.
2. Cooling Coil APD at wet condition.
3. Heating Coil APD at dry condition.
4. The weight listed in the table is the shipping weight.
5. The weight does not include water volumes.
4
ENERGY EFFICIENT EC MOTOR AHU SOLUTIONS MODEL YECAH
Technical Specifications
YECAH Air Flow Range
Unit Model
YECAH06
YECAH05
YECAH04
YECAH03
250
500
750
1000
1250
1500
1750
Air Flow L/s
5
Technical Specifications
MOTOR POWER INPUT(W)
MODEL
4 Rows Cooling Coil+1 Row Heating Coil
ESP (Pa)
550 L/S
680 L/S
750 L/S
175
391
567
744
225
YECAH03
460 L/S
620 L/S
730 L/S
377
560
741
275
360 L/S
540 L/S
680 L/S
360
545
742
325
460 L/S
620 L/S
531
734
720 L/S
870 L/S
565
738
1190 L/S
1350 L/S
1125
1450
375
MODEL
ESP (Pa)
750 L/S
910 L/S
1040 L/S
175
390
543
715
225
YECAH04
680 L/S
850 L/S
990 L/S
396
555
727
275
590 L/S
790 L/S
930 L/S
393
562
732
325
375
MODEL
ESP (Pa)
900 L/S
1160 L/S
1350 L/S
175
498
819
1161
225
YECAH05
800 L/S
1110 L/S
1290 L/S
527
782
1130
275
940 L/S
1250 L/S
1350 L/S
765
1138
1350
325
375
MODEL
ESP (Pa)
990 L/S
1350 L/S
1620 L/S
175
503
774
1088
225
YECAH06
275
325
375
1190 L/S
1500 L/S
1620 L/S
767
1071
1200
980 L/S
1390 L/S
1620 L/S
755
1090
1450
1240 L/S
1550 L/S
1080
1451
380 L/S
550 L/S
512
736
630 L/S
800 L/S
553
738
1010 L/S
1330 L/S
1154
1486
1050 L/S
1430 L/S
1074
1448
6
ENERGY EFFICIENT EC MOTOR AHU SOLUTIONS MODEL YECAH
MOTOR POWER INPUT(W)
MODEL
6 Rows Cooling Coil+1 Row Heating Coil
ESP (Pa)
570 L/S
680 L/S
700 L/S
175
530
715
745
225
YECAH03
460 L/S
610 L/S
630 L/S
507
704
744
275
350 L/S
520 L/S
550 L/S
477
683
745
325
410 L/S
480 L/S
645
743
690 L/S
840 L/S
571
738
1120 L/S
1350 L/S
1120
1480
375
MODEL
ESP (Pa)
740 L/S
890 L/S
1010 L/S
175
398
545
713
225
YECAH04
660 L/S
830 L/S
970 L/S
396
554
735
275
570 L/S
760 L/S
900 L/S
397
559
737
325
375
MODEL
ESP (Pa)
910 L/S
1200 L/S
1350 L/S
175
525
806
975
225
YECAH05
1080 L/S
1250 L/S
1350 L/S
793
975
1139
275
960 L/S
1240 L/S
1350 L/S
787
1131
1350
325
375
MODEL
ESP (Pa)
910 L/S
1260 L/S
1550 L/S
175
483
770
1082
225
YECAH06
1140 L/S
1410 L/S
1620 L/S
758
1090
1450
275
325
375
980 L/S
1280 L/S
1590 L/S
747
1086
1457
1180 L/S
1480 L/S
1071
1456
330 L/S
400 L/S
626
743
620 L/S
770 L/S
565
737
1020 L/S
1260 L/S
1108
1483
1050 L/S
1360 L/S
1049
1450
Note: Airflow and inputpower datas are for dry coil and without filter.
7
Performance Data
PERFORMANCE RATINGS
Model
Air Inlet Temp(Dry Bulb/Wet Bulb) 27℃/19℃
Air Inlet Temp(Dry Bulb/Wet Bulb) 23℃/17℃
Air Inlet Temp(Dry Bulb/Wet Bulb) 35℃/24℃
Inlet
Air Off
Air Off
Air Off
Chilled Total Sensible
Water Water
Total Sensible
Water Water
Total Sensible
Water Water
Airflow Rows
Temp
Temp
Temp
Water Cooling Cooling
Flow Pressure Cooling Cooling
Flow Pressure Cooling Cooling
Flow Pressure
(Dry Bulb/
(Dry Bulb/
(Dry Bulb/
Temp Capacity Capacity
Rate
Drop Capacity Capacity
Rate
Drop Capacity Capacity
Rate
Drop
Wet Bulb)
Wet Bulb)
Wet Bulb)
L/S
℃
kW
kW
℃
L/S
kPa
kW
kW
℃
L/S
kPa
kW
kW
℃
L/S
kPa
4
YECAH03
750
6
4
YECAH04
1000
6
4
YECAH05
1250
6
4
YECAH06
COOLING COIL
1500
6
5
6
7
8
9
5
6
7
8
9
5
6
7
8
9
5
6
7
8
9
5
6
7
8
9
5
6
7
8
9
5
6
7
8
9
5
6
7
8
9
14.5
13.0
11.6
10.4
9.3
18.2
16.4
14.8
13.2
11.7
20.0
18.1
16.3
14.5
12.9
26.6
24.1
21.6
19.3
17.2
22.2
19.9
17.9
15.9
14.1
29.0
26.4
23.9
21.3
18.9
28.0
25.3
22.8
20.4
18.2
36.5
33.0
29.6
26.4
23.4
10.8
10.1
9.5
9.0
8.4
12.9
12.1
11.3
10.7
10.0
14.4
13.5
12.7
11.9
11.2
18.5
17.3
16.2
15.2
14.3
16.7
15.6
14.7
13.8
12.8
20.5
19.3
18.2
17.0
15.9
20.7
19.5
18.3
17.2
16.1
25.9
24.3
22.8
21.4
20.1
14.9/13.2
15.7/13.9
16.3/14.4
17.0/15.0
17.6/15.4
12.6/11.5
13.5/12.3
14.3/13.1
15.1/13.8
15.8/14.4
14.9/13.0
15.7/13.6
16.3/14.2
17.0/14.8
17.6/15.3
11.5/10.7
12.5/11.6
13.4/12.4
14.2/13.2
15.0/13.9
15.8/13.7
16.5/14.3
17.1/14.8
17.8/15.3
18.4/15.8
13.3/11.9
14.0/12.6
14.8/13.3
15.6/14.0
16.3/14.6
15.4/13.4
16.1/14.0
16.7/14.5
17.4/15.1
18.0/15.5
12.5/11.5
13.4/12.3
14.2/13.1
15.0/13.8
15.8/14.4
0.50
0.44
0.40
0.35
0.32
0.62
0.56
0.50
0.46
0.40
0.68
0.61
0.56
0.50
0.44
0.91
0.83
0.74
0.66
0.59
0.76
0.68
0.61
0.54
0.48
0.98
0.90
0.82
0.72
0.64
0.95
0.86
0.78
0.69
0.62
1.24
1.12
1.01
0.89
0.79
36.7
30.5
25.3
21.3
17.5
37.1
30.7
25.8
21.8
17.4
41.4
34.1
29.5
23.6
19.1
58.3
48.4
39.3
32.4
26.0
23.9
19.2
16.1
12.7
10.2
47.7
41.7
35.2
28.1
22.6
55.6
46.6
39.4
31.6
25.5
40.2
33.5
27.3
21.6
17.4
10.5
9.1
7.8
6.6
5.7
13.4
11.7
10.2
8.7
7.5
15.0
13.2
11.4
9.8
8.4
19.9
17.4
15.1
13.0
11.0
15.9
14.0
11.9
10.1
8.7
22.0
19.3
16.8
14.4
12.4
21.0
18.2
15.9
13.7
11.7
27.2
23.8
20.5
17.6
14.9
8.1
7.5
6.8
6.2
5.6
9.8
9.0
8.3
7.6
6.9
11.0
10.2
9.4
8.6
7.8
14.2
13.0
12.0
11.0
10.0
12.5
11.6
10.5
9.5
8.5
15.9
14.6
13.4
12.3
11.3
15.9
14.6
13.5
12.3
11.1
19.9
18.3
16.8
15.4
13.9
14.0/12.7
14.7/13.3
15.4/13.9
16.1/14.3
16.8/14.7
12.2/11.3
13.0/12.1
13.8/12.8
14.6/13.5
15.3/14.0
13.9/12.3
14.5/12.9
15.2/13.5
15.9/14.0
16.5/14.5
11.3/10.6
12.2/11.5
13.1/12.3
13.9/13.0
14.7/13.6
14.7/13.1
15.3/13.6
16.0/14.1
16.7/14.6
17.3/14.9
12.5/11.4
13.3/12.2
14.1/12.9
14.8/13.5
15.5/14.0
14.2/12.7
14.9/13.3
15.6/13.8
16.2/14.2
16.9/14.7
12.0/11.2
12.9/12.0
13.7/12.8
14.5/13.4
15.3/14.0
0.35
0.31
0.27
0.23
0.20
0.46
0.40
0.35
0.29
0.25
0.51
0.45
0.39
0.34
0.29
0.68
0.59
0.51
0.44
0.38
0.54
0.48
0.41
0.34
0.29
0.75
0.66
0.57
0.49
0.42
0.72
0.62
0.54
0.47
0.39
0.93
0.82
0.70
0.60
0.50
22.0
17.2
12.9
9.7
7.4
22.6
18.0
14.4
10.5
8.2
24.9
20.2
15.3
11.5
8.8
34.3
26.5
20.6
15.4
11.3
12.9
10.3
7.5
5.5
4.1
30.6
23.9
18.6
14.0
10.5
34.1
25.8
20.3
15.4
11.1
23.7
18.4
13.7
10.3
7.3
25.1
23.6
21.8
20.1
18.6
28.2
26.5
24.6
22.8
20.9
29.5
27.4
25.0
23.1
21.1
38.1
35.5
32.9
30.2
27.6
37.5
34.6
32.0
29.3
26.6
42.4
39.3
36.3
33.6
30.6
47.0
44.0
40.7
37.6
34.7
56.8
53.2
49.5
45.9
42.0
16.1
15.5
14.8
14.1
13.5
17.6
16.9
16.0
15.3
14.6
19.0
18.2
17.2
16.4
15.6
24.0
22.9
21.8
20.8
19.8
24.5
23.4
22.3
21.2
20.2
27.0
25.6
24.4
23.3
22.2
30.3
29.1
27.8
26.5
25.3
35.6
34.0
32.5
31.0
29.4
16.6/15.0
17.2/15.6
18.1/16.3
18.9/17.0
19.6/17.6
14.9/13.6
15.7/14.4
16.7/15.2
17.5/16.0
18.4/16.7
18.7/16.2
19.4/16.9
20.3/17.6
20.9/18.1
21.6/18.7
14.4/13.5
15.4/14.3
16.3/15.2
17.2/16.0
18.1/16.8
18.2/16.1
19.0/16.8
19.7/17.4
20.5/18.0
21.2/18.6
16.5/14.8
17.4/15.6
18.3/16.4
19.0/17.0
19.8/17.7
17.7/15.7
18.3/16.3
19.1/16.9
19.9/17.5
20.5/18.1
14.7/13.5
15.5/14.3
16.5/15.1
17.3/15.9
18.2/16.7
0.85
0.81
0.75
0.68
0.63
0.96
0.91
0.84
0.78
0.71
1.01
0.94
0.85
0.79
0.72
1.29
1.20
1.12
1.03
0.94
1.28
1.17
1.10
1.00
0.90
1.44
1.34
1.23
1.14
1.04
1.60
1.50
1.38
1.29
1.18
1.92
1.81
1.69
1.57
1.43
43.7
39.7
34.2
29.0
26.0
26.5
24.1
20.6
18.3
15.7
13.3
11.5
9.6
8.5
7.1
18.7
16.4
14.2
12.1
10.2
19.1
16.0
14.1
11.8
9.8
17.1
14.8
12.6
11.0
9.1
44.0
39.0
33.4
29.2
25.6
33.2
28.8
25.4
22.2
18.4
Note: The temperature difference of inlet/outlet water is 7°C
8
ENERGY EFFICIENT EC MOTOR AHU SOLUTIONS MODEL YECAH
Performance Data
PERFORMANCE RATINGS
HEATING COIL
Air Inlet Temp(Dry Bulb)
Airflow
Rows
Model
YECAH04
YECAH05
YECAH06
21℃
15℃
Total
Heating
Capacity
Air Off
Temp
Water
Flow
Rate
Water
Total
Pressure Heating
Drop
Capacity
℃
kW
℃
L/S
kPa
1
80
9.9
31.9
0.12
2
80
21.6
44.8
1
80
15.5
2
80
1
7℃
Air Off
Temp
Water
Flow
Rate
kW
℃
L/S
kPa
2.0
11.3
27.3
0.14
0.27
2.5
24.8
41.8
33.8
0.19
7.5
17.6
34.2
49.3
0.42
9.3
80
16.9
32.2
0.21
2
80
38.6
46.6
1
80
20.6
2
80
47.0
L/S
YECAH03
Inlet Hot
Water
Temp
Water
Total
Pressure Heating
Drop
Capacity
Air Off
Temp
Water
Flow
Rate
Water
Pressure
Drop
kW
℃
L/S
kPa
2.6
13.2
20.9
0.16
3.53
0.30
3.2
29.1
37.7
0.36
4.36
29.3
0.21
9.6
20.4
23.1
0.25
12.67
39.0
46.7
0.48
12.0
45.5
42.9
0.56
15.93
8.8
19.3
27.5
0.23
11.3
22.4
21.1
0.28
15.09
0.47
11.7
44.0
43.6
0.54
14.9
51.3
39.4
0.63
20.03
32.4
0.25
15.0
23.4
27.7
0.29
19.2
27.2
21.3
0.33
25.38
46.9
0.58
19.7
53.5
43.9
0.66
25.1
62.3
39.8
0.76
33.75
750
1000
1250
1500
9
Acoustics
SOUND POWER LEVEL
Model
ESP(Pa)
YECAH03
175
YECAH04
YECAH05
YECAH06
4 Rows Cooling Coil+1 Row Heating Coil
Air Flow (L/S)
63Hz
125Hz
250Hz
500Hz
1kHz
2kHz
4kHz
8kHz
dB(A)
550
32.2
44.4
45.9
48.2
47.4
42.1
38.6
36.5
53.4
750
37.3
48.8
52.3
51.7
53.1
48.3
41.5
40.5
58.4
800
26.4
47.8
45.0
50.9
56.4
51.8
46.9
43.1
59.4
1000
30.1
43.2
47.9
53.2
58.6
53.8
48.9
44.8
61.3
1050
28.7
45.9
46.3
49.5
48.9
41.6
36.3
34.2
54.3
1250
31.2
45.8
48.6
53.4
52.2
44.0
37.9
35.6
57.3
1300
28.5
45.1
47.6
49.5
49.4
39.7
34.6
33.0
54.5
1500
31.1
45.0
49.6
52.1
51.9
41.5
35.4
34.4
56.7
175
175
175
SOUND POWER LEVEL
Model
ESP(Pa)
YECAH03
175
YECAH04
YECAH05
YECAH06
6 Rows Cooling Coil+1 Row Heating Coil
Air Flow (L/S)
63Hz
125Hz
250Hz
500Hz
1kHz
2kHz
4kHz
8kHz
dB(A)
550
34.4
45.8
47.9
51.5
52.4
48.7
42.7
38.9
57.2
700
37.2
48.8
51.1
52.7
55.1
51.2
45.3
40.4
59.5
800
29.0
43.7
49.0
53.5
55.2
51.8
45.0
40.2
59.3
1000
34.6
46.5
51.8
54.6
58.2
52.9
45.6
42.9
61.4
1050
36.7
50.6
52.9
52.7
52.2
42.5
34.4
30.1
58.4
1250
38.0
52.0
56.4
55.4
55.6
45.4
38.8
31.4
61.3
1300
31.6
48.2
50.7
52.6
52.5
42.8
37.7
36.1
57.6
1500
34.4
48.3
52.9
55.4
55.2
44.8
38.7
37.7
60.0
175
175
175
Casing Radiated Sound Power Test:
According to JBT4330-1999 and ISO3744, casing radiated sound power level is tested in hemi-anechoic room. Unit tested with 3 meters of inlet and 3 meters of outlet ductwork.
10
ENERGY EFFICIENT EC MOTOR AHU SOLUTIONS MODEL YECAH
Units Drawings
Cooling Only
11
Units Drawings
Cooling and Heating
W
Outlet flange size
Inlet flange
size
Piping position
Model
J
K
HK
HN
B
D
E
P
4 rows
6 rows
1 row
2 rows
1 row
2 rows
YECAH03
950
326
450
804
160.5
182.5
66
110
44
66
407
420
YECAH04
1500
451
600
1360
160.5
182.5
66
110
44
66
407
420
YECAH05
1500
329
950
1360
160.5
182.5
66
110
44
66
407
420
YECAH06
1750
376
1200
1610
160.5
182.5
66
110
44
66
407
420
with 1R HC with 2R HC
Notes:
1. The coil pipe connections use male threads(thread code R2)
1" - OD 34mm 1 1/2" - 48mm
2. The condensate pipe connections use 34mm O.D. male threads(thread code R2)
3. All dimensions are SI unit(mm)
12
ENERGY EFFICIENT EC MOTOR AHU SOLUTIONS MODEL YECAH
Fan Performance Curves
YECAH03 4R Cooling+1R Heating
YECAH03 6R Cooling+1R Heating
Note: Airflows are for dry coil and without filter. Reduce airflow by 10% in high moisture
removal conditions.
Note: Airflows are for dry coil and without filter. Reduce airflow by 10% in high moisture
removal conditions.
YECAH04 4R Cooling+1R Heating
YECAH04 6R Cooling+1R Heating
Note: Airflows are for dry coil and without filter. Reduce airflow by 10% in high moisture
removal conditions.
Note: Airflows are for dry coil and without filter. Reduce airflow by 10% in high moisture
removal conditions.
13
Fan Performance Curves
YECAH05 4R Cooling+1R Heating
YECAH05 6R Cooling+1R Heating
Note: Airflows are for dry coil and without filter. Reduce airflow by 10% in high moisture
removal conditions.
Note: Airflows are for dry coil and without filter. Reduce airflow by 10% in high moisture
removal conditions.
YECAH06 4R Cooling+1R Heating
YECAH06 6R Cooling+1R Heating
Note: Airflows are for dry coil and without filter. Reduce airflow by 10% in high moisture
removal conditions.
Note: Airflows are for dry coil and without filter. Reduce airflow by 10% in high moisture
removal conditions.
14
ENERGY EFFICIENT EC MOTOR AHU SOLUTIONS MODEL YECAH
Electrical Data and Wiring
MOTOR WIRING TAG
Power supply
230V ~ 50Hz
Alarm relay Interface 0-10VDC
output
for Modbus Input
Field wiring by User
QF
Wiring in Factory
NB1
L
N
PE
NC
C
RSA RSB 0-10V GND 10V
M
~
Notes:
Fan Motor(MF)
NB1 Option control interface: RS485 interface for Modbus.
L
N
PE
NC
8
COM 10V
7
AI
6
B
5
A
4
NC2
NC
C
C
NC1
NC
PE
PE
1
Motor Terminals
N
2
L
User Terminals(TB)
NB2
C
RSA RSB 0-10V GND 10V
M
~
Fan Motor(MF)
NB3
NB2 Terminal 10V: Fixed voltage output 10VDC, max 10mA. Fan Motor will run at full speed if 10V and AI terminals are shorted.
NB3 Single Fan Motor units do not have these parts of wiring.
15
TEC3000 Series Thermostat Controllers
TEC3000 Series Thermostat Controllers
are stand-alone and field-selectable
BACnet® Master-Slave/Token-Passing
(MS/TP) or N2 networked devices that
provide on/off, floating, and proportional
control of two or four-pipe fan coils with
variable-speed EC motors (0 to 10 VDC
control)
Some models have occupancy sensing
capability built into the device. These
thermostat controllers can deliver further
energy savings of up to 30% by using
additional standby set-points.
These thermostats feature two
configurable binary inputs that provide for
advanced functions such as remote night
The networked models feature a fieldsetback, service or filter alarms, motion
selectable Building Automation System
detector, and key switch or window status,
(BAS) BACnet MS/TP or N2 communication and configures the application to respond
capability that enables remote monitoring accordingly.
and programming for efficient space
temperature control. A Full Line of Remote TE-6300 Series
Temperature Sensors supports a wide
All models include a USB port configuration range of applications.
that reduces installation time by allowing
simple backup and restore features from
a USB drive, which enables rapid cloning
of the configuration between like units.
All models feature an intuitive user
interface with backlit display that makes
setup and operation quick and easy. The
Backlit Liquid Crystal Display (LCD) offers
real-time control status of the environment
in easy-to-read, plain text messages with
adjustable backlight that brightens during
user interaction.
16
ENERGY EFFICIENT EC MOTOR AHU SOLUTIONS MODEL YECAH
Guide Specifications
GENERAL
Furnish and install ceiling-mounted
compact air handling units not exceding
508mm height as indicated and scheduled
in the plans. Units shall be factory
assembled with coils that are pressure
tested individually to 400 psi (2.8 MPa).
The unit shall incorporate one or two
355mm diameter directly driven EC plug
fans with integral variable speed drive(s).
The units shall be suitable for operation
on 240 volt single phase 50 hz power. BASIC UNIT
The unit panels shall be fabricated out
of 1mm galvanized steel. The unit shall
be lined with 15 mm Class 1 PE thermal
insulation. The fan motor(s) shall be easily
removable for serviceability. A terminal
box with terminal strip shall be provided
for terminating the wiring. An inspection
panel with sash catches shall be provided
for easy inspection of coil and drain
pan.
COILS
Copper tube with corrugated aluminum
hydrophilic fins. Aluminum fins shall be
0.110mm thick and the coil shall have
maximum spacing of 2.3mm between
the fins. The coil shall be pressure tested
under water to 2.8 MPa (For a working
pressure of 1600 kpa) and dehydrated
before assembly. Coil shall be provided
with a manual air vent on the top. The
coil assembly shall be protected on the
side on which piping is to be fitted with a
cover made of GI sheet. A full drain pan
shall be provided to the base of the unit
manufactured of stainless steel to prevent
corrosion. MOTORS
TERMINAL BOX
All units shall be provided with factory
installed terminal box with the fan motor
wired to the box. the terminal box shall
include a DIN rail type terminal strip
that has connections for incoming 240v
power, 0-10v dc speed control, a common
fault contact, and a MODBUS high level
data interface. Where multiple fans are
provided they shall be factory wired to the
common terminal strip.
High efficiency electronically commutated
(EC) motors shall be fitted as standard on
all units. Motor can be regulated by 0-10V FILTER dc signal supplied by a BMS, thermostat
As an option, panel filters shall be provided
or DDC controller. The motor is resiliently to a 25mm channel frame mounted on the
mounted, self aligning and oiled for life.
air inlet of the unit.
A MODBUS high level connection shall be
provided.
FANS
The unit shall utilize one or two 355mm
diameter EC plug fan(s), dynamically
balanced, incorporating backward curved
impellers each with a direct drive EC
motor. The fan motor assembly shall be
designed for low-noise, variable speed
operation from a 0-10v dc control input.
EC fan assemblies shall be installed in
an insulated plenum section with large
removable access panels fitted to both
sides of the air handling unit for ease of
service and replacement.
17
Solutions for your success
Every building is unique in design and
technical requirements.
Our customers always receive customised
building solutions to meet their individual
needs.
Johnson Controls can handle many challenges with its innovative and flexible solutions.
From A to Z, from consulting to planning, installation, maintenance (service, inspection
and repair) and modernisation – Johnson Controls supports customers throughout the
entire life cycle of a building.
High Efficiency Chiller
Building Automation &
Chiller Plant Optimization
Variable Air Volume
18
ENERGY EFFICIENT EC MOTOR AHU SOLUTIONS MODEL YECAH
Our well thought-out solutions guarantee a high level of comfort and energy efficiency.
The majority of our products are already rated as Class A for Energy Efficiency, with
high levels of compatibility and flexibility allowing for future additions to be carried out
without difficulty.
External systems can be easily integrated
using BACnet® or proprietary solutions.
Our service team is available to you 24
hours a day with one of the largest service
networks in Europe.
EC Motor AHUs
EC Motor FCUs
EC Motor Ceiling AHUs
Service Solutions
Energy Management & Reporting
19
Office Locations
Australia (Melbourne)
Tel: +61 (3) 9751 5000
Fax: +61 (3) 9755 7566
Indonesia
Tel: +62 (21) 5366 8500
Fax: +61 (21) 5366 8300
Malaysia (Kuala Lumpur)
Tel: +60 (3) 7628 4300
Fax: +60 (3) 7874 1180
China (Shanghai)
Tel: +86 (21) 6276 6509
Fax: +86 (21) 6277 3543
Japan
Tel: +81 (3) 5738 6100
Fax: +81 (3) 5738 6298
New Zealand
Tel: +64 (9) 444 6434
Fax: +64 (9) 444 2092
Hong Kong
Tel: +852 2590 0012
Fax: +852 2516 5648
Korea
Tel: +822 554 5935
Fax: +822 554 5739
Singapore
Tel: +65 6748 0202
Fax: +65 6743 4420
India (Mumbai)
Tel: +91 (22) 6617 4107
Fax: +91 (22) 6683 7002
Macau
Tel: +853 2875 1820
Fax: +853 2875 1825
Thailand (Bangkok)
Tel: +66 (2) 717 1260-80
Fax: +66 (2) 717 1325-8
PUBL-7895 (1215)