Infrared Inspection Samples JT House Inspection 7-2-2008 Final.doc 1 (14) 2008-07-17 Thermography Inspection at (Site) Date: (date) Summary of Inspection Page Number 3 4 5 6 7 8 9 10 11 12 13 14 JT House Inspection 7-2-2008 Final.doc Category Energy/Missing Insulation Energy/Missing Insulation Energy/Missing Insulation Energy/Window Energy/Insulation Water Damage/High Heat Unit Water Damage/High Heat Unit Water Damage/High Heat Unit Mechanical Mechanical/Conductive Heat Element Tire Inspection Tire Inspection 2 (14) 2008-07-17 Thermograph Inspection at (Residential Home) Date: (7/1/2008) Photo and Identification IR Text Comment Value Location Residential Home Category Energy/Missing Insulation Analysis & Recommended action: This series of pictures shows the door leading to the attic closed and open. While it’s closed heat is still leaking into the room. The door should be checked to make sure it is flush with the frame and/or more insulation should be added. Thermogram 7/1/2008 FLIR Systems Label IR: Date Of Creation IR: Time Of Creation IR: Max IR: Min Sp1 Sp2 Sp3 100.1 °F 100 Sp1 95 Sp3 90 Li1 °F 100 98 96 94 92 90 88 86 84 82 80 78 85 80 Sp2 76.8 Label Li1 FLIR Systems 152.0 °F 140 Li1 Sp2 Sp1 120 100 80 76.5 3 (14) Cursor - Label IR: Date Of Creation IR: Time Of Creation IR: Max IR: Min Sp1 Sp2 Min 83.5 Max 101.1 Value 7/1/2008 2:09:24 PM 150.1 °F 76.2 °F 84.8 °F 148.1 °F °F 150 140 130 120 110 100 90 80 Label Li1 JT House Inspection 7-2-2008 Final.doc Value 7/1/2008 1:47:23 PM 101.1 °F 76.5 °F 81.6 °F 77.7 °F 78.7 °F Cursor Min Max - 82.4 148.5 2008-07-17 Thermography Inspection at (Residential Home) Date: (7/1/2008) Photo and Identification IR Text Comment Location Category Value Residential Home Energy/Missing Insulation Thermogram 7/1/2008 FLIR Systems 89.6 °F Sp2 Sp3 85 Li1 Label IR: Date Of Creation IR: Time Of Creation IR: Max IR: Min Sp1 Sp2 Sp3 Value 7/1/2008 1:51:35 PM 88.5 °F 73.4 °F 80.7 °F 74.3 °F 77.5 °F °F 80 Sp1 88 86 84 82 75 73.7 80 78 76 74 Label Li1 Cursor Min Ma - 75.3 88 Analysis & Recommended action: This picture shows a section of the ceiling drywall that was repaired but the insulation was not replaced in the attic.. Insulation should be replaced above the repaired section. JT House Inspection 7-2-2008 Final.doc 4 (14) 2008-07-17 Thermography Inspection at (Residential Home) Date: (7/1/2008) Thermography Inspection at (Commercial Building) Date: (2/3/2005) Photo and Identification IR Text Comment Location Category Value Residential Home Energy/Missing Insulation Thermogram 7/1/2008 FLIR Systems 89.9 °F Sp3 Li1 85 Sp1 Sp2 80 75 72.9 Label IR: Date Of Creation IR: Time Of Creation IR: Max IR: Min Sp1 Sp2 Sp3 Value 7/1/2008 1:58:55 PM 88.4 °F 73.4 °F 80.3 °F 76.3 °F 74.2 °F °F 88 86 84 82 80 78 76 74 Label Li1 Cursor - Min 74.9 Max 88.4 Analysis & Recommended action: Another view of the a repaired ceiling where insulation was not replaced in the attic. Insulation should be replaced in the attic. Photo and Identification JT House Inspection 7-2-2008 Final.doc 5 (14) 2008-07-17 IR Text Comment Location Category Value Commercial Building Energy/Window Thermogram 2/3/2005 FLIR Systems Sp2 55.1 °F Li1 50 Sp3 40 Label IR: Date Of Creation IR: Time Of Creation IR: Max IR: Min Sp1 Sp2 Sp3 Value 2/3/2005 11:55:40 AM 56.3 °F 24.3 °F 38.9 °F 27.4 °F 54.6 °F °F 55 50 45 40 Sp1 30 35 30 25.1 Label Li1 Cursor - Min 25.9 Max 54.2 Analysis & Recommended action This picture shows a window at a commercial building. Window seals should be inspected and replaced to prevent energy loss and or water from seeping in through the gap. JT House Inspection 7-2-2008 Final.doc 6 (14) 2008-07-17 Thermography Inspection at (Commercial Building) Date: (6/25/2008) Photo and Identification IR Text Comment Location Category Value Commercial Building Energy/Insulation Thermogram 6/25/2008 FLIR Systems 72.2 °F 70 Sp1 Sp2 60 Li1 50 40 30 25.4 Label IR: Date Of Creation IR: Time Of Creation IR: Max IR: Min Sp1 Sp2 Value 6/25/2008 9:38:19 AM 73.0 °F 19.6 °F 61.4 °F 19.7 °F °F 70 65 60 55 50 45 40 35 30 Label Li1 Cursor - Min 28.2 Max 57.1 Analysis & Recommended action: This picture shows the door to an outdoor walk in freezer. The door seals should be inspected and replaced to prevent energy loss. JT House Inspection 7-2-2008 Final.doc 7 (14) 2008-07-17 Thermography Inspection at (Residential Home) Date: (11/29/2007) Photo and Identification IR Text Comment Location Category Value Residential Home Water Damage/High Heat Unit Thermogram 11/29/2007 FLIR Systems Li1 Sp2 119.1 °F Sp1 115 110 105 Sp3 100 98.9 Label IR: Date Of Creation IR: Time Of Creation IR: Max IR: Min Sp1 Sp2 Sp3 Value 11/29/2007 3:01:02 PM 220.6 °F 90.7 °F 112.2 °F 100.6 °F 112.5 °F °F 118 116 114 112 110 108 106 104 102 100 Label Li1 Cursor Min Max - 100.3 113.9 Analysis & Recommended action: This picture shows the basement ceiling of a residential home. The dark spots is moisture from water pipes that broke in the main floor ceiling. The house was dried with minimal drywall tear out utilizing the Dry-Vex High Heat Unit. NOTE: Infrared Maximum temperature is due the recessed light being on. JT House Inspection 7-2-2008 Final.doc 8 (14) 2008-07-17 Thermography Inspection at (Commercial Building) Date: (1/22/2008) Photo and Identification IR Text Comment Location Category Value Commercial Building Water Damage/High Heat Unit Thermogram 1/22/2008 FLIR Systems 69.7 °F Sp3 Sp1 68 Sp2 66 64 Li1 62.2 Label IR: Date Of Creation IR: Time Of Creation IR: Max IR: Min Sp1 Sp2 Sp3 Value 1/22/2008 9:41:29 AM 106.2 °F 62.0 °F 68.0 °F 63.1 °F 64.7 °F °F 69 68 67 66 65 64 63 Label Li1 Cursor - Min 62.5 Max 66.6 Analysis & Recommended action: This picture shows a plaster ceiling in a commercial building. Darker areas are moisture. This ceiling and the rest of the building was dried with no tear out of walls, ceilings or carpet utilizing the Dry-Vex High Heat Unit. This picture was taken on January 22nd 2008, one day before the next picture. NOTE: The Infrared Maximum temperature is due to the fluorescent light fixture in the picture. JT House Inspection 7-2-2008 Final.doc 9 (14) 2008-07-17 Thermography Inspection at (Commercial Building) Date: (1/23/2008) Photo and Identification IR Text Comment Location Category Value Commercial Building Water Damage/High Heat Unit Thermogram 1/23/2008 FLIR Systems 84.9 °F Sp1 Sp3 80 Sp2 75 Li1 70 69.8 Label IR: Date Of Creation IR: Time Of Creation IR: Max IR: Min Sp1 Sp2 Sp3 Value 1/23/2008 9:19:56 AM 107.4 °F 72.0 °F 80.2 °F 78.0 °F 76.3 °F °F 84 82 80 78 76 74 72 70 Label Li1 Cursor Min Max - 73.1 76.6 Analysis & Recommended action: This picture shows a plaster ceiling in a commercial building. Darker areas are moisture. This ceiling and the rest of the building were dried with no tear out of walls, ceilings or carpets utilizing the Dri-Vex High Heat Unit. This picture was taken on January 23rd 2008 one day after the previous picture. NOTE: The Infrared Maximum temperature is due to the fluorescent light fixture in the picture. JT House Inspection 7-2-2008 Final.doc 10 (14) 2008-07-17 Thermography Inspection at (Commercial Building) Date: (1/1/3/2005) Photo and Identification IR Text Comment Location Category Value Commercial Building Mechanical Thermogram 1/13/2005 FLIR Systems 156.0 °F Li1 Sp2 140 Sp1 120 100 86.6 Label IR: Date Of Creation IR: Time Of Creation IR: Max IR: Min Sp1 Sp2 Value 1/13/2005 4:13:35 PM 157.2 °F 86.3 °F 156.9 °F 117.3 °F °F 150 140 130 120 110 100 90 Label Li1 Cursor - Min 108.1 Max 154.6 Analysis & Recommended action: This picture shows an electric motor. Infrared inspections can show wear patterns and can used in a preventative maintenance program. JT House Inspection 7-2-2008 Final.doc 11 (14) 2008-07-17 Thermography Inspection at (Commercial Building) Date: (6/25/2008) Photo and Identification IR Text Comment Location Category Value Commercial Building Mechanical/Conductive Heat Element Thermogram 6/25/2008 FLIR Systems 533.6 °F 520 Sp2 500 Sp1 480 Sp3 460 Label IR: Date Of Creation IR: Time Of Creation IR: Max IR: Min Sp1 Sp2 Sp3 Value 6/25/2008 9:56:34 AM 749.6 °F 89.1 °F 438.7 °F 697.6 °F 595.9 °F 440 428.4 Analysis & Recommended action: This picture shows the inside of a walk in smoke house. The conductive heating element is on and the darker areas indicate a much lower temperature than the brighter areas. The heating element should be inspected and repaired or replaced. JT House Inspection 7-2-2008 Final.doc 12 (14) 2008-07-17 Thermography Inspection at (Shop) Date: (7/2/2008) Photo and Identification IR Text Comment Location Category Value Shop Tire Inspection Thermogram 7/2/2008 FLIR Systems 105.8 °F Sp1 100 Sp2 90 Li1 80 70.7 Label IR: Date Of Creation IR: Time Of Creation IR: Max IR: Min Sp1 Sp2 Value 7/2/2008 2:47:45 PM 118.5 °F 71.7 °F 97.7 °F 93.7 °F °F 105 100 95 90 85 80 75 Label Li1 Cursor - Min 87.3 Max 101.5 Analysis & Recommended action: This picture shows the driver’s side tire on a Jeep. Compare with passenger side tire below. This type of inspection can be used as a part of a preventative maintenance program. JT House Inspection 7-2-2008 Final.doc 13 (14) 2008-07-17 Thermography Inspection at (Shop) Date: (7/2/2008) Photo and Identification IR Text Comment Location Category Value Shop Tire Inspection Thermogram 7/2/2008 FLIR Systems 106.2 °F Sp1 100 Sp2 Li1 90 Label IR: Date Of Creation IR: Time Of Creation IR: Max IR: Min Sp1 Sp2 Sp3 Value 7/2/2008 2:48:19 PM 140.5 °F 70.3 °F 101.5 °F 89.6 °F 95.8 °F °F 105 100 95 Sp3 80 90 85 80 74.2 75 Label Li1 Cursor Min Max - 84.3 104.2 Analysis & Recommended action: This picture shows the passenger side tire on a Jeep. The unusual heat patterns indicate unusual wear which could be due to improper inflation or tire imbalance. This type of inspection can be used as a part of a preventative maintenance program. JT House Inspection 7-2-2008 Final.doc 14 (14) 2008-07-17
© Copyright 2026 Paperzz