REPORT NO. 102633962CRT-001 July 25, 2016 RETURN AIR VOLUME VERSUS STATIC PRESSURE TESTS ON CORELITE BRIDGE™ RETURN AIR LIGHT FIXTURES EATON 18001 E COLFAX AVE AURORA, CO 80011-5108 TEST METHOD The fixtures were tested in accordance with the ASHRAE 70-2006 Standard “Method of Testing for Rating the Performance of Air Outlets and Inlets”, which incorporates ADC 1062: GRD-84 Test Code for Grilles, Registers and Diffusers. The unit was installed in the facility and supplied with measured volumes of air. DESCRIPTION OF TEST SPECIMENS The test specimens consisted of three models of air returns. The first was Model Bridge LED 2x2 which measured 24 inches long by 24 inches wide. The second Model Bridge LED 2x4 measured 48 inches long by 24 inches wide. The third Model Bridge LED 1x4 measured 48 inches long by 12 inches wide. A row of small openings along the two opposite sides, running the length of each unit, allowed the air to return. RESULTS OF MEASUREMENTS Bridge LED 2x2 Light Fixture Negative Static Pressure (inches H2O) 0.05 0.10 0.15 0.20 0.30 Return Air Volume (CFM) 31 44 53 62 76 Bridge LED 2x4 Light Fixture Return Negative Air Static Pressure Volume (inches H2O) (CFM) 0.01 32 0.05 68 0.10 96 0.20 137 0.30 173 Report No. 102633962CRT-001 Bridge LED 1x4 Light Fixture Return Negative Air Static Pressure Volume (inches H2O) (CFM) 0.01 30 0.05 67 0.10 95 0.20 136 0.30 165 Page 1 of 2 TD519020EN RESULTS OF MEASUREMENTS (CONTINUED) 0.3 0.25 0.2 0.15 0.1 0.05 Negative Static Pressure (iwg) Negative Static Pressure (iwg) Bridge LED 2x2 Light Fixture 0 30 40 50 60 Return Air Volume (CFM) 70 80 Bridge LED 2x4 Light Fixture 0.3 0.25 0.2 0.15 0.1 0.05 0 30 50 70 90 110 130 Return Air Volume (CFM) 150 170 Negative Static Pressure (iwg) Bridge LED 1x4 Light Fixture 0.3 0.25 0.2 0.15 0.1 0.05 0 30 50 70 90 110 130 Return Air Volume (CFM) Report No. 102633962CRT-001 150 Page 2 of 2 170 TD519020EN
© Copyright 2026 Paperzz