D-Component CMLDBLU1 CMLDBLU2 Vstall > Vbrk Eg. 0.9 > 0.86 Considered a data error and this instance of CMLD Model is not applied. Considered a data error and this instance of CMLD Model is not applied. Vstallbrk > Vbrk Eg. 0.9 > 0.86 Vstallbrk not programed. Considered a data error and this instance of CMLD Model should not be applied. NOT CHECKED – We need to make sure software vendors are checking for this data error. Vbrk > Vstall > Vstallbrk Eg. 0.86 > 0.65 > 0.55 As voltage goes down, trajectory transitions immediately from run curve to stall curve once userentered Vstall is reached (may result in a step transient if Vstall is not at intersection of run and stall curves and may result in numerical instability if Vstall is below intersection). Transition is not delayed by Tstall though Tstall timer begins timing. As voltage goes down, trajectory transitions from run curve to stall curve once user-entered Vstall is reached and user-entered Tstall timer times out (may result in a step transient). However, if intersection point between run and stall curves (at Vstallbrk) is reached before Tstall timer times out, transition to stall curve happens immediately and without delay, even if Tstall timer has not timed out. Trajectory continues down stall curve as voltage continues to go down. Depending on whether Tstall timer has timed out while voltage has existed below Vstall leads to two possibilities as voltage recovers: 1. Tstall timer does not time out. As voltage goes up with model in an “unofficial” stall mode, trajectory of 100 percent of D-component transitions from stall curve to run curve once Vstall(?) is reached. There is no delay in transition and Tstall, Trestart, Frst, and Vrst are not applicable. 2. Tstall timer does time out. As voltage goes up with model now in “official” stall mode and once trajectory reaches Vrst, Trestart timer begins timing and Frst fraction of D-component transitions from stall curve to run curve once Trestart timer times out. (Vstall should be <= Vrst) Remaining fraction Depending on whether Tstall timer has timed out while voltage has existed below Vstall leads to two possibilities as voltage recovers (the two conditions are shown graphically): 1. Tstall timer does not time out. As voltage goes up with model in an “unofficial” stall mode, trajectory of 100 percent of D-component transitions from stall curve to run curve once Vstallbrk intersection point is reached. There is no delay in transition and Tstall, Trestart, Frst, and Vrst are not applicable. 2. Tstall timer does time out. As voltage goes up with model now in “official” stall mode and once trajectory reaches Vrst, Trestart timer begins timing of D-component load remains in stall mode until heating logic possibly removes it. Vbrk > Vstallbrk > Vstall Eg. 0.86 > 0.55 > 0.2 One factor to consider here is contactor drop out. For the example thresholds given above, Motor D will drop out before reaching 0.2pu stall threshold. The contactor drop out is around 0.5pu. (Same as above; Vstallbrk not programmed) and Frst fraction of D-component transitions from stall curve to run curve once Trestart timer times out. (Vstall should be <= Vrst) Remaining fraction of D-component load remains in stall mode until heating logic possibly removes it. As voltage goes down, trajectory immediately transitions from run curve to stall curve once intersection point at Vstallbrk is reached. There is no delay in transition and Tstall is not applicable in this transition. However, Tstall timer will still begin timing once voltage drops below Vstall, and if Tstall timer times out while voltage remains below Vstall, model will “officially” enter stall mode. Note that we are still on stall curve. This then leads to same two possibilities as voltage recovers: 1. Tstall timer does not time out. As voltage goes up with model in an “unofficial” stall mode, trajectory of 100 percent of D-component transitions from stall curve to run curve once Vstallbrk intersection point is reached. There is no delay in transition and Tstall, Trestart, Frst, and Vrst are not applicable. 2. Tstall timer does time out. As voltage goes up with model now in “official” stall mode and once trajectory reaches Vrst, Trestart timer begins timing and Frst fraction of D-component transitions from stall curve to run curve once Trestart timer times out. (Vstall should be <= Vrst) Remaining fraction of D-component load remains in stall mode until heating logic possibly removes it. Vbrk > Vstall > Vstallbrk or Vbrk > Vstallbrk > Vstall Contactors and UV Relays Section of run curve below intersection of run and stall curves is applicable if Vstall < intersection voltage (Vstallbrk). Section of run curve below Vstallbrk is not applicable; model can never get there. That’s correct, the model will never be on the run characteristic below Vstallbrk. If either UV relay causes a trip, the specified fraction, Fuvr, is removed regardless of whether D-component is in run or stall mode. Same with contactors causing a trip except that 100 percent of D-component is removed. As voltage goes back up, there is no restoration from any prior UV relay tripping. Contactors restore a Dcomponent previously in run mode to run mode, or a D-component previously in stall mode, whether official or unofficial, to stall mode (with exception to follow). If contactor has been out for some time, model does NOT consider possibility of D-component having stalled if it had been in run mode upon contactor drop out. To repeat, if D-component was in stall mode upon contactor drop out, contactor returns it in stall mode. EXCEPTION: if contactor reclosing occurs above Vstall and Vstallbrk, D-component is returned on run curve if the mode had been unofficial stall mode (Tstall not timed out). Conversely, D-component is returned on stall curve if mode had transitioned to official stall mode by Tstall timer having timed out, even if voltage is above Vstall and Vstallbrk. Note: Tstall timer continues to time while voltage is below Vstall, even while contactor is out. As voltage goes above Vrst, restartable fraction restarts once Trestart timer times out. D-component is now split into Frst and 1-Frst fractions, Frst on run curve, 1-Frst on stall curve. Commented [GA1]: This needs to be verified. I am not sure how vendors are implementing the logic of connecting back Motor D once the contactor recloses. Commented [GA2]: I agree. We need to make sure the vendors are following this Commented [GA3]: I agree. Again, we need to confirm if the vendors are following this.
© Copyright 2026 Paperzz