Measuring transducers G 400 for phase angle PF 400 for cos

341E.3
Measuring transducers
G 400 for phase angle
PF 400 for cos ϕ proportional
PF400-FA
The G 400 measures the angle between sine wave formed current
and voltage.
The output signal is proportional to the angle in degrees.
There are two models, one for single-phase and one for 3-phase
systems.
The PF 400 for cos ϕ measures the angle between sine wave
formed current and voltage. The output signal is proportional to cos
phi. There are two models, one for single-phase and one for threephase systems.
The transducers in plastic cases are mounted directly on profiled
bar 35 EN 500022. Connection to selfopening clamps for 6 mm2
wires.
Transducers for mounting in 19" racks can be delivered in different
application types (see special leaflet). The rack modules are 8 TE
wide and in a 19" rack is place for 10 modules.
The transducers are manufactured according to IEC 688.
PF400-FB
Order facts:
Enclosed for mounting on
profiled bar 35 EN 50022
Angle deg cos ϕ
Type
Type
Single phase G 400-15x PF 400-15x
Three phase G 400-35x PF 400-35x
19" rack module
(width 8 TE)
Angle deg
cos ϕ
Type
Type
G 400R-15x PF 400R-15x
G 400R-35x PF 400R-35x
Replace x with last digit for output according to table below
External
Output
resistance load
Last digit x
0 -5 or ± 5 mA
0-3000 Ω
1
0 -10 or ± 10 mA
0-1500 Ω
2
0 -20 or ± 20 mA
0- 750 Ω
3
4 -20 mA
0- 750 Ω
4
0 -10 or ± 10 V
> 700 Ω
5
Order form:
Measuring transducer
Type
Connection
Range
Output
Power supply
Case for DIN-rail
for cos ϕ, three phase
PF 400-354
110 V, 5A, 50 Hz
cap. 0,5-1-0,5 ind.
4 - 12 - 20 mA
230 VAC
Technical data
Input
Voltage
any value between 10 and 500V
(rack version max 300 V)
Consumption (burden) < Uin × 2 mA, VA
Current
any value between 0,5 and 7,5 A
Consumption approx. 0,2 VA
Frequency
50 or 60 Hz
Measuring ranges
min 60 deg., max 360 deg.
Common measuring
cap 0,5-1-0,5 ind
ranges
cap 0,9-1-0,9 ind
Output
Current output signal min 0-1 mA, max 0-20 mA
Range
0...5/10/20 mA, 4-20 mA
Load
max 15 V
Current limitation
< 30 mA
Voltage:
0-10 V
Burden
> 700 Ω
Ripple
< 1% p.p.
General data
Accuracy
class 0,5 according to IEC 688
0,2 on request
Linearity error
< 0,1%
Response time
2 periods
Temperature influence < 0,1% / 10°C
Temperature range
–
25...+60°C operation
–
40...+70°C storage
Test voltage
5,6 kV, 50 Hz, 1 min (rack version 3,7 kV)
Power supply
24, 110, 230 VAC ± 15%, 47-70 Hz, ca 2 VA
24-130 VDC ± 20%, ca 2,5 W
Weight
0,5 kg
Options on request
Standards
General standards for measuring transducers EN 60688, IEC 688
EMC
emission EN 50081-2
immunity EN 50082-2 *
Safety
EN 61010-1, IEC 1010-1
Inputs
overvoltage cat III
Outputs
overvoltage cat II
Pollution degree
2
*) At certain frequences can minor deviations from class accuracy
occur during the disturbance
HUGO TILLQUIST AB • SWEDEN
Box 1120 • SE-164 22 KISTA • Tel +46 8 594 632 00 • Fax +46 8 751 36 95 • www.tillquist.com
341E.3
Design
GPF400BB
The two input quantities voltage and current are transformed in the
input transformer to a level adapted to the internal electronics and
give at the same time galvanic separation.
The noise on the input signals is filtered away in the phase true
lowpass filter.
In the following zero cross detector (Schmitt trigger) is the input sine
wave converted to a square wave.
The micro processor calculates the exact time difference T1
between the two input signals. Out of the relation T1/T is either the
phase angle (G) or the cosine (PF) between voltage and current
calculated.
The AC power supply comes from a transformer that gives a
galvanic separation. Those parts that need separate power get it via
a rectifying stage. The DC power comes from a switched unit that
gives galvanic separation and covers the span from 24 to 130 VDC.
Connecting diagrams
G/PF 400
GPF400AE
G/PF 400R
GPF400RE
Dimensions (mm)
G/PF 400
PQ400ME
G/PF 400R
400RM3
HUGO TILLQUIST AB • SWEDEN
Box 1120 • SE-164 22 KISTA • Tel +46 8 594 632 00 • Fax +46 8 751 36 95 • www.tillquist.com