POWERCORE™ Substation Control Enclosure — 8` x 19

POWERCORE™ Substation Control Enclosure —
8' x 19' Concrete
AC Cabinet
Exit
DC Cabinet
& Charger
Panel 1
Panel 2
Panel 3
Panel 4
Panel 5
Light
A/C
HEAT
Door
Battery Rack
Light
Light
Light
Light
8'W x 19'L (Exterior Dim.) x 9'H (Inside Dim.)
MAJOR FEATURES
• Structural loads of the proposed concrete shelter are as follows:
− 200 pounds-per-square-foot distributed floor loading while on foundation
− 125 pounds-per-square-foot distributed floor loading while lifting
− 100 pounds-per-square-foot distributed roof load
− 150 mph wind load
− Seismic Zone 4
• Exterior, exposed aggregate or buff color with clear-coat seal
• Shelter walls are capable of stopping 30.06-rifle fire per UL 752 requirements, excluding shelter door
• Shelter 4 in. concrete walls have a two-hour fire rating
• Interior walls and ceiling are insulated with hardboard insulation, R-11
• Interior walls and ceiling are sheathed with 1/2 in. white, Nu-Poly board
• Light-colored industrial-grade vinyl tile floor covering
• One (1) 42 in. W x 84 in. H insulated steel exterior door with stainless steel ball-bearing tamper-proof
hinges, panic bar hardware and fiberglass weather hood, hydraulic door closer
• Power distribution
− One (1) ac distribution panel, 225 A main breaker, 120/240 Vac, single phase, 60 Hz, 42-space main
breaker, NEMA 1 enclosure, and circuit breakers for all installed equipment
− Ten (10) ac 20 A specification-grade duplex receptacles and one (1) 20 A specification-grade exterior
ground fault duplex receptacle
− One (1) ac single-throw safety (disconnect) switch, 400 A, 225 A fused, 240 Vac, double pole,
NEMA 3R enclosure
− One (1) ac double-throw manual transfer switch, 400 A, 240 Vac, nonfused, double pole
− One (1) dc distribution panel, 125 Vdc, 30 A and 20 A 2-pole branch breakers, and circuit breakers
for all installed equipment
− One (1) dc single throw safety (disconnect) switch, 400 A, 125 Vdc, fused, double pole
• Lighting—Four (4) 64 W, 4-foot ceiling-wall mount and one (1) 2-foot fluorescent light fixtures and
two (2) 100 W metal halide exterior door lights
• A/C & heating unit—One (1) nominal 12,000 Btu/hr wall mount A/C unit, with low ambient and
compressor anti-cycle controls, integral 5 kW resistance heat strip and washable dust filter. Unit sizing
is site- and customer-specification dependent.
• Grounding system
− Two (2) NEMA pads, located opposite enclosure corners, external grounding connection point
− 4/0 AWG stranded bare copper halo, run-through cable tray, between the NEMA ground pads
− 2 AWG stranded bare copper jumper between 4/0 AWG and panel ground bars
• Cable ladder/tray, 18 in. W x 4 in. H, above panels and down exterior wall, cable entry hood
• Battery system
− 71 Ah, nickel cadmium cells, with Seismic Zone 4 battery rack
− Battery charger, microprocessor controlled, 120/240 Vac input, 130 Vdc, 12 A output with battery
eliminator filter, temperature compensation, alarm monitoring, serial DNP3 communications
• Protection and control panels—One (1) to five (5) 24 in. D x 32 in. W x 90 in. H swing rack panels
(see SEL-7000 Integrated Substation System for panel content)
• Alarm devices, contacts wired per customer specifications (no audible, visual or remote provisions)
− One (1) smoke detector
− One (1) heat detector
− One (1) intrusion alarm
• Accessories—Dry eraser/cork board, office chair
• Safety equipment—First aid kit, portable 20-pound ABC fire extinguisher and exit sign
• Foundation—Customer-supplied pier, slab, or compact gravel
• One (1) service manual, to include manufacturer documentation that comes with project equipment
• Three (3) sets of enclosure drawings, to include typical foundation drawings
• Warranty
− 10 years for SEL relays
− 10 years for structure
− 10 years for battery charger
− 10 years for NiCad batteries, plus additional 15 year prorated
− A/C & heating unit, electrical and non-SEL products are per manufacturer warranty
BUDGETARY PRICE *
•
•
•
•
•
•
•
8 ft. W x 19 ft. L (Exterior Dim.) x 9 ft. H (Interior Dim.) enclosure ......................... $65,000.00
71 Ahr NiCad battery bank, rack & 12 A charger ....................................................... $23,000.00
Estimated shipping costs per 500 miles from manufacturer plant ............................... $ 4,000.00
Off loading, crane, leveling, setup ............................................................................... $ 4,500.00
Lead time .................................................................................................................. 16–18 weeks
One (1) to five (5) swing panels (SEL-7000 Integrated Substation System).......$ Quote Request
Relay settings and integration/automation programming ....................................$ Quote Request
* Note: Pricing changes with particular project definition and scope.