MP Meter-Pak™ Meter Centers

MP Meter-Pak™ Meter Centers
Class 4141
Catalog
4141CT0701
2008
MP44125
MP86200
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
General and Application Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
MP Meter-Pak™ Meter Centers
Product Description
PRODUCT DESCRIPTION
Square D® brand MP Meter-Pak meter centers from Schneider Electric offer
a wide range of solutions for multi-metering applications:
MPH66125 with Horn Bypass
•
•
•
UL® Listed NEMA Type 3R construction
•
Meter socket jaws, constructed of tin-plated copper, are spring
reinforced on MP devices
•
Lever type bypass meter socket jaws are spring reinforced and
equipped with jaw release
•
Stainless steel cover hasps and latches meet tough coastal utility
sealing requirements
•
Barrel lock provisions on all ringless devices
Meets EUSERC standards
9-inch meter center spacing allows for more sockets per device creating
lighter, more compact branch enclosures
MP Meter-Pak Meter Centers
For 2- to 6-unit apartment buildings or light commercial applications.
•
•
•
•
•
Surface and semi-flush mounting
Suitable only for use as service equipment
Main bus ratings range from 200–800 A
125, 200, and 225 A (2 to 4 positions) tenant circuit breaker versions
Four meter socket configurations available:
— Ring type four-jaw without bypass
— Ringless type with 5th jaw without bypass
— Ringless type with 5th jaw and horn bypass
— Ringless type with 5th jaw and lever bypass with jaw release
•
120/240 Vac, 1φ3W or 120/208 Vac, 1φ3W (derived from a 208Y/120
Vac, 3φ4W network)
MPH33125
2
© 2008 Schneider Electric All Rights Reserved
03/2008
MP Meter-Pak™ Meter Centers
Product Description
Short Circuit Current Rating Selection Process
1. Review local utility requirements to ensure that metering equipment meets their standards.
2. Check with local utility to determine available fault current at the meter center.
3. Use the Short Circuit Current Ratings (SCCR) table below to:
a. Read down to select SCCR equal to or greater than desired rating.
b. Read across to select Tenant Circuit Breaker type.
4. With information obtained from Step 3, turn to the appropriate selection pages to determine catalog
numbers for Meter-Pak Device and Tenant Circuit Breakers.
UL Listed Meter Center Short Circuit Current Ratings (SCCR) 10,000, 22,000, 25,000. 42,000, 65,000 and 100,000 AIR
Short Circuit Current Rating (RMS
Symmetrical Amperes at 240 Vac
Maximum)1
MP Meter-Pak Meter Centers
Tenant Circuit Breakers2
QO (125 A max., 2-pole)
10,000 AIR 3
QOM2-MM (200 A max., 2-pole)
QBP-TM (70–225 A max., 2-pole)
22,000 AIR
QO-VH (125 A max., 2-pole)
3
QOM2-MVH (200 A max., 2-pole)
25,000 AIR 3
QDP-TM (70–225 A max., 2-pole)
42,000 AIR 3
QOH (125 A max., 2-pole)
65,000 AIR 3
QGP-TM (70–225 A max., 2-pole)
100,000 AIR 3
QJP-TM (70–225 A max, 2-pole)
MP Branch Compartments
Service
Disconnects
(6 Maximum)
Transformer
Main Lugs
Load Center
(Typical)
MP Main Lugs
Compartment
1
2
3
Meter center short circuit current rating is equal to the lowest short circuit current rating given in the table for any circuit breaker installed in any meter panelboard
in the meter center.
When slider type manual circuit closers are installed, the meter center short circuit current rating is limited to 10,000 RMS symmetrical amperes.
AIR = Amperes Interrupting Rating.
3
03/2008
© 2008 Schneider Electric All Rights Reserved
MP Meter-Pak™ Meter Centers
Table of Contents
Table of Contents
MP METER-PAK™ METER CENTERS
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
125 A Maximum MP Meter-Pak Meter Center Configurations . . . . . . . . .6
200 A Maximum MP Meter-Pak Meter Center Configurations . . . . . . . . .6
225 A Maximum MP Meter-Pak Meter Center Configurations . . . . . . . . .6
Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Mains Rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Branch Circuit Breaker Provisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Meter Sockets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Meter Socket Covers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Utility Pull Box Cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Customer/Tenant Compartment Cover . . . . . . . . . . . . . . . . . . . . . . . . . .11
Mounting Channel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Rotating Mounting Feet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Top Endwall Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
125 A Maximum MP Meter-Pak Meter Center Top Endwalls . . . . . . . . .12
200 and 225 A Maximum MP Meter-Pak Meter Center Top Endwalls . .12
Semi-Flush Flange Kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
MP Meter-Center Hub and Knockout Configurations . . . . . . . . . . . . . . .13
Main Lugs Section Service Conductor Termination Data . . . . . . . . . . . .14
Alternate Lug Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
NEMA/EUSERC Lug Landing Kit . . . . . . . . . . . . . . . . . . . . . . . . . . .14–15
Tenant Circuit Breaker Terminal Data . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Service Grounding/Load Neutral and Equipment Grounding
Termination Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Hinged Rain Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Underground Service Wireway . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17–18
Catalog Number Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Dimensions and Knockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
4
© 2008 Schneider Electric All Rights Reserved
03/2008
MP Meter-Pak™ Meter Centers
Application Data
Application Data
MP22125 (shown)
MPR22125, MPH22125
(Sealing Rings not shown)
MP33125, MPR33125, MPH33125 (shown)
MP44125 (shown)
MPR44125, MPH44125
MP55125, MPR55125, MPH55125, MP66125, MPR66125, MPH66125 (shown)
(Top Left Position Omitted on 5-Position Units)
MP42200 (shown)
MPR42200, MPH42200
MP43200, MPR43200
MPH43200 (shown)
5
03/2008
© 2008 Schneider Electric All Rights Reserved
MP Meter-Pak™ Meter Centers
Application Data
125 A Maximum MP Meter-Pak™ Meter Center Configurations
•
Ring-type MP supplied with 4-jaw meter socket without bypass (5th jaw
and manual slider type bypass kits can be ordered separately and
field-installed).
•
Ringless-type MPR supplied with 5-jaw meter socket without bypass
(horn-type bypass kits can be ordered separately and field-installed).
•
Ringless-type MPH supplied with 5-jaw meter socket with horn-type
bypass.
•
Both ring- and ringless-type units have provisions for mounting 2-pole,
plug-on type QO®, QO-VH, or QOH circuit breakers.
200 A Maximum MP Meter-Pak Meter Center Configurations
MP64200, MPR64200, MPH64200 (shown)
•
Ring-type MP supplied with 4-jaw meter socket without bypass (5-jaw
and manual slider type bypass kits can be ordered separately and
field-installed).
•
Ringless-type MPR supplied with 5-jaw meter socket without bypass
(horn-type bypass kits can be ordered separately and field-installed).
•
Ringless-type MPH supplied with 5-jaw meter socket with horn-type
bypass.
•
Both ring- and ringless-type units have provisions for mounting 2-pole,
bolt-on type QOM2-MM or QOM2-MVH circuit breakers.
225 A Maximum MP Meter-Pak Meter Center Configurations
MP85200, MPR85200, MPH85200, MP86200 (shown),
MPR86200, MPH86200
(Top Left Position Omitted on 5-Position Units)
•
Ringless-type MPL supplied with 5-jaw meter sockets with lever bypass
and jaw release.
•
MPL devices have provisions for mounting QBP-TM, QDP-TM, QGP-TM,
or QJP-TM 2-pole bolt-on type circuit breakers.
MPL32225, MPL53225 (shown), MPL64225
6
© 2008 Schneider Electric All Rights Reserved
03/2008
MP Meter-Pak™ Meter Centers
Application Data
Type
•
•
•
•
Enclosures are indoor/rainproof NEMA Type 3R
•
Designed to be wall mounted only, not suitable for use as floor standing
equipment
•
All unmetered conductor compartments are sealable by the utility
company
•
Finish: ANSI gray, baked powder coat epoxy electro-deposited over
cleaned phosphatized steel
•
UL Listed under File E-6294
MP, MPH and MPR available in 2-, 3-, 4-, 5-, or 6-position configurations
MPL available in 2-, 3-, or 4-position configurations
Suitable only for use as service entrance equipment (cannot be fed from
an upstream service disconnect)
Service
•
•
MPH66125
120/240 Vac, 1φ3W
120/208 Vac, 1φ3W (derived from a 208Y/120 Vac, 3φ4W network)
Mains Ratings
125 A Maximum MP Meter-Pak Meter Centers
200 A (2-position), 300 A (3-position), 400 A (4-position),
500 A (5-position), and 600 A (6-position) main bus ratings.
200 A Maximum MP Meter-Pak Meter Centers
400 A (2- and 3-position), 600 A (4-position) and 800 A (5- and 6-position)
main bus ratings.
225 A Maximum MP Meter-Pak Meter Centers
400 A Main Lugs
350 A (2-position), 500 A (3-position), 600 A (4-position) main bus ratings.
Branch Circuit Breaker Provisions
125 A Maximum MP Meter-Pak Meter Centers
Accepts 40–125 A, 2-pole, plug-on type QO, QO-VH, or QOH circuit
breakers. (Order circuit breakers separately.)
UL® Listed meter center short circuit current rating (RMS symmetrical
amperes) equal to the lowest interrupting rating of installed tenant
circuit breaker.
Ampere Rating
QO Plug-On
Mounting Base
QO2100
Plug-On Circuit
Breaker Installed
10,000 AIR
120/240 Vac
22,000 AIR
120/240 Vac
42,000 AIR
120/240 Vac
40
QO240
QO240VH
QOH240
50
QO250
QO250VH
QOH250
60
QO260
QO260VH
QOH260
70
QO270
QO270VH
QOH270
80
QO280
QO280VH
QOH280
90
QO290
QO290VH
QOH290
100
QO2100
QO2100VH
QOH2100
125
QO2125
QO2125VH
QOH2125
NOTE: For load center series ratings used downstream from metering
equipment, refer to the following Data Bulletins: 4100DB0301 and 2700DB9901.
7
03/2008
© 2008 Schneider Electric All Rights Reserved
MP Meter-Pak™ Meter Centers
Application Data
200 A Maximum MP Meter-Pak Meter Centers
Accepts 100–200 A, 2-pole, bolt-on type QOM2-MM or QOM2-MVH circuit
breakers. (Order circuit breakers separately.)
UL Listed meter center short circuit current rating (RMS symmetrical amperes)
equal to the lowest interrupting rating of tenant circuit breaker installed.
Ampere Rating
10,000 AIR 120/240 Vac
22,000 AIR 120/240 Vac
100
QOM2100MM
QOM2100MVH
125
QOM2125MM
QOM2125MVH
150
QOM2150MM
QOM2150MVH
175
QOM2175MM
QOM2175MVH
200
QOM2200MM
QOM2200MVH
QOM2-MM or QOM2-MVH Bolt-On Mounting Base
NOTE: For load center series ratings used downstream from metering
equipment, refer to Data Bulletins: 4100DB0301 and 2700DB9901.
225 A Maximum MP Meter-Pak Meter Centers
Accepts 70–225 A, 2-pole, bolt-on type, QBP-TM, QDP-TM, QGP-TM, or
QJP-TM circuit breakers. Also accepts 40–60 A, 2-pole, plug-on type QO,
QO-VH or QOH circuit breakers; but requires the use of EZM125QOA
adapter kit. (Order circuit breakers and adapter kit separately).
QOM2200MVH Bolt-On Circuit Breaker Installed
UL Listed meter center short circuit current rating (RMS symmetrical amperes)
equal to the lowest interrupting rating of tenant circuit breaker installed.
Ampere
Rating
QDP22200TM 2-Pole, Bolt-on Type Circuit Breaker
10,000 AIR
120/240 Vac
25,000 AIR
120/240 Vac
65,000 AIR
120/240 Vac
100,000 AIR
120/240 Vac
40
QO240 1
QO240VH 1 2
QOH240 1 3
—
50
QO250 1
QO250VH 1 2
QOH250 1 3
—
60
QO260 1
QO260VH 1 2
QOH260 1 3
—
70
QBP22070TM
QDP22070TM
QGP22070TM
QJP22070TM
80
QBP22080TM
QDP22080TM
QGP22080TM
QJP22080TM
90
QBP22090TM
QDP22090TM
QGP22090TM
QJP22090TM
100
QBP22100TM
QDP22100TM
QGP22100TM
QJP22100TM
110
QBP22110TM
QDP22110TM
QGP22110TM
QJP22110TM
125
QBP22125TM
QDP22125TM
QGP22125TM
QJP22125TM
150
QBP22150TM
QDP22150TM
QGP22150TM
QJP22150TM
175
QBP22175TM
QDP22175TM
QGP22175TM
QJP22175TM
200
QBP22200TM
QDP22200TM
QGP22200TM
QJP22200TM
225
QBP22225TM
QDP22225TM
QGP22225TM
QJP22225TM
1
Requires use of EZM125QOA adapter (order separately).
2
QOVH tenant circuit breakers are rated 22,000 AIR at 120/240 Vac.
3
QOH tenant circuit breakers are rated 42,000 AIR at 120/240 Vac.
Meter Sockets
Standard Meter Socket Configurations
Optional 5th Jaw Kit Installed on Ring-Type Device
Ringless-Type MPH
Includes 5-Jaw Meter Socket and Horn Bypass
•
•
Rated 200 A continuous duty.
•
•
Thermoset polyester with fiberglass reinforced base assembly.
•
•
•
Ring-type MP supplied with 4-jaw meter socket without bypass.
•
Ringless-type MPL supplied with 5-jaw meter socket with lever bypass
and jaw release.
Front removable spring reinforced jaws equipped with line and load side
blade guides.
5th jaw supplied factory-installed on ringless-type MPH and MPR in the
9 o'clock position, 5th jaw can be moved to the 3 or 6 o’clock position as
required.
Ringless-type MPR supplied with 5-jaw meter socket without bypass.
Ringless-type MPH supplied with 5-jaw meter socket with horn-type
bypass.
8
© 2008 Schneider Electric All Rights Reserved
03/2008
MP Meter-Pak™ Meter Centers
Application Data
Optional Meter Socket
•
5th jaw kit (catalog number 5J) can be field-installed on ring-type MP at
the 3, 6, or 9 o’clock position and is required for 120/208 Vac, 1φ3W,
service (derived from a 208Y/120 Vac 3φ4W network). One kit required
per meter socket, order separately.
•
Horn-type bypass kit, catalog number MMHB, can be field-installed on
ringless-type MPR. One kit required per meter socket, order separately.
•
Manual slider type bypass kit, catalog number MM125MB (for top
position only on 125 A, 2-position ring-type MP) or MM200MB (for 125 A
and 200 A ring-type MP). One kit required per meter socket, order
separately for field-installation.
NOTE: Manual slider type bypass kits limit meter center equipment short
circuit current rating to 10,000 RMS symmetrical amperes.
Ring-Type MP
4-Jaw Meter Socket without Bypass
Meter Socket Covers
Ring-Type MP Meter Socket Cover
Individual Ring-Type
Meter Socket Cover
•
Individual meter socket cover provided for each
meter socket.
•
Cover cannot be removed with meter installed in
meter socket.
•
Seal ring is required to secure base of meter onto
rim provided on meter socket cover.
•
Aluminum snap-type seal ring (catalog number
29209-100-01) is standard on all ring-type MP
meter socket covers.
Optional Meter Socket Sealing Rings for Type MP
Manual Slider-Type Bypass, Closed Position
MM125MB, MM200MB (shown)
•
Stainless steel snap-type sealing ring (catalog number ARP00026).
Order separately for field-installation.
•
Aluminum screw-type sealing ring (catalog number 29008W). Order
separately for field-installation.
Snap-Type Sealing Ring
Screw-Type Sealing Ring
Manual Slider-Type Bypass, Open Position
MM125MB, MM200MB (shown)
9
03/2008
© 2008 Schneider Electric All Rights Reserved
MP Meter-Pak™ Meter Centers
Application Data
Ringless-Type MPH, MPL, and MPR Meter Socket Covers
•
•
Individual meter socket cover provided for each meter socket.
•
Ringless meter socket covers are each supplied with a stainless steel
latch and hasp to accommodate utility seals including lead wire seals,
barrel locks, ribbon seals, padlocks, and snap-type seals.
•
Ringless meter socket covers are also supplied with a 3/4-inch knockout
to accommodate front-entry barrel locks.
•
Barrel lock bracket located behind 3/4-inch knockout in each ringless
meter socket cover.
•
Barrel lock head protector kit (catalog number MMBLC) includes ferrule,
lock nut, and seal cap to accommodate 1-inch long barrel lock (barrel
lock not included).
Individual Ringless-Type Meter Socket Cover
Base of meter is supported by brackets extending from meter socket
base assembly. Meter socket cover is installed over meter to seal meter
base to socket.
Support Brackets for Base of Meter
Stainless Steel Latch and Hasp,
Ringless Meter Socket Cover
Barrel Lock Installed Front Entry through Knockout in
Ringless Meter Socket Cover
(Reverse View)
Barrel Lock Head Protector Kit MMBLC Installed through
Knockout in Ringless Meter Socket Cover
10
© 2008 Schneider Electric All Rights Reserved
03/2008
MP Meter-Pak™ Meter Centers
Application Data
Utility Pull Box Cover
•
Supplied with handles on 3- through 6-position 125 A maximum,
2- through 6-position 200 A maximum, and 2- through 4-position 225 A
maximum Meter-Pak meter center units.
•
Supplied with rotating locking hasp to accommodate utility seals
including lead wire seals, barrel locks, ribbon seals, padlocks, and
snap-type seals.
Lifting Handles for Pull Box Cover
Hasp with Cover Installed
Rotating Locking Hasp
Customer/Tenant Compartment Cover
Circuit Breaker Cover,
Closed
•
•
Removable without interfering with meter covers.
•
Supplied with vertical rainproof tenant circuit breaker covers, one per
meter socket.
Supplied with rotating locking hasp to accommodate a padlock
(see rotating locking hasp above).
Tenant Circuit Breaker Covers
•
•
•
Constructed of impact resistant thermoplastic
Provisions for padlocking or sealing
Equipped with latch
Mounting Channel
Tenant Compartment
Circuit Breaker Cover
Circuit Breaker Cover,
Open
•
Mounting channel supplied with 3- through 6-position 125 A maximum
and all 200 A and 2- through 4-position 225 A maximum units.
•
Mounting flange is formed as a part of the top endwall to permit easy
installation.
•
Mount the channel to the wall at proper height. Hang unit on channel
from mounting flange.
Rotating Mounting Bracket
•
•
•
•
Mounting Channel
Permanently attached to save time
Easily moved for mounting hole drilling after marking
Accommodates slight mounting hole misalignment
Used for permanent mounting of device to wall
Rotating Mounting Bracket
11
03/2008
© 2008 Schneider Electric All Rights Reserved
MP Meter-Pak™ Meter Centers
Application Data
Top Endwall Configurations
125 A Maximum MP, MPR, and MPH Meter-Pak Meter Center Top Endwalls
Closing Plate ACP (supplied)
2-Position 125 A Top Endwall
Type A Hub Installed
2-Position 125 A Top Endwall
•
2-position unit has utility compartment provisions for mounting one
type A hub for use with 1- through 2.5-inch size conduit. Closing plate
(Catalog Number ACP) supplied, order hub separately.
•
3- and 4-position units have utility compartment provisions for mounting
one type A-L hub for use with 2- through 4-inch size conduit. Closing
plate (Catalog Number ACPL) supplied, order hub separately.
•
5- and 6-position units have utility compartment provisions for mounting
two type A-L hubs for use with 2- through 4-inch size conduits. Two
ACPL closing plates supplied, order hubs separately.
200 and 225 A Maximum MP, MPR, and MPH Meter-Pak Meter
Center Top Endwalls
2- through 6-position units have utility compartment provisions for mounting
two type A-L hubs for use with 2- through 4-inch size conduit. Two ACPL
closing plates supplied, order hubs separately.
Semi-Flush Flange Kits
Closing Plate ACPL (supplied)
3- and 4-Position 125 A Top Endwall
Prior to installation, semi-flush flange kits can be ordered separately for field
modification. (Refer to instructions included in kits for complete directions.)
To drill enclosure top endwall and box sides to secure mounting flanges:
1. Drill 5/16-inch diameter clearance holes at center punched marks
provided and secure flanges with 1/4-20 mounting hardware provided.
2. Secure mounting flanges of enclosure to stud wall on three sides (top,
left, and right).
3. Cover mounting flanges with building paper and caulk to seal between
enclosure and building paper.
225 A Maximum MPL Meter-Pak Meter Center Top Endwalls
Type A-L Hub Installed
3- and 4-Position 125 A Top Endwall
2- through 4-position units have utility compartment provisions for mounting
two type A-L hubs for use with 2- through 4-inch size conduit. Two ACPL
closing plates supplied, order hubs separately.
Semi-Flush Flange Kit
Description
Two Closing Plates ACPL (supplied)
5- and 6-Position 125 A Top Endwall and
2- through 6-Position 200 A Top Endwall
2- through 4-Position 225 A Top Endwall
Two Type A-L Hubs Installed
5- and 6-Position 125 A Top Endwall and
2- through 6-Position 200 A Top Endwall
2- through 4-Position 225 A Top Endwall
Catalog Number
125 A Maximum 2-Position
MPSF12
125 A Maximum 3- and 4-Position
MPSF14
125 A Maximum 5- and 6-Position
MPSF16
200 A Maximum 2- and 3-Position
MPSF23
200 A Maximum 4-Position
MPSF24
200 A Maximum 5- and 6-Position
MPSF26
Semi-Flush Flange Kit
MPSF23
12
© 2008 Schneider Electric All Rights Reserved
03/2008
MP Meter-Pak™ Meter Centers
Application Data
Knockouts
Conduit Size
Hole Diameter
Symbol
in.
[mm]
in.
[mm]
A
0.50
13
0.88
22
B
0.75
19
1.25
29
C
1.00
25
1.38
35
D
1.25
32
1.75
44
E
1.50
38
2.00
51
F
2.00
51
2.50
64
G
2.50
64
3.00
76
H
3.00
76
3.63
92
I
3.50
89
4.19
105
J
4.00
102
4.63
117
MP Meter-Pak Meter Center Hub and Knockout Configurations
Maximum Tenant
Circuit Breaker
Ampere Rating
and Number of
Positions
Top Endwall Pull Box Compartment
Catalog
Number
125 A
2-Position
MP22125
MPH22125
MPR22125
125 A
3-Position
MP33125
MPH33125
MPR33125
125 A
4-Position
MP44125
MPH44125
MPR44125
125 A
5-Position
MP55125
MPH55125
MPR55125
125 A
6-Position
MP66125
MPH66125
MPR66125
200 A
2-Position
MP42200
MPH42200
MPR42200
200 A
3-Position
MP43200
MPH43200
MPR43200
200 A
4-Position
MP64200
MPH64200
MPR64200
200 A
5-Position
MP85200
MPH85200
MPR85200
Bottom Endwall
Closing Plate(s)
Supplied
Factory-Installed
Hub Provisions
Pull Box
Compartment
Knockout and
Hub Provisions
(1) ACP
(1) Type A
(1) Type A Hub or
(1) B300 Hub or
(1) D, F, G, and (1) A
Tenant Circuit
Breaker
Compartment
Knockouts
(2) C, D, F and
(1) A
Box Back Tenant
Circuit Breaker
Compartment
Knockouts
(2) C, D, F 1
(1) ACPL
(1) Type A–L
(2) Type A–L Hubs or
(2) E, F, G, H
(4) C, D, F
and (1) A, B
Note: One knockout is and (1) A, B
provided with I and J
rings.
(2) ACPL
(2) Type A–L
(3) C, D, F and
(2) Type A–L Hubs or
(1) A, B
(2) G, H, I, J
Provided per
and (1) A
compartment.
(3) C, D, F
Provided per
compartment.
(2) ACPL
(2) Type A–L
(2) Type A–L Hubs or
(4) C, D, F and
(2) G, H, I, J
(1) A, B
and (1) A
(3) C, D, F
(2) ACPL
(2) Type A–L
(2) Type A–L Hubs or
(4) C, D, F
(2) G, H, I, J
and (1) A, B
and (1) A
(4) C, D, F
(2) ACPL
(2) Type A–L
(3) C, D, F
(2) Type A–L Hubs or
and (1) A, B
(2) G, H, I, J
Provided per
and (1) A, B, C
compartment.
(3) C, D, F
Provided per
compartment.
(4) C, D, F
200 A
6-Position
MP86200
MPH86200
MPR86200
225 A
2-Position
MPL32225
(2) ACPL
(2) Type A–L
(2) Type A–L Hubs or
(3) C, D, E, F and
(2) E, F, G, H, I, J and
(1) A, B
(1) A, B
(3) C, D, E, F
225 A
3-Position
MPL53225
(2) ACPL
(2) Type A–L
(2) Type A–L Hubs or
(4) C, D, E, F and
(2) E, F, G, H, I, J and
(1) A, B
(1) A, B
(4) C, D, E, F
225 A
4-Position
MPL64225
(2) ACPL
(2) Type A–L
(2) Type A–L Hubs or
(5) C, D, E, F and
(2) E, F, G, H, I, J and
(1) A, B
(1) A, B
(5) C, D, E, F
1
Same knockout pattern on side of box.
13
03/2008
© 2008 Schneider Electric All Rights Reserved
MP Meter-Pak™ Meter Centers
Application Data
Main Lugs Section
Service Conductor Termination Data
•
•
Neutral bus is bonded permanently to the enclosure
Suitable only for use as service equipment
125 A Maximum MP Meter-Pak™ Meter Center Service Conductor
Termination Data
Factory-Installed
Line Phase and
Number of Meter Main Bus Rating
Main Lugs Capacity Neutral Lug Wire Size
Socket Positions
(Amperes)
(Amperes)
Al/Cu AWG kcmil
2
200 A
200 A
3
300 A
300 A
(1) #4-250
4
400 A
400 A
5
500 A
400 A Al or 500 A Cu
6
600 A
400 A Al or 500 A Cu
(1) 1/0-600
or
(2) 1/0-250
200 A Maximum MP Meter-Pak Meter Center Service Conductor
Termination Data
Main Lugs Compartment
2
400 A
400 A
3
400 A
400 A
4
600 A
400 A Al or 500 A Cu
5
800 A
600 A Al or 750 A Cu
6
800 A
600 A Al or 750 A Cu
(1) 1/0-600
or
(2) 1/0-250
(2) 3/0-500
225 A Maximum MP Meter-Pak Meter Center Service Conductor
Termination Data
MMLK250
MMLK500
2
350 A
350 A
3
500 A
400 A
4
600 A
400 A
(1) 1/0-600
or
(2) 1/0-250
Alternate Lug Kits
Available for use on 3–6 position 125 A, all 200 A, and all 225 A Meter-Pak
meter center units (order separately):
MMSK2
Catalog Number
Lug Type (Mechanical)
Lug Wire Size Al/Cu AWG/kcmil
MMLK250 1
Double-Barrel
(1) 1/0-600 or (2) 1/0-250
MMLK500
Double-Barrel
(2) 3/0-500
MMLK600 2
Double-Barrel
(2) #2-600
1
Standard lug kit supplied factory-installed on 3–6 position 125 A units, 2–4 position 200 A units, and
2–4 position 225 A units.
2
Kit includes NEMA/EUSERC lug landing pads (MMSK2). Kit is rated 800 A maximum (600 A
maximum in EUSERC areas).
NEMA/EUSERC Lug Landing Kit
MMLK600
MMSK4
•
•
Catalog numbers MMSK2 and MMSK4 (order separately).
•
MMSK4 is available for use ONLY on MPL53225 and MPL64225, Not
required for MPL32225.
•
Kits include three bus bar lug landing pads and mounting hardware to
secure pads to main cross bus.
•
Each lug landing pad with MMSK2 is supplied with two 1/2-13 studs;
MMSK4 with four 1/2-13 studs; all on 1-3/4 inch center. Kits include lug
mounting hardware.
•
•
MMSK2 is rated 600A maximum when applied in EUSERC areas.
MMSK2 is available for use on 3- through 6-position 125 A and all 200 A
Meter-Pak meter center units.
Order one kit per Meter-Pak device, order lugs separately (refer to each
device wiring diagram for lug catalog numbers).
14
© 2008 Schneider Electric All Rights Reserved
03/2008
MP Meter-Pak™ Meter Centers
Application Data
Lugs for Use with NEMA/EUSERC Lug Landing Kit MMSK2
Mains Rating
Lug
Manufacturer
Anderson
ILSCO
800 A
1
4/0–500 Al/Cu
VC-6FT
VCEL-060-12H2
400–600 Al, 400–500 Cu
VC-6FT
VCEL-075-12H2
500 Cu
VC-6FT
Compression
4/0–500 Cu
VC-6FT
VHCL-400-12BN
4/0–400 Cu
VC-6FT
VHCL-350-12BN
3/0–350 Cu
VC-6FT
TA-600-2N 2
#2-600 Al/Cu
375 lb-in. (42 N•m)
(2) #2-600 Al/Cu
500 lb-in. (57 N•m)
Mechanical
VHCL-600-12BN
Compression
TA-600-2N 2
ILSCO
500–600 A
VACL-500-12BN
AU-600-2N
Anderson
400 A
Crimping Tool or
Torque
VHCL-500-12BN
300 A
MMSK2
Lug Wire Size
AWG/kcmil
Catalog Number 1 Lug Type
Mechanical
AU-600-2N
AU-600-2N
ILSCO
Mechanical
AU-600-2N
250–600 Cu
VC-6FT
#2-600 Al/Cu
375 lb-in. (42 N•m)
(2) #2-600 Al/Cu
500 lb-in. (57 N•m)
(2) #2-600 Al/Cu
500 lb-in. (57 N•m)
(2) 3/0-500 Al/Cu
500 lb-in. (57 N•m)
Lugs are not available from Schneider Electric and must be ordered separately from Anderson or ILSCO.
Available by ordering kit catalog number CMELK4 (kit includes 4 lugs).
2
Lugs for Use with NEMA Lug Landing Kit MMSK4
Catalog Number
Lug
Catalog Number 1 Lug Type
Manufacturer
L1D2-600
L1D2-800
MMSK4
Anderson
MPL32225
ILSCO
2/0–500 Al/Cu
VC-6FT
VC-6FT
VCEL-075-12H2
500–750 Al or 500 Cu
VC-6FT
VACL-500-12BN
4/0–500 Al/Cu
VC-6FT
350–600 Al or 350–500 Cu
VC-6FT or VC8
VC-6FT or VC8
Compression
VACL-750-12BN
500–750 Al or 500 Cu
VACL-1000-12BN
750–1000 Al
VC8
VHCL-500-12BN
4/0–500 Cu
VC-6FT or VC-7FT
VHCL-600-12BN
3/0–350 Cu
VC-6FT
TA-600-2N 3
#2-600 Al/Cu
375 lb-in. (42 N•m)
TA-800-2N
Mechanical
500 lb-in. (57 N•m)
500 lb-in. (57 N•m)
#2-600 Al/Cu
375 lb-in. (42 N•m)
2AB2-600
(2) #2-600 Al/Cu
375 lb-in. (42 N•m)
(3) #6-250 Al/Cu
275 lb-in. (31 N•m)
300–800 Al/Cu
550 lb-in. (62 N•m)
#2-600 Al/Cu
550 lb-in. (62 N•m)
3AB2-250
Mechanical
Mechanical
VCEL-050-12H2
2/0–500 Al/Cu
VC-6FT
VCEL-060-12H2
400–600 Al, 400–500 Cu
VC-6FT
VACL-500-12BN
Compression
VHCL-500-12BN
VHCL-600-12BN
1)
300–800 Al/Cu
(2) #2-600 Al/Cu
A1B2-600-2
L1D2-600
MPL53225
550 lb-in. (62 N•m)
550 lb-in. (62 N•m)
400–600 Al or 400–500 Cu
L1D2-800
Anderson
#2-600 Al/Cu
300–800 Al/Cu
VCEL-060-12H2
AU-600-2N
Connector
Manufacturing
Company
Crimping Tool or
Torque
VCEL-050-12H2
VACL-600-12BN
2
Mechanical
Lug Wire Size
AWG/kcmil
ILSCO
TA-600-2N 3
Connector
Manufacturing
Company
A1B2-600-2
3AB2-250
Mechanical
Mechanical
4/0–500 Al/Cu
VC-6FT
4/0–500 Cu
VC-6FT or VC-7FT
250–600 Cu
VC-6FT, VC-7FT, or VC-8
#2-600 Al/Cu
375 lb-in. (42 N•m)
#2-600 Al/Cu
375 lb-in. (42 N•m)
(3) #6-250 Al/Cu
275 lb-in. (31 N•m)
Lugs are not available from Schneider Electric and must be ordered separately from Anderson or ILSCO.
2)
Lug landing kit is not required for this device.
3)
Available by ordering kit catalog number CMELK4 (kit includes 4 lugs).
Continued on next page
15
03/2008
© 2008 Schneider Electric All Rights Reserved
MP Meter-Pak™ Meter Centers
Application Data
Lugs for Use with NEMA Lug Landing Kit MMSK4
Catalog Number
Lug
Catalog Number 1 Lug Type
Manufacturer
L1D2-600
Mechanical
L1D2-800
Anderson
MPL64225
ILSCO
Crimping Tool or
Torque
#2-600 Al/Cu
550 lb-in. (62 N•m)
300–800 Al/Cu
550 lb-in. (62 N•m)
2/0–500 Al/Cu
VC-6FT
VCEL-060-12H2
400–600 Al or 400–500 Cu
VC-6FT
VCEL-075-12H2
500–750 Al or 500 Cu
VC-6FT
VACL-500-12BN
4/0–500 Al/Cu
VC-6FT
350–600 Al or 350–500 Cu
VC6-FT or VC8
Compression
VACL-750-12BN
500–750 Al or 500 Cu
VC6-FT or VC8
VHCL-500-12BN
4/0–500 Cu
VC6-FT or VC7-FT
VHCL-600-12BN
250–600 Cu
VC6-FT, VC7-FT or VC8
TA-600-2N 3
#2-600 Al/Cu
375 lb-in. (42 N•m)
TA-800-2N
Mechanical
AU-600-2N
Connector
Manufacturing
Company
Lug Wire Size
AWG/kcmil
VCEL-050-12H2
VACL-600-12BN
MMSK4
Continued from previous page
300–800 Al/Cu
500 lb-in. (57 N•m)
(2) #2-600 Al/Cu
500 lb-in. (57 N•m)
A1B2-600-2
#2-600 Al/Cu
375 lb-in. (42 N•m)
2AB2-600
(2) #2-600 Al/Cu
375 lb-in. (42 N•m)
3AB2-250
Mechanical
L1D2-800
(3) #6-250 Al/Cu
275 lb-in. (31 N•m)
300–800 Al/Cu
550 lb-in. (62 N•m)
1
Lugs are not available from Schneider Electric and must be ordered separately from Anderson or ILSCO.
2
Lug landing kit is not required for this device.
3
Available by ordering kit catalog number CMELK4 (kit includes 4 lugs).
Tenant Circuit Breaker Termination Data
125 A Maximum MP Meter-Pak Meter Center Tenant Circuit Breaker Termination Data
Tenant Circuit Breaker
Type and Ampere Rating
Lug Wire Size
QO, QO-VH, and QOH 2-pole, 40–70 A
#8–#2 AWG Al/Cu
QO, QO-VH, and QOH 2-pole, 80–125 A
#4–2/0 AWG Al/Cu
200 A Maximum MP Meter-Pak Meter Center Tenant Circuit Breaker Termination Data
Tenant Circuit Breaker
1
Type and Ampere Rating
Lug Wire Size
Wire Bending Space
QOM2-MM and QOM2-MVH
2-pole, 100–200 A
#4 AWG–300 kcmil Al/Cu
#4 AWG–250 kcmil Al/Cu 1
Bottom tenant circuit breaker position has wire bending space to accommodate 300 kcmil wire, for bottom feed only.
225 A Maximum MP Meter-Pak Meter Center Tenant Circuit Breaker Termination Data
Tenant Circuit Breaker
Type and Ampere Rating
Lug Wire Size
Wire Bending Space
QBP-TM, QDP-TM, QGP-TM,
and QJP-TM,
2-pole, 70–225 A
#4 AWG–300 kcmil Al/Cu
#4 AWG–300 kcmil Al/Cu
16
© 2008 Schneider Electric All Rights Reserved
03/2008
MP Meter-Pak™ Meter Centers
Application Data
Service Grounding/Load Neutral and Equipment
Grounding Termination Data
•
Service grounding/load neutral lugs, located in the tenant compartment,
are bonded to the enclosure.
•
•
Two service grounding lugs provided per device.
One load neutral lug and one equipment grounding lug are provided for
each tenant circuit breaker position.
125 A Maximum MP, MPH, and MPR Meter-Pak Meter Centers
Load neutral and service grounding lugs will accept one #14-2/0 AWG Cu or
one #12-2/0 AWG Al conductor.
Equipment Grounding Lugs
200 A Maximum MP, MPH, and MPR Meter-Pak Meter Centers
Service Grounds and
Load Neutrals
Load neutral and service grounding lugs will accept one #6 AWG–300 kcmil
Al/Cu conductor.
225 A Maximum MP, MPH, and MPR Meter-Pak Meter Centers
Load neutral and service grounding lugs will accept one #4 AWG–300 kcmil
Al/Cu conductor.
Hinged Rain Channel
Rain channel is hinged at bottom of tenant compartment allowing easy
access to wiring gutter for pulling wires.
Underground Service Wireway
Square D brand Underground Service Wireways are a convenient solution
for protecting a utility's underground service conductors that terminate in MP
Meter-Pak Meter Centers.
Hinged Rain Channel
MP43X11PED Shown
with Cover Off (left) and
On (above)
These Underground Service Wireways are not load-bearing; they are
intended for use only as a means to cover and secure service entrance
cables prior to entering a wall-mounted Square D MP Meter-Pak device.
The units connect easily to any MP Meter-Pak Meter Center by attaching to
tapped hub provisions in the bottom endwall of the metering device.
•
•
Cover latch accommodates up to three different types of utility seals.
•
Mounts easily to MP Meter-Pak device’s underground, bolt-on hub
provisions using supplied hardware.
•
Open bottom with ½ inch srolled edge reduces possibility of cutting
conductor insulation.
•
•
Wireway covers are secured by latching means (no screws to lose).
•
Constructed of 14-gauge painted galvanneal steel for superior corrosion
protection in all applications.
All locking provisions are made of durable, corrosion-resistant stainless
steel for long-lasting security.
Gasketed, bushed openings in top provide watertight seal between the
wireway and MP Meter-Pak device.
17
03/2008
© 2008 Schneider Electric All Rights Reserved
MP Meter-Pak™ Meter Centers
Application Data
Underground Service Wireway Devices
Height
Catalog Number
Width
Description
in.
mm
in.
mm
279
MP43X11PED
Underground Service Wireway
43
1092
11
MP43X8PED
Underground Service Wireway
43
1092
8
203
MP35X11PED
Underground Service Wireway
35
889
11
279
MP12X11PEDEXT
Underground Service Wireway
One-foot Extension
12
305
11
279
MP12X8PEDEXT
Underground Service Wireway
One-foot Extension
12
305
8
203
Selection Chart
Grade to Meter
Wireway
Catalog
Number
Grade to
Device
Bottom
Bottom
Meter
Top Meter
in.
mm
in.
mm
42.5
1080
51.5
1308
MP
Meter-Pak
Device
MP22125
MP43X8PED
25 in.
[635 mm]
MPR22125
MPH22125
MP33125
54.0
1372
MPH33125
MP44125
63.0
36.0
1600
Top
Meter
Height
MPR33125
MPR44125
MP
Meter-Pak
Unit
Bottom
of
Device
MPH44125
914
MP55125
MPR55125
54.0
1372
MPH55125
Bottom
Meter
Height
Wireway
Unit
Grade
MP66125
MPR66125
18 in.
MPH66125
MP42200
MP43X11PED
25 in.
[635 mm]
46.25
1175
MPR42200
MPH42200
MP43200
55.25
1403
MPR43200
Wireway
Extension
12 in.
Measurement
Guide
MPH43200
MP64200
37.25
946
64.25
1632
MPR64200
MPH64200
MP85200
MPR85200
55.25
1403
MPH85200
MP86200
Underground Service Wireway
One-Foot Extension Selection Guide*
For applications requiring additional depth, or for sloped grades,
the one-foot extension can be installed to the bottom of the
underground service wireway with supplied hardware.
MPR86200
MPH86200
16.625 in.
50.625
MP35X11PED
[422 mm]
1286
64.625
1642
MPL32225
MP43X11PED
25 in.
[635 mm]
38.375
975
66.375
1686
MPL43225
MP35X11PED
16.625 in.
[422 mm]
30.0
762
72.0
1829
MPL64225
Wireway Extension
Catalog Number
Wireway Catalog Number
MP12X11PEDEXT
MP43X11PED
MP35X11PED
MP12X8PEDEXT
MP43X8PED
*Selection based on Underground Service Wireway catalog numbers.
18
© 2008 Schneider Electric All Rights Reserved
03/2008
MP Meter-Pak™ Meter Centers
Catalog Number Description
Catalog Number Description
Number
Segment
Device Name
Socket/Bypass
Type
Character
Description
MP
MP
Meter-Pak Meter Center
Blank
Ring Type
R
Ringless with 5th Jaw
H
Ringless with Horn Bypass and 5th
Jaw
L
Ringless with Lever Bypass, Jaw
Release and 5th Jaw
2
200 A
3
300 A
4
400 A
5
500 A
6
600 A
8
800 A
2
2-Positions MP, MPH, MPL, and MPR
3
3-Positions MP, MPH, MPL, and MPR
4
4-Positions MP, MPH, MPL, and MPR
5
5-Positions MP, MPH, and MPR
6
6-Positions MP, MPH, MPL, and MPR
125
125 A
200
200 A
225
225 A
H
4
4
125
Bus Ampacity
Number of
Meter Sockets
Max. Tenant
Circuit Breaker
Amperage
19
03/2008
© 2008 Schneider Electric All Rights Reserved
MP Meter-Pak™ Meter Centers
Select MP Meter-Pak meter center short circuit current rating RMS symmetrical amperes from table on page 3,
then make selections from the following:
Step 1:
Select Ring or
Ringless Type MP
Meter-Pak™
Meter Centers
Metering Equipment
Number of
Positions
Ampere Rating
125 A
(Use QO® Circuit
Breakers)
200 A
(Use QOM2
Circuit Breakers)
225 A
(Use QB, QD, QG or QJ
Circuit Breakers)
1
Ringless Type, 5-Jaw
Ring-Type, 4-Jaw
Catalog Number
No Bypass
Catalog Number
Horn Bypass
Catalog
Number
Lever Bypass
Catalog
Number
2
MP22125
MPR22125
MPH22125
—
3
MP33125 1
MPR33125
MPH33125
—
4
MP44125 1
MPR44125
MPH44125
—
5
MP55125 1
MPR55125
MPH55125
—
6
MP66125 1
MPR66125
MPH66125
—
2
MP42200 1
MPR42200
MPH42200
—
3
MP43200 1
MPR43200
MPH43200
—
4
MP64200 1
MPR64200
MPH64200
—
5
MP85200 1
MPR85200
MPH85200
—
6
MP86200 1
MPR86200
MPH86200
—
2
—
—
—
MPL32225
3
—
—
—
MPL53225
4
—
—
—
MPL64225
Meets EUSERC standards with addition of lug landing kit, MMSK2.
Step 2:
Select Tenant
Circuit Breakers
Device
Type
125 A
200 A
225 A
Ampere
Rating
10,000 AIR
120/240 Vac
22,000 AIR
120/240 Vac
25,000 AIR
120/240 Vac
42,000 AIR
120/240 Vac
65,000 AIR
120/240 Vac
100,000 AIR
120/240 Vac
40
QO240
QO240VH
—
QOH240
—
—
50
QO250
QO250VH
—
QOH250
—
—
60
QO260
QO260VH
—
QOH260
—
—
70
QO270
QO270VH
—
QOH270
—
—
80
QO280
QO280VH
—
QOH280
—
—
90
QO290
QO290VH
—
QOH290
—
—
100
QO2100
QO2100VH
—
QOH2100
—
—
125
QO2125
QO2125VH
—
QOH2125
—
—
100
QOM2100MM
QOM2100MVH
—
—
—
—
125
QOM2125MM
QOM2125MVH
—
—
—
—
150
QOM2150MM
QOM2150MVH
—
—
—
—
175
QOM2175MM
QOM2175MVH
—
—
—
—
200
QOM2200MM
QOM2200MVH
—
—
—
—
40
QO240 2
QO240VH 2
—
QOH240 2
—
—
50
QO250 2
QO250VH 2
—
QOH250 3
—
—
60
2
2
—
QOH260 3
—
—
QO260
QO260VH
70
QBP22070TM
—
QDP22070TM
—
QGP22070TM
QJP22070TM
80
QBP22080TM
—
QDP22080TM
—
QGP22080TM
QJP22080TM
90
QBP22090TM
—
QDP22090TM
—
QGP22090TM
QJP22090TM
100
QBP22100TM
—
QDP22100TM
—
QGP22100TM
QJP22100TM
110
QBP22110TM
—
QDP22110TM
—
QGP22110TM
QJP22110TM
125
QBP22125TM
—
QDP22125TM
—
QGP22125TM
QJP22125TM
150
QBP22150TM
—
QDP22150TM
—
QGP22150TM
QJP22150TM
175
QBP22175TM
—
QDP22175TM
—
QGP22175TM
QJP22175TM
200
QBP22200TM
—
QDP22200TM
—
QGP22200TM
QJP22200TM
225
QBP22225TM
—
QDP22225TM
—
QGP22225TM
QJP22225TM
2
Requires use of EZM125QOA adapter (order separately).
3
Order only. Not stocked in PDS.
20
© 2008 Schneider Electric All Rights Reserved
03/2008
MP Meter-Pak™ Meter Centers
Product Selection
Step 3: Choose
Accessories
Accessories—Description
and / or
Replacement Parts
Catalog
Number
5th Jaw Kit (one per kit)
5J
Barrel Lock Head Protector Kit (use on MPH, MPL and MPR only; barrel lock not included)
MMBLC
QO Adapter for Bolt-on QB, QD, QG and QJ Tenant Circuit Breakers (40–125 A, 2-pole)
EZM125QOA
Horn Bypass Kit (use on MPR and MPH only)
MMHB
Manual Slider Type Bypass:
125 A Ring Type 2-Position Top Meter (only)
MM125MB 1
125 A and 200 A Ring Type
MM200MB 1
Sealing Rings:
Snap-type Aluminum (standard)
29209-100-01
Screw-type Aluminum
29008W
Snap-type Stainless Steel
ARP00026
LEXAN® Meter Socket Closing Plate
29007
Optional Lug Kits (3 Lugs per kit):
(1) 1/0-600 AWG/kcmil or (2) 1/0-250 per phase Al/Cu
MMLK250 2 3
(2) 3/0-500 AWG/kcmil per phase Al/Cu
MMLK500 3
(2) 2-600 AWG/kcmil per phase Al/Cu
MMLK600 3
Semi-flush Kits:
125 A, 2-Position
MPSF12
125 A, 3- and 4-Position
MPSF14
125 A, 5- and 6-Position
MPSF16
200 A, 2- and 3-Position
MPSF23
200 A, 4-Position
MPSF24
200 A, 5- and 6-Position
MPSF26
NEMA/EUSERC Lug Landing Kit:
For 3- through 6-position 125 A and all 200 A devices.
Each pad rated 600 A maximum and includes (2) 1/2-13 studs and mounting hardware.
MMSK2 3
NEMA Lug Landing Kit:
For use ONLY on MPL32225, MPL53225 and MPL64225 with optional lugs (see Table on page 16 for lugs)
MMSK4
1
The meter center short circuit current rating is 10,000 RMS symmetrical amperes when manual slider-type bypass is used. Not rated for continuous duty.
2
Standard lug for 3- through 6-position 125 A and 2- through 4-position 200 A devices.
3
Cannot be installed on 2-position 125 A devices.
21
03/2008
© 2008 Schneider Electric All Rights Reserved
MP Meter-Pak™ Meter Centers
Dimensions
Supplied with ACP Closing Plate
(for Underground Service).
Order Type A Hub Separately
(for Overhead Service).
1.97
[50]
3.67
[93]
7.10
[180]
0.19
[5]
12.28
[312]
9.37
[238]
1.38
[35]
2.56
[65]
Embossed Mounting Holes
(4 Locations)
0.25 Dia.
[6]
From Top to Center
of Embossed
Mounting Holes
2.56
[65]
0.42 Dia.
[11]
0.09 Dia.
[2]
37.50
[953]
24.31
[617]
0.09 0.33 Slot
[2] x [8]
24.31
[617]
9.00
[229]
Ringless Cover Latch
Line
Phase
Lugs 18.50
C, D, F
[470]
11.25
[286]
C, D, F
8.62
[219]
6.97
[177]
3.77
[96]
4.70
[119]
2.32
[60]
Line
Neutral
Lug
6.97
[177]
1.75
[44]
3.77
[96]
0.10 0.40 Slot
0.10 Dia.
x
[3]
[10]
[3]
0.42 Dia.
[11]
Seal Bracket
12.13
[308]
1.79
[45]
C, D, F
1.75
[44]
4.70
[119]
3.08
[78]
A or B300
Hub Provision
D, F, G
A
0.95
[24]
0.38 Dia.
[10]
1.73
[44]
0.83
[21]
8.14
[207]
2.09
[53]
Mounting Feet
MP22125
MPR22125
MPH22125
Dimensions:
Knockouts
Conduit Size
Hole Diameter
Symbol
in.
mm
in.
mm
A
0.50
13
0.88
22
B
0.75
19
1.25
32
C
1.00
25
1.38
35
D
1.25
32
1.75
44
E
1.50
38
2.00
51
F
2.00
51
2.50
64
G
2.50
64
3.00
76
H
3.00
76
3.63
92
I
3.50
89
4.13
105
J
4.00
102
4.63
118
22
© 2008 Schneider Electric All Rights Reserved
03/2008
in.
[mm]
MP Meter-Pak™ Meter Centers
Product Selection
Supplied with ACPL Closing Plate
(for Underground Service).
Order Type A–L Hub Separately
(for Overhead Service).
6.07
[154]
2.76
[70]
24.34
[618]
4.87
[124]
7.28
[185]
(NTS)
12.00
[305]
Top Position Omitted
on 3-Position Unit
0.09 Dia.
[2]
Line
Phase
Lugs
3.44
[87]
Typical Cover
Lifting
Handles
48.12
[1222]
0.75
[19]
5.58
[142]
13.50
[343]
6.85
[174]
10.05
[255]
1.75
[44]
47.37
[1203]
0.95
[24]
24.19
[614]
A–L Hub Provision
E, F, G, H, I, J
A–L Hub Provision
E, F, G, H
A, B
3.20
[81]
1.78
[45]
0.10 0.40 Slot
0.10 Dia.
x
[10]
[3]
[3]
0.42 Dia.
[11]
Seal Bracket
6.53
[166]
5.25
[133]
C, D, F A, B
1.80
[46]
4.75
[121]
0.09 0.33 Slot
[2] x [8]
Ringless Cover Latch
9.00
[229]
Typical
23.62
2.84
[600]
[72] 11.19
[284]
C, D, F
2.29
[58]
0.42 Dia.
[11]
9.00
[229]
1.73
[44]
0.38 Dia.
[10]
Mounting Feet
3.00
[76]
MP33125 MP44125
MPR33125 MPR44125
MPH33125 MPH44125
Dimensions:
Knockouts
Conduit Size
Hole Diameter
Symbol
in.
mm
in.
mm
A
0.50
13
0.88
22
B
0.75
19
1.25
32
C
1.00
25
1.38
35
D
1.25
32
1.75
44
E
1.50
38
2.00
51
F
2.00
51
2.50
64
G
2.50
64
3.00
76
H
3.00
76
3.63
92
I
3.50
89
4.13
105
J
4.00
102
4.63
118
23
03/2008
© 2008 Schneider Electric All Rights Reserved
in.
[mm]
MP Meter-Pak™ Meter Centers
Product Selection
Supplied with ACPL Closing
Plate (for Underground Service).
Order Type A Hub Separately
(for Overhead Service).
15.23
[387]
6.00
[152]
2.76
[70]
39.46
[926]
12.00
[305]
4.70
[119]
7.28
[185]
(NTS)
7.36
[187]
Line
Phase
Lugs
Top Position
Omitted on
5-Position Unit
0.75
[19]
N
3.44
[87]
Typical
C, D, F
5.85
[149]
7.75
[197]
9.05
[230]
A, B
2.61
[66]
6.22
[158]
20.75
[527]
3.20
[81]
18.02
[458]
A
0.09 Dia.
[2]
0.09 0.33 Slot
[2] x [8]
Ringless Cover Latch
6.53
[166]
0.10 Dia.
[3]
0.42 Dia.
[11]
A-L Hub Provision
G, H, I, J
15.07
[383]
3.00
[76]
2.99
[76]
3.20
[81]
0.10 0.40 Slot
x
[3]
[10]
Seal Bracket
0.95
1.73 [24]
[44]
0.38 Dia.
[10]
Mounting Feet
MP55125
MPR55125
MPH55125
MP66125
MPR66125
MPH66125
Knockouts
Conduit Size
3.02
[77]
9.42
[239]
36.31
[922]
14.92
[379]
C, D, F
1.75
[44]
41.62
[1057]
9.00
[229]
Typical
23.62
[600]
11.19
[284]
Cover
Lifting
Handles
2.95
[75]
2.65
[67]
0.42 Dia.
[11]
42.37
[1076]
Dimensions:
Hole Diameter
Symbol
in.
mm
in.
mm
A
0.50
13
0.88
22
B
0.75
19
1.25
32
C
1.00
25
1.38
35
D
1.25
32
1.75
44
E
1.50
38
2.00
51
F
2.00
51
2.50
64
G
2.50
64
3.00
76
H
3.00
76
3.63
92
I
3.50
89
4.13
105
J
4.00
102
4.63
118
24
© 2008 Schneider Electric All Rights Reserved
03/2008
in.
[mm]
MP Meter-Pak™ Meter Centers
Product Selection
Supplied with ACPL Closing
Plate (for Underground Service).
Order Type A Hub Separately
(for Overhead Service).
9.70
[246]
3.70
[94]
2.58
[66]
29.44
[748]
Top Position
Omitted on
2-Position Unit
0.42 Dia.
[11]
8.28
[210]
(NTS)
7.25
[184]
0.09 Dia.
[2]
Line
Phase
Lugs
Ringless Cover Latch
43.41
[1103]
Line
Neutral
Lugs
C, D, F
2.25
[57]
2.70
[69]
C, D, F
12.15
[309]
42.66
[1084]
31.50
9.00
[800]
[229]
28.00
Typical
[711]
24.62
[625]
12.22
[310]
8.38
[213]
12.55
[319]
6.10
[155]
0.09 0.33 Slot
[2] x [8]
0.75
[19]
7.53
[191]
0.10 Dia.
[3]
0.42 Dia.
[11]
0.10 0.40 Slot
x
[3]
[10]
Seal Bracket
29.31
[744]
A, B
10.41
[264]
1.94
[49]
A-L Hub Provision
G, H, I, J
0.38 Dia.
[10]
0.95
1.73 [24]
[44]
Mounting Feet
2.66
[68]
3.33
[85]
(Typ.)
3.00
[76]
3.04
[77]
9.20
[234]
15.48
[393]
MP42200
MPR42200
MPH42200
MP43200
MPR43200
MPH43200
in.
Dimensions: [mm]
Knockouts
Conduit Size
Hole Diameter
Symbol
in.
mm
in.
mm
A
0.50
13
0.88
22
B
0.75
19
1.25
32
C
1.00
25
1.38
35
D
1.25
32
1.75
44
E
1.50
38
2.00
51
F
2.00
51
2.50
64
G
2.50
64
3.00
76
H
3.00
76
3.63
92
I
3.50
89
4.13
105
J
4.00
102
4.63
118
25
03/2008
© 2008 Schneider Electric All Rights Reserved
MP Meter-Pak™ Meter Centers
Product Selection
Supplied with ACPL Closing
Plate (for Underground Service).
Order Type A-L Hub Separately
(for Overhead Service).
9.70
[246]
3.70
[94]
2.58
[66]
9.82
[249]
29.44
[748]
0.42 Dia.
[11]
8.25
[210]
(NTS)
7.36
[187]
0.09 Dia.
[2]
0.75
[19]
Line
Phase
Lugs
0.09 0.33 Slot
[2] x [8]
Ringless Cover Latch
52.00
[1321]
51.25
[1302]
Line
Neutral
Lugs
C, D, F
2.23
[57]
5.65
[144]
2.45
[62]
C, D, F
1.94
[49]
2.66
[68]
5.85
[149]
12.15
[309]
12.55
[319]
31.50
[800]
9.00
[229] 28.00
[711]
Typ.
24.62
[625]
12.22
[310] 7.53
[191]
0.10 Dia.
[3]
0.42 Dia.
[11]
0.10 0.40 Slot
x
[3]
[10]
Seal Bracket
8.38
[213]
0.95
[24]
29.31
[744]
10.37
[263]
A, B
3.00
[76]
9.20
[234]
3.33
[85]
(Typ.)
15.48
[393]
A-L Hub
Provision
G, H, I, J
1.73
[44]
3.04
[77]
0.38 Dia.
[10]
Mounting Feet
MP64200
MPR64200
MPH64200
Knockouts
Conduit Size
in.
Dimensions: [mm]
Hole Diameter
Symbol
in.
mm
in.
mm
A
0.50
13
0.88
22
B
0.75
19
1.25
32
C
1.00
25
1.38
35
D
1.25
32
1.75
44
E
1.50
38
2.00
51
F
2.00
51
2.50
64
G
2.50
64
3.00
76
H
3.00
76
3.63
92
I
3.50
89
4.13
105
J
4.00
102
4.63
118
26
© 2008 Schneider Electric All Rights Reserved
03/2008
MP Meter-Pak™ Meter Centers
Product Selection
Supplied with ACPL Closing
Plate (for Underground
Service). Order Type A-L
Hub Separately (for
Overhead Service).
9.82
[249]
Top Left
Position
Omitted on
5-Position
Unit
7.36
[187]
26.34
[669]20.34
[517]
0.42 Dia.
[11]
2.58
[66]
46.68
[1186]
12.00
[305]
8.28
[210]
(NTS)
9.82
[249]
Line
Phase
Lugs
0.75
[19]
43.41
[1321]
31.50
9.00
[800]
[229]
28.25
Typ.
[718]
24.50
[622]
12.22
[310]
Line
Neutral
Lugs
C, D, F
2.23
[57]
6.35
[161]
8.60
[218]
12.15
[309]
2.95
[75]
Seal Bracket
0.95
[24]
A-L Hub Provision
G, H, I, J
3.04
A, B, C
0.10 0.40 Slot
x
[3]
[10]
0.10 Dia.
[3]
0.42 Dia.
[11]
14.20
[361]
46.56
[1183]
1.93
[49]
0.09 0.33 Slot
[2] x [8]
Ringless Cover Latch
42.66
[1084]
7.53
[191]
5.00
[127]
10.81
[275]
29.25
[743]
C, D, F
0.09 Dia.
[2]
0.38 Dia.
[10]
1.73
[44]
[77]
Mounting Feet
2.66
[68] 20.12
[511]
6.20
[68]
3.33
[85]
(Typ.)
MP85200
MPR85200
MPH85200
4.53
[115]
MP86200
MPR86200
MPH86200
in.
Dimensions: [mm]
Knockouts
Conduit Size
Hole Diameter
Symbol
in.
mm
in.
mm
A
0.50
13
0.88
22
B
0.75
19
1.25
32
C
1.00
25
1.38
35
D
1.25
32
1.75
44
E
1.50
38
2.00
51
F
2.00
51
2.50
64
G
2.50
64
3.00
76
H
3.00
76
3.63
92
I
3.50
89
4.13
105
J
4.00
102
4.63
118
27
03/2008
© 2008 Schneider Electric All Rights Reserved
MP Meter-Pak™ Meter Centers
Product Selection
Supplied with ACPL Closing
Plate (for Underground Service).
Order Type A-L Hub Separately
(for Overhead Service).
9.62
[244]
(NTS)
8.36
[212]
2.62
[67]
1.50
[38]
2.81
[71]
19.43
[494]
Tenant Circuit Breaker
Doors (Lockable)
60.25
[1530]
Cover Knockout for use
with Utility Barrel Lock
0.75
[19]
To Top of
Mounting Channel
Mounting Channel Detail
1.75
[44]
14.00
[356]
Individual Meter Socket Covers;
Ringless Style (Supplied with
Cover Sealing Latches)
5.72
[145]
21.87
[556]
7.10
[180]
C, D, E, F
4.50
[114]
Line
Phase
Lugs
Line
Neutral
Lugs
4.43
[113]
10.47
[266]
2.20
[56]
4.12
[105]
1.89
[48]
Lug Detail
26.76
[680]
3.25
[83]
5.34
[138]
(2) 1/2–13
Studs
1.75
[44]
34.00
[864]
C, D, E, F
0.34
[9]
A, B
0.09 Dia.
[2]
0.09 0.33 Slot
[2] x [8]
Ringless Cover Latch
3.00
[76]
8.87
[225]
1.87
[48]
5.37
[136]
0.42 Dia.
[11]
2.68
[68]
5.93
[151]
A-L Hub Provision
E, F, G, H, I, J
0.13 Dia.
[3]
0.44 Dia.
[11]
0.10 0.50 Slot
x
[3]
[13]
Seal Bracket
9.00
[229]
MPL32225
0.95
1.73 [24]
[44]
0.38 Dia.
[10]
Mounting Foot
Knockouts
Conduit Size
Hole Diameter
Symbol
in.
mm
in.
mm
A
0.50
13
0.88
22
B
0.75
19
1.25
32
C
1.00
25
1.38
35
D
1.25
32
1.75
44
E
1.50
38
2.00
51
F
2.00
51
2.50
64
G
2.50
64
3.00
76
H
3.00
76
3.63
92
I
3.50
89
4.13
105
J
4.00
102
4.63
118
in.
Dimensions: [mm]
28
© 2008 Schneider Electric All Rights Reserved
03/2008
MP Meter-Pak™ Meter Centers
Product Selection
Supplied with ACPL Closing
Plate (for Underground Service).
Order Type A-L Hub Separately
(for Overhead Service).
11.30
[287]
9.68
[246]
2.75
[70]
0.34
[9]
4.80
[122]
35.37
[898]
10.87
[276]
Tenant Circuit Breaker
Doors (Lockable)
1.50
[38]
Line
Phase
Lugs
Cover Knockout for use
with Utility Barrel Lock
Line
Neutral
Lugs
Individual Meter Socket Covers:
Ringless Style (Supplied with
Cover Sealing Latches}
14.00
[356]
6.32
[161]
24.10
[612]
17.62
[448]
13.32
[338]
2.53
[84]
10.10
[257]
13.90
[353]
26.40
[671]
A-L Hub Provision
E, F, G, H, I, J
0.09 Dia.
[2]
0.09 0.33 Slot
[2] x [8]
Ringless Cover Latch
0.10 0.50 Slot
x
[3]
[13]
Seal Bracket
3.11
[79]
A, B
2.07
[53] 5.86
[149]
0.42 Dia.
[11]
0.13 Dia.
[3]
0.44 Dia.
[11]
35.25
[895]
2.11
[54]
To Top of
Mounting Channel
Mounting Channel Detail
4.50
[114]
C, D, E, F
6.00
[152]
53.12
[1349]
28.10
[714]
C, D, E, F
3.20
[81]
0.75
[19]
0.95
[24]
10.25
[260]
9.65
[245]
13.44
[341]
2.84
[72]
4.05
[103]
0.38 Dia.
[10]
1.73
[44]
Mounting Foot
MPL53225
Knockouts
Conduit Size
Dimensions:
in.
[mm]
Hole Diameter
Symbol
in.
mm
in.
mm
A
0.50
13
0.88
22
B
0.75
19
1.25
32
C
1.00
25
1.38
35
D
1.25
32
1.75
44
E
1.50
38
2.00
51
F
2.00
51
2.50
64
G
2.50
64
3.00
76
H
3.00
76
3.63
92
I
3.50
89
4.13
105
J
4.00
102
4.63
118
29
03/2008
© 2008 Schneider Electric All Rights Reserved
MP Meter-Pak™ Meter Centers
Product Selection
Supplied with ACPL Closing
Plate (for Underground Service).
Order Type A-L Hub Separately
(for Overhead Service)
11.30
[287]
2.75
[70]
9.68
[246]
(NTS)
4.80
[122]
0.34
[9]
35.37
[898]
Line
Phase
Lugs
Line
Neutral
Lugs
Tenant Circuit Breaker
Doors (Lockable)
Cover Knockout for use
with Utility Barrel Lock
1.50
[38]
41.87
[1064]
7.00
[178]
14.00
[356]
2.53
[64]
3.20
[81]
6.32
[161]
38.50
[978]
31.62
[803]
13.32
[338]
0.42 Dia.
[11]
0.09 Dia.
[2]
0.09 0.33 Slot
[2] x [8]
Ringless Cover Latch
0.13
Dia.
[3]
10.10
[257]
C, D, E, F
6.00
[152]
To Top of
Mounting Channel
Mounting Channel Detail
Individual Meter Socket Covers;
Ringless Style (Supplied with
Cover Sealing Latches)
C, D, E, F
0.75
[19]
67.37
[1711]
26.40
[671]
4.50
[114]
13.90
[353]
A–L Hub Provision
E, F, G, H, I, J
35.25
[895]
A, B
2.11
[54]
3.11
[79]
0.44
Dia.
[11]
Seal Bracket
0.95
[24]
2.07
[53]
5.86
9.65 [149]
[245]
13.44
[341]
2.84
[72]
MPL64225
0.38
Dia.
[10]
1.73
[44]
Mounting Foot
Dimensions:
Knockouts
Conduit Size
10.25
[260]
4.05
[103]
0.10 0.50 Slot
x
[3]
[13]
in.
[mm]
Hole Diameter
Symbol
in.
mm
in.
mm
A
0.50
13
0.88
22
B
0.75
19
1.25
32
C
1.00
25
1.38
35
D
1.25
32
1.75
44
E
1.50
38
2.00
51
F
2.00
51
2.50
64
G
2.50
64
3.00
76
H
3.00
76
3.63
92
I
3.50
89
4.13
105
J
4.00
102
4.63
118
30
© 2008 Schneider Electric All Rights Reserved
03/2008
MP Meter-Pak™ Meter Centers
Product Selection
125 A Devices
Omitted on 3-Position Unit
Fifth Jaw
Factory Installed
on Ringless Device
Omitted on 5-Position Unit
ø
ø ø
øø
ø ø
øø
ø
ø
N
Line
øø
ø
ø ø
ø ø
N
ø
Neutral,
Service Ground
and Equipment
Grounding Terminals
ø
Line
Fifth Jaw
Factory Installed
on Ringless Device
N
MP22125
MPR22125
MPH22125
øø
Fifth Jaw
Factory Installed
on Ringless Device
øø
øø
Equipment
Grounding
Terminals
øø
Neutral and
Service Ground
Equipment
Grounding
Terminals
Neutral and
Service Ground
MP33125
MPR33125
MPH33125
MP66125
MPR66125
MPH66125
MP55125
MPR55125
MPH55125
MP44125
MPR44125
MPH44125
Omitted on 5-Position Unit
200 A Devices
ø
Omitted on 2-Position Unit
ø
ø
ø
ø
ø
ø
ø
ø
ø
ø
N
Line
ø
ø
N
ø
ø
ø
ø
ø
Line
ø
ø
ø
ø
Fifth Jaw
Factory Installed
N on Ringless Device
Line
Fifth Jaw
Factory Installed
on Ringless Device
ø
ø
ø
ø
ø
ø
Fifth Jaw
Factory Installed
on Ringless Device
ø
ø
Equipment
Grounding
Terminals
Neutral and
Service Ground
MP42200
MPR42200
MPH42200
MP43200
MPR43200
MPH43200
Equipment
Grounding
Terminals
ø
ø
Neutral and
Service Ground
MP85200
MPR85200
MPH85200
Equipment
Grounding
Terminals
Neutral and
Service Ground
MP64200
MPR64200
MPH64200
MP86200
MPR86200
MPH86200
øø
225 A Devices
øø
øø
øø
Line
ø
ø
øø
øø
Line
ø
ø
øø
ø ø
Line
Neutral and Service
Grounding Terminals
Equipment Grounding
Terminals
MPL32225
øø
Equipment Grounding
Terminals
Neutral and Service
Grounding Terminals
MPL53225
øø
Equipment Grounding
Terminals
Neutral and Service
Grounding Terminals
MPL64225
31
03/2008
© 2008 Schneider Electric All Rights Reserved
Schneider Electric USA
Schneider Electric Canada
1601 Mercer Road
Lexington, KY 40511 USA
1-888-SquareD
(1-888-778-2733)
www.us.SquareD.com
19 Waterman Avenue,
M4B 1 Y2
Toronto, Ontario
1-800-565-6699
www.schneider-electric.ca
Square D, [D], Meter-Pak, and QO are trademarks or registered trademarks of
Schneider Electric and/or its affiliates in the United States and/or other countries.
Other marks used herein may be the property of their respective owners.
4141CT0701 © 2008 Schneider Electric All Rights Reserved
03/2008