62-0387—03 - TB-WALL 10K NTC Type II Wall

TB-WALL 10K Ohm NTC Type II
Wall Temperature Sensors
INSTALLATION INSTRUCTIONS
PRODUCT OVERVIEW
Honeywell 10K ohm NTC Type II remote wall sensors are
for use with the TB7200, TB7300, and TB7600 Series
communicating thermostats and other devices requiring
a 10K ohm NTC Type II sensor. These robust sensors
provide accurate and stable temperature readings using
a 10K ohm NTC thermistor element.
These wall sensors can also be used for temperature
averaging applications.Two or three TB wall sensors can
be used and are quickly configured with the onboard dip
switches. Temperature averaging with the usual 4, 9, 16,
25, etc. sensors can also be done with the TB wall
sensors. See table below for specific model numbers:
Table 1. TB Sensor Models.
Model
TB-WALL-1014
Description
Room sensor
Application
• Remote room sensing
• 3 thermistors with 2 dip switches are provided with each sensor
for various averaging combinations
TB-WALLOVR-1014 Room sensor with
• Remote room sensing with override key and occupancy LED
temporary override key and • 3 thermistors with 2 dip switches are provided with each sensor
occupancy LED
for various averaging combinations
Contents
Product Overview .............................................................
Wall Sensor Installation ....................................................
Sensor Wiring ...................................................................
1
2
2
62-0387-03
TB-WALL 10K OHM NTC TYPE II WALL TEMPERATURE SENSORS
WALL SENSOR
INSTALLATION
Location
•
•
•
•
•
Should not be installed on an outside wall.
Must be installed away from any heat source.
Should not be installed near an air discharge grill.
Should not be affected by direct sun radiation.
Nothing must restrain vertical air circulation to the
sensor.
PCB
RETAINING
TABS
To install the wall sensor:
1.
2.
Remove security screw on the bottom of sensor
cover.
Open up by pulling on the bottom side of sensor
(see Fig. 1).
PCB
RETAINING
TABS
M21301
Fig. 2. Mounting the sensor.
Sensor Dimensions
5
(125)
M32834
3-2/5 (86)
Fig. 1. Remove sensor cover.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
Pull cables 6” out of the wall.
Insert cable in the central hole of the base.
Flip printed circuit board to access mounting hole
Align the base and mark the location of the two
mounting holes on the wall. Install proper side of
base up.
Install anchors in the wall.
Insert screws in mounting holes on each side of the
base. Do not over tighten.
Strip each wire 1/4 inch.
Insert each wire according to wiring diagram.
Gently push excess wiring back into the wall.
Press printed circuit board back into place
Install the cover, top side first.
Install security screw.
1-3/20 (29)
M16984
Fig. 3. Dimensions in in (mm).
SENSOR WIRING
This section provides wiring examples with the TB wall
sensors and the TB7600, TB7300, and TB7200 Series
Communicating Thermostats.
See Fig. 5-10 for typical sensor wiring and DIP switch
settings. See Fig. 4 for the location of the DIP switches on
the TB sensors.
ON
1
2
M32839
Fig. 4. Dip switch location.
62-0387—03
2
TB-WALL 10K OHM NTC TYPE II WALL TEMPERATURE SENSORS
TB7600 Wiring
REMOTE WIRING 1 SENSOR
TB7600 SERIES
THERMOSTAT
TB7600 SERIES
THERMOSTAT
TB-WALLOVR-1014
Scom
Scom
RS
RS
RS
AU
AUX
AU
C
C
C
Scom
RS
DIP SWITCHES
S1 = ON S2 = ON
DI
D1
D1
DIP SWITCHES
S1 = ON S2 = ON
1
D2
TB-WALL-1014
Scom
D2
1 EITHER D1 OR D2 CAN BE USED ON THE TB7600 FOR CONNECTION FROM THE DI ON THE WALL MODULE WITH OVERRIDE.
M32836
Fig. 5. Wiring example of single remote room sensor.
REMOTE WIRING 2 SENSORS 1
TB7600 SERIES
THERMOSTAT
TB-WALLOVR-1014
TB-WALL-1014
Scom
TB7600 SERIES
THERMOSTAT
TB-WALLOVR-1014
TB7600 SERIES
THERMOSTAT
TB-WALLOVR-1014
Scom
Scom
RS
RS
RS
RS
AU
DIP SWITCHES
S1 = OFF
S2 = ON
AU
Scom
Scom
RS
RS
AUX
C
AUX
AUX
C
C
D1
C
C
D1
DI
D2
DI
DI
D2
2
DIP SWITCHES
S1 = OFF
S2 = ON
2
DIP SWITCHES
S1 = OFF
S2 = ON
RS
RS
AU
D1
TB-WALL-1014
Scom
Scom
RS
C
D2
TB-WALL-1014
Scom
Scom
DIP SWITCHES
S1 = OFF
S2 = ON
DIP SWITCHES
S1 = OFF
S2 = ON
DIP SWITCHES
S1 = OFF
S2 = ON
1
TB-WALL-1014 AND TB-WALLOVR-1014 CAN BE MIXED AND MATCHED
TB-WALL-1014 AND TB-WALLOVR-1014 ARE TO BE WIRED IN PARALLELL
ENSURE THE DIP SWITCH SETTING IS CORRECT IN EACH REMOTE SENSOR
2
EITHER D1 OR D2 CAN BE USED ON THE TB7600 FOR CONNECTION FROM THE DI ON THE WALL MODULE WITH OVERRIDE.
M32837
Fig. 6. Wiring examples with 2 remote room sensors for averaging applications.
REMOTE WIRING 3 SENSORS
TB7600 SERIES
TB-WALLOVR-1014 TB-WALL-1014 TB-WALL-1014
THERMOSTAT
Scom
Scom
Scom
Scom
RS
RS
RS
RS
AU
DIP SWITCHES
AUX
S1 = OFF
C
S2 = OFF
TB7600 SERIES
THERMOSTAT
Scom
1
D2
AU
C
D1
DI
D2
DIP SWITCHES
S1 = OFF
S2 = OFF
1
TB-WALLOVR-1014 TB-WALL-1014
Scom
Scom
RS
RS
AUX
AUX
Scom
RS
C
D1
TB-WALLOVR-1014
1
C
C
DI
DI
RS
DIP SWITCHES
S1 = OFF
S2 = OFF
DIP SWITCHES
S1 = OFF
S2 = OFF
EITHER D1 OR D2 CAN BE USED ON THE TB7600 FOR CONNECTION FROM THE DI ON THE WALL MODULE WITH OVERRIDE.
M32838
Fig. 7. Wiring examples of 3 remote room sensors for averaging applications.
3
62-0387—03
TB-WALL 10K OHM NTC TYPE II WALL TEMPERATURE SENSORS
TB7200 & TB7300 Wiring
NOTE: If LED indicator is desired at the TB-WALL-OVR-1014:
1.
2.
Set the Aux Cont installer parameter (which controls BO5) to option 2, Auxiliary NC.
Install a jumper across the BO5 terminal and 24 Vac Hot.
REMOTE WIRING 1 SENSOR
TB7300 SERIES
THERMOSTAT
TB7300 SERIES
THERMOSTAT
TB-WALLOVR-1014
Scom
RS
AUX
DIP SWITCHES
S1 = ON S2 = ON
24 VAC
COM
DI
BI 2
RS
BO 5
C
24 VAC
COM
Scom
RS
RS
BO 5
TB-WALL-1014
Scom
Scom
BI 2
DIP SWITCHES
S1 = ON S2 = ON
M32847
Fig. 8. Wiring example of single remote room sensor.
REMOTE WIRING 2 SENSORS 1
TB7300 SERIES
THERMOSTAT
TB-WALLOVR-1014
TB7300 SERIES
THERMOSTAT
TB-WALL-1014
Scom
Scom
Scom
RS
24 VAC
COM
RS
C
BI 2
TB-WALL-1014
Scom
Scom
RS
RS
24 VAC
COM
AUX
AUX
BI 2
C
C
DI
DI
DI
DIP SWITCHES
S1 = ON
S2 = OFF
1
TB7300 SERIES
THERMOSTAT
BO 5
24 VAC
COM
TB-WALL-1014
Scom
Scom
RS
BO 5
DIP SWITCHES
S1 = ON
S2 = OFF
AUX
TB-WALLOVR-1014
Scom
RS
RS
BO 5
TB-WALLOVR-1014
Scom
RS
RS
DIP SWITCHES
S1 = ON
S2 = OFF
DIP SWITCHES
S1 = ON
S2 = OFF
BI 2
DIP SWITCHES
S1 = ON
S2 = OFF
DIP SWITCHES
S1 = ON
S2 = OFF
TB-WALL-1014 AND TB-WALLOVR-1014 CAN BE MIXED AND MATCHED
TB-WALL-1014 AND TB-WALLOVR-1014 ARE TO BE WIRED IN PARALLELL
ENSURE THE DIP SWITCH SETTINGS ARE CORRECT IN EACH REMOTE SENSOR
M32848
Fig. 9. Wiring examples of 2 remote room sensors for averaging applications.
REMOTE WIRING 3 SENSORS
TB7300 SERIES
THERMOSTAT
TB-WALLOVR-1014
Scom
Scom
TB-WALL-1014 TB-WALL-1014
Scom
Scom
RS
RS
RS
BO 5
AUX
24 VAC
COM
C
BI 2
RS
DIP SWITCHES
S1 = OFF
S2 = OFF
TB7300 SERIES
THERMOSTAT
TB-WALL-1014
Scom
TB-WALL-1014
Scom
Scom
RS
RS
RS
BO 5
24 VAC
COM
TB-WALL-1014
Scom
RS
ALL DIP SWITCHES
S1 = OFF
S2 = OFF
BI 2
DI
DIP SWITCHES
S1 = OFF
S2 = OFF
1
TB-WALL-1014 AND TB-WALLOVR-1014 CAN BE MIXED AND MATCHED
TB-WALL-1014 AND TB-WALLOVR-1014 ARE TO BE WIRED IN PARALLELL
ENSURE THE DIP SWITCH SETTINGS ARE CORRECT IN EACH REMOTE SENSOR
Fig. 10. Wiring examples of 3 remote room sensors for averaging applications.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark
© 2011 Honeywell International Inc.
62-0387—03 M.S. Rev. 06-11
Printed in U.S.A.
M32849