ICC Educational Program Spring 2001. Tan Delta / Dissipation Factor As An Effective Tool In Determining The Insulation Condition Of Power Cables Using The BAUR PHG VLF System. Craig Goodwin, HV Diagnostics Inc. GA, USA e-mail: [email protected] ICC Educational Program Spring 2001. Summary of Presentation • Theory / Background • Description of Diagnostic Method/s • Field Examples ICC Educational Program Spring 2001. Benefits of Voltage Testing with VLF Sinusoidal Waveforms in the field. Low Power Requirement for on site testing. Compact portable design of test equipment. Easier diagnosis of water tree deteriorated insulation at low frequencies compared to higher frequencies such as 60Hz using TD. Easier to integrate Cable diagnostic interfaces such as TD and PD etc. ICC Educational Program Spring 2001. "WATER TREEING" in polymeric insulation (schematic layout) electrical field ● water ● disturbance field ● time ● conditions for possible development of "water trees" "bow-tie trees" outer semiconducting layer insulation inner semiconducting layer conductor "vented trees" ICC Educational Program Spring 2001. Vented- tree growing from the inner semicon layer of a 30 kV- PE- cable ICC Educational Program Spring 2001. Dielectric Failure of insulation originating from a water tree ICC Educational Program Spring 2001. What is Dissipation Factor ( tan δ) ?? voltage current 0 time/sec dissipation factor tan δ= true power U² / R 1 = = reactive power U².ωC ωC.R 10 ICC Educational Program Spring 2001. Simplified Dielectric Equivalent Circuit of a Water Tree wt R2 C1 C2 >> R1 ICC Educational Program Spring 2001. AC Pure Sinewave Output Voltage and Current. ICC Educational Program Spring 2001. Q&A Do I have a DF dependancy regarding the total length or the amount of joints in a cable? NO! ICC Educational Program Spring 2001. Voltage Dependence of 0,1 Hz Tan Delta on New and Service-aged XLPE-insulated Medium Voltage Cables. -3 T a nD e lta . (1 0 ) 0 .1 H z D i s s ip a ti o n F a c 10 9 8 7 6 5 4 3 2 1 0 0 0 .5 1 1 .5 2 2 .5 3 V /V 0 (A p p lie d V o lta g e ) G o o d c a b le S lig h tly s e r vic e -a g e d ( 1 ) M o d e r a te ly s e r vic e -a g e d (3 ) S tr o n g ly s e rv ic e - a g e d ( 4 ) M o d e r a te ly s e r vic e -a g e d (2 ) ICC Educational Program Spring 2001. Criteria For tan δ – for PE or XLPE Cables are still in good condition, if : tan δ (2 Uo) < 1,2 ‰ and [tan δ (2 Uo) - tan δ (Uo)] < 0,6 ‰ Cables in bad condition (or to be replaced immediately ) if : tan δ (2 Uo) ≥ 2,2 ‰ or [tan δ (2 Uo) - tan δ (Uo)] ≥ 1,0 ‰ EPR and TR - XLPE cables have higher absolute values of Tan Delta than the above XLPE values, however the change in Tan Delta is still the important criteria to take note of. ICC Educational Program Spring 2001. Field Test Result for an 1974 XLPE Cable Good Result for an old Cable. ICC Educational Program Spring 2001. Field Test Result for an 1984 XLPE Cable Nominal Operating Voltage: Vo = 14kV PDIV: only at 19kV Note: TD values are poor even at Vo. ICC Educational Program Spring 2001. Comparison of Cable Diagnostic Systems IR C R e c o v e ry D is s . F a c t o r S p e c tr o s c o p y A n a ly s is V o lt a g e V L F ta n d V L F ta n d D i a g n o s is s t r o n g ly a g e d c a b le s 0 - + + I n f lu e n c e o f d is tu r b a n c e s - 0 + + R e p r o d u c ib ility o f m e a s u r e m e n ts - + + + D i a g n o s t ic t e s t t im e - - + + I n f lu e n c e o f T e m p e r a tu r e + - + - R E F .: S I N T E F R e p o r t, N 7 4 6 5 T r o n d h e im S . H v id s te n , J .T . B e n ja m in s e n T R A 5 0 7 2 , A ug . 2 0 0 0 R E F .: D r . I n g . R . P la th P ro f . D r. W . K a lk n e r D ip l. I n g . I . K r a g e I P H B e r lin T U B e r lin VEW EURO TEST Key: 0 OK + Pos. - Neg. ICC Educational Program Spring 2001. Other Applications and Techniques available using the Tan Delta measurement: ● Measurement of TD and Capacitance with respect to Frequency ( Dielectric Spectroscopy). Application of TD as a reference signature and method ● for determining moisture ingress for PILC cables. ICC Educational Program Spring 2001. Conclusions of Tan Delta Diagnostics A TD cable assessment system can clearly distinguish between new, medium and strongly aged extruded cable insulation. ● ● ● ● Water trees which are a major original source of insulation failures in aged extruded cables can be detected in a non-destructive manner. Excellent Field Results. To detect singular defects, a combined assessment system including the application of partial discharge measurement and location in addition to TD is necessary.
© Copyright 2026 Paperzz