FLEX DC Radius Installation Guide

213.250.6069
[email protected]
www.opticarts.com
Please read entire guide prior to
starting installation.
FLEX RADIUS INSTALLATION GUIDE
Indoor - IP40
NOTES
1. IP40 and lower tape must be installed indoors only. Installing outdoors will void the warranty.
2. Installation must be carried out by a licensed electrician & executed in accordance with local codes.
3. The installing contractor assumes all liability for the safety and code compliance of the installation.
4. Optic Arts is not liable for any damages caused by improper wiring, driver overloading, driver under-loading, power surges, poor system design or layout, negligence or other conditions.
INSTALLATION DIRECTLY TO
MOUNTING SURFACE
1.
2.
1.1 T
horoughly clean mounting surface.
1.2 Apply DBTAPE10M by removing one side of the
2.1 A
pply firm pressure to entire length of tape so
the tape may bond to the mounting surface.
liner, unroll and adhere to surface. The lining
on the top of the tape should remain until you
are ready to apply FLEX RADIUS. For best results
the tape should be installed without bubbles
or ripples. If you make a mistake in application,
remove the tape and all residue and discard and
then start over with new tape.
3.
3.1 P
repare to mount FLEX RADIUS by removing the
remaining liner from the double sided tape & the
back of the FLEX RADIUS.
3.2 Start at one end of the FLEX RADIUS and place
directly on top of the double sided tape (adhesive
to adhesive). Work your way down the surface,
pressing the FLEX RADIUS onto the DBTAPE10M
as you go.
Optic Arts reserves the right to modify this specification without prior notice.
Last Modified: February 08, 2017
1 of 8
© Optic Arts 2016; 1130 Monterey Pass Rd, Monterey Park, CA 91754
213.250.6069
[email protected]
www.opticarts.com
FLEX RADIUS INSTALLATION GUIDE
Indoor - IP40
INSTALLATION DIRECTLY TO MOUNTING SURFACE
4.
4.1 Y
ou can bend the product and fold it over on
itself up to 90° at the cutout bend points.
Bending should be done once, repeated
bending can damage the product.
4.2 Apply pressure to the entire length of FLEXDC
firmly, but gently, using your fingers.
5.
6”
3.1 Install one FLEXMNT.SIL.INT mounting strap
every 6”.
Optic Arts reserves the right to modify this specification without prior notice.
Last Modified: February 08, 2017
2 of 8
© Optic Arts 2016; 1130 Monterey Pass Rd, Monterey Park, CA 91754
213.250.6069
FLEX RADIUS INSTALLATION GUIDE
[email protected]
www.opticarts.com
Indoor - IP40
ELECTRICAL INSTALLATION
MLV
ELECTRONIC DRIVER - NON-DIM
24V DC+
24V DC+
24V DC-
MLV
DRIVER
24V DC-
ELECTRONIC
DRIVER
120 VAC
120 - 277 VAC
PURE DC MLV
ELECTRONIC DRIVER W/0-10V MODULE
120 VAC WIRING
24V DC+
24V +
24V -
0-10 +
0-10 -
24V DC-
ELECTRONIC
DRIVER
PURE DC
DRIVER
+
120 VAC
277 VAC WIRING
120 - 277 VAC
–
0 - 10 V CONTROLLER
24V DC+
FIELD INSTALLED IN LOW VOLTAGE WIRING COMPARTMENT
- Install DIM-010V Module in low voltage wiring compartment.
- Max number of 25 modules on one dimmer. Consult dimmer datasheet for maximum device
limitation of a specific controller.
24V DC-
PURE DC
DRIVER
GRAY WIRE TO 0-10V CONTROLLER VIOLET WIRE TO 0-10V CONTROLLER +
277 VAC
DIM-010V
0-10V MODULE
BLACK WIRE TO DC - OUTPUT OF DRIVER
RED WIRE TO DC + OUTPUT OF DRIVER
+
BLUE WIRE TO LED YELLOW WIRE TO LED +
–
1.1 C
onfirm that all power is off prior to starting installation. Landing hot wires
1.3 E
MCOD MLV drivers must be loaded between 80% and 100%. Use of any
1.6 M
ake certain that the polarity is correct prior to energizing system. Reverse
to the FLEXDC wire leads can damage the strip and will not be covered under
other driver must be approved by Optic Arts prior to use in order to maintain
polarity wiring can damage the FLEXDC strip and will not be covered under
warranty.
warranty.
warranty.
1.2 W
ire FLEXDC strip to Optic Arts supplied driver. Use of any other driver must
be approved by Optic Arts prior to use in order to maintain warranty.
Optic Arts reserves the right to modify this specification without prior notice.
Last Modified: February 08, 2017
1.4 Justin MLV drivers and electronic drivers have no minimum load.
1.5 E
nsure that the proper wire gauge is used in order to minimize voltage drop.
3 of 8
© Optic Arts 2016; 1130 Monterey Pass Rd, Monterey Park, CA 91754
213.250.6069
[email protected]
www.opticarts.com
FLEX RADIUS INSTALLATION GUIDE
Indoor - IP40
ELECTRICAL INSTALLATION
ELECTRONIC DRIVER W/DMX MODULE
120 - 277 VAC
ELECTRONIC
DRIVER
®
24V DC24V DC+
DMX MODULE
LED+
CH1 CH2 CH3 CH4 -
DMX in +
DMX in DMX in shield
FROM DMX CONTROLLER (BY OTHERS)
OUT TO NEXT MODULE (32 MAX)
Optic Arts reserves the right to modify this specification without prior notice.
Last Modified: February 08, 2017
4 of 8
W/A
B
G
R
LED+
© Optic Arts 2016; 1130 Monterey Pass Rd, Monterey Park, CA 91754
213.250.6069
[email protected]
www.opticarts.com
FLEX RADIUS INSTALLATION GUIDE
Indoor - IP40
ELECTRICAL INSTALLATION
LUTRON HI-LUME® 1% 2-WIRE:
2-WIRE CONTROL FORWARD PHASE
LUTRON HI-LUME® 1% 2-WIRE:
2-WIRE CONTROL FORWARD PHASE
DIMMER WITH NEUTRAL
DIMMER WITHOUT NEUTRAL
24V DC +
24V DC +
24V DC -
24V DC -
LUTRON HI-LUME®
1% 2-WIRE
DIMMED LINE
(BLACK)
NEUTRAL-WIRE
DIMMER/MODULE/PANEL
LUTRON HI-LUME®
1% 2-WIRE
LINE/HOT
DIMMED LINE
(BLACK)
NEUTRAL
NEUTRAL (WHITE)
FORWARD PHASE DIMMER
WITHOUT NEUTRAL
LINE/HOT
NEUTRAL
NEUTRAL (WHITE)
Optic Arts reserves the right to modify this specification without prior notice.
Last Modified: February 08, 2017
5 of 8
NEUTRAL
© Optic Arts 2016; 1130 Monterey Pass Rd, Monterey Park, CA 91754
213.250.6069
[email protected]
www.opticarts.com
FLEX RADIUS INSTALLATION GUIDE
Indoor - IP40
ELECTRICAL INSTALLATION
LUTRON HI-LUME® 1%:
3-WIRE/ECOSYSTEM
LUTRON HI-LUME® 1%:
3-WIRE/ECOSYSTEM
3-WIRE
ECOSYSTEM
24V DC +
24V DC +
24V DC -
24V DC -
TO ECOSYSTEM
DIGITAL LINK
E1 (Purple)
E1 (Purple)
E2 (Purple)
E2 (Purple)
LUTRON HI-LUME®
1% 3-WIRE
SWITCHED LINE
(BLACK)
DIMMED LINE
(ORANGE)
3-WIRE
DIMMER/MODULE/PANEL
NEUTRAL (WHITE)
NEUTRAL
Optic Arts reserves the right to modify this specification without prior notice.
Last Modified: February 08, 2017
LINE/HOT
LUTRON HI-LUME®
1% 3-WIRE
DIMMED LINE
(ORANGE)
LINE/HOT
NEUTRAL
NEUTRAL
6 of 8
© Optic Arts 2016; 1130 Monterey Pass Rd, Monterey Park, CA 91754
213.250.6069
[email protected]
www.opticarts.com
FLEX RADIUS INSTALLATION GUIDE
Indoor - IP40
ELECTRICAL INSTALLATION
LUTRON HI-LUME® PREMIER:
3-WIRE/ECOSYSTEM
LUTRON HI-LUME® PREMIER:
3-WIRE/ECOSYSTEM
3-WIRE
ECOSYSTEM
24V +
24V +
24V -
24V -
LUTRON HI-LUME®
PREMIER DRIVER
LUTRON HI-LUME®
PREMIER DRIVER
(WITH ECOSYSTEM CONTROL & SOFT-ON
FADE TO BLACK TECHNOLOGY)
LINE/HOT
3-WIRE
DIMMER/MODULE/PANEL
SWITCHED LINE/HOT (L)
TO ECOSYSTEM
DIGITAL LINK
DIMMED HOT (DH)
NEUTRAL
E2 (Purple)
120-277 VAC
NEUTRAL
Optic Arts reserves the right to modify this specification without prior notice.
Last Modified: February 08, 2017
E1 (Purple)
7 of 8
© Optic Arts 2016; 1130 Monterey Pass Rd, Monterey Park, CA 91754
213.250.6069
[email protected]
www.opticarts.com
FLEX RADIUS INSTALLATION GUIDE
REMOTE DRIVER DISTANCE CHART
Indoor - IP40
DRIVER
NOTES:
JUNCTION BOX
1. Calculated using 4 amp draw (96 Watts at 24VDC).
2. Calculation includes 6’ 18 AWG factory lead connected to home run.
3. Home run can be increased if factory lead length is decreased.
FLEX DC
HOME RUN
FACTORY LEAD
6’, 18 AWG
HOME RUN DISTANCE
MINIMUM GAUGE
VOLTS
% DROP
5’
18 AWG
23.44
2.38%
10’
16 AWG
23.38
2.62%
15’
14 AWG
23.43
2.41%
20’
14 AWG
23.34
2.78%
25’
12 AWG
23.38
2.60%
30’
12 AWG
23.32
2.87%
35’
10 AWG
23.42
2.45%
40’
10 AWG
23.38
2.61%
45’
10 AWG
23.34
2.78%
50’
10 AWG
23.30
2.95%
55’
8 AWG
23.42
2.43%
60’
8 AWG
23.40
2.54%
65’
8 AWG
23.37
2.64%
70’
8 AWG
23.35
2.75%
75’
8 AWG
23.32
2.85%
80’
8 AWG
23.30
2.96%
85’
6 AWG
23.43
2.40%
90’
6 AWG
22.41
2.47%
95’
6 AWG
23.40
2.53%
100’
6 AWG
23.38
2.60%
Optic Arts reserves the right to modify this specification without prior notice.
Last Modified: February 08, 2017
8 of 8
© Optic Arts 2016; 1130 Monterey Pass Rd, Monterey Park, CA 91754