Cable Design
Screened Pair
Stranded Bare Cu wire, 0.75mm² (24x0.20mm)
Insulation
Foam Polyolefin Ø 2,95 mm
Assembly
2 cores twisted to a pair (1x2x0,75mm 2) Blue & White
Screen
Al-/polyester tape >100% coverage
Earth Conductor
Stranded Tinned Cu wire, 0.75mm² (24x0.20mm)
Insulation
Foam Polyolefin Ø 2,95 mm
Cable Core
1 x screened pair + 1 earth core + Fillers
Screen
Tinned Cu-braid >80% optical coverage
Fire Barrier
Flame barrier tape >100% coverage
Outer Jacket
Black LSZH FireFighter® SHF-2
Diameter
Ø 11,10 mm
Weight
200 kg/km
Application
System bus cable for use over or under deck. The cable has good oil and chemical resistance, due to
the special outer jacket of SHF2 cross linked compound. The cable is specially designed for CAN-bus
systems.
Applicable Standards
approved by DNV & ABS
Flamability Rating
IEC 60332-1, IEC 60332-3-22, IEC 60754-1/2, IEC 61034-1/2, NES 713
Ozone resistance
acc. to DIN VDE 0472 part 805 test B
Specification
Part Number
Type
1087380
CAN Bus 1x2x0,75/0,75mm 2 SHF-2
T: 01279 871150 | F: 01279 871129 | www.belcom.co.uk
CAN Bus 1x2x0,75/0,75mm 2 SHF-2
Standards
Page 2 / 2
Cable excellence engineered through quality
Electrical & Mechanical Characteristics
Tempearture range
-40 to +90
Operating voltage
Test voltage
Resistance inner conductor
≤
Insulation resistance
≥
Nom. capacitance @ 800Hz
Characteristic impedance @ 1MHz
Nom. attenuation @ 1MHz
≤ 13,2dB/km
Min. bending radius
˚C
100V
1000
V dc
26Ohm/km
1
GW x km
40pF/m
120
Ohm ± 10%
fixed
10
xØ
moved
20
xØ