establish ratings which will produce the limiting amount of annealing. Fortunately, convergence is rapid, since ratings too low give negligible annealing, and those too high exceed the limit of annealing in short order. In a graphical method, these effects are easily noted. Transmission Conductor Ratings G. M. BEERS MEMBER IEEE S. R. GILLIGAN SENIOR MEMBER IEEE H. W. LIS MEMBER IEEE J. M. SCHAMBERGER SENIOR MEMBER IEEE Summary: The purpose of this paper is to describe a method of calculating transmission conductor ratings. These ratings are limited by the amount of annealing which can be tolerated during the life of the conductor. The method includes an approach to weather-data analysis, use of a digital computer for bulk calculations, and a graphical method of calculating annealing. The resulting ratings can be used with confidence, since they reflect both local weather experience and operating practices. SEVERAL operating electric com- panies in Connecticut and Massachusetts* jointly plan new generation and transmission facilities in order to coordinate both area and local requirements. The need for a common basis of establishing transmission conductor ratings was recognized and a joint study group was formed to determine both the basis and the ratings. General The basic method itself is general. It may be used in any area where routine weather observations have been made and where tr4nsmission operating practices are known. It will remain for any user of this method to determine his own limiting physical parameters and life of the plant. Several previous papers have suggested the use of local weather observations or the use of a computer in making calculations.' New data are available on conductor annealing and resistance characteristics.2 The method to be described makes use of these techniques and data to establish unique ratings for local conditions. Conductors must be rated in order to limit the total loss of strength due to annealing to a prescribed amount during the stated life of the conductor. In addition, ratings must be based on the maximum conductor temperature to be tolerated. Depending upon local weather conditions or operating practices, several ratings for a single conductor may be desired, such as summer versus winter, or normal versus emergency, ratings. These ratings can be established only if the operation under the various conditions can be predicted. The method consists of the following steps: 1. Reduction of local weather observations to a table of total hours of occurrence of each condition of wind and ambient temperature which may be expected to produce any appreciable annealing during the life operation of the conductor. 2. Assignment of the load characteristics to be assumed, giving the load duration in one form or another, together with any assumptions or requirements for emergency operation. 3. Assignment of the maximum loss of conductor strength due to annealing which can be permitted over life of the conductor. 4. Preparation of a table of conductor temperatures as a function of current, wind velocity, and ambient temperature. 5. Calculation of the total annealing by a step-by-step graphical method. Some trialand-error work is required here, in order to The Connecticut Light & Power Company, The Hartford Electric Light Company, The United Illuminating Company, and the Western Massachusetts Electric Company. OCTOBER 1963 Factors Affecting Ampere Rating CONDUCTOR CHARACTERISTICS There are several characteristics associated with transmission line conductors which may establish the maximum rating. These are, principally: loss of strength due to annealing, conductor sag increase due to operating temperatures, and the ability of line hardware, splices, and connectors to meet the capability of the conductor itself. Most important of these characteristics is the permanent loss of tensile strength due to annealing. This effect is cumulative and depends upon conductor temperature and time. 300 o 250 ACTUAL IN z 0 Paper 63-86, recommended by the AIEE Transmission and Distribution Committee and approved by the AIEE Technical Operations Department for presentation at the IEEE Winter General Meeting, New York, N. Y., January 27-February 1, 1963. Manuscript submitted October 18, 1962; made available for printing November 30, 1962. G. M. BEERS iS with the United Illuminating Company, New Haven, Conn.; S. R. GILLIGAN is with the Hartford Electric Light Company, Hartford, Conn.; H. W. Lis is with the Western Massachusetts Electric Company, West Springfield, Mass.; and J. M. SCHAMBERGER is with The Connecticut Light & Power Company, Berlin, Conn. * The method has one particular advantage: The resulting ratings are tailored to local conditions and requirements. As such, they can be used with confidence. The use of arbitrary or uncertain average temperatures or wind velocities is avoided, as are unrealistic "continuous" ratings. Despite this advantage, the method can produce some disconcerting results: In the light of actual local weather experience, even a modest ampere rating may, at times, result in conductor temperatures (and sags) far exceeding those which formed the basis of line design. Conversely, at other times, the line may be capable of currents which exceed the capabilities of series devices or terminal equipment. 5 200 ASSUME DISTRI m o Fig. 1. Wind distribution at 70 F (68 F-72 F) b0 150 z 100 WIND VELOCITY - KNOTS Beers, Gilligan, Lis, Schamberger-Conductor Ratings Authorized licensed use limited to: CHILECTRA. Downloaded on May 13,2010 at 15:48:10 UTC from IEEE Xplore. Restrictions apply. 767 Fig. 2. Wind hours at 70 F (68 F-72 F) .0 I OBSERVATIONS AT EACH INTERVAL (HOURS IN 5 YRS.) U) 0 'F- 50 O0 0 0.375 1.0 .5 2.o 0 WIND VELOCITY Based upon the line design and its economic life it should be possible to state the loss of tensile strength that can be permitted over the life of the conductor. This method of calculating conductor ratings is based entirely on the annealing limitation. For an existing line, the resulting sag and the demands on various line devices and hardware must be checked. For a new line, a co-ordinated design can be based upon the ratings established by loss of tensile strength. AMBIENT CONDITIONS In order to evaluate annealing, it is necessary to know the conductor temperature and the time period at such temperatures. The principal source of heat tending to raise the conductor temperature is the I2R loss; cooling is primarily by convection in the surrounding air. The degree of cooling is based on air temperature and wind velocity. The most important of these aspects is the wind. For example, if we can count on a minimum 10-fps (feet per second) wind velocity, ambient temperature will have little effect on the cooling, and the rating will be high. On the other hand, if there is no wind, cooling is entirely by radiation and natural convection. Under this condition, ambient temperature does play a part, but the ratings will be low due to the lack of wind. After examining the equations for conductor heating and cooling found in the House and Tuttle paper,3 it becomes apparent that essentially all annealing will take place well below 10-fps wind velocity and that it is necessary to know the conditions of wind and temperature which are within this range. 768 LOAD CHARACTERISTICS The third factor affecting conductor ratings is the loading of the line. It is important to know whether a line will be operated at a continuous load, which is rare, or whether peak loading will occur for only a short time each day. Similarly, the requirements for emergency load conditions must be known or assumed. From such requirements can be determined whether a single rating may be established, or if several ratings will be desirable. For example, a winter peak load may justify the use of a high winter rating, if a reduced summer capability is acceptable; or a single year-round value may more nearly match the load requirements. Weather Data In order to determine the conductor temperatures at times when annealing is appreciable, it is necessary to know what the expected frequency of low-velocity winds combined with temperatures may be for the local area. These data are available in the "Local Climatalogical Data (Supplement)" which is prepared monthly from local observations by the Weather Bureau of the U.S. Department of Commerce. From such data at two locations in Connecticut, about 2,100 simultaneous hourly observations of wind velocity and temperature representing a 5-year period were transcribed to punched cards for sorting and tabulation. Only the hours between 7 a.m. and 10 p.m. were included, as this is the time period in which the lines can be expected to be heavily loaded. Readings were grouped in intervals of 5 F (degrees Fahrenheit) and one knot (nautical mile per hour) for all observed temperatures and for velocities up to 6 knots (about 10 fps). A typical group of velocities for the 70 F interval (68-72 F) is shown plotted in Fig. 1. An apparent inconsistency is noted in the small number of observations at 1 and 2 knots. From discussion with Weather Bureau personnel, it developed that the indicating anemometers are not accurate below about 4 knots and, in fact, will not start to turn much below 2 or 3 knots. For these reasons, and because the low-velocity winds are such an important factor, it was decided to "smooth" the readings between zero and 4 knots, assuming that the probability of a true zero velocity approached zero. This was done with the curve shown in Fig. 1. The curve was adjusted so that the total number of hourly observations was correct; i.e., the area under the curve between zero and 6.5 knots was made just equal to the total observations. Preliminary calculations of conductor temperatures (and annealing) indicated that for the local ambient temperature range, only those wind velocities of 3 fps and below would involve the conductor in appreciable annealing. The curve of Fig. 1 is shown replotted in Fig. 2 on a larger scale, and block intervals centered at C.375, 1.0, 1.5, 2.0, 2.5, and 3.0 fps are shown. The areas of each interval were measured and represent the equivalent number of observations (hours) in each block. Similar constructions were made for each 5 F block of temperatures, and from the results, a wind-velocity-amnbient-temperature chart was prepared. The 5-year totals were prorated to 30 years and a correction factor of 4 included. This f actor is a wrultiplier, and is used to Table 1. Assumed Hours of Weather in 30 Years for a Typical Protected Area Wind Velocity-Fps Ambient Temperature, 2.0 2.5 Degrees F 0.375 1.0 1.5 90. 85 . 80. 75 . 70 . 65 . 60 . 55 . 50 . 45 . 40 . 35 . 30 . 25 . 20. Beers, Gilligan, Lis, Schamberger-Conductor Ratings 15 . 10. 5. 3.0 3... 7... 13... 20... 28... 38 4... 18 ... 36... 58... 84.. 115 5.. .23 ... 47... 77.. 113.. 155 31.. .77.. .140.. .223.. 312.. 395 38.. 92 ... 168.. 271.. 363.. 500 38.. .92 ... 168.. 271.. 363.. .500 24.. 68 ... 130.. 208.. 294.. .376 24.. 68 .. 130.. .208.. 294.. 376 22.. 58 .. 105... 163.. 235.. 309 23.. 62 .. 118.. .191.. 276.. .353 31.. .77 .. 140.. 223.. .312.. .395 35.. 86. .160.. 260.. 371.. .471 35.. 86 .. 160.. 260.. 371.. 471 22.. 55 ... 96.. 146.. .206.. 267 9.. 28... 55... 87... 127.. .168 5.. .18... 36... 57... 83.. 110 4... 15 ... 30... 47... 65... 83 4.. .15 ... 30... 46... 62... 78 OCTOBER 1963 Authorized licensed use limited to: CHILECTRA. Downloaded on May 13,2010 at 15:48:10 UTC from IEEE Xplore. Restrictions apply. Fig.13. Typical anneaing of aluminum (from reference 2, permission of Alcoa) HEATING PERIOD IN HOURS acknowledge the fact that the observations were made in elevated and exposed locations, while most of the lines run through hilly, wooded terrain which may be quite sheltered from the wind. The factor of 4 was determined by comparing simultaneous observation from both sheltered and exposed locations. A similar relationship was noted in- the Schurig and Frick article in 1930. However, there is still a distinct need for more accurate data on the variability of wind, particularly with respect to terrain, elevation, and locale. The summary of hours of wind velocity and temperature for 30 years is shown in Table I. Conductor Temperature Calculations The second step in determining annealing is to prepare a table of conductor temperatures as a function of current and the ambient conditions derived previously. The basic equations used were those determined by House and Tuttle in their 1958 paper, and include the effects of I2R and solar heat sources, and convection and OCTOBF-R 1963 radiation heat losses. The equations for convection heat loss cover two situations. The first is for forced convection cooling where the wind velocity is 2 fps or greater, and the second covers natural vertical convection (wind velocity of zero). Since the significant area of conductor annealing was known to exist between 0 and 3 fps of wind, it was necessary to modify the two equations to accept the velocity values of 0.375, 1.0, and 1.5 fps. This was done by calculating the vertical natural convection velocities which could be combined with horizontal wind to resuilt in the. correct cooling effects at the zero (natural convection) and2-fps points. Since a table of conductor temperatures at discrete current steps was required, the solution of the equations for conductor temperature involves "cut and try" methods. This led to the use of a high-speed digital computer to produce, by iterative methods, the required tables of conductor temperature. Tables were prepared for 9 different ACSR (steel-reinforced aluminum cable) conductors, with about 800 temperature values calculated for each conductor. Included in the com- puter program is automatic temperature correction of conductor resistance, which has an important effect on the ratings. Information regarding this program [for IBM (International Business Machines Corporation) 70701 and its availability can be obtained from the authors. A portion of the table for 795-MCM (thousand circular mils) ACSR "Tern" is reproduced as Tab-le V. It will be noted that the first velocity column is headed "0.0" fps. Although zero wind was not used in calculating total annealing, it provides an indication of the maximum attainable conductor temperatures. While the probability of these temperatures ever occurring is assumed to be zero, they represent a design limit in considering sags and clearances. Calculation of Rating The final step in determining the ratings is to calculate the actual conductor loss of tensilestrength due to annealing, using the tables previously described in combination with an assumed loading schedule. The annealing characteristics of aluminum (or the aluminum portion of ACSR), Beers, Gilligan, Lis, Schamberger-Conductor Ratings Authorized licensed use limited to: CHILECTRA. Downloaded on May 13,2010 at 15:48:10 UTC from IEEE Xplore. Restrictions apply. 769 Table II. Reduced Hours of Observed Weather in 30 Years for a Typical Protected Area (5%o of Total Hours of Table I) Ambient Temperature, Degrees F 90. 85. 80. 75. 70. 65. 60. 55 . 50 . 45 40. 35. 30. 25 . 20 . 15. 10. 5. Wind Velocity-Fps 0.375 1.0 1.5 2.0 2.5 3.0 0... 1... 1 .... 1.... 1.... 2 0... 1... 2... . 1... 2 .... 3.... 4.... 6 1... 2 .... 4.... 6.... 8 4... 7 ... 11... 16... 20 2... 5... 8 .... 14.... 18... 25 2... 5... 8 .... 14... 18... 25 ... l.3 .6 ... 10... 15... 19 1... 3... 6.... 10... 15... 19 1... 3... 5.... 8.... 12.... 15 1.... 3... 6... .10... 14... 18 2... .4 .7 ... 11... 16... 20 2... .4 .8 ... 13... .19... 24 2... 4... 8 ... 13... 19... 24 1... 3... 5 .... 7... 10... 13 1.... 1... 3 .... 4.... 6.... 8 0... .1... 2 .... 3.... 4.... 5 0. 1...2 .... 2.... 3.... 4 ... 0... ..... 1.... 2.... 3.... 4 Table Ill. 795-MCM (45/7) ACSR Conductor Accumulated Hours at Annealing Temperatures for 1,060 Amperes, Normal Operation Conductor Temperature, Degrees C 130 125 120 115 Expected Hours in 30 Years .. .. .. .. 1tO .. 105 .. 100 ...21. 95 .. 90 .. 85 .. 80 .. 75 .. 70 .. 65* .. 1 4 4 4 11 13 42 60 59 117 99 76 41 552 * Hours below 65 C cause only negligible annealing. for example, are shown in Fig. 3, taken from reference 2. On this family of curves, it is possible to plot the cumulative effects of annealing for all conductor temperatures 65 C (degrees centigrade) and above, and so to determine the loss of tensile strength. The simplest loading schedule to consider is a single year-round continuous load. In this situation, the conductor will experience all the hours of simultaneous wind and temperature obtained from the analysis of weather data. Total annealing is calculated for an assumed value of current by combining Tables I and V to determine the hours of operation at each 5 C interval of conductor temperature. This in turn is plotted on annealing curves of Fig. 3. Total annealing is calculated for several values of current until, by approximation or interpolation, a value 770 of current is found which will just produce the maximum allowable loss of strength. This is the single continuous rating for year-round use. The first modification might be a requirement for a summer rating and a winter rating. In this case, the weather data should be set up as two tables, one covering the summer period and the other the winter. It would now have to be determined which period should be favored in establishing the ratings. This is to say, whether more of the allowable annealing should take place in the warm weather or in cold weather. A second modification might be to have dual ratings independent of the season of the year-a normal rating and an emergency or contingent rating which could be tolerated during abnormal system conditions. In this case, it would be necessary to assume (by estimation or past experience) how often and for how long these abnormal conditions might exist. In the sample calculation of the Appendix, for example, it was assumed -that contingency conditions would exist for no more than 600 hours in the 30-year conductor life. If it is further assumed that these hours occur at random, it is possible to build a new table of expected hours of emergency operation when unfavorable ambient conditions might exist. Under such assumptions, contingency ratings appreciably higher than normal can be achieved. These ratings have the added quality that they can be permitted to persist whenever they occur, without load curtailment or apprehension about conductor damage. In the study whose method this paper describes, the contingency rating was felt to be as significant as normal loading and approximately half of the total loss of tensile strength were allocated to the contingency period. In fact, the system operation under normal conditions is determined by the contingency rating to the extent that the study assumed that normal maximum loading would occur for not more than 5% of the hours in the life of the conductor. To assume that normal loading is cQntinuous (100% load factor) is costly in terms of amperes and would result in ratings well below any of the currently published figures. Conclusions The method of determining transmission-line conductor ratings discussed here is a general method by which any conductor can be given a rating suitable to the area and conditions. Despite the considerable data required and the step- by-step calculation, this rating method will permit taking maximum advantage of local conditions and practices. It may be of interest to see some of the ratings established by the actual study, and these are shown in Table VI. Readers are cautioned that these values are valid only under the conditions and assumptions outlined in the Appendix. An interesting and unexpected situation developed when it was noted that different sizes of similar type conductors developed the same maximum conductor temperature when loaded for a given percent loss of tensile strength due to annealing. Thus, it was possible for other sizes to be rated by a single direct calculation using the maximum conductor temperature to determine the ampere value. The range of conductor temperatures, from 140 C to 180 C, suggests conductor sags well above those anticipated a few years ago. Existing lines must be checked before the new ratings are applied. Appendix To illustrate the application of the method outlined in the text, a sample calculation of the ratings for the 795-MCM (45/7) ACSR conductor will be made. This Table IV. 795-MCM 45/7-Strand ACSR Conductor Accumulated Hours at Annealing Temperatures for 1,340 Amperes, Contingent Operation Conductor Temperature, Degrees C Hours in 30 Years Probable Actual Hours 3 190............ 185 ............ 9 180 ........... 69. *1 62 ..1. 0 175 ........... 170 . 1 ........... *1 165.154 ........... *1 . 160 1....27.....127. 1.0 155 . -265 . 2.0O (1. 0+ *1) 150 ............ 327 ............ 1.2 145 ............ 393 ............ 1.4 140 ............ 684 ............ 2.5 135 ............ 654 ............ 2.4 130 ............ 1.574. ........... 5.7 125 ............ 1,156 ............. 4.2 120 ............ 1,512 ............ 5.5 .869 . 6.88 115... 110 ............ 1,290 ............ 4.7 105 ...... . .....2,100 ............ 7.6 12,319 .49 Probability that the combination of wind and ambient temperature will cause conductor temperatures above 100 C with a current of 1,340 amperes: 12,319 = 0.075 164,000 Probable number of hours of operation at these temperatures: 0.075 X 600 = 45 hours * Four extra hours were inserted at temperatures above 150 C to provide a safety factor of 2 in the high-temnperature range. Beers, Gilligan, Lis, Schamberger.-*Conductor Ratings OCTOBER 1 963 Authorized licensed use limited to: CHILECTRA. Downloaded on May 13,2010 at 15:48:10 UTC from IEEE Xplore. Restrictions apply. calculation will use the data and assumptions used in the original study. Normal and Contingent Rating Table V. Conductor Temperatures of 795-MCM (45/7) ACSR in Degrees C Current, Amperes For our systems, we chose to develop yearround normal and contingent ratings for each conductor size. The normal rating is defined as the rating for continuous operation. The contingent rating is defined as the rating which will be permitted following an unscheduled outage on the system. In developing the normal rating, it is assumed that no line can reasonably be expected to operate at, or near, its normal rating for more than 5% of the hours in its 30-year life. Either economic loading, or the possible loss of another facility, would dictate a lower loading. In addition, the load factor of the system would indicate very few hours per year that a line would be loaded at or near its miaximum normal rating. For these reasons, the hours of wind for various ambient temperatures, shown in Table I, are reduced to 5% of the total hours, anld are shown in Table II. It is believed that this assumption is conservative for most lines in our system. In developing the contingent rating, it is assumed that the number of hours of emergency operation would not exceed 600 in the life of the conductor. It is further assumed that these 600 hours occur in a random fashion. Annealing Annealing for the aluminum portion of the various sizes of ACSR was permitted to fall between 12% and 15%. The permissible annealing was varied, depending upon the percentage of the conductor strength accounted for by the steel core. In general, an over-all reduction in conductor strength of 7'0-8<%o was permitted. Information for the air density, absolute air viscosity, and the coefficient of thermal conductivity are found in the tables of reference 3. A computer printout using the equations of reference 3 at various currents for the 795-MCM (45/7) ACSR conductor is shown in Table V. Calculation of the Normal Current Rating In the calculation of the annealing associated with the normal and contingency ratings, the step-by-step graphical method is used. To determine the normal rating, it was first assumed that 1,060 amperes would produce a satisfactory amounlt of OCTOBER 1 963 0.375 1.5 1.0 2.0 2.5 3.0 41.1 ..... 34.8 44.3 ..... 38.0 47.4 ..... 41.1 50.6 ..... 44.3 53.8 ..... 47.4 787 ..... 56.9 . 50.6 81.6..... 60.1. 53.8 84.5..... 87.4 ..... 63.3. 56.9 90.4..... 66.4.... 60.0 69.5 ..... 63.2 93.3 ..... 1,060........ 445 . 72.7 ..... 66.3 50 . 116.7... 112.8..... 96.2 ..... 75.8 . 69.4 55 . 119.4....'115.5 . 99.1 ..... '''' 72.6 79.0 ..... 60 . 122.1... 118.2 ...101.9 ..... 82.1 ..... 75.7 65 .......... 124.8..... 120.9.....104.8..... 78.8 85.2...... 70 . 127.5... 123.6 ... 107.7..... 88.3 ..... 82.0 75 .......... 130.2..... 126.2 ..... 110.6 ..... 85.1 91.4 . . 80 132.8 ... 128.9 .....1134... .....95.7..... 102.6 ..... 88.2 94.5 85 . 135.5 ... 131.6 ... 116.3 ... 105.6..... 98.7. ..... 91.3 i90 . 138.1 ... 134.2 ... 119.1... 108.5 ..... 101.7. 97.6 ..... 0.. . 5. 10 . 15 . 20 . 25 . 30 . 35 . 40 . 1 ,130........ 45 . 50 . 55 . 60 . 65 . 70 . 75 . 80 . 85 . 90 . 1,270........ In calculating the conductor temperatures using the equation found itn the House and Tuttle paper,3 the following were used: west 0.0 0. 5. 10 . 15 . 20 . 25 . 30 . 35 . 40 . Calculation of Conductor Temperature 1. Coefficient of emissivity = 0.5 2. Coefficient of solar absorption 0.5 3. Altitude of sun = 65 degrees 4. Azimuth of sun= 148.5 degrees for 41.5 degrees north latitude 5. Azimuth of line = 270 degrees, or east to Wind Velocity-Fps Ambient Temperature, Degrees F 49.7. 52.9. 56.1. 59.2. 66.8...... 62.4. 69.8 ..... 65.6. 72.8 ..... 68.7. 75.8 ..... 71.2. 78.8.71.5. 81.8.74.5. 84.8..... 77.6. 87.8 ..... 80.6. 90.8 ..... 83.6. 93.9 ..... 86.7..... 96.7..... 89.7. 99.7..... 92.7 .... 66.8 ..... 54.6..... 69.8 ..... 57.6 ..... 72.7 .....60.7 . 75.7 ..... 63.7..... 101.3..... 98.2 ..... 78.4 ..... 64.7 ..... 59.6 ..... 49.5 ..... 42.2 104.2 .... 107.0 .... 109.8 .... 112.6 .... 115.4 .... 118.1 .... 120.9 .... 123.6 .... 126.3 .... 129.0 .... 131.7 .... 134.4 .... 137.1 .... 139.7 .... 142.4 .... 145.0 .... 147.6 .... 150.3 .... 100.9 ..... 81.3 ..... 67.8 ..... 62.8 ..... 52.8 ..... 103.7 ..... 84.3 ..... 70.9..... 66.0 ..... 56.0 ..... 106.4..... 87.3..... 73.9. '''' 69.2 ..... 59.2 ..... 109.1..... 90.2 ..... 77.0 ..... 72.5..... 62.5..... 111.8 ..... 93.2.... 80.1 ..... 75.6 ..... 65.7 ..... 74.8 ..... 68.9..... 114.6 ..... 96.1 ..... 83.1. '''' 117.3 ..... 99.0 ..... 86.1 ..... 77.9. 72.1..... 120.0 ..... 102.0,.... 89.1 ..... 81.0..... 75.3 ..... 122.7 ..... 104.9 ..... 92.2 ..... 84.1 ..... 78.5..... 125.4 ..... 107.8..... 95.2 ..... 87.2 ..... 81.7..... 128.0 ..... 110.7 ..... 98.2 ..... 90.2 ..... 84.9 ..... 130.7 ..... 113.6.....101.2 ..... 93.3 ..... 88.0..... 133.4 ..... 116.4 ..... 104.2 ..... 96.4..... 91.2..... 136.0 ..... 119.3.... 107.1 ..... 99.4..... 94.4 ..... 138.7.....122.2 ..... 110.1.102.4 ..... 97.5..... 141.4.....125.1 ..... 113.1.105.5 ..... 100.7..... 144.0 ..... 127.9 ..... 116.1. 108.5 ..... 103.9 ..... 146.7 ..... 130.7 ..... 119.0 ..... 111.5 ..... 107.0 ..... 45.5 48.7 51.9 55.1 58.3 61.5 64.7 67.9 71.1 74.3 77.5 80.7 83.9 87.0 90.2 93.4 96.5 99.7 69.5 ..... 59.8 72.9..... 63.1 76.3..... 66.5 79,.6..... 69.8 82.9...... 73.2 86.3 ..... 76.5 89.6..... 79.8 92.9 ..... 83.2 96.2..... 86.5 131.1 ... 116.0 ..... 106.4 ..... 99.5..... 89.8 134.0 ... 119.0 ..... 109.5 ..... 102.8 ..... 93.1 136.9 ... 122.0 ..... 112.7 ..... 106.1 ..... 96.4 139.8... 125.0 ...... 115.8 ..... 109.4..... 99.7 142.6 ... 128.1 ..... 118.9 ..... 112.7.....103.0 145.5 ... 131.0 ..... 122.0 ..... 115.9 ..... 106.2 148.3 ... 134.0 ..... 125.0 ..... 119.2 ..... 109.5 151.2 ... 137.0 ..... 128.1.....122.4 ..... 112.8 154.0 ... 140.0 ..... 131.2 ..... 124.8 ..... 116.0 156.8 ...143.0 ..... 134.2 ..... 124.2 ..... 119.3 0... 129.2 .... 126.1 ..... 104.7 ..... 88.2 ..... 82.9 ..... 132.0 .... 128.9 ..... 107.7 ..... 91.3 ..... 86.2 ..... 134.7 .... 131.6.....110.6 ..... 94.5 ..... 85.2 ..... 137.5 .... 134.3 ..... 113.6 ..... 97.6 ..... 87.4 ..... 140.2 .... 137.0 ..... 116.5 ..... 100.6...... 90.6 ..... 142.9 ..... 139.6 .... 119.5..... 103.7 ..... 93.8..... 145.6 ... 142.3... 122.4 ... 106.8 ..... 97.0 ..... 148.3 ... 145.0 ... 125.3 ... 109.9 ..... 100.1..... 151.0 ... 147.7 ... 128.2 ... 112.9 ..... 103.3 ..... 5. 10 . 15 . 20 . 25 ......... 30 . 35 . 40 . 45 . 50 . 55 . 60 . 65 . 70 . 75 . 80 . 1,340 .... 88.8 ..... 85.5 ..... 91.7 ..... 88.2..... 94.5 ..... 91.0 ..... 97.3 ..... 93.7 ..... 100.1 ..... 96.5 ..... 102.9 . 99.2 ..... 105.7 ... 102.0 ..... 108.5 ... 104.7 ..... 111.2 ... 107.4..... 114.0 ... 110.1 ..... 153.6 ... 156.2 ... 158.9 ... 161.5 ... 164.1 ... 166.6 ... 169.2 171.8 ... 174.3... 150.3 ... 153.0 ... 155.6 ... 158.2... 160.9 ... 163.5... 166.1 ... 168.7 ... 171.3 ... 173.9 ... 85 . 90 . 176.9 ... 0. 5. 10 . 15 . 20 . 25 . 30 . 35 . 40 . 45 . 50 . 55 . 60 . 65 . 70 . 75 . 80 . 85 . 101.7 ..... 90.9..... 81.3..... 70.1 104.8 ..... 93.8 ..... 84.7..... 73.5 149.9 ... 146.8 ... 107.9..... 97.0..... 88.2..... 76.9 152.6 ... 149.5 ... 128.3... 111.1 ..... 100.2 ..... 91.6..... 80.3 155.3 ... 152.1... 131.3 ... 114.2 ... 103.4 ..... 95.0. 83.7 158.0 ... 154.8 ... 134.2 ... 117.3 ... 106.6 ... 98.4 . 87.1 160.6 ... 157.4 ... 137.1 ... 120.3... 109.8... 101.8 ..... 90.5 163.2 ... 160.1... 140.0 ... 123.4 ... 113.0 ... 105.1..... 93.9 165.9 ... 162.7 ... 142.9 ... 126.5... 116.1 ... 108.5 ..... 97.3 168.5 ... 165.3 ... 145.8 ... 129.5... 119.3 ... 111.9.....100.7 171.0 ... 168.0 ... 148.6... 132.5 ... 122.4 ... 115.2 ..... 104.0 173.6 ... 170.6... 151.5 ... 135.6 ... 125.6 ... 118.5 ..... 107.4 176.2 ... 173.2 ... 154.3... 138.6 ...128.7 ... 121.8 ..... 110.7 178.7 ... 175.8 ... 157.2 ... 141.6 ... 131.8 ... 125.2 ..... 114.1 181.3... 178.4... 160.0 ... 144.6 ... 135.0... 128.4 ..... 117.4 183.8 ... 180.9 ... 162.8 ... 147.6 ... 138.1... 130.3.....120.7 186.3... 183.5 ... 165.6 ... 150.6 ... 141.1... 129.6 ..... 124.1 188.8 . 186.1 ... 168.4 ... 153.5 ... 144.2... 132.8 ... 127.4 191.2 . 188.7 ... 171.3 ... 156.5 ... 147.3 ... 135.9 ... 130.7 t90 . 144.5 ... 147.2 ... 141.4 ... 144.1... annealing. The amount of annealing associated with this rating was found as follows: Entering Table V at 1,060 aniperes to obtain conductor temperatures at this loading, and using the hours of Table II, the first significant point of annealing is one hour at an ambient temperature of 80 F and 0.375-fps 119.5 ... 122.4 ... 125.4 ... The corresponding temis 128.9 C, rounded to 130 C. At a 75 F and 70 F ambient temperature with a 0.375-fps wind velocity, the conductor temperatures are 126.2 C (rounded to 125 C) and 123.6 C (rounded to 125 C). This 125 C conductor tempera- wind (Table II). peratnre (Table V) Beers, Gilligan, Lis, Schamberger-Conductor Ratings Authorized licensed use limited to: CHILECTRA. Downloaded on May 13,2010 at 15:48:10 UTC from IEEE Xplore. Restrictions apply. 771 Table VI. Transmission Conductor Ratings Rating in Amperes Wire Size, ACSR 2/0 (6/1) 4/0 (6/1) 336.4 MCM 336.4 MCM 397.5 MCM 556.5 MCM 795 MCM 1, 113 MCM 1,272 MCM Normal Contingency 270 ...... 320 400 ...... 470 (18/1) ....... 580 ...... 685 (26/7) ....... 610 ...... 725 (18/1) ....... 660 ...... 770 (24/7) ....... 860 ...... 1,020 (45/7).......1,075 ...... 1,285 (45/7) ....... 1,365 ...... 1,640 ....... ....... (45/7)....1...1,475 ...... 1,770 Note: Normal ratings result in a conductor temperature of about 140 C with a 90 F ambient air temperature and no wind. Contingent ratings result in a conductor temperature of about 180 C with a 90 F ambient air temperature and no wind. ture can be expected for 4 hours every 30 years. Table III is made up in this manner to tabulate the accumulated hours at annealing temperatures. The accunmulated hours at the various temnperatures are used with the annealing curves of Fig. 3 to determine the conductor annealing. Assuniing the initial tensile strength of the aluminum at 27,100 psi (pounds per square inch) and projecting 41 hours along the 65 C annealing curve, reveals that the tensile strength of the aluminum is reduced to 26,985 psi. Projecting 76 hours along the 70 C annealing curve from the reduced (26,985-psi) tensile strength, shows that the alunminum strength is now reduced to 26,850 psi. By projecting the remaining values on the annealing curves in the foregoing' manner, the total annealing for the normnal conductor rating will result in a 5.7% loss of tensile strength of the aluminum portion of the conductor. Calculation of the Contingent Rating To determine the contingent rating, it was first assumed that'1,340 amperes would produce a satisfactory amount of annealing. The amount of annealing associated with this rating was found as follows: Entering Table V at 1,340 amperes to obtain conductor temperatures at this loading and using the hours of Table I, it is seen that there are 3 hours in 30 years in which the ambient temperature is 90 F and the wind velocity is 0.375 fps. This results in a conductor temperature of 188.7 C (rounded to 190 C). The first two columns of Table IV are made up in this manner. The total hours of column 2 are then divided by the total number of hours between 7 a.m. and 10 p.m. in 30 years to give the probability that any one contingent hour would fall at a time when the ambient temperature and wind velocity would produce any appreciable annealing. This probability is then multiplied by 600 to give the probable hours of actual operation under contingent loading. The total probable hours of operation at the contingent ratings were then spread on the basis of probability of their occurrence and are shown in the third column of Table IV. The probable hours, together with the appropriate temperatures, are used to compute the annealing during contingent loading. The annealing is computed in the same step- 772 by-step method as for the normal rating. From Fig. 3, this resulted in an additional 10.2% loss of tensile strength. Final Conductor Ratings From the curves of Fig. 3, it is seen that the total annealing was 15.9%, which was beyond the allowable limits of 12% to 15%. Adjustments for the normal and contingent ratings therefore had to be made. Because an infinite number of ratings could be developed for the normal and contingent ratings and still be within the limits set for allowable annealing, it was decided to set temperature limits for the conductor at normal and contingent loading. As noted in the conclusion, ratings obtained by annealing limits for different sizes of similar conductors generally resulted in about the same maximum temperature. Normal ratings generally resulted in a conductor temperature of about 140 C with a 90 F ambient air temperature and no wind, and the contingency ratings generally resulted in a conductor temperature of about 180 C with a 90 F ambient air temperature and no wind. Interpolation of the computer data of Table V at these temperatures shows that the normal rating would be 1,075 amperes and the contingent rating 1,285 amperes. Following the same procedure as outlined previously, annealing was again determined for these new ratings and was found to be approximately 12.7% which is within the limits set for allowable annealing. Conductor ratings as calculated for nine ACSR conductors are shown in Table VI. References 1. AMPERE LOAD LIMITS FOR COPPER IN OVERHEAD LINEs, A. H. Kidder, C. B. Woodward, AIEE Transactions, vol. 62, Mar. 1943, pp. 148-52. 2. ALCOA ALUMINUM OVERHEAD CONDUCTOR ENGINEERING DATA. Aluminum Company of America, Pittsburgh, Pa., sect. 5, 1960; sect. 7, 1959. 3. CURRENT-CARRYING CAPACITY oF ACSR, H. E. House, P. D. Tuttle. AIEE Transactions, pt. III (Power Apparatus and Systems), vol. 77, 1958 (Feb. 1959 section), pp. 1169-77. 4. HEATING AND CURRENT-CARRYING CAPACITY OF BARE CONDUCTORS FOR OUTDOOR SERVICE, 0. R. Schurig, C. W. Frick. General Electric Review, Schenectady, N. Y., 1930, pp. 141-57. Discussion E. Jaboolian (Gibbs & Hill, Inc., New York, N. Y.): The authors have presented a comprehensive method for calculating conductor ratings to be used for any transmission line where adequate weather conditions can be determined. Their method, in general, equates accumulated annealing with conductor currents under existing long-time ambient temperature and wind conditions. It is a very timely paper, since many operating companies now feel that published ratings are too conservative, and consequently, allow higher currents in both new and existing lines. However, these increases have often been based on judgment and experience. The method, as outlined by the authors, permits a rigorous answer. It is interesting to note that, under the observed conditions of 5 years of Connecticut weather, actual load characteristics of four companies, and a permissible loss of 15% in aluminum tensile strength, the norinal ratings of Table VI average within a quarter of 1 % Alcoa ratings published in Section 6 for rises 40 C to 100 C in a 2-fps wind. Although the averages are equal, for the smaller conductors Table VI ratings are a little lower than Alcoa and for the larger conductors a little higher. The Table VI contingency ratings average 19% higher than the normal with a range of only 117 to 120%. The increase is constant enough to use 119% and omit calculation of contingency annealing, at least for Connecticut weather and the 15% tensile loss limit. The paper states that, "based upon the line design and its economic life, it should be possible to state the loss of tensile strength that can be permitted over the life of the conductor." Evidently, the authors derived the annealing limits for the conductors studied to be economically 15% for the aluminum portion or 7 to 8% when the tensile strength of the steel core was included. This raises the question: Why not pick a conductor with more percentage steel so that the aluminum could be permiitted to anneal far enough to contribute much less, or even none, of the tension required in the total conductor because of sag considerations? The loss of tensile strength then in the aluminum would not be a limitation. The new limit would be the ability of all types of compression hardware, bolted clamps, splices, etc., to preserve their tightness on completely annealed aluminum. With the hardware, rather than the aluminum strength, limiting the conductor temperatures, much higher ratings could be tolerated, at least for the contingency basis. Theoretically, the 15% loss in tensile strength limitation could become 100%. It should be realized that the ratings of Table VI are based on 15% annealing in 30 years. An economic life of more than 30 years, other conditions remaining the same, would lower the ratings. However, the method described can be applied to any annealing and life condition. If the assumed conditions result in ratings much higher than nominal, economics should be studied so that the 12R loss in dollars is not more than the annual investment charges would be for a larger wire with less losses. As a final comment, it is hoped that the NESC (National Electric Safety Code) will define more rigorously their required vertical clearances. The Code now defines clearances for bare wire sags at 60 F corrected for voltages and maximum sag increase. Presumably, these requirements are stringent enough to allow for greater sags under higher wire temperatures. However, it would be more satisfactory to specify the minimum clearance under any condition of wire temperature so that the various utilities would not have to use varying judgments for hot-wire clearance. Peter Ralston (Hydro-Electric Power Commission of Ontario, Toronto, Ont., Canada): The problem of annealing aluminum and ACSR conductorsunder high loads isone that Beers, Gilligan, Lis, Schamberger-Conductor Ratings OC-TOBER 1963 Authorized licensed use limited to: CHILECTRA. Downloaded on May 13,2010 at 15:48:10 UTC from IEEE Xplore. Restrictions apply. Fig. 4. Ampacity of 795MCM (Drake) ACSR operating at 160 F (71 C) with varying wind speeds %TIME AMPACITY IS LESS THAN ORDI NATE Fig. 5. Ampacity of 795 MCM (Drake) ACSR on per cent of time base operating at 160 F (71 C). (Computed from Malton, Ont., weather data, 1947-1961 included) A-Winter season, Novem. ber-March included B-Summer season, Apri 1October included has been with us for some time, particularly with older transmission lines which are expected to carry loads greater than they were designed for. The authors have made a significant contribution in this direction by attempting to establish the amount of annealing on a statistical basis. In principle, the approach appears to be sound, although details raise questions. The authors assume that the maximum normal loading occurs for not more than 5% of the hours in the life of the conductor, anid calculate the amount of annealing under normal loading on that basis. Do they consider that somewhat lesser loads, say 80% to 95% of normal maximum, have no annealing effect? The authors also assume that with the loads of the order contemplated no annealing can take place if the effective wind is greater than 3 fps. To explain what is intended by these two comments, Fig. 4 of this discussion shows the current-carrying capacity of a 795-MCM 26 X 7 Drake conductor at 160 F, with varying wind speeds and ambient temperature. This corresponds to a conductor temperature of 71 C, which is just above what is treated in this paper as the start of the annealing range. Since these curves have been calculated by the use of slightly different values of solar. absorption and emissivity, with wind speeds in miles per hour rather than fps, an exact comparison cannot be made with the data given in the paper. Nevertheless, they are close enough to illustrate the point. It can be seen that at 1,075 amperes (the normal rating assigned to this conductor by the authors), when the ambient temperature is high, effective wind speeds up to 5 mph (or 7 fps) must be taken into consideration when calculating the number of hours in the annealing range. Similarly, loads as low as 80% of the normal rating (860 amperes) can bring the conductor into the annealing range. Thus, the shape of the load curve should be considered. For instance, Table VII is an approximate tabulation taken from a typical daily load curve of one of Ontario Hydro's stations. It can be seen that the load can be more than 80% of the daily peak for more than 29% of the time. This is not an extreme case, the daily load factor being higher on a system basis. This illustrates the importance of considering the load-duration curves of the system being studied. One also wonders whether the contingent ratings assigned by the authors might be Fig. 5 shows the unduly restrictive. ampacity of Drake conductor at 71 C against per cent of time, based on an analysis of the Malton, Ont., weather records for the period 1947-1961, inclusive. It can be seen that even with such a low conductor temperature most of the time the ampacity is well above the contingent rating of 1,285 amperes during the winter season. Although it might not be economic to operate lines normally with higher loads, at times it may be necessary. At such times nomograms such as suggested by Waghorne and Ogorodnikov might prove valuable.' It would be interesting to see the results of a study along lines similar to the method suggested in this paper, whereby the prob- ,OCTOBERR 1963 ability of high loads occurring coinicident with adverse weather conditions is taken into account. Would the authors care to comment on the feasibility of such a study? Perhaps some utilities are already unknowingly operating their lines in a partially annealed state. This hlso raises the question of how far we should go in this direction, perhaps even as far as fully annealed aluminum. Precisely what are the problems involved, and how can these problems best be solved? It is perhaps time that we had some of the answers, so that the problem of whether to anneal or not to anneal can be decided strictly on the basis of economics rather than by limitations in technology. Another very significant point is mentioned by the authors. The loads which they suggest for various conductors can, under some conditions, raise the conductor temperature to 140 C for normal ratings, and up to 180 C for contingency ratings. Would the authors care to comment on which is the governing consideration, and on what basis they would design lines with regard to sags and clearances? That is, although the contingencies mlight be of such short duration that the amount of annealing can be neglected, the high conductor temperature will, of course, cause greater sag. This discusser would like to see permissible clearances reduced during "contingencies," and taking this one step further, let any adverse weather conditions worse than 90 F and 2-fps wind also be considered a contingency, even with nortmal loads. REFERENCE 1. CURRENT CARRYING CAPACITY OF ACSR CONDUCTORS, J. H. Waghorne, V. E. Ogorodnikov. AIEE Transactions, vol. 70, pt. II, 1951, pp. 115962. D. H. Sandell (Aluminum Company of America, Pittsburgh, Pa.): The authors have shown effectively that fundamental laboratory test data and basic engineering analyses can be applied to specific problems relating to normal and emergency conductor current ratings. They have correctly concluded that each electric system must be analyzed individually in order to determine safe current ratings. For the general case, we believe it is somewhat risky to plan even contingent current ratings that will result in conductor temperatures above 300 F (150 C). The authors correctly analyze the behavior of the conductor mechanical properties at higher temperatures, but sometimes weak links in the circuit, such as possibly splices or clamps, can fail at these high contingent Table VIl. Duration of Loads as Percentage of Daily Peak Duration, Percentage of Peak 100 96 93 86 80 Total. Hours Percentage of Day 1...1............. 4.17 1............... 4.17 2.............. 8.34 ... ... 1.............. 4.17 2.............. 8.34 . . .. .. 7............. 29.19 Beers, Gilligan, Lis, Schamberger-Conductor Ratings Authorized licensed use limited to: CHILECTRA. Downloaded on May 13,2010 at 15:48:10 UTC from IEEE Xplore. Restrictions apply. 773 Table Vil. Comparison of Conductor Clearance to Ground for Elevated Temperature Operation (2) (1) Maximum ACSR Conductor Size and Stranding Dfsign Tension, Pounds (3) Span Length, Feet 230-K? Lines: 954 MCM 54/7 ....... 12,000 ....... 138-Kv Lines: 477 MCM 30/7 ........ 9,000 ....... 795 MCM 45/7 ........ 9,000 69-Kv Lines: (5) 5th Edition 6th Edition NESC NESC (6) Sag (Feet) 60 F (7) (8) (9) Increase Over Sag at 60 Degrees (Feet) 120 F 200 F 300 F (10) Required Clearance at Elevated Temperature* (11) (12) Clearance of Line Designed Under 5th Edition NESC When Operating at 200 Ft 300 Ft 600 ...... 30.5 ...... 25.73 ........ 10.0 ....... 3.0 ..... 5.5 ...... 7.5 ....... 22.73 ....... 25.0 ...... 23.0 800 ... 30.5 ...... 25.73 ... 30.5 ...... 25.73 ... 18.0 .. 28.0 .. 3.3 . 4.0. 6.3 7.9 ...... ...... 9.0. 10.4 .. 600 . 800 .. 8.2 . 26.07 ... 23.38 ... 26.07 . 23.38 . 16.0 .... 26.0 ... 26.07 . 23.38 . 26.3 ...... 23.8 ........ 14.8 . 2.9 . 3.0 . 3.0 . 3.2 . 4.8 ...... 5.0 ...... 5.8 ...... 6.7 ...... 6.9 . 7.9 ... 8.4 ... 9.1 . 1,000 ... 1,000 .. 3,000 . 4/0-6/1 .......... 336.4 MCM 18/1 ...... 4,000 . * (4) Required Ground Clearance (Feet) at 60 F 660 . 22.43 ... 21.73 ... 24.2 ...... 21.5 22.6 ...... 20.10 20.48 ....-.21.27 .... 21.07 . 20.38 . 20.38 . 20.27 . 20.6 ........ 19.6 ..... 19.17 18.17 17.67 17.2 250 . 22.2 ...... 21.5 ........ 2.5 .. 1.8 . 2.4 ...... 3.3 . 19.7 ........ 19.8 ..... 18.9 350 ...... 22.2 ...... 21.5 ........ 5.8........ 2.0...... 2.7 ...... 4.0 ........ 19.5 ........ 19.5 ...... 18.2 2.2 . 4.65 ...... 7.1 . 350 . 22.4 ...... 21.6 ........ 4.7 . 19.4 ........ 17.75.;.....15.3 Column (5) less column (7). t Column (4) less column (8). 2 Column (4) less column (9). temperatures. Any temperature limita- tion selected is, of course, arbitrary. We have selected 300 F for purposes of standardization when making sag and tension computations, and this standard could also be used for evaluating any device that would be used on the conductor. We have also selected 200 F (93 C) for maximum normal temperature and use this for making sag-tension computations. Aluminum will be significantly annealed above 200 F, as indicated in reference 2 of the authors' paper. C. Robert North (Philadelphia Electric Company, Philadelphia, Pa.): The Philadelphia Electric Company has employed probability theory in rating of aerial conductors for approximately 20 years. The basic principles and data used in these ratings were published in 1943 in reference 1 of the paper. Our experience with the ratings based on these principles has been very good and investment in oversized conductors has been avoided. The Philadelphia Electric Company has initiated a review of weather conditions similar to that outlined in the paper. The methods described should be most helpful in setting up the data handling for digital-computer anialysis. It is unfortunate that accurate wind velocity data could not be obtained at the critical conditions of less than 4 knots. The authors made a logical assumption in adjusting the curve of Fig. 1 of the paper. However, confirmation of this critical region would be very valuable since it is so important to the conclusions. Whenever preparing standard ratings for conductors on a system, or area-wide, basis it is necessary to make a number of very broad assumptions, such as loss of. aluminum strength to be tolerated due to annealing, hours of the day during which critical weather conditions could occur, factors for variations in wind velocities over the area served, percentage of total hours that the conductors will operate at the normal rating, and the probable number of hours of contingency or emergency operation. Each designer must choose the values which will most nearly describe the actual service conditions. His choices will greatly affect the answers provided by the computers in the 774 form of printed out ampacity tables. The Philadelphia Electric Company has used aerial conductor ratings generally higher than any other utility that has come to our attention. The calculation methods used, apart from the assumptions mentioned, yield results comparable to our ratings, indicating agreement on method. Loss of strength in the aluminum strands is important in determining pernlissible ratings, but there are other factors to be considered. Recent tests conducted by the Philadelphia Electrid Company on 4/0 Awg (American wire gage) 6/1 Penguin ACSR conductors indicated that the aluminum strands actually go into compression and "birdcage" from the steel strand. For this conductor birdcaging occtrs at a temperature of approximately 100 C when installed with standard sags. At this temperature the steel strand is supporting 100% of the weight of the conductor. After 4 consecutive hours of operation at 140 C, the aluminum strands tightened around the steel core when cooled to ambient. After 4 consecutive hours of operation at 170 C, the aluminum strands failed to tighten around the steel core wire. If this should occur in service, the core would be exposed to possible corrosion and the increased diameter would permit a larger build-up of sleet or ice exceeding the design limits at a time when the conductor is actually in a weakened condition. The harmful effects of residual birdcaging of the aluminum strands must be considered when there is a possibility of ACSR conductors operating at teniperatures above 140 C. Actually, the temperature at which this effect becomes harmful will vary with the conductor strand make-up and the installation conditions. R. H. Sarikas and Z. J. Andracki (Illinois Power Company, Decatur, Ill.): The authors note in their paper that when operating at elevated temperatures there is an increase in sag and this results in reduced clearances over ground, as well as other utility lines. We would be interested in knowing the policy used in determining the' amount of clearance reduction permitted without taking remedial action. The NESC specifies the required clearance at 60 F, and then makes provision by the use of the so-called "maximum sag increase" for increasing the required clearance by an amount very nearly equal to the difference between 60 F final sag and 120 F final sag or sag under heavy load conditions, for all spans of the length ordinarily associated with transmission lines. While not stated in the language of the code, the intent appears to be one of basing clearance requirements at 60 F on the assumption that the line will not operate at temperatures much in excess of 120 F. As a consequence, it seems appropriate to provide additional clearance if conductor temperatures are to exceed 120 F by a significant amount. An appropriate increase, in the opinion of the. discussers, is one that will provide an absolute minimum clearance equal to that required under the 6th edition at 120 F. Table VIII of this discussion shows pertinent data for operation at 200 F and 300 F, respectively, for ACSR conductor sizes in common use on 230-, 138-, and 69-kv lines. Since most existing lines have been built with the clearances specified in the 5th edition of the NESC, use of the reduced clearances permitted under the 6th edition may permit operation at the elevated temperatures and still meet the criterion suggested by the discussers. Table VIII of this discussion shows that an existing 230-kv line using 954-MCM 54/7 ACSR conductor constructed under the 5th edition of the NESC can be operated at 200 F without modification but not at 300 F. A 138-kv line could operate at 200 F with slight modification, depending upon span length and conductor type, but could not operate at 300 F. Most 69-kv lines would require modification to operate at 200 F. Operation at elevated tenperatures will probably discourage the use of all aluminum conductors in view of the large sag increase and possible annealing associated with such conductors. If the authors design initially for increased clearances, has the relative economics of increased conductor size versus increased structure height been compared? Also, if additional clearances are provided, what efforts have been made to insure that the future construction of other utilities will not then begin to encroach uponl these additional clearances? Beers, Gilligan, Lis, Schamberger-Conductor Ratings OCTOBER 10863 Authorized licensed use limited to: CHILECTRA. Downloaded on May 13,2010 at 15:48:10 UTC from IEEE Xplore. Restrictions apply. G. M. Beers, S. R. Gilligan, H. W. Lis, and J. M. Schamberger: There has been some indication on the authors' systems that failures of splices can and do occur under normal daily loadings more often than under extreme conditions. This is probably because of the very infrequent occurrence of the extreme conductor temperatures and the fact that a deteriorating splice matures to failure in the long normal periods. Mr. Sandell's arbitrary limit of 300 F is practically coincident with the limitation established for ACSR (356 F) in that there are only 7 hours in 30 years when conductor temperatures in the 300 F-356 F range are expected. There did not seem to be any practical load limit that would guarantee no failures of joints. As Mr. Jaboolian notes, similar types of conductors attained fairly uniform per-cent normal and contingency ratings over other base figures. The authors have used this feature to obtain ratings for intermediate conductors without the full sequence of calculation. The limiting loss of tensile strength was broadly set at between 5% and 10% of the initial value without economic analysis. It was felt that this would be a practical amount of annealing which could be absorbed by both existing plant and future designs without special provisions. One deterrent from greater annealing is the fact that each increment of loss of strength produces an even smaller marginal increase in rating. This is because the heating increases with 12, and annealing accelerates with increased temperature,, at least until most of the cold worked strength is gone. Mr. Jaboolian, Mr. Ralston, Mr. Sarikas, and Mr. Andracki all raise the question about clearances at high temperatures and the interpretation of the NESC. The authors' companies presently follow the policy outlined by Mr. Sarikas and Mr. Andracki; namely, that the calculated sag increase (all, not 75%) between 120 F and the maximum expected operating temperature (356 F for ACSR) is added to the 60 F sag determined from NESC 6th editioil. This results in no less clearance than the Code provides at 120 F operation. On the practical side, we felt that the 120 F 6th edition Code clearances, particularly at wire crossings, were the smallest values we could accept under present operating and construction practices. Our experience with designs based on these higher temperatures indicates a penalty of about 5 feet of additional structure height at 115 kv. Mr. North comments on the possibility of permanent birdcaging of a single layer ACSR at or about 170 C (338 F). This would seem to add further emphasis to Mr. Sandell's suggested 300 F limit and indicates that only very limited operation should be permitted at these temperatures. We feel that there is very little probability of obtaining anything like 4 hours of continuous operation at 170 C. Mr. Ralston is quite correct in saying that some additional conductor annealing will take place (a) with wind velocities above 3.0 fps and (b) at loading less than maximum normal rating. The amount of this additional annealing is insignificant, however, when the annealing curves are considered. For example, in a rigorous calculation, there will be about 415 hours of additional operation at normal loading (1,075 amperes) when winds are between 3.0 and 5.5 fps, which will produce conductor temperatures of 65 C to 85 C. These hours, when plotted on the annealing curves, along with the hours of higher conductor temperature, reduce the tensile strength of the aluminum from 25,570 psi to 25,560 psi--a truly insignificant amount. It is characteristic of this annealing property that a very few hours at high annealing temperatures will overshadow many hours at the low temperatures. This same characteristic applies to annealing accumulations at loads lower than normal maximum. For example, if we assume another 5% (of 30 years) block of hours at 900-ampere operation (84% of Radio Interference from Lines High-Voltage Part 11-Distri6ution and Correlation R. J. MATHER SENIOR MEMBER IEEE Summary: Randomly varying quantities, contingent upon other independent variables, are not amenable to easy analysis. Continuously recorded radio noise data collected from operating lines over a 3-year period have been subjected to statistical techniques. Some anticipated relationships were established; others failed to be verified. The results presented are based upon records obtained at two high-voltage levels and with three different single-conductor diameters. OCTOBER 1 963 B. M. BAILEY MEMBER IEEE SCIENTIFIC research normally involves one of two general approaches: deductive or inductive. One either may postulate a general relationship and test the experimental results for validity, or avoid basic premises and derive conclusions from the experimental results regardless of their apparent logic. Many times, certain relationships have been maximum), it turns out that there are only 305 additional hours when the conductor will be at 65 C or above, and most of these are at 65, 70, and 75 C. The additional annealing is so small that it cannot be measured on the graphical plot. All of these are fortutnate circumstances and permit considerable simplification of the assumptions. Mr. Ralston's comparison of the yearround contingency rating of 1,285 amperes (in effect determined by summer load requirements in southern New England) with the winter capabilities of the same conductor in Ontario, seems to emphasize the need to analyze weather, loads, and operating practices in establishing the basis of line ratings. If variable rating charts are used (and Mr. Ralston does not explain how he uses his), it would seeni to require continuous analysis of load and weather. It does not seem practical to rate a line at 1,400 amperes one day, and 1,000 amperes the next day, unless loads are somehow controlled or interruptible. In the method we have outlined, it was assumed that weather and loads were independent random variables having the distribution characteristics outlined. As Mr. Ralston suggests, this is probably not the case. We know, for example, that system loads tend to increase with extremes of temperature. Seemingly, many systems might have available enough data to permit more refined analysis of these relationships. On the other hand, as we have discussed previously, great refinement of data or method is not likely to produce more than a small increase in rating; a rapidlv diminishing return. Several discussers have touched on the economic aspects of line loadings. For any new line, the conductor should be selected on the basis of a sound application of engineering economics. The authors' companies presently design all new construction with adequate clearances to permit the use of contingent conductor ratings. accepted as axiomatic and only the data which seemed to confirm this relationship were accepted and published. Both the deductive and inductive approach have value and have influenced radio noise investigations, but the authors feel that the intuitive attitude has predominated in much of the published literature. Adams' series of papersl-3 estabPaper 63-92, recommended by the AIEE Transmission and Distribution Committee and approved by the AIEE Technical Operations Department for presentation at the IEEE Winter General Meeting, New York, N. Y., January 27-February 1, 1963. Manuscript submitted April 17, 1962; made available for printing November 20, 1962. R. J. MATHER is with the Federal Power Commission, Washington, D. C.; and B. M. BAILEY is with the Bonneville Power Administration, Portland, Oreg. The authors wish to express their appreciation to M. G. Poland, through whose efforts these data were obtained, and to many other members of the Bonneville Power Administration, who assisted in designing and maintaining the complex instrumentation necessary for collecting the information. Oather, Bailey-Radio Interference from High- Voltage Lines-I7 Authorized licensed use limited to: CHILECTRA. Downloaded on May 13,2010 at 15:48:10 UTC from IEEE Xplore. Restrictions apply. 775
© Copyright 2026 Paperzz