Roof Exhaust Performance and Dimensional Data XRED

Roof Exhaust
Performance and Dimensional Data
XRED-060 and 065 - Direct Drive
193/8
(492)
*121/8
(308)
13/4 (44)
17
(432)
cfm
Damper Size = 8 x 8 (203 x 203)
Roof Opening = 101/2 x 101/2 (267 x 267)
^Approximate Unit Weight = 18 lbs. (8 kg)
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Static Pressure (in. wg)
Fan
RPM
XRED-060-E
1/200
1050
XRED-060-G
1/100
1300
XRED-060-D
1/60
1550
XRED-065-E
1/100
1050
XRED-065-G
1/60
1300
XRED-065-D
1/30
1550
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
0
138
0.00
1.7
170
0.01
2.9
203
0.01
4.2
187
0.01
2.2
231
0.01
3.2
276
0.02
4.9
0.05
116
0.00
1.7
153
0.01
2.8
188
0.01
3.9
161
0.01
2.1
211
0.01
3.1
259
0.02
4.6
0.1
90
0.01
1.7
135
0.01
2.8
173
0.01
3.8
130
0.01
1.9
189
0.01
3.0
241
0.02
4.5
0.125
73
0.01
1.7
125
0.01
2.7
166
0.01
3.8
110
0.01
1.8
178
0.01
2.9
232
0.02
4.5
0.15
53
0.01
1.7
113
0.01
2.7
158
0.02
3.8
87
0.01
1.7
163
0.01
2.9
223
0.02
4.4
0.2
0.25
0.3
85
0.01
2.6
140
0.02
3.7
120
0.02
3.7
92
0.2
3.6
130
0.01
2.8
201
0.02
4.3
92
0.01
2.7
176
0.02
4.3
145
0.02
4.1
0.375
0.4
96
0.02
4.0
­­­
Performance
certified is for installation Type A Free inlet, Free outlet. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for installation Type A Free inlet fan sone levels.
[ 235 ]
Roof Exhaust
Performance and Dimensional Data
XRED-070 and 075 - Direct Drive
193/8
(492)
*121/8
(308)
13/4 (44)
17
(432)
Damper Size = 8 x 8 (203 x 203)
Roof Opening = 101/2 x 101/2 (267 x 267)
^Approximate Unit Weight = 18 lbs. (8 kg)
cfm
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Static Pressure (in. wg)
Fan
RPM
XRED-070-E
1/100
1050
XRED-070-G
1/60
1300
XRED-070-D
1/30
1550
XRED-075-E
1/80
1050
XRED-075-G
1/50
1300
XRED-075-D
1/25
1550
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
0
253
0.01
2.7
314
0.01
4.1
374
0.02
5.6
297
0.01
3.6
367
0.02
4.1
438
0.03
6.1
0.05
226
0.01
2.1
292
0.1
3.7
356
0.02
5.4
260
0.01
3.1
338
0.02
3.9
413
0.03
5.8
0.1
195
0.01
1.7
269
0.02
3.4
337
0.02
5.2
222
0.01
2.9
309
0.02
3.7
389
0.3
5.6
0.125
179
0.01
1.5
2557
0.02
3.3
327
0.03
5.2
200
0.01
2.8
293
0.02
3.7
377
0.04
5.4
0.15
152
0.01
1.2
244
0.02
3.2
317
0.03
5.1
176
0.01
2.6
277
0.02
3.7
364
0.04
5.3
0.2
0.25
0.3
0.375
214
0.02
2.9
297
0.03
4.9
171
0.02
2.6
274
0.03
4.7
244
0.03
4.5
190
0.03
4.1
241
0.02
3.6
337
0.04
5.1
195
0.02
3.5
309
0.04
4.9
277
0.04
4.9
214
0.03
4.8
0.4
­­­
Performance
certified is for installation Type A Free inlet, Free outlet. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for installation Type A Free inlet fan sone levels.
[ 236 ]
Roof Exhaust
Performance and Dimensional Data
XRED-080 and 085 - Direct Drive
213/4
(552)
*145/8
(371)
13/4 (44)
17
(432)
cfm
Damper Size = 10 x 10 (254 x 254)
Roof Opening = 121/2 x 121/2 (318 x 318)
^Approximate Unit Weight = 26 lbs. (12 kg)
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Static Pressure (in. wg)
Fan
RPM
XRED-080-E
1/40
1050
XRED-080-G
1/30
1300
XRED-080-D
1/20
1550
XRED-085-E
1/40
1050
XRED-085-G
1/30
1300
XRED-085-D
1/20
1550
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
0
335
0.01
3.8
415
0.02
5.4
495
0.04
7.3
398
0.01
4.0
493
0.02
5.5
588
0.04
7.6
0.1
268
0.02
3.7
361
0.03
5.4
450
0.04
7.3
326
0.02
3.9
436
0.03
5.3
541
0.04
7.4
0.125
249
0.02
3.6
348
0.03
5.4
439
0.04
7.3
307
0.02
3.9
420
0.03
5.3
528
0.05
7.4
0.15
230
0.02
3.7
333
0.03
5.4
427
0.05
7.3
286
0.02
3.9
405
0.03
5.3
515
0.05
7.4
0.2
189
0.02
3.9
303
0.03
5.4
404
0.05
7.3
240
0.02
4.1
375
0.03
5.3
490
0.05
7.4
0.25
134
0.02
4.2
272
0.03
5.5
379
0.05
7.2
179
0.02
4.3
340
0.04
5.3
464
0.05
7.4
0.3
0.375
0.5
239
0.03
5.6
354
0.05
7.3
174
0.03
5.9
314
0.06
7.3
237
0.6
7.6
302
0.04
5.4
439
0.06
7.4
233
0.04
5.5
394
0.06
7.4
308
0.06
7.6
0.625
168
0.06
8.1
­­­
Performance
certified is for installation Type A Free inlet, Free outlet. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for installation Type A Free inlet fan sone levels.
[ 237 ]
Roof Exhaust
Performance and Dimensional Data
XRED-090 and 095 - Direct Drive
213/4
(552)
*145/8
(371)
13/4 (44)
17
(432)
Damper Size = 10 x 10 (254 x 254)
Roof Opening = 121/2 x 121/2 (318 x 318)
^Approximate Unit Weight = 26 lbs. (12 kg)
cfm
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Static Pressure (in. wg)
Fan
RPM
XRED-090-E
1/40
1050
XRED-090-G
1/25
1300
XRED-090-D
1/15
1550
XRED-095-E
1/30
1050
XRED-095-G
1/12
1300
XRED-095-D
1/8
1550
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
0
520
0.01
4.0
644
0.03
5.4
768
0.05
7.6
717
0.03
5.4
888
0.06
7.6
1059
0.10
9.6
0.1
441
0.02
3.9
580
0.03
5.4
714
0.05
7.5
606
0.03
4.5
802
0.06
6.8
987
0.10
9.4
0.125
420
0.02
3.9
565
0.04
5.4
701
0.06
7.5
570
0.04
4.5
780
0.06
6.7
969
0.10
9.3
0.15
398
0.02
4.0
549
0.04
5.4
688
0.06
7.5
534
0.04
4.5
754
0.06
6.6
950
0.11
9.2
0.2
351
0.02
4.1
515
0.04
5.4
662
0.06
7.5
468
0.04
4.4
695
0.07
6.5
912
0.11
9.0
0.25
293
0.02
4.2
478
0.04
5.5
633
0.06
7.4
389
0.04
4.5
640
0.07
6.4
863
0.11
8.8
0.3
0.375
0.5
0.625
440
0.04
5.5
605
0.07
7.4
290
0.03
4.6
586
0.07
6.4
814
0.11
8.7
373
0.05
5.6
557
0.07
7.4
473
0.08
7.4
338
0.07
7.8
493
0.07
6.4
745
0.12
8.7
184
0.05
6.8
623
0.12
8.7
474
0.11
8.7
­­­
Performance
certified is for installation Type A Free inlet, Free outlet. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for installation Type A Free inlet fan sone levels.
[ 238 ]
Roof Exhaust
Performance and Dimensional Data
XRED-101 and 121 - Direct Drive
245/8
(625)
*20
(508)
13/4 (44)
19
(483)
cfm
Damper Size = 12 x 12 (304 x 304)
Roof Opening = 141/2 x 141/2 (368 x 368)
^Approximate Unit Weight = 43 lbs. (20 kg)
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Static Pressure (in. wg)
Fan
RPM
XRED-101-C
1/8
860
XRED-101-B
1/6
1140
XRED-101-A
1/4
1725
XRED-121-C
1/8
860
XRED-121-B
1/6
1140
XRED-121-A
1/4
1725
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
0
766
0.02
4.3
1015
0.05
7.1
1536
0.17
12.1
922
0.03
5.6
1222
0.06
8.1
1849
0.22
14.1
0.1
625
0.03
4.2
917
0.06
7.0
1470
0.18
11.9
767
0.03
5.2
1107
0.07
7.9
1772
0.23
14.0
0.125
588
0.03
4.2
893
0.06
7.0
1454
0.19
11.8
723
0.04
5.2
1078
0.07
7.9
1753
0.24
13.9
0.25
0.3
0.375
0.5
0.625
0.75
747
0.06
6.8
1374
0.20
11.6
450
0.04
5.2
918
0.08
7.8
1659
0.25
13.8
683
0.06
6.8
1340
0.20
11.5
569
0.06
6.6
1277
0.20
11.3
1181
0.21
11.2
1086
0.22
11.3
974
0.22
11.7
848
0.09
7.8
1621
0.26
13.6
734
0.09
8.1
1560
0.27
13.4
335
0.07
9.8
1453
0.28
13.4
1341
0.29
13.4
1223
0.3
13.4
1
911
0.29
14.1
­­­
Performance
certified is for installation Type A Free inlet, Free outlet. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for installation Type A Free inlet fan sone levels.
[ 239 ]
Roof Exhaust
Performance and Dimensional Data
XRED-131 and 141 - Direct Drive
287/8
(733)
*20
(508)
13/4 (44)
22
(559)
Damper Size = 16 x 16 (406 x 406)
Roof Opening = 181/2 x 181/2 (470 x 470)
^Approximate Unit Weight = 59 lbs. (27 kg)
cfm
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Static Pressure (in. wg)
Fan
RPM
XRED-131-C
1/8
860
XRED-131-B
1/6
1140
XRED-131-A
1/2
1725
XRED-141-C
1/8
860
XRED-141-B
1/6
1140
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
0
1193
0.04
6.5
1581
0.094
9.9
2393
0.325
19.2
1376
0.055
6.8
1824
0.129
10.4
0.1
1050
0.049
6.1
1482
0.105
9.8
2340
0.339
18.9
1205
0.064
6.6
1701
0.141
10.4
0.125
1011
0.051
6.0
1452
0.108
9.7
2327
0.342
18.9
1161
0.066
6.5
1667
0.144
10.3
0.25
771
0.056
5.9
1304
0.12
9.4
2225
0.366
18.4
919
0.074
6.4
1498
0.158
9.8
0.3
626
0.055
5.9
1239
0.123
9.2
2186
0.376
18.4
798
0.074
6.6
1425
0.163
9.5
0.375
0.5
0.625
0.75
1
1130
0.13
9.0
2127
0.389
18.2
489
0.063
8.0
1314
0.17
9.1
889
0.129
8.8
2030
0.407
18.1
1931
0.423
18.1
1817
0.426
17.8
1555
0.453
17.4
1113
0.175
8.7
794
0.158
8.4
­­­
Performance
certified is for installation Type A Free inlet, Free outlet. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for installation Type A Free inlet fan sone levels.
[ 240 ]
Roof Exhaust
Performance and Dimensional Data
XRED-150 and 160 - Direct Drive
351/2
(902)
*211/8
(537)
13/4 (44)
26
(660)
Model XRED-150
Damper Size = 16 x 16 (406 x 406)
Roof Opening = 181/2 x 181/2 (470 x 470)
^Approximate Unit Weight = 59 lbs. (27 kg)
cfm
351/2
(902)
*215/8
(549)
13/4 (44)
30
(762)
Model XRED-160
Damper Size = 18 x 18 (457 x 457)
Roof Opening = 201/2 x 201/2 (521 x 521)
^Approximate Unit Weight = 81 lbs. (37 kg)
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Static Pressure (in. wg)
Fan
RPM
XRED-150-C
1/8
860
XRED-150-B
1/4
1140
XRED-160-C
1/8
860
XRED-160-B
1/3
1140
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
0
1772
0.09
7.9
2349
0.21
11.7
2008
0.10
8.0
2662
0.23
13.6
0.1
1598
0.09
7.8
2217
0.21
11.6
1828
0.11
7.7
2521
0.25
13.4
0.125
1553
0.10
7.8
2185
0.21
11.6
1784
0.12
7.7
2489
0.25
13.4
0.2
1415
0.12
7.5
2085
0.21
11.3
1637
0.13
7.5
2392
0.27
13.3
0.25
1304
0.12
7.4
2017
0.23
11.1
1535
0.13
7.4
2319
0.28
13.1
0.3
1194
0.13
7.5
1949
0.25
11.0
1421
0.13
7.3
2245
0.28
13.1
0.375
1005
0.13
7.7
1836
0.27
10.9
1230
0.14
7.3
2135
0.29
13.1
.5
.625
.75
1628
0.29
11.2
1397
0.29
11.8
1114
0.28
12.8
1933
0.31
12.9
1697
0.32
12.7
1411
0.32
12.6
­­­
Performance
certified is for installation Type A Free inlet, Free outlet. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for installation Type A Free inlet fan sone levels.
[ 241 ]
Roof Exhaust
Performance and Dimensional Data
XRED-170 and 180 - Direct Drive
351/2
(902)
*215/8
(549)
13/4 (44)
30
(762)
Models XRED-170
Damper Size = 18 x 18 (457 x 457)
Roof Opening = 201/2 x 201/2 (521 x 521)
^Approximate Unit Weight = 81 lbs. (37 kg)
cfm
351/2
(902)
*223/4
(578)
13/4 (44)
30
(762)
Model XRED-180
Damper Size = 18 x 18 (457 x 457)
Roof Opening = 201/2 x 201/2 (521 x 521)
^Approximate Unit Weight = 118 lbs. (54 kg)
All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight
shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Static Pressure (in. wg)
Fan
RPM
XRED-170-C
1/4
860
XRED-170-B
1/2
1140
XRED-180-C
1/3
860
XRED-180-B
3/4
1140
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
cfm
Bhp
sones
0
2572
0.172
9.7
3409
0.4
16.3
3240
0.24
12.1
4295
0.559
19.5
0.1
2379
0.187
9.6
3263
0.421
16.2
3053
0.262
12.4
4156
0.589
19.4
0.125
2330
0.191
9.5
3227
0.426
16.2
3002
0.268
12.4
4121
0.596
19.4
0.25
2077
0.208
9.2
3043
0.45
16.1
2733
0.296
12.5
3933
0.634
19.3
0.3
1961
0.214
9.1
2969
0.46
16.1
2603
0.306
12.5
3855
0.649
19.5
0.375
1782
0.223
9.1
2857
0.473
16.1
2390
0.321
12.3
3731
0.671
19.7
0.5
1416
0.228
9.1
2647
0.494
16.1
1978
0.332
11.9
3509
0.707
19.8
0.625
0.75
1
2428
0.514
16.1
1438
0.316
11.9
3241
0.74
20
2181
0.532
16.1
1457
0.488
17.2
2971
0.771
20
2246
0.759
21
­­­
Performance
certified is for installation Type A Free inlet, Free outlet. Performance ratings include the effects of a birdscreen in the airstream. The sound ratings shown are loudness
values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation Type A Free inlet fan sone levels.
[ 242 ]