Time synchronization (1 msec) of PowerLogic

Time synchronization (<1 msec) of
PowerLogic CM4xxx, CM3xxx, PM870
Trimble AcutimeTM Gold GPS
Antenna (”Smart Antenna”)
RS-422 signal,
Antenna interface cable: CAB-ACU-xxx
xxx = length (50, 100, 200 or 400 feet)
STR-100
Satellite Time Reference
Satellite Time Reference
DCF OUT
PWR
24Vdc
9
9
&ODVV
32:(56833/<
/
1
GPS INTERFACE
DCF
SYNC
CH 1
STAT
CH 2
DCF77
IRIG-B input
(modulated)
DCF77
Daisy-chain wiring, Belden 8760 cable
or equivalent, 1000 feet (300m) max.
*
24Vdc power supply
(e.g., PS-24V-15W or PS-24V-50W)
1 to 16
devices
1 to 16
devices
DCF77 devices
(e.g., PowerLogicTM meters:
CM4xxx, CM3xxx or PM870)
DCF77 devices
(e.g., PowerLogicTM meters:
CM4xxx, CM3xxx or PM870)
Typical SER system architecture drawing: STR-100 provides time reference for PowerLogic meters