THIS DRAWING IS TO BE READ IN CONJUNCTION WITH THE PERSIMMON EAST WALES DIVISION TECHNICAL SPECIFICATION
Internal Opening Schedule
External Opening Schedule
ISSUE
DATE
-
WALL LEGEND
EXTERNAL CAVITY WALL
328mm overall wall consisting of 100mm aerated concrete blockwork inner skin using Celcon Solar with 'k' value of 0.11 w/m
K and compressive strength of 2.9 N/mm2, 75mm PIR with 'k' value of 0.023 w/m k partial cavity fill insulation board, 50mm
clear cavity, 103mm face brickwork or 100mm reconstructed stone. Inner skin to be lined with 12.5mm plasterboard mounted
on plaster dabs with taped joints for direct decoration.
328
opening
reference
NOTE : ALL EXTERNAL
OPENINGS TO HAVE CHECK
REVEALS
INTERNAL LOADBEARING WALLS
Walls to be Dense concrete blocks 7.0N/mm2 strength.
Walls abutting party walls to be Dense concrete blocks
70
STANDARD PARTITIONS/FIRE RATED PARTITIONS
95mm overall finished comprising of 70x50mm sw or metal studs at 600mm centres (400mm for kitchens & bathrooms) finished
with 12.5mm wallboard drylining with taped joints. Bottom rail to be secured to 70x50mm timber sole.
EXTERNAL
70
INSULATED PARTITIONS
All partitions enclosing bedrooms, bathrooms & WC's to be lined with 25mm mineral wool quilt; Comprising of 70mm sw or metal
studs at 600mm centres (400mm for kitchens & bathrooms) finished with 12.5mm wallboard drylining (to provide sound reduction
to AD Part E). En-suite partitions to associated bedrooms not to be insulated. No insulation to partitions facing on to a
hall/landing.
INDICATIVE PLAN OF OPENING
SCALE 1:10
BRACED
70
BRACED PARTITIONS
114mm overall finished comprising of 70mm sw studs at 600mm centres (400mm for kitchens & bathrooms) with 9.5mm plywood
fixed to each side of stud to brace external wall, finished with 12.5mm wallboard drylining with taped joints.
structural
opening
D1
838 x 1981
934 x 2031
1350
D2
762 x 1981
858 x 2031
1200x215
W1
D3
838 x 1981
934 x 2031
1350x140
W2
D4
838 x 1981
934 x 2031
1350x140
D5
686 x 1981
782 x 2031
D6
838 x 1981
D7
F/R
lintel length
opening
reference
lintel type
Standard
1350
960x1050
Standard
1350
W3
735x1050
Eaves
1050
1200
W4
1298x1200
Standard
1650
934 x 2031
1350
W5
1635x1200
Standard
1950
838 x 1981
934 x 2031
1350x140
W6
960x1050
Eaves
1350
D8
838 x 1981
934 x 2031
1350x140
W7
960x1050
Eaves
1350
D9
686 x 1981
782 x 2031
1200
W8
735x1050
Standard
1050
D10
838 x 1981
934 x 2031
1350
W9 #
1298x1200
Eaves
1650
D11
686 x 1981
782 x 2031
1200
W10 #
1635x1200
Eaves
1950
D12
838 x 1981
934 x 2031
1350
ED1
1010x2100
Standard
1350
ED2
1010x2100
Standard
1350
ob
ob
BY
-
-
lintel size
960x1050
BF Bifold doors
M Modified to suit opening
FOR LINTEL REFS, REFER TO MANUFACTURERS SCHEDULE
PARTY WALLS in accordance with RSD E-WM-20
300mm overall consisting of 2 skins of 100mm, 7N/mm2 Lightweight aggregate blocks (min density 1350kg/m3 / max density
1600kg/m3). 100mm cavity filled with 100mm Saint Gobain-Isover RD Party Wall Roll. Internal face of wall finished with 12.5mm
plasterboard (nominal 9.8kg/m2) mounted on dabs with taped joints to both sides.
300
door size
DIMENSION X
INTERNAL
-
REVISION
NB: ALL LINTELS TO HAVE A MINIMUM OF 150MM BEARING
O Optional window - refer to site layout
# Egress hinges for escape
*SG
Escape windows with removable central mullion
SAFETY GLASS TO WINDOWS & DOORS
Easy Clean hinges
Obscure glazing
E
ob
FOR LINTEL REFS, REFER TO MANUFACTURERS SCHEDULE
EXTERNAL STRUCTURAL OPENINGS (Checked Reveals)
All structural openings to have checked reveals.
Dimensions on floor plans are to brickwork (external skin), allow
25mm to each side of windows/door opening
328
7898
2338
1585
3660
100
3660
328
328
328
3775
3775
1160
328
1814
2014
100
2239
1350
100
960
2014
5884
2370
2685
300
328
665
1358
685
328
665
1814
450
910
REFER TO STRUCTURAL ENGINEERS
DRAWING FOR FOUNDATION INFORMATION
PROVIDE UNDERGROUND DUCTS AS
REQUIRED FOR WATER, ELECTRIC & GAS
SERVICES
100
960
910
7898
140
275
934
Nett Floor Area:
GF:
FF:
TOTAL:
539 sq ft
598 sq ft
1137 sq ft
F
284
318
2175
547 sq ft
608 sq ft
1156 sq ft
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
svp
328
WATER
store
450
1160
100
2464
2240
100
910
1350
2729
100
2370
910
150
885
7898
c.l.
2370
890
782
Gross Floor Area:
GF:
FF:
TOTAL:
kitchen
934
100
3350
2690
1350
store
328
WATER
c.l.
Do Not Scale!
All Dimensions Are In Millimetres Unless
Otherwise Stated
If In Doubt Ask!
This plan is drawn as hand/drawing
150
885
5884
A
All substructure lintels to be 100 x 75mm
pre-stressed concrete lintels. Location to be
co-ordinated with individual plot drainage
879
2014
7898
Substructure Plan
100
284
1041
svp
855
1358
510
782
1175
9884
685
F
gas
riser
BT
D
2626
75
140
7921
7921
7921
140
Underside of precast stairs in store to have
12.5mm plasterboard mass per unit 10kg/m2 on
38x50 sw battens. Void to be filled with an
absorbet layer mineral wool min density 10kg/m3.
328
960
1748
GD-ACC-01
or 02
GD-ACC-01
or 02
bath
1
kitchen
extract
lobby
A SUITABLE NUMBER (AT LEAST ONE ON EACH FLOOR)
OF SELF CONTAINED SMOKE ALARMS MUST BE
INSTALLED. THE ALARMS SHOULD BE
INTERCONNECTED AND FIXED TO THE CEILING IN A
CENTRAL POSITION BUT AT LEAST 300MM FROM ANY
LIGHT FITTING.
THE ALARM MUST BE FIXED STRICTLY IN ACCORDANCE
WITH THE MANUFACTURERS INSTRUCTIONS.
3
1284
shower
extract
B
4
2
1963
198
934
10 11 12 13
6
svp
2144
553
853
4546
3775
271
100
1960
2290
1160
100
DWN
5
LINTEL OVER
gas
riser
9
8
svp
UP
c.l.
328
kitchen
F
100
landing
7
hall
Plots
As
Opp -
553
328
450
electric
riser
BT
store
934
dining
B
510
201
F
1
960
1635
threshold
GD-ACC-01
or 02
riser
electric
svp
B
328
475
threshold
150
lounge
2626
shower
1160
2
106
Beam span
direction
3
901
150
4038
svp
5
4
GD-ACC-01
or 02
3660
PROVIDE POLYTHENE WRAPPED MINERAL WOOL
CAVITY CLOSER FULL HEIGHT OF CAVITY WALL AT
PARTY/EXTERNAL WALL JUNCTIONS AND TOP CAVITY
WALL AND OPENINGS
D
dining
SHW
4038
Beam span
direction
300
100
1350
2626
3350
934
934
275
100
100
782
215
100
100
2125
100
(home office)
934
261
store
100
75
934
858 161
70
140
2150
3350
100
215
1960
1160
3660
1162
328
328
328
261
100
9884
B
1170
1290
932
140
140
215
1170
100
Beam span
direction
SHW
328
9884
Beam span
direction
1585
bed 1
lounge
2365
1760
215
100 510 100
7921
1190
70
215
c.l.
2338
B
3705
3775
3705
2150
10
38
4
100
1295
328
7898
1248
B
bed 1
Beam span
direction
1565
150
300
(home office)
Beam span
direction
1162
1635
3660
1248
328
100
328
3660
328
328
A
c.l.
7921
1565
7898
3350
A
c.l.
PROJECT:
A
St. Vincent's, Monmouth.
Code 3+ House Types
DRG TITLE:
Ground Floor Plan
First Floor Plan
HOUSE TYPE 2.1.1
SUBSTRUCTURE & FLOOR PLANS
JOB NO:
DRG NO:
REV:
1073
C3+2.1.1-1
-
SCALE:
DRN BY:
1:50 @ A1
DATE:
CKD BY:
08/2011
Together, we make a home
Persimmon Homes East Wales Division
Persimmon House,
Llantrisant Business Park,
Llantrisant,
Rhondda Cynon Taff,
CF72 8YP.
Tel:01443 223653 Fax: 01443 237328
Drawing Revisions
THIS DRAWING IS TO BE READ IN CONJUNCTION WITH THE PERSIMMON EAST WALES DIVISION TECHNICAL SPECIFICATION
ISSUE
-
REVISION
BY
-
-
995
1010
-
DATE
1200
1200
Stair Well
W8
Sand/cement Screed reinforced
over angle with mild steel
wrapping fabric to minimise risk of
shrinkage/cracking, as per
manufactures details
150x150x15RSA S275
cast into Stair Flight c/w
100x100x10 flat plate
welded into RSA
1141
13
kitchen
extract
Soft covering to stairs
min 6mm thick securely
fixed (e.g. glued)
12
11
10
9
Underside of precast stairs to have
12.5mm plasterboard mass per
unit 10kg/m2 on 38x50 sw battens.
Void to be filled with an absorbet
layer mineral wool min density
10kg/m3.
2800
8
Bathroom
extract
SVP
SVP
dpc
GL
FOUNDATIONS ARE
SUBJECT TO
CONFIRMATION BY
STRUCUTRAL ENGINEER
OB
E
G
4000
head of window
2800
OB
cill of window
4800
head of window
5010
underside of truss
FAF
Section B-B
2696
floor to floor
kitchen
extract
2100
head of window
2475
underside of concrete planks
shower
extract
E
G
GD-ACC-01 or 02
NOTE: Aluminum flue shield should
be used if the distance between the
boiler flue extract and the RWP is
less than 300 mm.
398
RS
Movement joints indicated for
Clay Brick, Recon Stone and
Render, for other materials
consult Structural Engineer.
RS
42
42
Side Elevation
Front Elevation
398
42
398
RS
7265
1536
7465
1736
Truss Profile
NOTE: For rainwater downpipe locations,
refer to plot specific drawings.
398
O/H
398
398
O/H
7465
span overall wallplates
168 Cant
168 Cant
400mm insulation quilt.
(100mm laid between
chords, 300mm cross
laid over)
RS
3345
stairwell opening
W9
B
9
8
7
ha
nd
6
Underside of precast stairs to
have 12.5mm plasterboard mass
per unit 10kg/m2 on 38x50 sw
battens. Void to be filled with an
absorbet layer mineral wool min
density 10kg/m3.
HD lintel over
ra
5
il
Soft covering to stairs
min 6mm thick securely
fixed (e.g. glued)
4
St
3
2
Rear Elevation
Side Elevation
W3
PROJECT:
St. Vincent's, Monmouth.
Code 3+ House Types
1
DRG TITLE:
150
dpc
GD-ACC-01 or 02
Do Not Scale!
All Dimensions Are In Millimetres Unless
Otherwise Stated
If In Doubt Ask!
This plan is drawn as hand/drawing
1050
2696 floor to floor
1200
W4
900
floor to underside of plank
2248
10
398
O/H
168 Cant
1050
12
900 Handrail
13
2000
minimum clear head room
bedroom 1
11
floor to finished ceiling
2475
1735
wall to over
wallplate
210
1200
RS
1500
top of plank to top of wallplate
RS
150
2299
#
433
#
finished floor to finished ceiling
2385
210
J
GL
FOUNDATIONS ARE SUBJECT TO
CONFIRMATION BY STRUCUTRAL
ENGINEER
Section A-A
Staircase
Total rise: 2696mm
13No. risers @ 207.38mm
12No. goings @ 300mm
Width of structural stairs: 1160mm
(1110mm clear finished face)
Headroom - 2000mm minimum clear above
pitch line measured vertically
A
HOUSE TYPE 2.1.1
ELEVATIONS & SECTIONS
JOB NO:
DRG NO:
REV:
1073
C3+2.1.1-2
-
SCALE:
DRN BY:
1:50 @ A1
DATE:
CKD BY:
08/2011
Together, we make a home
Persimmon Homes East Wales Division
Persimmon House,
Llantrisant Business Park,
Llantrisant,
Rhondda Cynon Taff,
CF72 8YP.
Tel:01443 223653 Fax: 01443 237328
Drawing Revisions
THIS DRAWING IS TO BE READ IN CONJUNCTION WITH THE PERSIMMON EAST WALES DIVISION TECHNICAL SPECIFICATION
ISSUE
-
DATE
-
REVISION
BY
-
-
100x50mm s/w
wallplate
LRS
boarding to roof space,
ensuring that any tanks or
cisterns may be
easily reached from ceiling
hatch. Access boarding to
be capable of carrying an
LRS
LRS
LRS
Platform to be raised as to
not compromise insulation.
LRS
Standard roof
trusses by
specialist fixed at
maximum 600mm
centres, strictly in
accordance with
manufacturers
instructions
3520 overall span of planks
3345 stairwell opening
Extracts to be
ducted within
ceiling void below
concrete planks
Water supply
buried in screed
F
svp
svp
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
LRS
LRS
F
SVP to have
intumescent fire
collar at floor level
to provide min.
60mins FR
Boiler flue
terminated
at roof level
F
SVP to
vent tile
Bathroom
extract to
tile vent
kitchen
extract
planks
Floor Concrete Plank Layout
LRS
LRS
LRS
Standard roof
trusses by
specialist fixed at
maximum 600mm
centres, strictly in
accordance with
manufacturers
instructions
LRS
B
LRS
kitchen
extract to
tile vent
F
kitchen
extract to
tile vent
F
LRS
SVP to
vent tile
WATER
shower Extracts to be ducted within
extract ceiling void below concrete
LRS
LRS
C
WATER
LRS
B
C
2150 stairwell opening
SVP to have
intumescent fire
collar at floor level
to provide min.
60mins FR
Party wall taken up to
underside of roofing
felt and fire stopped
with minimum 50mm
reinforced mineral
wool.
4035
Floor manufacturer to allow
for M8 bolt @ 900mm c/c
for head restraint fixing to
top of masonry walls
3945 overall span of planks
4020 overall span of planks
Party wall taken up to
underside of roofing
felt and fire stopped
with minimum 50mm
reinforced mineral
wool.
Concrete planks
to share bearing
over 140mm wall
stairwell
LRS
100x50mm s/w
wallplate
Boiler flue
terminated
at roof level
F
SVP to
vent tile
SVP to
LRS vent tile
LRS
Bathroom
extract to
tile vent
C
REFER TO MANUFACTURERS DRWGS FOR DETAILS OF CONCRETE PLANK FLOOR
LRS
Direction of span
Plan at Ceiling Level
LRS
Plan at Rafter Level
ROOF TRUSSES TO COMPLY WITH BS 5268, PART 3, 1985.
ADDITIONAL ROOF BRACING AS REQUIRED TO MEET BS
5268, PART 3, 1985 (AS AMENDED JUNE 1988)
1500x30x5mm GMS lateral restraint strap on
150x50mm solid noggin with packing
between wall and 1st ceiling joist
100x25mm s/w bracing to BS 5268, Part 3, 1985
Denotes 30x2.5mm GMS wallplate straps at
maximum 2000mm centres
A
B
C
D
Longitudinal bracing at ridge level
Longitudinal bracing at rafter node point
Longitudinal bracing at ceiling level
Diagonal rafter bracing
LRS
1500x30x5mm GMS lateral restraint strap on
150x50mm solid noggin with packing
between wall and 1st ceiling joist
Electrical Symbols Legend
bed 1
bed 1
lounge
(home office)
lounge
(home office)
GR
2
2
bathroom
dining
661
dining
Twin switched
mounted 450 above
socket outlet 13A
f.f.l.
Twin switched
mounted 1050
socket outlet 13A
above f.f.l.
13A socket in
separately switched
appliance space
from grid ring
13A socket in
separately
switched
appliance space
Fused switch to cylinder / cooker hood & extract
fans (N) = Neon indicator (mounted 1050 above f.f.l)
Fused connection to boiler where applicable
(mounted 1050 above f.f.l)
mounted 1800
Shaver socket blank
above f.f.l.
mounted 1050
Cooker control panel
above f.f.l.
mounted 1200
Consumer unit & DB
above f.f.l.
(distribution board)
mounted 1050
Grid switch control panel
above f.f.l.
mounted 1050
Energy usage Transmitter
above f.f.l.
mounted 1050
Energy Display Device
above f.f.l.
mounted 1050
Thermostat
above f.f.l.
Energy Efficient
Track lighting with spot lights
Fluorescent or LED only
Pendant lamp
490
Batten holder lamp
landing
GR
Low level boxing
store
store
DWN
N
External lamp with
integral photocell
GR
ATTIC
store
S
Wall light
Switch
kitchen
N
kitchen
2 3
2
S
svp
rising
main
WATER
hall
SHW
WATER
WATER
WATER
WATER
WATER
F
Digital TV outlet
bath
shower
Telephone junction box
N
2
Plan of Bathroom 1:20
Setting out for appliances
UP
Fluorescent or LED only
Energy Efficient
Fluorescent or LED only
Energy Efficient
Fluorescent or LED only
Energy Efficient
Fluorescent or LED only
mounted 1050
above f.f.l.
mounted 1050
above f.f.l.
Pull switch
F
WATER
F
2 way Switch
Energy Efficient
F
2
LINTEL OVER
Twin Telephone junction box
Telephone master socket
store
mounted 450
above f.f.l.
mounted 450
above f.f.l.
mounted 450
above f.f.l.
mounted 450
above f.f.l.
Do Not Scale!
All Dimensions Are In Millimetres Unless
Otherwise Stated
If In Doubt Ask!
This plan is drawn as hand/drawing
PROJECT:
St. Vincent's, Monmouth.
Code 3+ House Types
DRG TITLE:
HOUSE TYPE 2.1.1
ROOF, JOISTS & ELEC'S
JOB NO:
DRG NO:
REV:
1073
C3+2.1.1-3
-
SCALE:
DRN BY:
1:50 @ A1
F
Ceiling mounted extract fan
DATE:
S
Fully automatic smoke detector to BS 5466 (minimum
2No.) interlinked and hardwired to mains
08/2011
CKD BY:
Boiler programmer
Bell push
Bell sounder
lobby
High level isolator switch (breaker) within 3m of DB
S
Together, we make a home
Immersion heater
Note; - Dimensions shown are to u/s of electrical plate
- All internal lighting to be Fluorescent or LED
Energy Efficient lighting
Ground Floor Electrics
First Floor Electrics
Persimmon Homes East Wales Division
Persimmon House,
Llantrisant Business Park,
Llantrisant,
Rhondda Cynon Taff,
CF72 8YP.
Tel:01443 223653 Fax: 01443 237328
Drawing Revisions
ISSUE
.
lounge
3675 [12'-0.7"]
bed 1
lounge
(home office)
dining
.
.
dining
landing
store
store
BY
3560 [11'-8.2"]
store
DWN
1860 [6'-1.2"]
shower
2025 [6'-7.7"]
2270 [7'-5.4"]
kitchen
1975 [6'-5.8"]
hall
SHW
3250 [10'-8.0"]
kitchen
bath
Low level boxing
2140 [7'-0.3"]
3250 [10'-8.0"]
3605 [11'-9.9"]
bed 1
(home office)
3560 [11'-8.2"]
.
REVISION
3675 [12'-0.7"]
3560 [11'-8.2"]
3675 [12'-0.7"]
3560 [11'-8.2"]
DATE
2270 [7'-5.4"]
Do Not Scale!
All Dimensions Are In Millimetres Unless
Otherwise Stated
If In Doubt Ask!
store
UP
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
WATER
PROJECT:
St. Vincent's, Monmouth.
Code 3+ House Types
LINTEL OVER
DRG TITLE:
HOUSE TYPE 2.1.1
lobby
SALES PLANS
JOB NO:
DRG NO:
1073
C3+2.1.1-SA .
SCALE:
DRN BY:
1:50 @ A2
Ground Floor Sales Plan
First Floor Sales Plan
DATE:
CKD BY:
08/2011
Together, we make a home
Persimmon Homes East Wales Division
Persimmon House,
Llantrisant Business Park,
Llantrisant,
Rhondda Cynon Taff,
CF72 8YP.
Tel:01443 223653 Fax: 01443 237328
REV: